Вы находитесь на странице: 1из 9

ENGLISH

CE DECLARATION OF CONFORMITY
Manufacturer: FAAC S.p.A.

Address: Via Benini, 1 - 40069 Zola Predosa BOLOGNA - ITALY

Declares that: 452 MPS control board,

• conforms to the essential safety requirements of the following directives:

73/23/CEE and subsequent amendment 93/68/CEE.


89/336/CEE and subsequent amendment 92/31/CEE and 93/68/CEE

Additional note:
This product underwent tests in a typical uniform configuration
(all products manufactured by FAAC S.p.A.).

Bologna, 01 January 2001


The Managing Director
A. Bassi

INSTALLATION WARNINGS
GENERAL SAFETY OBLIGATIONS

1) CAUTION! It is important for personal safety to follow all the instructions 14) Check that the earthing system is correctly made and connect the closure
carefully. Incorrect installation or misuse of the product may cause metal parts to it. Also connect the Yellow/Green wire of the automated
people serious harm. system to the earthing system.
2) Read the instructions carefully before starting to install the product. 15) The automated system includes an intrinsic anti-crushing device consisting
of a torque control which, however, must be installed together with other
3) Packaging material (plastic, polystyrene, etc.) must not be left within reach safety devices.
of children as it is a potential source of danger.
16) The safety devices (EN 12978 Standard) protect any dangerous areas
4) Keep the instructions in a safe place for future reference. against Mechanical movement risks, such as crushing, dragging, and
5) This product was designed and manufactured strictly for the use indicated shearing.
in this documentation. Any other not expressly indicated use may damage 17) Use of at least one indicator-light (e.g. FAAC LAMP MINILAMP, etc.) is
the product and/or be a source of danger. recommended for every system, as well as a warning sign adequately
6) FAAC accepts no responsibility due to improper use of the automated fixed to the frame structure, in addition to the devices mentioned at point
system or use other than that intended. "16".
7) Do not install the equipment in an area subject to explosion hazard: 18) FAAC accepts no responsibility regarding safety and correct operation
inflammable gases or fumes are a serious safety hazard. of the automated system, should components made by manufacturers
other than FAAC be used in the system.
8) Mechanical construction elements must meet the provisions of UNI8612,
EN 12604 and EN 12605 Standards. 19) Use only FAAC original spare parts for maintenance.
To obtain an adequate level of safety in non EU countries, the above 20) Do not make any alterations to the components of the automated system.
mentioned Standards must be observed in addition to national Standards. 21) The installer must supply full information regarding manual operation of
9) FAAC will not accept responsibility if the principles of Good Workmanship the system in case of an emergency and hand to the user of the system the
are disregarded in constructing the closing elements to be motorised, and “User’s Guide” included with the product.
if any deformation occurs during use of the said elements. 22) Do not allow children or other persons to stand near the product while in
10) Installation must meet the following Standards: UNI8612, EN 12453 and EN operation.
12445. 23) Keep remote controls or any other pulse generator well away from
11) Before carrying out any work on the system, switch off the power supply. children, to prevent the automated system from being activated
accidentally.
12) The mains power supply of the automated system must be fitted with a all-
pole switch with contact opening distance of 3mm or greater. Use of a 6A 24) The user must refrain from attempting to repair or adjust the system
thermal breaker with all-pole circuit break is recommended. personally and should contact qualified personnel only.
13) Make sure there is a differential switch with 0.03A threshold upstream of the 25) Anything not expressly provided for in these instructions is not permitted.
system.

10
ENGLISH

CONTROL BOARD 452 MPS


1. WARNINGS 3. LAYOUT AND COMPONENTS OF 452 MPS
Important: Before attempting any work on the control board
(connections, maintenance), always turn off power. F2 F2
DS2
DS1
- Install, upstream of the system, a differential thermal breaker 1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4
with adequate tripping threshold. J2
J2

- Connect the earth cable to the appropriate terminal on the J3 F


DL10
connector of the equipment (see fig.2). F
DL10
- Always separate power cables from control and safety cables
(push-button, receiver, photocells, etc.). To avoid any electric
noise, use separate sheaths or a shielded cable (with earthed
shield). F1 OP_A
Led OP_B

F1

STOP FSWCL FSWOP

J1 J5
J3 J4 J5

2. TECHNICAL SPECIFICATIONS J3
J4 J1
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Power supply 230 V~ ( +6% -10%) - 50 Hz PE N
MAIN
L OP
COM M1
OP
COM M2 CL LAMP
A
OPEN
B STP CL OP
FSW
- - - +
+24V
+ -TX
FSW W.L.
LOCK

Absorbed power 10 W
Motor max. load 800 W Fig. 1
Accessories max. load 0,5 A
Electric lock max. load 15 VA
Led OP_A TOTALLY OPEN LED
Operating ambient temperature -20 °C +55 °C
Protection fuses 2 (see fig. 1) Led OP_B LED: OPEN LEAF 1 / CLOSE
Function logics Automatic / Semi-automatic / Safety devices / Led STOP LED STOP
Semi-automatic B / Dead-man C / "Stepped" semi-automatic Led FSWCL LED: CLOSING SAFETY DEVICES
Opening/closing time Programmable (from 0 to 120 s)
Led FSWOP LED: OPENING SAFETY DEVICES
Pause time 0, 10, 20, 30, 60, 120 s
Closing leaf delay 0, 5, 10, 20 s DL10 LED: TIME LEARNING SIGNALLING
Opening leaf delay 2 s (Can be disabled with the dip-switch) J1 LOW VOLTAGE TERMINAL BOARD
Thrust force Dip-switch adjustable on 8 levels for each motor J2 CONNECTOR FOR DECODER/MINIDEC/RP RECEIVER
Terminal board inputs Open / Open free leaf / Stop /
J3 230 VAC POWER SUPPLY TERMINAL BOARD
Opening safety devices / Closing safety devices / Power supply + Earth
Terminal board outputs Flashing lamp - Motors - 24 Vdc accessories J4 MOTORSANDFLASHINGLAMPCONNECTIONTERMINALBOARD
power supply - 24 Vdc indicator-light - Fail safe - J5 INDICATOR-LIGHT AND ELECTRIC LOCK TERMINALBOARD
12 Vac electric lock power supply F1 MOTORS AND TRANSFORMER PRIMARY WINDING FUSE (F 5A)
Rapid connector To connect Minidec, Decoder or RP cards
Selectable functions Logics and pause times - Thrust force - F2 LOW VOLTAGE AND ACCESSORIES FUSE (T 800mA)
Opening and closing leaf delay - Reversing stroke - F TIME LEARNING PUSH-BUTTON
Fail safe - Closing safety devices logic - Pre-flashing
DS1 1ST GROUP OF MICROSWITCH PROGRAMMING
Programming key work time learning
DS2 2ND GROUP OF MICROSWITCH PROGRAMMING

4. ELECTRIC CONNECTIONS

J5

J3
J4 J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
PE N L OP
COM M1
OP
COM M2 CL LAMP
A B STP CL OP - - - + + -TX LOCK
MAIN OPEN FSW +24V FSW W.L.
BLUE

BLUE

C1 C2

M1 M2 230 VAC
max.60W 24 Vdc
3W

230 VAC
50 Hz

For connection of
12 V ac
TOTALLY OPEN the photocells
and safety
OPEN LEAF 1 devices, see
paragraph 4.1
STOP (page 12).

NB.: Capacitors are supplied with the operators.


Fig. 2

11
ENGLISH

4.1. Connection of photocells and safety devices


Before connecting the photocells (or other devices) we advise Opening/closing safety devices: they operate during the gate
you to select the type of operation according to the movement opening and closing movements and, therefore, they
area they have to protect (see fig.3): are suitable for the opening and closing areas against
the risk of impact.
Opening safety devices: they operate only during the gate
opening movement and, therefore, they are suitable for FAAC recommends use of the lay-out in fig. 4 (in the event of fixed
protecting the area between the opening leaves and obstacles at opening) or in fig. 5 (no fixed obstacles).
fixed obstacles (walls, etc) against the risk of impact
and crushing. N.B. If two or more devices have the same function (opening or
Closing safety devices: they operate only during the gate closing closing), they should be connected to each other in series (see
movement and, therefore, they are suitable for fig. 12). N.C. contacts must be used.
protecting the closing area against the risk of impact.

Opening/closing safety devices Connection of a pair of closing photocells and a pair of


opening/closing photocells (recommended lay-out)

9 10 11 12 13 14 15 16 17 18 19 20 21
A B STP CL OP - - - + + -TX LOCK
OPEN FSW +24V FSW W.L.

RX CL TX CL
1
2
- 1
3
+ 2
4 -
Closing safety devices 5 +
Opening
Fig. 3 safety devices

Connection of a pair of closing photocells, a pair of 1


opening photocells and a pair of opening/closing 2
photocells (recommended lay-out) 1
3
9 10 11 12 13 14 15 16 17 18 19 20 21 2
4
A B STP CL OP - - - + + -TX LOCK
OPEN FSW +24V FSW W.L. 5
TX OP/CL RX OP/CL

RX CL TX CL Fig. 5
1
2
- 1
3
+ 2 Connection of a closing safety device and an opening
4 -
safety device
5 +

9 10 11 12 13 14 15 16 17 18 19 20 21
A B STP CL OP - - - + + -TX LOCK
OPEN FSW +24V FSW W.L.
1
2
1 Fig. 6
3
2
4

5
TX OP/CL RX OP/CL
Connection of no safety device

9 10 11 12 13 14 15 16 17 18 19 20 21
A B STP CL OP - - - + + -TX LOCK
RX OP TX OP OPEN FSW +24V FSW W.L.
1
2
- 1
3
+ 2
4 -
5 + Fig. 7

Fig. 4

12
ENGLISH

Connection of 1 pair of opening photocells Connection of two pairs of closing photocells

9 10 11 12 13 14 15 16 17 18 19 20 21 9 10 11 12 13 14 15 16 17 18 19 20 21
A B CL OP + + -TX LOCK A B STP CL OP - - - + + -TX LOCK
STP - - - +24V FSW W.L. OPEN FSW +24V FSW W.L.
OPEN FSW

RX TX RX CL1 TX CL1
1 1

2 2
- 1
3 - 1 3
+ 2
4 + 2 4 -
-
+ 5 +
5

Fig. 8
TX CL2 RX CL2
1
2
1
Connection of 1 pair of closing photocells 3
2
4
9 10 11 12 13 14 15 16 17 18 19 20 21 5
A B STP CL OP - - - + + -TX LOCK
OPEN FSW +24V FSW W.L.

Fig. 11
RX TX
1
2
- 1
3
+ 2 Connection of 2 N.C. contacts in series
4 -
(e.g. Photocells, Stop)
5 +

Fig. 9

Fig. 12

Connection of a pair of opening photocells and a pair of


closing photocells
Connection of 2 N.O. contacts in parallel
9 10 11 12 13 14 15 16 17 18 19 20 21 (e.g. Open A, Open B)
A B STP CL OP - - - + + -TX LOCK
OPEN FSW +24V FSW W.L.

RX OP TX OP
1
2
3
- 1 Fig. 13
+ 2
4 -
5 +
4.2. Terminal board J3 - Power supply (fig. 2)
PE: Earth connection
N : 230 V~ power supply ( Neutral )
TX CL RX CL
L : 230 V~ power supply ( Line )
1
2 NB.: For correct operation, the board must be connected to the
1 - earth conductor in the system. Install an adequate differential
3
2 + thermal breaker upstream of the system.
- 4
+ 5 4.3. Terminal board J4 - Motors and flashing lamp (fig. 2)
M1 : COM / OP / CL: Connection to Motor 1
Can be used in the single-leaf application
M2 : COM / OP / CL: Connection to Motor 2
Cannot be used in the single-leaf application
LAMP : Flashing lamp output ( 230 V ~)
Fig. 10

13
ENGLISH

4.4. Terminal board J1 - Accessories (fig. 2) LOCK - Power supply to electric lock
OPEN A - "Total Opening" command (N.O.): any pulse generator If necessary, connect a 12 V ac electric lock between
(push-button, detector, etc.) which, by closing a contact, this terminal and the +24V supply.
commands opening and/or closing of both gate leaves.
4.6. Connector J2 - Rapid connection (fig.2)
To install several full opening pulse generators, connect
the N.O. contacts in parallel (see fig. 13). This is used for rapid connection of Minidec, Decoder and RP
receivers (see fig. 14, 15, 16 and 17). Connect the accessory, with
OPEN B - "Partial Opening" command (N.O.) / Closing: any the components side facing the inside of the card. Insert and
pulse generator (push-button, detector, etc.) which, by remove after cutting power.
closing a contact, commands opening and/or closing
of the leaf driven by motor M1. In the B and C logics, it
always commands closing of both leaves.
To install several partial opening pulse generators, PLUS
connect the N.O. contacts in parallel (see fig. 13). 433 / 868

STP - STOP contact (N.C.): any device (e.g. a push-button)


which, by opening a contact, is able to stop gate
movement.
To install several STOP devices, connect the N.C. contacts
in series (see fig. 12). 452 MPS

NB.: If STOP devices are not connected, jumper connect


the STP terminals and -.
CL FSW - Closing safety devices contact (N.C.): The purpose
of the closing safety devices is to protect the leaf movement MINIDEC
SL / DS / SLH
area during closing. During closing, in the A-S-E-EP logics,
the safety devices reverse the movement of the gate Fig. 14
leaves, or stop and reverse the movement when they are
released (see programming of microswitch DS2 - SW2).
During the closing cycle in logics B and C, they interrupt PLUS
movement. They never operate during the opening 433 / 868

cycle. If the closing safety devices operate when the


gate is open, they prevent the leaf closing movement.
NB.: If no closing safety devices are connected, jumper
connect terminals CL and -TX FSW (fig. 7).
452 MPS
OP FSW - Opening safety devices contact (N.C.): The purpose
of the opening safety devices is to protect the leaf
movement area during opening. During opening,in the A-
S-E-EP logics, the safety devices stop the movement of the DECODER
gate leaves and reverse the movement when they are SL / SLH

released. During the opening cycle in logics B and C, they


interrupt movement. They never operate during the closing
Fig. 15
cycle.
If the opening safety devices operate when the gate is
closed, they prevent the leaf opening movement. N.B.: Never put two
NB.: If no opening safety devices are connected, jumper PLUS 433 / 868
accessories (Plus 433 or 868,
connect inputs OP and -TX FSW (fig. 7). DIGIKEY Digicard, Digikey) in parallel
DIGICARD
on the same decoder, but
– - Negative for power supply to accessories use a decoder for every
accessory.
+ - 24 Vdc - Positive for power supply to accessories
Important: Accessories max. load is 500 mA. To calculate
absorption values, refer to the instructions for individual
accessories. 452 MPS

-TX FSW - Negative for power supply to photocell transmitters.


If you use this terminal for connecting the negative for
supplying power to the photocell transmitters, you may,
if necessary, also use the FAIL SAFE function (see
programming of microswitch DS2 - SW3).
If this function is enabled, the equipment checks Fig. 16
operation of the photocells before every opening or
closing cycle.
4.5. Terminal board J5 - Indicator-light and Electric lock (fig.2)
W.L. - Power supply to indicator-light
Connect a 24 Vdc - 3 W max. indicator-light, if necessary,
between this terminal and the +24V supply. To avoid
compromising correct operation of the system, do not RP 433 DS / SL
RP 868 DS / SLH
exceed the indicated power.
452 MPS

Fig. 17

14
ENGLISH

5. MICROSWITCH PROGRAMMING

LEAF 1 FORCE SW1 SW2 SW3 LEAF 2 FORCE SW4 SW5 SW6

1 (MIN) ON ON ON 1 (MIN) ON ON ON
2 OFF ON ON 2 OFF ON ON
OPENING LEAF DELAY (s) SW1
3 ON OFF ON 3 ON OFF ON
4 OFF OFF ON 4 OFF OFF ON
2 ON
5 ON ON OFF 5 ON ON OFF
6 6 0 OFF
OFF ON OFF OFF ON OFF
7 ON OFF OFF 7 ON OFF OFF
8 (MAX) OFF OFF OFF 8 (MAX) OFF OFF OFF
CLOSING PHOTOCELL LOGIC SW2

REVERSES ON RELEASE ON
REVERSES IMMEDIATELY OFF

1 2 3 4 5 6 7 8 9 10 11 12

LOGIC PAUSE (s) SW7 SW8 SW9 SW10


1 2 3 4
E / ON ON ON ON
EP / OFF ON ON ON
B / ON OFF ON ON
FAIL SAFE SW3
C / OFF OFF ON ON
A 0 ON ON OFF ON CLOSING LEAF YES ON
A 10 OFF ON OFF ON DELAY (s) SW11 SW12
NO OFF
A 20 ON OFF OFF ON
20 ON ON
A 30 OFF OFF OFF ON
10 OFF ON
A 60 ON ON ON OFF REVERSING STROKE
5 ON OFF SW4
A 120 OFF ON ON OFF + OVER-PUSHING STROKE
0 OFF OFF
S 0 ON OFF ON OFF YES ON
S 10 OFF OFF ON OFF
NO OFF
S 20 ON ON OFF OFF
S 30 OFF ON OFF OFF
S 60 ON OFF OFF OFF
S 120 OFF OFF OFF OFF

DS1 DS2
Fig. 18a Fig. 18b

The equipment is endowed with two groups of microswitches - 5.2. MICROSWITCHES DS2 (fig. 18b)
DS1 (fig. 18a) and DS2 (fig.18b) - which make it possible to program
Opening leaf delay
the gate operation parameters.
Programming of microswitch SW1 enables delay of the opening
5.1. MICROSWITCHES DS1 fig. 18a) start of leaf 2 with respect to leaf 1, in order to avoid the leaves
obstructing each other during the initial stage of movement.
Leaf l and 2 force
By using microswitches SW1, SW2 and SW3, the force (and thus Closing photocells logic
anti-crushing safety) of the operator connected to leaf 1 can be By using microswitch SW2, you can select the type of behaviour
programmed. The same operation has to be repeated on the of the automated system if the photocells protecting the gate
motor connected to leaf 2, by using microswitches SW4, SW5 and closing movement are engaged. You can obtain either immediate
SW6. reversing of the leaves or a stop followed by reversing when the
photocells are disengaged.
N.B. As concerns the hydraulic operators, select maximum
force (level 8) on the equipment and adjust thrust with Fail safe
the operator by-pass valves. Programming the microswitch SW3 makes it possible to activate
or de-activate the photocells control test. When Fail safe is active,
Function logic the equipment checks the photocells before every opening or
The automated system's function logic can be selected with closing movement.
microswitches SW7, SW8, SW9 and SW10. By selecting an automatic
Reversing stroke + over-pushing stroke
logic (A, S), the combination of microswitches enables selection
By using the microswitch SW4, you can activate the "reversing
of pause time too (waiting time, in opening position, before
stroke" and the "over-pushing stroke". The "reversing stroke" pushes
automatic re-closing).
the leaves to close for a few moments before opening the gate,
The available logics - their operation is described in tables 3/a-
thus facilitating release of the electric lock. The "over-pushing
b-c-d-e-f, are as follows: A - S (Automatic), E - EP - B (Semi-
stroke" commands a closing thrust at full force when the gate has
automatic), C (Dead-man).
already reached its stop limit, thus facilitating the locking of the
Closing leaf delay electric lock.
Programming of microswitches SW11 and SW12 enables delay of
the closing start of leaf 1 with respect to leaf 2, in order to avoid
the leaves overlapping during movement, and thus increase the
safety of the system.

15
ENGLISH

6. START-UP 6.4. PRE-FLASHING


6.1. LED CHECK If you wish to increase the equipment's safety level, you can
activate the pre-flashing function which enables the flashing
The table below shows the status of the LEDs in relation to to the
lamp to go on 5 seconds before the leaf starts to move.
status of the inputs.
Pre-flashing activation procedure:
Note the following: LED LIGHTED = closed contact
LED OFF = open contact 1 - check if the gate is closed
Check the state of the LEDs as per Table. 2 - open and keep open the Stop contact
Operation of the status signalling LEDs 3 - check if the DL10 LED is OFF (if lighted, pre-flashing is
already active)
LEDs LIGHTED OFF 4 - briefly press the F push-button and check if the DL10 LED
OP_A Command activated Command inactive lights up.
OP_B Command activated Command inactive 5 - close the Stop contact (DL10 goes OFF).
STOP Command inactive Command activated
FSWCL Safety devices disengaged Safety devices engaged Procedure for disabling the function:
FSWOP Safety devices disengaged Safety devices engaged 1 - check if the gate is closed
NB.: The status of the LEDs while the gate is at rest are shown in 2 - open and keep open the Stop contact
bold. 3 - check if the DL10 LED is lighted (if OFF, pre-flashing is
Furthermore, the DL10 LED is on the board and functions as already disabled)
detailed in the following table: 4 - briefly press the F push-button and check if the DL10 LED
DL10 is OFF.
5 - close the Stop contact
Gate closed at rest: Gate moving or on Time learning:
OFF pause: flashes rapidly
like indicator-light 7. AUTOMATED SYSTEM TEST
When you have finished programming, check if the system is
operating correctly.
6.2. ROTATION DIRECTION AND FORCE CHECK Most important of all, check if the force is adequately adjusted
1) Program the microswitches of the 452 MPS control board and if the safety devices are operating correctly.
according to need, as shown in Chapter 5.
2) Cut power to the electronic control equipment.
3) Release the operators and manually move the gate to the
mid-point of the opening angle.
4) Re-lock the operators.
5) Restore power.
6) Send and opening command on the OPEN A input (fig.2)
and check if the gate leaves are being commanded to
open.
N.B.:If the first OPEN A pulse commands a closing, cut power and
change over the phases of the electric motor (brown and
black wires) on the 452 MPS terminal board.
7) Check power setting of the motors and, if necessary, modify
it (see Chapter 5.1).
8) Stop leaf movement with a STOP command.
9) Release the operators, close the leaves and re-lock the
operators.
6.3. LEARNING OF OPERATING TIME
WARNING: during the learning procedure, the safety devices are
disabled! Therefore any transit must be avoided in the leaf
movement area when this operation is carried out.
Opening/closing time is established by a learning procedure.
- LEARNING PROCEDURE:
Check if the leaves are closed, and then press F push-button for
one second: DL10 LED begins flashing and the leaves begin the
opening movement.
Wait for the leaf to reach the opening stop limit and then supply
an OPEN A pulse (with the radio control or with the key controlled
push-button) to stop the movement: the leaves stop and the
DL10 LED stops flashing.
The procedure has ended and the gate is ready to operate.

16
Table 3/a
LOGIC "A" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.
CLOSED Opens leaves and closes them Opens the free leaf and closes No effect (OPEN disabled) No effect No effect (OPEN disabled) OFF
after pause time (1) after pause time (1)
OPEN on PAUSE Reloads pause time (1) Reloads pause time (1) No effect Freezes pause until release (2) (OPEN disabled) lighted
Stops operation
AT CLOSING Re-opens the leaves immediately (1) Re-opens the leaf immediately (1) No effect (saves OPEN) see paragraph 5.2. Locks and, on release, reverses at opening flashing

AT OPENING No effect (1) Reverses at closing No effect Locks and, on release, continues opening lighted

LOCKED Closes the leaf/leaves No effect (OPEN disabled) No effect No effect (OPEN disabled) lighted

Table 3/b
LOGIC "S" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.
CLOSED Opens leaves and closes them Opens the free leaf and
No effect (OPEN disabled) No effect No effect (OPEN disabled) OFF
after pause time closes after pause time
OPEN on PAUSE Re-closes the leaves immediately Re-closes the leaf immediately No effect Closes after 5" (OPEN disabled) lighted
Stops operation

17
AT CLOSING Re-opens the leaves immediately Re-opens the leaf immediately No effect (saves OPEN) see paragraph 5.2. Locks and, on release, reverses at opening flashing

AT OPENING Re-closes the leaves immediately Re-closes the leaf immediately Reverses at closing No effect Locks and, on release, continues opening lighted
LOCKED Closes the leaf/leaves No effect (OPEN disabled) No effect No effect (OPEN disabled) lighted

Table 3/c
LOGIC "E" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.

CLOSED Opens the leaves Opens the free leaf No effect (OPEN disabled) No effect No effect (OPEN disabled) OFF

OPEN Re-closes the leaves immediately Re-closes the leaf immediately No effect No effect (OPEN disabled) lighted
Stops operation
AT CLOSING Re-opens the leaves immediately Re-opens the leaf immediately (1) No effect (saves OPEN) see paragraph 5.2. Locks and, on release, reverses at opening flashing

AT OPENING Stops operation Reverses at closing No effect Locks and, on release, continues opening lighted
Closes the leaf/leaves No effect (OPEN disabled) No effect No effect (OPEN disabled) lighted
LOCKED (with CLOSING SAFETY DEVICES active, opens at 2nd pulse)
ENGLISH
Table 3/d
LOGIC "EP" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.
ENGLISH

CLOSED Opens the leaves Opens the free leaf No effect (OPEN disabled) No effect No effect (OPEN disabled) OFF

OPEN Re-closes the leaf/leaves immediately No effect (OPEN disabled) No effect (OPEN disabled) lighted
Stops operation
AT CLOSING Stops operation No effect (saves OPEN) see paragraph 5.2. Locks and, on release, reverses at opening flashing

AT OPENING Stops operation Reverses at closing No effect Locks and, on release, continues opening lighted

Restarts moving in reverse direction No effect


LOCKED (always closes after a Stop )
No effect (OPEN disabled) No effect (if it must open, it disables OPEN) No effect (OPEN disabled) lighted
(if it must close, it disables OPEN)

Table 3/e
LOGIC "B" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.
No effect No effect No effect No effect OFF
CLOSED Opens the leaf or leaves No effect (OPEN-A disabled) (OPEN-A disabled) (OPEN-A disabled)
(OPEN-B disabled)

No effect No effect No effect No effect


OPEN No effect Closes the leaves or leaf (OPEN-A disabled) (OPEN-B disabled) lighted
(OPEN-B disabled) (OPEN-B disabled)
Stops operation Stops operation
AT CLOSING Reverses at opening No effect No effect flashing
Stops operation (OPEN-B disabled) (OPEN-A/B disabled)

18
No effect Stops operation
AT OPENING No effect No effect No effect lighted
(OPEN-A disabled) (OPEN-A/B disabled)
No effect No effect No effect (OPEN-B disabled) No effect lighted
LOCKED Opens the leaf or leaves Closes the leaves or leaf
(OPEN-A/B disabled) (OPEN-A disabled) (OPEN-A/B disabled)

Table 3/f
LOGIC "C" COMMANDS ALWAYS PRESSED PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP/CLOS. SAFETY DEVICE W.L.
No effect No effect No effect No effect OFF
CLOSED Opens the leaf or leaves No effect
(OPEN-A disabled) (OPEN-A disabled) (OPEN-B disabled) (OPEN-A disabled)

No effect No effect No effect No effect


OPEN No effect Closes the leaves or leaf (OPEN-A disabled) (OPEN-B disabled) lighted
(OPEN-B disabled) (OPEN-B disabled)
Stops operation Stops operation
AT CLOSING Stops operation No effect flashing
Stops operation (OPEN-B disabled) (OPEN-A/B disabled)
Stops operation Stops operation
AT OPENING Stops operation No effect lighted
(OPEN-A disabled) (OPEN-A/B disabled)

(1) If maintained, it prolongs the pause until disabled by the command (timer function)
(2) If remaining pause time is shorter than 5 sec., when safety devices are released, it closes after 5 sec.
NB.: Effects on other active pulse inputs in brackets.

Вам также может понравиться