Вы находитесь на странице: 1из 1

FIAMM Sizing Tool 2.1.

22 Date: 3 / 6 / 2016
Sized By: Minou van Nooijen

CUSTOMER : FLEXENCLOSURE
PROJECT : 7620-UPS Battery
SYSTEM :
275 kW 45 min 1.67 Vpc 276-300 cells - 12 FIT 180

BATTERY REQUIREMENT

UPS Power
Power requirement from the battery 275.0 Kwatt
Max current at the end of discharge 597 Amps.
Discharge time 45 min.

Maximum system voltage 627.1 Volt


Minimum system voltage 460.92 Volt

Number of cells 276


Design temperature 20 °C
Design margin 1
Aging factor 1
Battery type VALVE REGULATED (AGM)

RECOMMENDED BATTERY

Cell type 12FIT180


Q.ty of cells or units 4 x 46
Nominal capacity (C10) 720 Ah
Electrolyte specific gravity N/A
Nominal voltage of the battery 552 Volt
Real back-up time 51 min.

Internal resistence per cell 3.2000 Ohm


Short circuit current 3740 Ampere

Weight Total battery each cell/unit


10616.8 Kg 57.7 Kg
Voltage
Minimum voltage at the end of discharge 460.9 Volt 1.67 Volt
Float voltage at 20°C 626.5 Volt 2.27 Volt
Maximum boost voltage permissible 662.4 Volt 2.4 Volt

All data printed in this document are preliminary and must be confirmed by Fiamm