7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

elecmont27 / Folder / 7SJ622 V4.9 Var

MLFB: 7SJ6225**B901FE2
Parameter-set version: V04.93.01
Device path: C:\Siemens\DIGSI4\D4PROJ\elecmo_1\P7DI\GV\ST\00000002
Author:
Creation date: 05.04.19 08:21:57
Last modified: 07.04.19 00:44:51
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Settings - Masking I/O (Configuration Matrix) - elecmont27 / Folder / 7SJ622 V4.9 Var/7SJ622 ................................... 2
1.1 Matrix - printout ............................................................................................................................................................... 2
1.1.1 Device ............................................................................................................................................................................. 2
1.1.2 Power System Data 1 ..................................................................................................................................................... 4
1.1.3 Oscillographic Fault Records .......................................................................................................................................... 4
1.1.4 Power System Data 2 ..................................................................................................................................................... 6
1.1.5 DMT / IDMT Phase/Earth Overcurrent ............................................................................................................................ 6
1.1.6 Over / Under Voltage ...................................................................................................................................................... 7
1.1.7 Unbalance Load (Negative Sequence) ........................................................................................................................... 8
1.1.8 Frequency Protection ...................................................................................................................................................... 8
1.1.9 QV-Protection .................................................................................................................................................................. 9
1.1.10 Measurement Supervision .............................................................................................................................................. 9
1.1.11 Fault Locator ................................................................................................................................................................. 10
1.1.12 Breaker Failure .............................................................................................................................................................. 10
1.1.13 Control Authorization ..................................................................................................................................................... 11
1.1.14 Control Device ............................................................................................................................................................... 11
1.1.15 Process Data ................................................................................................................................................................. 11
2 Measurement ................................................................................................................................................................ 12
2.0.1 Set Points (Measured Values) ...................................................................................................................................... 12
3 Energy ........................................................................................................................................................................... 12
3.0.1 Statistics ........................................................................................................................................................................ 12
3.0.2 Set Points (Statistic) ...................................................................................................................................................... 12
3.0.3 Protocol ......................................................................................................................................................................... 12
3.0.4 Threshold-Switch .......................................................................................................................................................... 12
3.0.5 Flx 01 ............................................................................................................................................................................ 13

Page 1 of 13
7SJ622 V4_9 Var_prn
Settings - Masking I/O (Configuration Matrix) - elecmont27 / Folder / 7SJ622 V4.9 Var/7SJ622
SIMATIC Matrix - short view 07.04.19 00:46:30

Settings - Masking I/O (Configuration Matrix) - elecmont27 / Folder / 7SJ622 V4.9 Var/7SJ622
1

1.1 Matrix - printout

Information: Indications only


Filter: No filter

1.1.1 Device

Device
No. D L T BI F C BO LEDs O S T C

00003 >Time Synch >Synchronize Internal Real Time Clock SP_Ev


00005 >Reset LED >Reset LED SP H2
>Light on >Back Light on SP H3 IO
00051 Device OK Device is Operational and Protecting OUT IO
00052 ProtActive At Least 1 Protection Funct. is Active IntSP IO
00055 Reset Device Reset Device OUT I
00056 Initial Start Initial Start of Device OUT I
Reset LED Reset LED IntSP I
00067 Resume Resume OUT I
00068 Clock SyncError Clock Synchronization Error OUT IO
00069 DayLightSavTime Daylight Saving Time OUT IO
00110 Event Lost Event lost OUT_Ev I
00113 Flag Lost Flag Lost OUT I
00125 Chatter ON Chatter ON OUT IO
00140 Error Sum Alarm Error with a summary alarm OUT IO
00160 Alarm Sum Event Alarm Summary Event OUT IO
00144 Error 5V Error 5V OUT IO
00145 Error 0V Error 0V OUT IO
00146 Error -5V Error -5V OUT IO
00147 Error PwrSupply Error Power Supply OUT IO
00177 Fail Battery Failure: Battery empty OUT IO
00070 Settings Calc. Setting calculation is running OUT IO
00071 Settings Check Settings Check OUT
00072 Level-2 change Level-2 change OUT IO
00183 Error Board 1 Error Board 1 OUT IO
00184 Error Board 2 Error Board 2 OUT IO
00185 Error Board 3 Error Board 3 OUT IO
00186 Error Board 4 Error Board 4 OUT IO
00187 Error Board 5 Error Board 5 OUT IO
00188 Error Board 6 Error Board 6 OUT IO
00189 Error Board 7 Error Board 7 OUT IO

Page 2 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

Device(2)
CM

Page 3 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

Device(3)
No. D L T BI F C BO LEDs O S T C

DataStop Stop data transmission IntSP IO


00016 >DataStop >Stop data transmission SP X
Test mode Test mode IntSP IO
00015 >Test mode >Test mode SP
FdrEARTHED Feeder EARTHED IntSP X
Brk OPENED Breaker OPENED IntSP X
HWTestMod Hardware Test Mode IntSP IO
SynchClock Clock Synchronization IntSP_Ev X
00193 Alarm NO calibr Alarm: NO calibration data available OUT IO
17565 >Blk.offset s. >Blocking of the offset supervision SP IO
00191 Error Offset Error: Offset OUT IO
00320 Warn Mem. Data Warn: Limit of Memory Data exceeded OUT IO
00321 Warn Mem. Para. Warn: Limit of Memory Parameter exceeded OUT IO
00322 Warn Mem. Oper. Warn: Limit of Memory Operation exceeded OUT IO
00323 Warn Mem. New Warn: Limit of Memory New exceeded OUT IO
Distur.CFC Disturbance CFC OUT IO
17566 Dist.CFC Src Disturbance CFC Source VI IO
00545 PU Time Time from Pickup to drop out VI IO
00546 TRIP Time Time from Pickup to TRIP VI IO
236.2127.01 BLK. Flex.Fct. BLOCK Flexible Function IntSP IO

1.1.2 Power System Data 1

Power System Data 1


No. D L T BI F C BO LEDs O S T C CM

05145 >Reverse Rot. >Reverse Phase Rotation SP IO


05147 Rotation L1L2L3 Phase Rotation L1L2L3 OUT IO
05148 Rotation L1L3L2 Phase Rotation L1L3L2 OUT IO

1.1.3 Oscillographic Fault Records

Oscillographic Fault Records


No. D L T BI F C BO LEDs O S T C CM

00004 >Trig.Wave.Cap. >Trigger Waveform Capture SP X


00203 Wave. deleted Waveform data deleted OUT_Ev I
FltRecSta Fault Recording Start IntSP X IO
30053 Fault rec. run. Fault recording is running OUT

Page 4 of 13
7SJ622 V4_9 Var_prn
Power System Data 2
SIMATIC Matrix - short view 07.04.19 00:46:30

Device(4)
CM

Page 5 of 13
7SJ622 V4_9 Var_prn
Power System Data 2
SIMATIC Matrix - short view 07.04.19 00:46:30

1.1.4 Power System Data 2

Power System Data 2


No. D L T BI F C BO LEDs O S T C CM

00356 >Manual Close >Manual close signal SP


02720 >Enable ANSI#-2 >Enable 50/67-(N)-2 (override 79 blk) SP IO
00533 IL1 = Primary fault current IL1 VI IO
00534 IL2 = Primary fault current IL2 VI IO
00535 IL3 = Primary fault current IL3 VI IO
00501 Relay PICKUP Relay PICKUP OUT I
00511 Relay TRIP Relay GENERAL TRIP command OUT U3 I X
00561 Man.Clos.Detect Manual close signal detected OUT IO
04601 >Brk Aux NO >Breaker contact (OPEN, if bkr is open) SP H5 IO
04602 >Brk Aux NC >Breaker contact(OPEN, if bkr is closed) SP H4 IO
00126 ProtON/OFF Protection ON/OFF (via system port) IntSP IO

1.1.5 DMT / IDMT Phase/Earth Overcurrent

DMT / IDMT Phase/Earth Overcurrent


No. D L T BI F C BO LEDs O S T C CM

01761 Overcurrent PU Time Overcurrent picked up OUT IO


01791 OvercurrentTRIP Time Overcurrent TRIP OUT U3 I
01704 >BLK Phase O/C >BLOCK Phase time overcurrent SP
01718 >BLOCK I>>> >BLOCK I>>> SP
01721 >BLOCK I>> >BLOCK I>> SP H1
01722 >BLOCK I> >BLOCK I> SP
01723 >BLOCK Ip >BLOCK Ip SP
01751 O/C Phase OFF Time Overcurrent Phase is OFF OUT IO
01752 O/C Phase BLK Time Overcurrent Phase is BLOCKED OUT IO IO
01753 O/C Phase ACT Time Overcurrent Phase is ACTIVE OUT IO
01762 O/C Ph L1 PU Time Overcurrent Phase L1 picked up OUT L1 IO
01763 O/C Ph L2 PU Time Overcurrent Phase L2 picked up OUT L2 IO
01764 O/C Ph L3 PU Time Overcurrent Phase L3 picked up OUT L3 IO
01767 I>>> picked up I>>> picked up OUT IO
01769 I>>> TRIP I>>> TRIP OUT I
01800 I>> picked up I>> picked up OUT IO
01805 I>> TRIP I>> TRIP OUT I
01810 I> picked up I> picked up OUT IO
01815 I> TRIP I> TRIP OUT U3 I
01820 Ip picked up Ip picked up OUT IO
01825 Ip TRIP Ip TRIP OUT U3 I
01787 I>>> Time Out I>>> Time Out OUT
01804 I>> Time Out I>> Time Out OUT
01814 I> Time Out I> Time Out OUT

Page 6 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

DMT / IDMT Phase/Earth Overcurrent(2)


No. D L T BI F C BO LEDs O S T C CM

01824 Ip Time Out Ip Time Out OUT


10034 I>>> BLOCKED I>>> BLOCKED OUT IO IO
01852 I>> BLOCKED I>> BLOCKED OUT IO IO
01851 I> BLOCKED I> BLOCKED OUT IO IO
01855 Ip BLOCKED Ip BLOCKED OUT IO IO
01714 >BLK Earth O/C >BLOCK Earth time overcurrent SP
01719 >BLOCK IE>>> >BLOCK IE>>> SP
01724 >BLOCK IE>> >BLOCK IE>> SP H1
01725 >BLOCK IE> >BLOCK IE> SP
01726 >BLOCK IEp >BLOCK IEp SP
01756 O/C Earth OFF Time Overcurrent Earth is OFF OUT IO
01757 O/C Earth BLK Time Overcurrent Earth is BLOCKED OUT IO IO
01758 O/C Earth ACT Time Overcurrent Earth is ACTIVE OUT IO
01765 O/C Earth PU Time Overcurrent Earth picked up OUT IO
01768 IE>>> picked up IE>>> picked up OUT IO
01770 IE>>> TRIP IE>>> TRIP OUT I
01831 IE>> picked up IE>> picked up OUT IO
01833 IE>> TRIP IE>> TRIP OUT I
01834 IE> picked up IE> picked up OUT IO
01836 IE> TRIP IE> TRIP OUT U3 L4 I
01837 IEp picked up IEp picked up OUT IO
01839 IEp TRIP IEp TRIP OUT I
01788 IE>>> Time Out IE>>> Time Out OUT
01832 IE>> Time Out IE>> Time Out OUT
01835 IE> Time Out IE> Time Out OUT
01838 IEp TimeOut IEp Time Out OUT U3 L4
10035 IE>>> BLOCKED IE>>> BLOCKED OUT IO IO
01854 IE>> BLOCKED IE>> BLOCKED OUT IO IO
01853 IE> BLOCKED IE> BLOCKED OUT IO IO
01856 IEp BLOCKED IEp BLOCKED OUT IO IO

1.1.6 Over / Under Voltage

Over / Under Voltage


No. D L T BI F C BO LEDs O S T C CM

06503 >BLK Under Volt >BLOCK undervoltage protection SP


06505 >I SUPRVSN U< >Under volt-Switch current superv. ON SP U3 IO
06506 >BLOCK U< >BLOCK Undervoltage protection U< SP U3 IO
06508 >BLOCK U<< >BLOCK Undervoltage protection U<< SP U3 IO
06530 Under Volt. OFF Undervoltage protection switched OFF OUT IO
06531 Under Volt. BLK Undervoltage protection is BLOCKED OUT IO IO
06532 Under Volt. ACT Undervoltage protection is ACTIVE OUT IO

Page 7 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

Over / Under Voltage(2)


No. D L T BI F C BO LEDs O S T C CM

06533 U< picked up U< Undervoltage picked up OUT IO


06534 U< PU CS U< Undervoltage PICKUP w/curr. superv OUT IO
06537 U<< picked up U<< Undervoltage picked up OUT IO
06538 U<< PU CS U<< Undervoltage PICKUP w/curr. superv OUT IO
06539 U< TRIP U< Undervoltage TRIP OUT U3 I
06540 U<< TRIP U<< Undervoltage TRIP OUT U3 I
06513 >BLOCK U>/U>> >BLOCK Overvoltage protection U>/U>> SP
06565 U> OFF U>-Overvoltage protection switched OFF OUT IO
06566 U> BLOCKED U>-Overvoltage protection is BLOCKED OUT IO IO
06567 U> ACTIVE U>-Overvoltage protection is ACTIVE OUT IO
06568 U> picked up U> picked up OUT IO
06570 U> TRIP U> TRIP OUT L1 I
06571 U>> picked up U>> picked up OUT IO
06573 U>> TRIP U>> TRIP OUT I
234.2100.01 U<, U> blk U<, U> blocked via operation IntSP IO X

1.1.7 Unbalance Load (Negative Sequence)

Unbalance Load (Negative Sequence)


No. D L T BI F C BO LEDs O S T C CM

05143 >BLOCK I2 >BLOCK I2 (Unbalance Load) SP


05151 I2 OFF I2 switched OFF OUT IO
05152 I2 BLOCKED I2 is BLOCKED OUT IO IO
05153 I2 ACTIVE I2 is ACTIVE OUT IO
05159 I2>> picked up I2>> picked up OUT IO
05165 I2> picked up I2> picked up OUT IO
05166 I2p picked up I2p picked up OUT IO
05170 I2 TRIP I2 TRIP OUT U3 L5 I
05171 I2 Dsk pickedup I2 Disk emulation picked up OUT

1.1.8 Frequency Protection

Frequency Protection
No. D L T BI F C BO LEDs O S T C CM

05203 >BLOCK Freq. >BLOCK Frequency Protection SP IO


05206 >BLOCK F1 >BLOCK F1 SP IO
05207 >BLOCK F2 >BLOCK F2 SP IO
05208 >BLOCK F3 >BLOCK F3 SP IO
05209 >BLOCK F4 >BLOCK F4 SP IO
05211 Freq. OFF Frequency Protection is OFF OUT IO
05212 Freq. BLOCKED Frequency Protection is BLOCKED OUT IO IO

Page 8 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

Frequency Protection(2)
No. D L T BI F C BO LEDs O S T C CM

05213 Freq. ACTIVE Frequency Protection is ACTIVE OUT IO


05214 Freq UnderV Blk Frequency Protection Under Voltage Blk OUT IO IO
05232 F1 picked up F1 picked up OUT IO
05233 F2 picked up F2 picked up OUT IO
05234 F3 picked up F3 picked up OUT IO
05235 F4 picked up F4 picked up OUT IO
05236 F1 TRIP F1 TRIP OUT U3 L7 I
05237 F2 TRIP F2 TRIP OUT U3 L7 I
05238 F3 TRIP F3 TRIP OUT U3 L7 I
05239 F4 TRIP F4 TRIP OUT U3 L7 I

1.1.9 QV-Protection

QV-Protection
No. D L T BI F C BO LEDs O S T C CM

06401 >QV Block >QV-Protection Blocked SP


06411 QV OFF QV-Protection off OUT IO
06412 QV block QV-Protection blocked OUT IO IO
06413 QV ACT QV-Protection activ OUT IO
06421 QV Gen TRIP QV-Protection Gen TRIP OUT IO
06422 QV Grid TRIP QV-Protection Grid TRIP OUT IO
06423 QV PICKUP QV-Protection PICKUP OUT IO
06424 Reclosure rel. Reclosure release OUT IO
06425 QV PU blk.b.Inr QV pickup blocked by Inrush OUT IO IO

1.1.10 Measurement Supervision

Measurement Supervision
No. D L T BI F C BO LEDs O S T C CM

00253 VT brk. wire Failure VT circuit: broken wire OUT U4 U6 IO X


00255 Fail VT circuit Failure VT circuit OUT IO X
00256 VT b.w. 1 pole Failure VT circuit: 1 pole broken wire OUT IO X
00257 VT b.w. 2 pole Failure VT circuit: 2 pole broken wire OUT IO X
00258 VT b.w. 3 pole Failure VT circuit: 3 pole broken wire OUT IO X
00169 VT FuseFail>10s VT Fuse Failure (alarm >10s) OUT IO
00170 VT FuseFail VT Fuse Failure (alarm instantaneous) OUT IO
00162 Failure Sum I Failure: Current Summation OUT U4 U6 IO
00163 Fail I balance Failure: Current Balance OUT U4 U6 IO
00167 Fail U balance Failure: Voltage Balance OUT U4 U6 IO
00161 Fail I Superv. Failure: General Current Supervision OUT IO
00171 Fail Ph. Seq. Failure: Phase Sequence OUT IO

Page 9 of 13
7SJ622 V4_9 Var_prn

SIMATIC Matrix - short view 07.04.19 00:46:30

Measurement Supervision(2)
No. D L T BI F C BO LEDs O S T C CM

00176 Fail Ph. Seq. U Failure: Phase Sequence Voltage OUT U4 U6 IO


00175 Fail Ph. Seq. I Failure: Phase Sequence Current OUT U4 U6 IO
00197 MeasSup OFF Measurement Supervision is switched OFF OUT IO
06509 >FAIL:FEEDER VT >Failure: Feeder VT SP IO
06510 >FAIL: BUS VT >Failure: Busbar VT SP IO

1.1.11 Fault Locator

Fault Locator
No. D L T BI F C BO LEDs O S T C CM

01106 >Start Flt. Loc >Start Fault Locator SP I


01114 Rpri = Flt Locator: primary RESISTANCE VI IO
01115 Xpri = Flt Locator: primary REACTANCE VI IO
01117 Rsec = Flt Locator: secondary RESISTANCE VI IO
01118 Xsec = Flt Locator: secondary REACTANCE VI IO
01119 dist = Flt Locator: Distance to fault VI IO
01120 d[%] = Flt Locator: Distance [%] to fault VI IO
01123 FL Loop L1E Fault Locator Loop L1E OUT I
01124 FL Loop L2E Fault Locator Loop L2E OUT I
01125 FL Loop L3E Fault Locator Loop L3E OUT I
01126 FL Loop L1L2 Fault Locator Loop L1L2 OUT I
01127 FL Loop L2L3 Fault Locator Loop L2L3 OUT I
01128 FL Loop L3L1 Fault Locator Loop L3L1 OUT I
01132 Flt.Loc.invalid Fault location invalid OUT I

1.1.12 Breaker Failure

Breaker Failure
No. D L T BI F C BO LEDs O S T C CM

01403 >BLOCK BkrFail >BLOCK Breaker failure SP IO


01431 >BrkFail extSRC >Breaker failure initiated externally SP IO
01451 BkrFail OFF Breaker failure is switched OFF OUT IO
01452 BkrFail BLOCK Breaker failure is BLOCKED OUT IO IO
01453 BkrFail ACTIVE Breaker failure is ACTIVE OUT IO
01456 BkrFail int PU Breaker failure (internal) PICKUP OUT IO
01457 BkrFail ext PU Breaker failure (external) PICKUP OUT IO
01471 BrkFailure TRIP Breaker failure TRIP OUT I
01480 BkrFail intTRIP Breaker failure (internal) TRIP OUT I
01481 BkrFail extTRIP Breaker failure (external) TRIP OUT I
01494 BkrFail TRIP 2 Breaker failure TRIP 2 OUT I

Page 10 of 13
7SJ622 V4_9 Var_prn
Control Authorization
SIMATIC Matrix - short view 07.04.19 00:46:30

1.1.13 Control Authorization

Control Authorization
No. D L T BI F C BO LEDs O S T C CM

ModeREMOTE Controlmode REMOTE IntSP IO


Cntrl Auth Control Authority IntSP IO
ModeLOCAL Controlmode LOCAL IntSP IO

1.1.14 Control Device

Control Device
No. D L T BI F C BO LEDs O S T C CM

Breaker Breaker DP X4 IO X
Disc.Swit. Disconnect Switch DP IO X
EarthSwit Earth Switch DP IO X
Brk Open Interlocking: Breaker Open IntSP X
Brk Close Interlocking: Breaker Close IntSP X
Disc.Open Interlocking: Disconnect switch Open IntSP X
Disc.Close Interlocking: Disconnect switch Close IntSP X
E Sw Open Interlocking: Earth switch Open IntSP X
E Sw Cl. Interlocking: Earth switch Close IntSP X
UnlockDT Unlock data transmission via BI IntSP X
Q2 Op/Cl Q2 Open/Close DP IO
Q9 Op/Cl Q9 Open/Close DP IO
Fan ON/OFF Fan ON/OFF DP IO

1.1.15 Process Data

Process Data
No. D L T BI F C BO LEDs O S T C CM

>CB ready >CB ready Spring is charged SP X


>DoorClose >Door closed SP X
>Door open >Cabinet door open SP IO X
>CB wait >CB waiting for Spring charged SP IO X
>No Volt. >No Voltage (Fuse blown) SP IO X
>Err Mot U >Error Motor Voltage SP IO
>ErrCntrlU >Error Control Voltage SP IO
>SF6-Loss >SF6-Loss SP IO
>Err Meter >Error Meter SP IO
>Tx Temp. >Transformer Temperature SP IO
>Tx Danger >Transformer Danger SP IO

Page 11 of 13
7SJ622 V4_9 Var_prn
Measurement
SIMATIC Matrix - short view 07.04.19 00:46:30

2 Measurement

No information available
2.0.1 Set Points (Measured Values)

Set Points (Measured Values)


No. D L T BI F C BO LEDs O S T C CM

00284 SP. I< Set Point I< alarm OUT X IO


00285 SP. PF(55)alarm Set Point 55 Power factor alarm OUT X IO

3 Energy

No information available
3.0.1 Statistics

Statistics
No. D L T BI F C BO LEDs O S T C CM

01020 Op.Hours= Counter of operating hours VI


00409 >BLOCK Op Count >BLOCK Op Counter SP IO
01021 Sum L1 = Accumulation of interrupted current L1 VI
01022 Sum L2 = Accumulation of interrupted current L2 VI
01023 Sum L3 = Accumulation of interrupted current L3 VI

3.0.2 Set Points (Statistic)

Set Points (Statistic)


No. D L T BI F C BO LEDs O S T C CM

00272 SP. Op Hours> Set Point Operating Hours OUT IO

3.0.3 Protocol

Protocol
No. D L T BI F C BO LEDs O S T C CM

SysIntErr. Error Systeminterface IntSP IO X

3.0.4 Threshold-Switch

Threshold-Switch
No. D L T BI F C BO LEDs O S T C CM

ThreshVal1 Threshold Value 1 IntSP IO X

Page 12 of 13
7SJ622 V4_9 Var_prn
Flx 01
SIMATIC Matrix - short view 07.04.19 00:46:30

3.0.5 Flx 01

Flx 01
No. D L T BI F C BO LEDs O S T C CM

235.2110.01 >BLOCK Flx01 >BLOCK Flx01 SP IO IO


235.2111.01 >Flx01 instant. >Flx01 instant. SP IO IO
235.2113.01 >Flx01 BLK.TDly >Flx01 BLK.TDly SP IO IO
235.2114.01 >Flx01 BLK.TRIP >Flx01 BLK.TRIP SP IO IO
235.2118.01 Flx01 BLOCKED Flx01 BLOCKED OUT IO IO
235.2119.01 Flx01 OFF Flx01 OFF OUT IO
235.2120.01 Flx01 ACTIVE Flx01 ACTIVE OUT IO
235.2121.01 Flx01 picked up Flx01 picked up OUT IO IO
235.2125.01 Flx01 Time Out Flx01 Time Out OUT IO IO
235.2126.01 Flx01 TRIP Flx01 TRIP OUT IO I
235.2128.01 Flx01 inval.set Flx01 inval.set OUT IO IO

Page 13 of 13