Proposal/Calculation

Ref. No. : JZY-16-03-2019

Date : 26-Mar-19

Contractor / Client : Crimsign Graphics Pte Ltd

Contact Person : Mr Sashi

Contact No. : 9025 4021

Project Name : Integrated Totem Exit/CCTV Sign Post for MRT Stations

Anchors : HSL-3 Heavy Duty Anchor M12

Hilti Far East


Account Manager : Kelvin Tan

Technical Engineer : Juay Zhen Yu

Office : No. 20 Harbour Drive #06-06/08 PSA Vista Singapore 117612 Tel:(65)777 7887 Fax:(65)777 3057

Hilti Centres : 113 Jalan Besar Tel: 6377-0777, Blk 52 Ubi Ave 3 Frontier Bldg #01-43 Tel: 6547-5477
Crimsign Graphics Pte Ltd

Integrated Totem Exit/CCTV Sign Post for MRT Stations

1.0. Important Note

1.1. The Calculations shown are Proposals only and should be finally checked and
approved by the Architect or Engineer responsible for the Project.

1.2. PE Endorsement where necessary, to certify safe anchoring loading design at the
discretion and expenses of others.

1.3. Setting Procedure must be strictly adhered to FTM 2018.

1.4. Site mock-up can be arranged to verify loading if necessary.

1.5. Propose all openings to be filled up with HILTI Sealant and Firestop system
1.0 Data / Information (Drawing) [Provided]

Z
X
Y

2.0 Bracket Configuration

Concrete Grade G = 40 [Provided]

Total Weight of Tanking Weight = 86 kg [Provided]

Height of Centre of Gravity 1/2 x Pole Height = 1335 mm [Provided]


= 1.335 m

Shock Load Requirement γSEL = 12.5 * g [Provided]

2
Gravity g = 10.0 m/s [Assumed]

3.0 Design Criteria

1. Determine Shock Load Direction ( X-Y-Z)


2. Determine Shock Load and Self Weight
3. Design Criteria
4. Determine Shock Design Load (X-Y-Z)
5. Worst Reaction of Support (X-Y-Z)
6. Propose Hilti CD approved anchor bolt
4. Determine Reactions of Support (X-Y-Z)

4.1.1 Determine design load acting on the bracket, Fload(total) X-Direction

Design Load acting on bracket Fload(x) = Weight * γSEL * g


= 86 * 12.5 * 10.0
= 10750 N
= 10.75 kN

Mload(x) = Fload(x) * 1/2 x Pole Height


= 10.75 * 1.335
= 14.35 kNm

4.1.2 PROFIS Check Result for X-Direction (Design Overview And Load Analysis)

4.1.3 Determine Shock Design Load


Maximum Shear Load VSd = 1.792

Maximum Tensile Load NSd = 16.677 kN

R-load R (X) = √[Vsd2] + [Nsd2]


= 16.77300191
6.0 Propose Hilti CD approved anchor bolt

Allowable Shock Load Rclass = 17.0 kN

6.1 Check

Rclass = 17.0 kN > Rw = 16.77 kN OK