Printed in Great Britain 0 1985 Pergamon Press Ltd.
Abstract-It is well established that the inclination angle between plate corrugations and the overall flow
direction is a major parameter in the thermohydraulic performance ofplate heat exchangers. Application ofan
improved flow visualization technique has demonstrated that at angles up to about 80” the fluid flows mainly
along the furrows on each plate. A secondary, swirling motion is imposed on the flow along a furrow when its
path is crossed by streams flowing along furrows on the opposite wall. Through the use of the electrochemical
mass transfer analogue, it is proved that this secondary motion determines the transfer process; as a
consequence of this motion the transfer is fairly uniformly distributed across the width of the plates. The
observed maximum transfer rate at an angle of about 80” is explained from the observed flow patterns. At
higher angles the flow pattern becomes less effective for transfer ; in particular at 90” marked flow separation is
observed.
NOMENCLATURE
This equation allows the estimation of the diffusion exchanger the test plate surfaces were machined in the
coefficient from viscosity measurements. form of sinusoidal corrugations, of wave-length 10 mm
and amplitude 2.5 mm, running the full width of the
2.2. Apparatus plate. Test plates were fitted into the test section with
The experimental set-up is shown schematically in the corrugations abutting at an angle of 28. The test
Fig. 1. The most important part was an acrylic cell with plates were 100 mm wide and 440 mm long. The ends
a test section into which test plates were fitted (see Fig. were chamfered to smooth the transition from the
2). The cell formed a rectangular channel with a low rectangular duct to the flow passage of the plate heat
aspect ratio, having a width of 100 mm and a height of exchanger.
10 mm. Wire mesh screens were used at the inlet to The test plates contained embedded nickel-plated
break up flow vortices. A converging section improved brass electrodes. The cathode plates were divided into
the velocity profile and reduced the turbulent intensity, three electrode segments each 112 mm long, and the
while the inlet length of 600 mm allowed final flow anode plates were continuous with their ridges
development. constructed from an epoxy resin to prevent electrical
To simulate a single compartment in a plate heat contact between the electrodes. The use of opposing
electrodes was essential to ensure limiting current
conditions over the total length of the cathodes.
Plates with corrugation inclination angles of /3 = O”,
30”, 4.S”,60”, 72”, 80”, and 90” relative to the main flow
direction were tested. The angles, /3 = 72” and 80”, were
chosen on the basis of the study by Rosenblad and
Kullendorff [ 11, which indicated local extrema in the
heat transfer for these angles. The resulting channels
varied from a set of ten separate channels (sine-ducts) in
parallel (fi = 0”) to a single undulating channel of
constant rectangular cross-section (/I = 90’). In the
CENTRIFUGAL latter case the corrugations of the two plates were in
IWMP
phase and therefore did not abut (see Fig. 7); the plate
FIG. 1. Experimental set-up. spacing was kept the same as in the other
The effect of corrugation angle on the performance of heat exchangers 1471
SIDE VIEW
CUT A-A’
configurations. Intermediate angles resulted in three- up daily and the ferricyanide concentration checked by
dimensional multiply-connected Sow passages. iodometric titration with thiosulphate. Solution
Flow rates were measured with a set of rotameters, densities and viscosities were determined with
and temperature to +O.l”C with precision mercury pycnometers and an Ub~lohde viscometer,
thermometers. Limiting currents were measured using respectively.
a constant voltage supply and a digital multimeter. Nitrogen was bubbled continuously through the
Pressure drop was measured with a Gould DR3000 reservoir tank to remove any dissolved oxygen. The
series differential pressure transmitter using distilled experiments were performed in a dark-room to prevent
water as the medium. Pressure taps were located 100 the light-catalysed decomposition of ferricyanide.
mm upstream and 300 mm downstream of the test Voltage scans were made before each set of runs to
section. Corrections were made for the additional determine the extent of the limiting current plateau. A
flowpath length and for entrance and exit losses. The potential in the midrange of the current plateaus was
corrections were based on measurements with a then applied to all the experiments in the particular run.
rectangular channel (flat plates with the same chamfer
angle) of similar cross-sectional free flow area (0.5
3. RESULTS AND DISCUSSION
x 10m3 m2). The corrections ranged from a maximum
of N 12% and -4% for 30” and 45” plates, to less than The characteristic length dimension (equivalent
1% of total pressure drop for the other plates. diameter) was defined as the maximum passage gap.
In the case of 0” plates, no correction was necessary The concept of a hydraulic diameter is applicable only
since pressure taps were located on the test plate : in the for estimating transfer for the two-dimensional sine duct,
trough of a furrow and in the centre of the plate as well from transfer analogies. Table 1 gives characteristic
as 100 mm downstream. No measurements could be dimensions of the plate patterns chosen.
obtained in the laminar flow regime as the pressure The experimental results are presented in Figs. 3-6 in
drop signal was too small. the form of friction factors or Colburn j-factor vs
Reynolds number. Empirical correlations (for /? > O”)
2.3. Procedure obtained by least-squares methods are given in Tables 2
Before the experiments the electrodes were cleaned and 3. Standard deviations from the experimental data
by polishing them with optical-grade abrasive powder were less than 5 and 7% for the Colbum j-factor and
and washing them with carbon tetrachloride. The friction factor, respectively. The (heat) transfer data are
electrodes were then activated cathodically by based on the projected rather than the developed
hydrogen evolution at a current density of 200 A mm2 transfer surface area. Transfer data were obtained from
for 20 min in a solution containing potassium measurements done with the central cathode only.
carbonate only.
The electrolyte solutions contained approximately 3.2. Parallel corrugations (/I = 0) : sine ducts
1.5 M K&O3 and 0.001-0.003 M potassium Fully developed laminar flow through a sine duct can
ferricyanide; ferrocyanide concentrations three times be analysed mathematically. The friction factor is
in excess of the ferricyanide ensured that the cathodic obtained by solving Poisson’s equation (Appendix A).
reaction was rate-limiting. Fresh solutions were made Then, using Leveque’s approximation, the entrance
1472 W. W. FOCKE,J. ZACHARIADES and 1. OLEVIER
region heat transfer is estimated (Appendix B). The asymptotic form of the conventional transfer analogy
resulting equation is converted to the plate heat (Appendix D). The resulting equation (17) is also
exchanger conventions (Appendix C). This correlation plotted in Fig. 4(a). The experimental results fall
[equation (1611 has been plotted in Fig. 4(a) for an approx. 4”/, below this semi-theoretical correlation.
entrance length of 0.112 m, which corresponds to the
electrode length. The experimental data fall slightly 3.2. E&zct of corrugation ~n~~~~~t~o~
angle
below the theoretical curve but show a similar trend. The effect of the corrugation inclination angle to the
For high Prandtl (Schmidt) numbers, the turbulent main Bow direction, 8, on the~ohydrauIic perfor-
transfer rate is estimated from the friction factor and the mance is highlighted in Figs. 5 and 6. The main features
.50- -I
IO -_
5-
‘c
I=
0.5 -
0.t -
0.05 -
I L ,,,I I I1111
IO3 IO4
R8
Fro. 3. ~x~~rneutal friction factors
The effect of corrugation angle on the performance of heat exchangers 1473
1.
._
16’r
5.lo-2
-
2.ld’ -
16’ -
._
5.1ci2 -
ICP -
5.d’ -
lG2 :
5.163 -
Re
FIG. 4(a). Colbum j-factors.
1.1”
._ I
IO-'
5.16’
3.16
1
t
._
I6
5.162
4.16
1
._
IO-’
5.10*
i
2.142 I I I1111 ,,,I I
IO’ Id IO’
Re
FIG. 4(b). Colburn j-factors.
1474 W. W. FOCKE. J. ZACHARIADES and I. OLIVIER
P/[ded
300 60' 90’
2.5 -
_ 0.Q
_ w-4
o-cl
.
2.0 -
3
>
.-
\ 1.5 -
5.-
1.0f
.:’
. .. . I , I I , ,
0
“/s “‘2
@adIT
Corrugation
angle, B
(degrees) Re-Range f-Correlation
* This correlation was obtained by combining equations (Al) and (A3) and
equation (A16).
The effect of corrugation angle on the performance of heat exchangers 1475
Corrugation
angle, B
(degrees) Re-Range j-Correlation
-213
0 35 < Re < 800 2.53(d,/L)“3Re- (16) theory*
7OOC<Rei35000 0.021 Rem’.132 (17)
30 120 < Re < 1000 0.77 Re-0,46 (18)
lOOO<Re<42000 0.44 Re-0,36 (19)
45 45 < Re < 300 1.67 Re-0.56 (20)
3OO<Re<2000 0.405 Re-0.30 (21)
2OOOiRe<20000 0.84 Re-0.40 (22)
60 20<Re< 150 1.89 Re-0.54 (23)
150 < Re < 600 0.57 Re-0.30 (24)
6OO<Re<16000 1.12 Re-0.40 (25)
72 2OOcRec4000 1.45 Re-0.42 (26)
80 27 < Re < 500 1.05 Re-0.“6 (27)
SOOiRe<2800 1.98 Re-0,46 (28)
90 3OO<Re<14000 0.98 Re-0,37 (29)
*Equations (16) and (17) are the same as equations (AS) and (A21),
respectively.
With increasing Reynolds number the separated furrow is the velocity component of the fluid moving
regions grow in size until they fill the major part of the along the opposite furrows in adirection perpendicular
furrows. At Re N 200 the free shear layers become to the furrow. It is therefore proportional to :
unstable and at higher Reynolds numbers the main flow
ii, sin (2/I) = 215,sin /l cos fi (30)
becomes turbulent.
/I = 45”. The fluid flows predominantly along the and is at a maximum when a = 45”. For angles below
furrows, i.e. between the corrugations on each of the fi = 45”, the interaction between the fluid streams is
plates. On reaching the plate edge the fluid streams are positive, i.e. each of the crossing streams has a velocity
‘reflected’ and return to the opposite plate edge along component in the same direction as the stream it
the furrows on the opposite side. crosses. For /3 > 45”, the interaction is negative in the
Flow patterns similar to those of fi = 45” are sense that crossing streams have a retarding effect on
expected for any p in the range up to about 60” (72”?). each other owing to their velocity components being in
The essential feature of the flow for these angles is the opposite directions. We speculate that this retarding
two sets of criss-crossing streams which induce effect, which increases with 8, eventually leads to the
secondary swirling motions in the flow along the change in flow pattern observed for /I = 80”.
furrows. The driving force that produces swirl in a /I = 80”. The fluid still flows mainly along the furrows
P= 80” p = 45’
but ‘reflection’ occurs between plate contact points (see transfer rates can be estimated from pressure drop data
Fig. 7). The flow forms zig-zag patterns in parallel. using conventional transfer analogies.
The complex interactions between fluid streams lead 30 5 /j 5 60 ‘. Sets ofcriss-crossing streams flowing
to early transition to turbulence. The basic flow along the furrows on either side of the flow passage
structures appear to persist even in turbulent flow. inducing secondary swirling motions ; these determine
the heat transfer enhancement process.
3.4. Interpretation of transfer data in terms of flow fi = 80”. Flow consisting of parallel zig-zag patterns ;
patterns pressure drop and heat transfer are about at their
/I = 90”. Heat (mass) transfer at Reynolds numbers maximum but only marginally higher than for fl = 72”.
below 300 is relatively low since the laminar free shear /I = 90”. Separated flow regions causing heat transfer
layers of the separated regions are an additional and pressure drop to be considerably lower and of
resistance. Transfer across turbulent-free shear layers approximately the same magnitude as for p = 60”.
is, however, usually very effective owing to the absence Experimental results obtained for plates with
of a restraining effect such as a solid wall. The p = 45” indicate that transfer rates are almost uniform
additional resistance is therefore effectively removed across the plate width. Pitch-averaged transfer rates are
when the free shear layers become turbulent and there is also independent of plate length.
a sudden increase in heat (mass) transfer [see Fig. 4(b)].
A similar sharp increase in the friction factor is REFERENCES
observed at Re _ 200.
I. G. Rosenblad and A. Kullendorff, Estimating heat
The friction factor plot suggests that fully turbulent transfer rates from mass transfer studies on plate heat
flow is established only at Re - 30OO(seeFig. 3), but for exchanger surfaces, B&me-u. Stofltibertr.8, 1877191
heat (mass) transfer effectively turbulent conditions (1975).
prevail above Re - 300. 2. K. Okada, M. Ono, T. Tomimura,T. Okuma, H. Konno
and S. Ohtani, Design and heat transfer characteristics of
Intermediate angles. It is demonstrated in Appendix new plate heat exchanger, Heat Transfer Jap. Res. 1,90-
E that the secondary swirling motions induced by the 95 (1972).
streams criss-crossing along the furrows are the main 3. A. F. Savostin and A. M. Tikhonov, Investigation ofplate-
determinant in heat (mass) transfer. At constant plate tvue heatine surfaces. Teobneraetika 17.75-78 (19701.
4. J:’ R. Selman and’ C.’ W. Tobias, ‘Mass transfer
Reynolds number the velocity of the flow along a
measurements by the limiting current technique, Adu.
furrow is proportional to l/cos /I (Appendix C). The them. Engng 10,211-318 (1978).
effective driving force that produces swirl at constant 5. F. P. Berger and A. Ziai, Optimization of experimental
plate Reynolds number is therefore proportional to conditions for electrochemical mass transfer measure-
sin fi for 30 < p < 72 [see equation (30)]. The transfer ments, Chem. Engng Res. Deu. 61,377-382 (1983).
6. M. Baan Hofman, The diffusion coefficients of ferri- and
curve at constant plate Reynolds number then flattens ferrocyanide ions in the presence of potassium carbonate
above b = 60” in accordance with the attenuation of as supporting electrolyte, CERG Memo 81/15, CSIR,
the driving force, as shown in the experimental results in Pretoria (1981).
Fig. 6. 7. W. W. Focke and P. G. Knibbe, Flow visualization in flat
ducts with corrugated walls using an electrode-activated
An important implication of the transfer being
pH-indicator. Submitted for publication.
determined by the secondary motions is that plate 8. International Mathematical and Statistical Libraries,
width is of minor importance for average heat transfer Program TWODEPEP (5th edn), IMSLTDP-0005,
coefficients. This means that zig-zag corrugated Houston, Texas (1983).
patterns (multiple chevrons in parallel) are not expected 9. R. K. Shah, Laminar flow friction and forced convection in
ductsofarbitrarygeometry, Int. J. Heat Mass Transfer 18,
to produce significant increases in heat transfer
8499862 (1975).
coefficients compared with plates having corrugations 10. M. A. Leveque, Les lois de la transmission de chaleur par
funning their full width. The former could, however, convection, Annls Mines Mem.,Ser. 12,13,201-415(1928).
lead to higher pressure drops owing to the increased 11. B. S. Petukhov and V. N. Popov, Theoretical calculation
ofheat exchange and frictional resistance in turbulent flow
number of turns the flow has to make.
in tubes of an incompressible fluid with variable physical
properties. Trans. High Temp. 1, 69983 (1963).
12. S. W. Churchill. Comprehensive correlating equations for
heat, mass and momentum transfer in fully developed flow
4. CONCLUSIONS
in smooth tubes, Ind. Engng Chem. Fundam. 16, 109-l 15
The corrugation inclination angle, 8, is a major (1977).
13. 0. T. Hanna and 0. C. Sandall, Developed turbulent
parameter influencing the performance of plate heat
transport in ducts for large Prandtl or Schmidt numbers,
exchangers: this is because a change in /i affects the A.1.Ch.E. JI 18, 527-533 (1972).
basic flow structure which is the primary factor
influencing pressure drop and heat transfer. Increasing
fi (at constant Reynolds number) from 0” to 80” leads to APPENDIX A: FRICTION FACTOR FOR
pressure drop increases of over 2+ orders of magnitude, FULLY-DEVELOPED LAMINAR FLOW
although heat transfer increases by a factor of only 4- IN A SINE DUCT.
10. The flow patterns found for various values of b are : The friction factor for fully-developed laminarflow in a two-
b = 0”. Two-dimensional channel flow for which dimensional duct is best evaluated from the geometric
The effect of corrugation angle on the performance of heat exchangers 1477
647)
Inserting the numerical values for the dimensions of the sine
duct and the plate heat exchanger channel gives
j = 2.53(d,/L)“’ Re-2’3. (A8)
KEY
*ez’ *eI =2
0 0 0 0 0
J
RATIO FOR EVEN
DISTRIBUTION OF
HEAT TRANSFER
OVER PLATE WIDTH. -
01 I ,,*.I I
IO2 5.102 IO3 5.103
Re
FIG. A2. Transfer to a segmented electrode with and without a partition between test plates with b = 45”.
For heat transfer in tubes at high Prandtl numbers electrode into two parts covering f and f of the electrode area
Churchill [12] proposed respectively.
Overall heat (mass) transfer rates measured with the
j = 0.0157 Re-0~‘25. (Al9) combined electrodes were in agreement with the results
This equation is in good agreement with the results obtained obtained for nickel-plated brass electrodes presented in the
by other investigators [12, 131. By substituting the Blasius main text. This result suggests that pitch-averaged heat
friction factor correlation for tubes transfer coefficients are uniform across the plate length.
The results obtained when the smaller electrode segment
f = 0.3164 Re-‘.“. 6420) was placed on the upstream side are presented in Fig. A2 as the
ratio of smaller-segment current to total current. No
into equation (A18), a value for B = 0.0279 is deduced from
significant variation of this ratio with Reynolds number is
equation (A19).
observed. Since the current ratios are slightly above the value
Assuming now that equation (A18), with B = 0.0279, is also
of f (which would indicate an even current distribution), a
valid for channels other than those of circular cross-section,
small edge effect is indeed present.
one obtains for the sine duct (on inserting the experimental
The unsymmetrical partitioning of the electrode allows
friction factor correlation)
measurements to be made with two different geometric
j = 0.021 Re-0.132 6421) arrangements, i.e. smaller electrode segment downstream or
upstream. With data for these two arrangements it is possible
to estimate the magnitude of the edge effects at both edges,
APPENDIX E: THE FEATURE OF THE FLOW THAT provided that it can be assumed that these edge effects are
DETERMINES HEAT (MASS) TRANSFER limited to a distance that is shorter than the length of the
ENHANCEMENT smaller segment. Based on this assumption, the incremental
contributions of upstream and downstream edge effects are 5
Flow visualization studies [7] on plates with /I = 45” have and 2%, respectively at Re - 2000. These low values suggest
shown that: that the secondary swirling motion is the main determinant in
--the fluid flows along the furrows on either side of the the heat transfer enhancement process. The small deviations
passage, from edge to edge ; and may well represent the effect of the turning of the flow at the
-the two sets of criss-crossing fluid streams induce secondary edges.
swirling motions in the flow along the furrows, As a further check, the experiments were repeated under
conditions in which the interaction between the two sets of
It is of interest to determine which, if either, of these two fluid streams was effectively eliminated. This was achieved by
main features of the flow determines the heat transfer inserting a rigid celluloid sheet -0.1 mm thick and 70 mm
enhancement process. For flow along a short path length, wide between the test plates. This left 15 mm open on each side
entrance region conditions are expected because the boundary of the passage to allow the fluid streams to turn. Current ratios
layers are still developing. In this case, higher transfer rates are measured for this case are also shown in Fig. A2 and a marked
expected in the upstream parts of the furrows. However, a increase in the upstream edge (or entrance) effect is indicated.
swirling motion of sufficient strength could lead to a more The smaller electrode segment registered roughly the same
uniform transfer rate across the plate width. current as the downstream segment which had twice the area.
Additional experiments were done with plates (/? = 45”) Estimated positive edge effects for Re - 2000 are 29 and lo%,
containing a segmented graphite cathode. The cathode shape respectively for the upstream and downstream parts. In
was a parallelogram. It extended over the width of the plate addition, overall transfer decreased to 65% of the value for
with the electrode edges running parallel to the corrugation plates without a partition. These observations confirm the
crests. It covered three adjacent furrows from crest to crest. A dominant role of the secondary motion resulting from fluid
gap of 1 mm running parallel to the cell axis divided the stream interactions.
The effect of corrugation angle on the performance of heat exchangers 1479
Zusammenfaasung-Der Neigungswinkel zwischen Plattenwellen und der allgemeinen Fliessrichtung ist ein
wichtiger Parameter in der thermodynamischen Leistungeines Plattenwamre-austauschers. Die Anwendung
einer verbesserten Technik der Sichtbarmachung der Fliessbewegung hat bewiesen, dass bei Winkeln bis 80
die Fliissigkeit griisstenteils l&rings
der Furchen an jeder Platte fliesst. Die Striimung Iangs einer Furche erfahrt
eine sekundiire Wirbelbewegung durch die querlaufenden Striimungen liings der entgegengesetzten Wand.
Die Anwendung der elektrochemischen Masseniibertragungsanalogie liefert den Beweis, dass diese
sekundlre Wirbelbewegung den Ubertragungsprozess bestimmt ; als Konsequenzdieser Bewegung wird eine
ziemlich gleichmiissige Verteilung der Ubertragung ilber die Breite der Platte erreicht. Das beobachtete
Maximum der Ubertragungsgeschwindigkeit bei einem Winkel von ungeftir 80” wird durch das beobachtete
Fliessprofil erkllrt. Bei hijheren Winkeln wird das Fliessprofil weniger effektiv fiir die Ubertragung; im
einzelnen erscheint bei 90” eine klar sichtbare Trennung des Flusses.