MECHANICAL CALCULATION
STORAGE TANK 110 KL (T-04)
1. PURPOSE
This calculation will determine the Storage Tank data sheet parameters, and minimum thickness required.
2. DESIGN CRITERIA/INPUTS
2.1. INPUTS
Design Code : API 650 (Appendix A) Welded Oil Storage Tank
Nominal Capacity : - KL
Net Working Capacity (Capacity at HHLL) : 110 KL
Size
Inside Diameter : 4.8 m
Height : 6.3 m
Design Internal Pressure : ATM
Design Temperature : 40 o
C
Operating Pressure : ATM
Operating Temperature : AMB o
C
Fluid : B20
Specific Gravity : 0.850
Type of Roof : Cone Roof + Supported
Slope : 1:6
Min. Design Metal Temp. (MDMT) : 30 o
C
Insulation (If required.
Roof : - mm
Shell : - mm
Corrosion Allowance
Bottom : 3 mm
Shell : 3 mm
Roof : 1.60 mm
Radiography : Full
Post Weld Heat Treatment (PWHT) : No
Impact Test : No
2.2. MATERIAL :
Shell : SA 36 / SS 400
Roof : SA 36 / SS 400
Bottom : SA 36 / SS 400
Structurals : SA 36 / SS 400
Reinforcement Pad : SA 36 / SS 400
Nozzle
Pipe : SA 53 Gr. B
Plate : SA 36 / SS 400
Flange : SA 105
Gasket : Non asbestos Fiber joint sheet
External Bolt / Nut : SA 193 Gr. B7 / SA 194 GR. 2H
Internal pipe / plate : SA 106 Gr. B / SA 36
Anchor Bolt : SA 307 Gr. B
4. CALCULATION RESULT
4.1. Calculations were performed using AMETANK developed in house by PT. Intesco Global Internusa for thickness Shell, Roof, Annular and Bottom.
4.2. Calculation for structural using Staad Pro, developed in house by PT.Intesco Global Internusa, (If Required)
4.3. The result of the calculations are placed in subsequent pages.
SUMMARY OF CALCULATION
Calculation Requirement
Shell Course 1 : 6 mm 6 mm
Shell Course 2 : 5 mm 5 mm
Shell Course 3 : 5 mm 5 mm
Shell Course 4 : 5 mm 5 mm
Anchor Bolt
Diameter : 25 mm
Quantity : 6 ea
Bolt Circle Diameter : 2500 mm
Hydrostatic Test Pressure : Full of Water 0
Hydrostatic Test Pressure : Full of Water
ESTIMATED WEIGHT
Empty : 271,466 Kg
Operating : 8,771,688 Kg
Full Water : 10,271,727 Kg
5. CONCLUSION
5.1. Base on the calculation report, minimum requirement for the thickness each part (Shell, Roof, Bottom, Etc) shall be fulfilled.