Вы находитесь на странице: 1из 71

STRUCTURAL DESIGN CALCULATIONS OF 132 KV SINGLE CIRCUIT TOWER

TYPE – C (15°-30°)

REPORT PREPARED FOR:

SANIMA HYDRO AND ENGINEERING (P.) LIMITED

NAME OF THE PROJECT:


MAI HYDROPOWER PROJECT 132 KV TRANSMISSION LINE

REPORT PREPARED BY:

M/S. ASTER PRIVATE LTD.,


INTERNATIONAL BUSINESS AND OPERATIONS

DESIGNED BY SREEDHAR TOWER TYPE C


CHECKED BY MANOHAR DATE 08-06-13
APPROVED BY MUTHUKRISHNAN REV. 01
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER PROJECT 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE Approved by Muthukrishnan
Rev 01

Table of Contents

1. DESIGN PARAMETERS 3

2. INDEX OF LOADINGS 5

3. SAG TENSION CALCULATIONS 7

4. LOAD CALCULATIONS 10

5. WIND LOAD ON TOWER BODY 16

6. DESIGN CALCULATIONS 29

7. LOAD TREE DRAWINGS 59

8. FOUNDATION FORCES: 64

9. LINE DIAGRAM 66

10. CLEARANCE DIAGRAM 71

2
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER PROJECT 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE Approved by Muthukrishnan
Rev 01

1. DESIGN PARAMETERS
1) GENERAL

VOLTAGE/CIRCUIT : 132kV (Single circuit)


TOWER CONFIGURATION : Vertical (Triangular shape of conductors arrangement)
NO. OF EARTHWIRE : One

2) SPAN DETAILS

NORMAL SPAN : 350m


WIND SPAN
NORMAL CONDITION : 350m
BROKENWIRE CONDITION : 210m
WEIGHT SPAN
NORMAL CONDITION Max/ Min : 1000 / 600 m
BROKENWIRE CONDITION Max/Min : -700/ -420 m

3) CONDUCTOR AND GROUNDWIRE PROPERTIES

CONDUCTOR TYPE : ASCR "Wolf"


OVERALL DIAMETER (cm) : 1.814
CROSS SECTIONAL AREA (sq.cm) : 1.9494
UNIT WEIGHT (kg/m) : 0.727
ULTIMATE TENSILE STRENGTH (kg) : 8809
COEF. OF THERMAL EXPANSION (/degC) : 0.00001843
MODULUS OF ELASTICITY (kg/sq.cm) : 850444

GROUNDWIRE TYPE : OPGW-36


OVERALL DIAMETER (cm) : 1.04
CROSS SECTIONAL AREA (sq.cm) : 0.68
UNIT WEIGHT (kg/m) : 0.485
ULTIMATE TENSILE STRENGTH (kg) : 8857
COEF. OF THERMAL EXPANSION (/degC) : 0.000013
MODULUS OF ELASTICITY (kg/sq.cm) : 1653000

3
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER PROJECT 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE Approved by Muthukrishnan
Rev 01

4) TOWER TYPE

TOWER : Angle Tower (Tension Tower)


DEVIATION ANGLE : 15-30 Deg
TYPE : “C”

5) ELECTRICAL CLEARENCE

MIN GROUND CLEARENCE : 7000 mm


SHEILD ANGLE : 30°
INSULATOR SWING (0 – 15 ) : 1500 mm
o

INSULATOR SWING (15 – 40o) : 1000 mm

6) TOWER DESIGN DETAILS

Legs/ Arm Redundant Peak


x - arms Diagonals tops members
members
Min. Thickness (mm) 6 4 4 4 6
KL/R 150 200 200 250 150

STEEL GRADE
Grade Yield (Mpa)
Mild Steel IS - 2062 250
High Tensile IS - 2062 350

BOLTS & NUTS


Dia. Grade
16 5.6

7) WIND LOAD DETAILS

Wind Pressure on conductor : 75 kg/sq.m


Wind Pressure on ground wire : 75 kg/sq.m
Wind Pressure on insulator : 75 kg/sq.m
Wind Pressure on tower : 207 kg/sq.m

4
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

2. INDEX OF LOADINGS
________________________________________________________________________________________
Sl. Title Code Nature Category
________________________________________________________________________________________
1 NC NC perm catn
2 SEGW & TC B SEGT perm catb
3 SEGW & MC B SEGM perm catb
4 SEGW & BC B SEGB perm catb
5 SETC & MC B SETM perm catb
6 SW s.w. perm deds
7 SETC & BC B SETB perm catb
8 DUMMY TRAN WIND (0 Deg.Wind) deft perm wins
9 SEMC & BC B SEMB perm catb
10 NC UP LIFT NC- perm catn
11 SEGW & TC B UP LIFT SGT- perm catb
12 SETC & MC B UP LIFT STM- perm catb
13 SANC SANC perm cats
14 SA GW B SAGW perm casb
15 SA TCB SATC perm casb
16 TRAN WIND ON tw01 (0 Deg. Wind) T001 perm wins
17 TRAN WIND ON tw02 (0 Deg. Wind) T002 perm wins
18 TRAN WIND ON tw03 (0 Deg. Wind) T003 perm wins
19 TRAN WIND ON tw04 (0 Deg. Wind) T004 perm wins
20 TRAN WIND ON tw05 (0 Deg. Wind) T005 perm wins
21 TRAN WIND ON tw06 (0 Deg. Wind) T006 perm wins
22 TRAN WIND ON tw07 (0 Deg. Wind) T007 perm wins
23 TRAN WIND ON tw08 (0 Deg. Wind) T008 perm wins
________________________________________________________________________________________

tw01 Tower combination of NT - 3m BE


tw02 Tower combination of NT - 3m BE + 0 m BE
tw03 Tower combination of NT - 3m BE + 3 m BE
tw04 Tower combination of NT - 3m BE + 12 m BE
tw05 Tower combination of NT - 3m BE + 3m LE
tw06 Tower combination of NT - 3m BE + 4.5m LE
tw07 Tower combination of NT - 3m BE + 6m LE
tw08 Tower combination of NT - 3m BE + 7.5m LE

5
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

SAG TENSION CALCULATIONS

6
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

3. SAG TENSION CALCULATIONS

DATA :-

Basic Span (m) : 350.00


Wind Pressure (kg/sq.m) : 75

CONDUCTOR DETAILS :-

Type : ASCR "Wolf"


Overall Diameter (cm) : 1.814
Cross Sectional Area (sq.cm) : 1.9494
Unit Weight (kg/m) : 0.727
Ultimate Tensile strength (kg) : 8809
Coef. of Thermal Expansion(/degC) : 0.00001843
Modulus of Elasticity (kg/sq.cm) : 850444
Increase in Vertical sag (%) : 0
Shape factor : 1
Gust factor : 1
Drag factor : 1

Basic Condition:-
Temperature (deg C) : 32.0000
Wind factor : .0000
Ice thickness (cm) : .0000
Factor of Safety : 6.2710

SAG_TENSION_FOS COMPUTATIONS :
________________________________________________________________________________________________________________

Sl. Environmental Wind Ice Vertical Tension FOS REMARKS


No. Temperature (deg.C) Factor Thickness (cm) Sag (m) (Kg)
________________________________________________________________________________________________________________

1. 32.00 .0000 .00 7.963 1404.78 6.271


2. .00 1.0000 .00 4.052 2763.09 3.188
3. 32.00 1.0000 .00 4.542 2468.44 3.569
4. 80.00 .0000 .00 9.837 1139.98 7.727
________________________________________________________________________________________________________________

Max Vertical Sag (m) : 9.837


Max Tension (kg) : 2763.09

7
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

DATA :-

Basic Span (m) : 350.00


Wind Pressure (kg/sq.m) : 75

SHIELD WIRE DETAILS :-

Type : OPGW-36
Overall Diameter (cm) : 1.04
Cross Sectional Area (sq.cm) : 0.68
Unit Weight (kg/m) : 0.485
Ultimate Tensile strength (kg) : 8857
Coef. of Thermal Expansion(/degC) : 0.000013
Modulus of Elasticity (kg/sq.cm) : 1653000
Increase in Vertical sag (%) : 0
Shape factor : 1
Gust factor : 1
Drag factor : 1

Basic Condition:-
Temperature (deg C) : 32.0000
Wind factor : .0000
Ice thickness (cm) : .0000
Factor of Safety : 7.0000

SAG_TENSION_FOS COMPUTATIONS :
________________________________________________________________________________________________________________

Sl. Environmental Wind Ice Vertical Tension FOS REMARKS


No. Temperature (deg.C) Factor Thickness (cm) Sag (m) (Kg)
________________________________________________________________________________________________________________

1. 32.00 .0000 .00 5.885 1265.36 7.000 % GW/CON sag = 73.90


2. .00 1.0000 .00 3.639 2048.37 4.324 % GW/CON sag = 89.81
3. 32.00 1.0000 .00 4.036 1848.20 4.792 % GW/CON sag = 88.87
4. 50.00 .0000 .00 6.414 1161.54 7.625 % GW/CON sag = 65.20
________________________________________________________________________________________________________________

Max Vertical Sag (m) : 6.414


Max Tension (kg) : 2048.37

8
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

CONDUCTOR AND GROUND WIRE LOAD CALCULATIONS

9
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

4. LOAD CALCULATIONS
DESIGN DATA :
DESCRIPTION UNITS NC BWC SAFETY
SPANS :

WIND SPAN m 350 210 0


WEIGHT SPAN ( MAX ) m 1000 600
WEIGHT SPAN ( MIN ) m -700 -420
WIND PRESSURES :

WIND PRESSURE ON CONDUCTOR Kg/m^2 75 75 0


WIND PRESSURE ON EARTH WIRE Kg/m^2 75 75 0
WIND PRESSURE ON INSULATOR Kg/m^2 75 75 0

COND.,EW & INSULATORS :

DIA.OF.CONDUCTOR m 0.01814 0.01814


DIA.OF.EARTH WIRE m 0.0104 0.0104
DIA.OF.INSULATOR m 0.254 0.254
LENGTH OF INSULATOR m 2.050 2.050
NO OF SUB CONDUCTORS 1 1
NO OF INSULATOR SETS 2 2
WEIGHT OF CONDUCTOR Kg/m 0.727 0.727
WEIGHT OF INSULATOR PER SET Kg 150 150
WEIGHT OF EARTH WIRE Kg/m 0.485 0.485

TENSION OF WIRES :

TENSION OF CONDUCTOR Kg 2763 2763 1405


TENSION OF EARTH WIRE Kg 2048 2048 1265
TENSION DIFFERENCE OF CONDUCTOR Kg 0
TENSION DIFFERENCE OF EARTH WIRE Kg 0

DEVIATION ANGLE - MAX. DEG 30 30


DEVIATION ANGLE - MIN. DEG 15 15
LONG FACTOR FOR CONDUCTOR NIL 1 1
FACTOR OF SAFETY NIL 1 1

10
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

NORMAL CONDITION

TRANSVERSE LOADS :

CONDUCTOR:-
WIND ON CONDUCTOR = 1 x 75 x 0.0181 x 350 = 477
WIND ON INSULATOR = = 40
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 2763 x 1 = 1431
TOTAL TRANSVERSE LOAD = = 1948 Kg

EARTH WIRE:-
WIND ON EARTH WIRE = 1 x 75 x 0.0104 x 350 = 273
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 2048 x 1 = 1061
TOTAL TRANSVERSE LOAD = 1334 Kg

VERTICAL LOADS :

CONDUCTOR:- MAX MIN


WEIGHT OF CONDUCTOR = 1 x 1000 x 0.727 = 727 -509
WEIGHT OF INSULATOR = 2 x 150 = 300 300
TOTAL VERTICAL LOAD = 1027 -209

EARTH WIRE:- MAX MIN


WEIGHT OF EARTH WIRE = 1 x 1000 x 0.485 = 485 -340
TOTAL VERTICAL LOAD = = 485 -340

LONGITUDINAL LOADS :-

CONDUCTOR:-
LONGITUDINAL LOAD OF
CONDUCTOR = 1 x 0 x 1 = 0 Kg

EARTH WIRE:-
LONGITUDINAL LOAD OF EARTH
WIRE = 1 x 0 = 0 Kg

NOTE: 1. LOADS ABOVE ARE TO BE MULTIPLIED BY THEIR RESPECTIVE F.O.S AND APPLIED ON THE TOWER.
2. FACTOR OF SAFETY FOR NORMAL CONDITION = 2.
3. FACTOR OF SAFETY FOR BROKEN WIRE CONDITION = 1.5.

11
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

SECURITY - BROKEN WIRE CONDITION

TRANSVERSE LOADS :

CONDUCTOR:-
WIND ON CONDUCTOR = 1 x 75 x 0.0181 x 210 = 286
WIND ON INSULATOR = = 40
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 2763 x 0.5 = 716
TOTAL TRANSVERSE LOAD = = 1042 Kg

EARTH WIRE:-
WIND ON EARTH WIRE = 1 x 75 x 0.0104 x 210 = 164
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 2048 x 0.5 = 531
TOTAL TRANSVERSE LOAD = 695 Kg

VERTICAL LOADS :

CONDUCTOR:- MAX MIN


WEIGHT OF CONDUCTOR = 1 x 600 x 0.727 = 437 -305
WEIGHT OF INSULATOR = 2 x 150 = 300 300
TOTAL VERTICAL LOAD = = 737 -5

EARTH WIRE:- MAX MIN


WEIGHT OF EARTH WIRE = 1 x 600 x 0.485 = 291 -204
TOTAL VERTICAL LOAD = = 291 -204

LONGITUDINAL LOADS :-

CONDUCTOR:-
LONGITUDINAL LOAD OF CONDUCTOR = 1 x 2763 x 0.9914 x 1 = 2740 Kg

EARTH WIRE:-
LONGITUDINAL LOAD OF EARTH WIRE = 1 x 2048 x 0.9914 = 2031 Kg

NOTE: 1. LOADS ABOVE ARE TO BE MULTIPLIED BY THEIR RESPECTIVE FOS AND APPLIED ON THE TOWER .
2. FACTOR OF SAFETY FOR NORMAL CONDITION = 2.
3. FACTOR OF SAFETY FOR BROKEN WIRE CONDITION = 1.5.

12
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

SAFETY-NORMAL

TRANSVERSE LOADS :

CONDUCTOR:-
WIND ON CONDUCTOR = 1 x 75 x 0.0181 x 0 = 0
WIND ON INSULATOR = = 0
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 1405 x 1 = 728
TOTAL TRANSVERSE LOAD = = 728 Kg

EARTH WIRE:-
WIND ON EARTH WIRE = 1 x 75 x 0.0104 x 0 = 0
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 1265 x 1 = 655
TOTAL TRANSVERSE LOAD = 655 Kg

VERTICAL LOADS :

CONDUCTOR:- MAX
WEIGHT OF CONDUCTOR = 1 x 1000 x 0.727 x 2 = 1454
WEIGHT OF INSULATOR = 2 x 150 x 2 = 600
= = 357
ERECTION LOADS = = 157
TOTAL VERTICAL LOAD = = 2568

EARTH WIRE:- MAX


WEIGHT OF EARTH WIRE = 1 x 1000 x 0.485 x 2 = 970
TOTAL VERTICAL LOAD = = 970

LONGITUDINAL LOADS :-

CONDUCTOR:-
LONGITUDINAL LOAD OF
CONDUCTOR = 1 x 0 x 0.9914 x 1 = 0 Kg

EARTH WIRE:-
LONGITUDINAL LOAD OF EARTH
WIRE = 1 x 0 x 0.9914 = 0 Kg

NOTE: 1. LOADS ABOVE ARE TO BE MULTIPLIED BY THEIR RESPECTIVE FOS AND APPLIED ON THE TOWER .
2. FACTOR OF SAFETY FOR NORMAL CONDITION = 2.
3. FACTOR OF SAFETY FOR BROKEN WIRE CONDITION = 1.5.

13
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

SAFETY - BROKEN WIRE CONDITION

TRANSVERSE LOADS :

CONDUCTOR:-
WIND ON CONDUCTOR = 1 x 0 x 0.0181 x 210 = 0
WIND ON INSULATOR = = 0
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 1405 x 0.5 = 364
TOTAL TRANSVERSE LOAD = = 364 Kg

EARTH WIRE:-
WIND ON EARTH WIRE = 1 x 0 x 0.0104 x 210 = 0
DUE TO ANGLE OF DEVIATION = 2 x 0.259 x 1265 x 0.5 = 328
TOTAL TRANSVERSE LOAD = 328 Kg

VERTICAL LOADS :

CONDUCTOR:- MAX
WEIGHT OF CONDUCTOR = 1 x 600 x 0.727 x 2 = 873
WEIGHT OF INSULATOR = 2 x 150 x 2 = 600
LINE MAN WITH TOOLS = = 357
ERECTION LOADS = = 157
TOTAL VERTICAL LOAD = = 1987

EARTH WIRE:- MAX


WEIGHT OF EARTH WIRE = 1 x 600 x 0.485 x 2 = 582
TOTAL VERTICAL LOAD = = 582

LONGITUDINAL LOADS :-

INTACT BKN
CONDUCTOR:-
LONGITUDINAL LOAD OF CONDUCTOR = 1 x 1405 x 1.5 ( 2 ) / 2 = 1054 1405

EARTH WIRE:-
LONGITUDINAL LOAD OF EARTH WIRE = 1 x 1265 x 1.5 ( 2 ) / 2 = 949 1265

NOTE: 1. LOADS ABOVE ARE TO BE MULTIPLIED BY THEIR RESPECTIVE FOS AND APPLIED ON THE TOWER .
2. FACTOR OF SAFETY FOR NORMAL CONDITION = 2.
3. FACTOR OF SAFETY FOR BROKEN WIRE CONDITION = 1.5.

14
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

WIND ON TOWER BODY

15
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

5. WIND LOAD ON TOWER BODY


___________________________________________________________________________
TRAN WIND ON tw01 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between AA0,BA0,AA2,BAA :- Solidity Ratio : .1204


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
Diagonals
^^^^^^^^^^^^
D2 :1.000 4.905 x .045 x 2 = .4415 1.000 .4415
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 =
.1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 =
.1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 =
.1358 1.000 .1358
_______ _______
1.4014 1.4014
WIND LOAD
= 1.0x207.000x1.00x1.4014
= 290 kg
Panel between BA0,BA1,BAA,BAB :- Solidity Ratio : .1424
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M2 :1.000 2.715 x .100 x 2 = .5430 1.000 .5430
Diagonals
^^^^^^^^^^^^
D3 :1.000 4.245 x .065 x 2 = .5518 1.000 .5518
Redundants
^^^^^^^^^^^^
R4 :1.000 1.642 x .050 x 2 = .1642 1.000 .1642
_______ _______
1.2590 1.2590
WIND LOAD
= 1.0x207.000x1.00x1.2590
= 261 kg
Panel between BA1,BA2,BAB,BAC :- Solidity Ratio : .1625
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M3 :1.000 2.514 x .100 x 2 = .5028 1.000 .5028
Diagonals
^^^^^^^^^^^^
D5 :1.000 3.696 x .065 x 2 = .4805 1.000 .4805
Redundants
^^^^^^^^^^^^
R5 :1.000 1.367 x .045 x 2 = .1230 1.000 .1230
_______ _______
1.1063 1.1063
WIND LOAD

16
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

= 1.0x207.000x1.00x1.1063
= 229 kg
Panel between BA2,BA3,BAC,BAD :- Solidity Ratio : .1851
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M4 :1.000 2.212 x .090 x 2 = .3982 1.000 .3982
Diagonals
^^^^^^^^^^^^
D7 :1.000 3.127 x .065 x 2 = .4066 1.000 .4066
Redundants
^^^^^^^^^^^^
R6 :1.000 1.117 x .045 x 2 = .1006 1.000 .1006
_______ _______
.9054 .9054
WIND LOAD
= 1.0x207.000x1.00x.9054
= 187 kg
Panel between BA3,BA4,BAD,BAE :- Solidity Ratio : .2299
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M5 :1.000 1.559 x .090 x 2 = .2806 1.000 .2806
Diagonals
^^^^^^^^^^^^
D9 :1.000 2.394 x .060 x 2 = .2873 1.000 .2873
Redundants
^^^^^^^^^^^^
R7 :1.000 .915 x .045 x 2 = .0823 1.000 .0823
_______ _______
.6502 .6502
WIND LOAD
= 1.0x207.000x1.00x.6502
= 135 kg

Panel between BA4,AB0,BAE,AB2 :- Solidity Ratio : .2906


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M6 :1.000 1.559 x .090 x 2 = .2806 1.000 .2806
Diagonals
^^^^^^^^^^^^
D11 :1.000 2.153 x .060 x 2 = .2584 1.000 .2584
Horizontals
^^^^^^^^^^^^
H2 :1.000 1.330 x .050 x 1 = .0665 1.000 .0665
Redundants
^^^^^^^^^^^^
R8 :1.000 .752 x .045 x 2 = .0677 1.000 .0677
_______ _______
.6732 .6732
WIND LOAD
= 1.0x207.000x1.00x.6732
= 139 kg

17
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

Panel between AB0,CA0,AB2,CA0 :- Solidity Ratio : 1.0000


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Arms
^^^^^^^^^^^^
B1 :1.000 .665 x .070 x 2 = .0931 1.000 .0931
Redundants
^^^^^^^^^^^^
R20 :1.000 .665 x .045 x 1 =
.0299 1.000 .0299
R22 :1.000 .998 x .045 x 1 =
.0449 1.000 .0449
_______ _______
.1679 .1679
WIND LOAD
= 1.0x207.000x1.00x.1679
= 35 kg
Panel between CA0,BBE0,CA0,BBE2 :- Solidity Ratio : .4038
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Redundants
^^^^^^^^^^^^
R9 :1.000 1.290 x .050 x 1 = .0645 1.000 .0645
R19 :1.000 .640 x .045 x 1 = .0288 1.000 .0288
R21 :1.000 1.108 x .045 x 1 = .0499 1.000 .0499
Arm Tops
^^^^^^^^^^^^
T1 :1.000 1.259 x .055 x 2 = .1385 1.000 .1385
_______ _______
.2817 .2817
WIND LOAD
= 1.0x207.000x1.00x.2817
= 58 kg
Panel between AB0,BBE0,AB2,BBE2 :- Solidity Ratio : .2324
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M7 :1.000 1.082 x .070 x 2 = .1515 1.000 .1515
Diagonals
^^^^^^^^^^^^
D14 :1.000 1.270 x .070 x 2 = .1778 1.000 .1778
_______ _______
.3292 .3293
WIND LOAD
= 1.0x207.000x1.00x.3293
= 68 kg
Panel between BBE0,BB0,BBE2,BB6 :- Solidity Ratio : .2878
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M7 :1.000 1.018 x .070 x 2 = .1426 1.000 .1426
Diagonals
^^^^^^^^^^^^
D14 :1.000 1.195 x .070 x 2 = .1674 1.000 .1674
Horizontals
^^^^^^^^^^^^
H4 :1.000 1.252 x .050 x 1 = .0626 1.000 .0626
_______ _______
.3726 .3726
WIND LOAD
= 1.0x207.000x1.00x.3726
= 77 kg

18
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

Panel between BB0,BB1,BB6,BB7 :- Solidity Ratio : .2577


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M8 :1.000 2.100 x .060 x 2 = .2520 1.000 .2520
Diagonals
^^^^^^^^^^^^
D17 :1.000 2.425 x .060 x 2 = .2910 1.000 .2910
Horizontals
^^^^^^^^^^^^
H6 :1.000 1.174 x .045 x 1 = .0528 1.000 .0528
Redundants
^^^^^^^^^^^^
R10 :1.000 1.212 x .050 x 1 =
.0606 1.000 .0606
_______ _______
.6565 .6564
WIND LOAD
= 1.0x207.000x1.00x.6564
= 136 kg
Panel between BB1,BB2,BB7,BB8 :- Solidity Ratio : .2498
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M9 :1.000 1.000 x .050 x 2 = .1000 1.000 .1000
Diagonals
^^^^^^^^^^^^
D20 :1.000 1.528 x .045 x 2 = .1375 1.000 .1375
Horizontals
^^^^^^^^^^^^
H8 :1.000 1.137 x .045 x 1 = .0512 1.000 .0512
_______ _______
.2887 .2887
WIND LOAD
= 1.0x207.000x1.00x.2887
= 60 kg
Panel between BB2,AC0,BB8,AC2 :- Solidity Ratio : .2544
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M10 :1.000 1.000 x .050 x 2 = .1000 1.000 .1000
Diagonals
^^^^^^^^^^^^
D23 :1.000 1.500 x .045 x 2 = .1350 1.000 .1350
Horizontals
^^^^^^^^^^^^
H10 :1.000 1.100 x .045 x 1 = .0495 1.000 .0495
_______ _______
.2846 .2845
WIND LOAD
= 1.0x207.000x1.00x.2845
= 59 kg

Panel between BB1,CC0,BB7,CC0 :- Solidity Ratio : 1.0000


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Arms
^^^^^^^^^^^^
B3 :1.000 .587 x .060 x 2 = .0705 1.000 .0705

19
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

Redundants
^^^^^^^^^^^^
R32 :1.000 .587 x .045 x 1 =
.0264 1.000 .0264
R34 :1.000 .881 x .050 x 1 =
.0440 1.000 .0440
_______ _______
.1409 .1409
WIND LOAD
= 1.0x207.000x1.00x.1409
= 29 kg
Panel between CC0,BB2,CC0,BB8 :- Solidity Ratio : .3455
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Redundants
^^^^^^^^^^^^
R31 :1.000 .565 x .045 x 1 = .0254 1.000 .0254
R33 :1.000 .989 x .045 x 1 = .0445 1.000 .0445
Arm Tops
^^^^^^^^^^^^
T3 :1.000 1.150 x .055 x 2 = .1265 1.000 .1265
_______ _______
.1964 .1964
WIND LOAD
= 1.0x207.000x1.00x.1964
= 41 kg
Panel between AC0,JA0,AC2,JA0 :- Solidity Ratio : .2973
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Redundants
^^^^^^^^^^^^
R11 :1.000 1.338 x .045 x 1 = .0602 1.000 .0602
R12 :1.000 .825 x .045 x 1 = .0371 1.000 .0371
R13 :1.000 1.156 x .045 x 1 = .0520 1.000 .0520
R14 :1.000 .550 x .045 x 1 = .0247 1.000 .0247
R15 :1.000 1.017 x .045 x 1 = .0458 1.000 .0458
R16 :1.000 .275 x .045 x 1 = .0124 1.000 .0124
Peak Memb
^^^^^^^^^^^^
P1 :1.000 3.760 x .050 x 2 = .3760 1.000 .3760
_______ _______
.6083 .6082
WIND LOAD
= 1.0x207.000x1.00x.6082
= 126 kg
___________________________________________________________________________
TRAN WIND ON tw02 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between LA0,GA0,jB0,GA2 :- Solidity Ratio : .1344


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M12 :1.000 1.508 x .110 x 2 = .3318 1.000 .3318
Diagonals
^^^^^^^^^^^^
D30 :1.000 2.712 x .045 x 2 = .2441 1.000 .2441
Horizontals
^^^^^^^^^^^^

20
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

H14 :1.000 2.100 x .045 x 2 = .1890 1.000 .1890


Redundants
^^^^^^^^^^^^
R40 :1.000 1.226 x .045 x 2 =
.1104 1.000 .1104
R41 :1.000 .754 x .045 x 2 =
.0679 1.000 .0679
_______ _______
.9432 .9432
WIND LOAD
= 1.0x207.000x1.00x.9432
= 195 kg
Panel between GA0,BA0,GA2,BAA :- Solidity Ratio : .1393
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M11 :1.000 1.508 x .110 x 2 = .3318 1.000 .3318
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D26 :1.000 2.453 x .045 x 2 = .2207 1.000 .2207
D28 :1.000 1.508 x .050 x 2 = .1508 1.000 .1508
Horizontals
^^^^^^^^^^^^
H12 :1.000 4.200 x .045 x 1 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R37 :1.000 1.356 x .045 x 2 = .1220 1.000 .1220
R38 :1.000 .754 x .045 x 2 = .0679 1.000 .0679
_______ _______
2.5328 2.5326
WIND LOAD
= 1.0x207.000x1.00x2.5326
= 524 kg
___________________________________________________________________________
TRAN WIND ON tw03 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between jD0,GB0,jF0,GB2 :- Solidity Ratio : .1183


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M12 :1.000 1.508 x .110 x 2 = .3318 1.000 .3318
Diagonals
^^^^^^^^^^^^
D30 :1.000 2.712 x .045 x 2 = .2441 1.000 .2441
Horizontals
^^^^^^^^^^^^
H18 :1.000 2.100 x .045 x 2 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R40 :1.000 1.226 x .045 x 2 = .1104 1.000 .1104
R41 :1.000 .754 x .045 x 2 = .0679 1.000 .0679

21
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

_______ _______
.9432 .9432
WIND LOAD
= 1.0x207.000x1.00x.9432
= 195 kg

Panel between GB0,XA0,GB2,XA2 :- Solidity Ratio : .1470


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M14 :1.000 1.508 x .110 x 2 = .3318 1.000 .3318
Diagonals
^^^^^^^^^^^^
D34 :1.000 2.453 x .045 x 2 = .2207 1.000 .2207
D36 :1.000 1.574 x .045 x 2 = .1417 1.000 .1417
Horizontals
^^^^^^^^^^^^
H16 :1.000 4.838 x .045 x 1 = .2177 1.000 .2177
Redundants
^^^^^^^^^^^^
R48 :1.000 1.356 x .045 x 2 =
.1220 1.000 .1220
R49 :1.000 .754 x .045 x 2 =
.0679 1.000 .0679
_______ _______
1.1019 1.1018
WIND LOAD
= 1.0x207.000x1.00x1.1018
= 228 kg
Panel between XA0,BA0,XA2,BAA :- Solidity Ratio : .1137
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M13 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D32 :1.000 3.662 x .055 x 2 = .4028 1.000 .4028
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R42 :1.000 1.209 x .045 x 2 = .1088 1.000 .1088
R43 :1.000 1.831 x .045 x 2 = .1648 1.000 .1648
R44 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
_______ _______
2.8660 2.8660
WIND LOAD
= 1.0x207.000x1.00x2.8660
= 593 kg

___________________________________________________________________________
TRAN WIND ON tw04 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor

22
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________

Panel between LE0,GC0,jI0,GC2 :- Solidity Ratio : .0702


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M19 :1.000 3.017 x .110 x 2 = .6637 1.000 .6637
Diagonals
^^^^^^^^^^^^
D48 :1.000 3.854 x .050 x 2 = .3854 1.000 .3854
Horizontals
^^^^^^^^^^^^
H22 :1.000 2.100 x .045 x 2 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R69 :1.000 1.050 x .045 x 2 =
.0945 1.000 .0945
R70 :1.000 1.744 x .045 x 2 =
.1570 1.000 .1570
_______ _______
1.4896 1.4896
WIND LOAD
= 1.0x207.000x1.00x1.4896
= 308 kg
Panel between GC0,XD0,GC2,XD2 :- Solidity Ratio : .1275
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M18 :1.000 1.508 x .110 x 2 = .3318 1.000 .3318
Diagonals
^^^^^^^^^^^^
D44 :1.000 2.453 x .045 x 2 = .2207 1.000 .2207
D46 :1.000 1.969 x .050 x 2 = .1969 1.000 .1969
Horizontals
^^^^^^^^^^^^
H20 :1.000 6.432 x .050 x 1 = .3216 1.000 .3216
Redundants
^^^^^^^^^^^^
R66 :1.000 1.356 x .045 x 2 = .1220 1.000 .1220
R67 :1.000 .754 x .045 x 2 = .0679 1.000 .0679
_______ _______
1.2610 1.2609
WIND LOAD
= 1.0x207.000x1.00x1.2609
= 261 kg
Panel between XD0,XC0,XD2,XC2 :- Solidity Ratio : .0853
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M17 :1.000 3.017 x .110 x 2 = .6637 1.000 .6637
Diagonals
^^^^^^^^^^^^
D42 :1.000 4.171 x .050 x 2 = .4171 1.000 .4171
Redundants
^^^^^^^^^^^^
R60 :1.000 1.608 x .050 x 2 = .1608 1.000 .1608
R61 :1.000 2.085 x .045 x 2 = .1877 1.000 .1877
R62 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
_______ _______
1.5650 1.5651

23
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

WIND LOAD
= 1.0x207.000x1.00x1.5651
= 324 kg

Panel between XC0,XB0,XC2,XB2 :- Solidity Ratio : .1014


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M16 :1.000 4.525 x .110 x 2 = .9956 1.000 .9956
Diagonals
^^^^^^^^^^^^
D40 :1.000 6.965 x .055 x 2 = .7661 1.000 .7661
Redundants
^^^^^^^^^^^^
R54 :1.000 1.449 x .045 x 2
.1304 = 1.000 .1304
R55 :1.000 2.103 x .045 x 2
.1893 = 1.000 .1893
R56 :1.000 2.263 x .050 x 2
.2263 = 1.000 .2263
R57 :1.000 1.318 x .045 x 2
.1186 = 1.000 .1186
_______ _______
2.4263 2.4263
WIND LOAD
= 1.0x207.000x1.00x2.4263
= 502 kg
Panel between XB0,BA0,XB2,BAA :- Solidity Ratio : .1159
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M15 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D38 :1.000 5.424 x .045 x 2 = .4882 1.000 .4882
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R51 :1.000 1.260 x .045 x 2 = .1134 1.000 .1134
R52 :1.000 1.452 x .045 x 2 = .1307 1.000 .1307
R53 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
_______ _______
2.9218 2.9219
WIND LOAD
= 1.0x207.000x1.00x2.9219
= 605 kg
___________________________________________________________________________
TRAN WIND ON tw05 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between LI0,BA0,jL0,BAA :- Solidity Ratio : .1173


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^

24
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M20 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D50 :1.000 3.854 x .060 x 2 = .4624 1.000 .4624
Horizontals
^^^^^^^^^^^^
H12 :1.000 4.200 x .045 x 1 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R72 :1.000 1.050 x .045 x 2 = .0945 1.000 .0945
R73 :1.000 1.744 x .045 x 2 = .1570 1.000 .1570
_______ _______
2.9567 2.9567
WIND LOAD
= 1.0x207.000x1.00x2.9567
= 612 kg

___________________________________________________________________________
TRAN WIND ON tw06 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between LM0,BA0,jO0,BAA :- Solidity Ratio : .1193


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M21 :1.000 4.525 x .110 x 2 = .9956 1.000 .9956
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D52 :1.000 5.186 x .060 x 2 = .6224 1.000 .6224
Horizontals
^^^^^^^^^^^^
H12 :1.000 4.200 x .045 x 1 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R75 :1.000 .700 x .045 x 2 = .0630 1.000 .0630
R76 :1.000 1.594 x .045 x 2 = .1435 1.000 .1435
R77 :1.000 1.400 x .045 x 2 = .1260 1.000 .1260
R78 :1.000 1.927 x .045 x 2 = .1734 1.000 .1734
R79 :1.000 1.512 x .045 x 2 = .1361 1.000 .1361
_______ _______
3.8994 3.8994
WIND LOAD

25
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

= 1.0x207.000x1.00x3.8994
= 807 kg

___________________________________________________________________________
TRAN WIND ON tw07 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between LQ0,BA0,jR0,BAA :- Solidity Ratio : .1163


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M22 :1.000 6.034 x .110 x 2 = 1.3274 1.000 1.3274
Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D54 :1.000 6.595 x .065 x 2 = .8574 1.000 .8574
Horizontals
^^^^^^^^^^^^
H12 :1.000 4.200 x .045 x 1 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R83 :1.000 .525 x .045 x 2 = .0472 1.000 .0472
R84 :1.000 1.544 x .045 x 2 = .1390 1.000 .1390
R85 :1.000 1.050 x .045 x 2 = .0945 1.000 .0945
R86 :1.000 1.744 x .045 x 2 = .1570 1.000 .1570
R87 :1.000 1.575 x .050 x 2 = .1575 1.000 .1575
R88 :1.000 1.927 x .045 x 2 = .1734 1.000 .1734
R89 :1.000 1.544 x .045 x 2 = .1390 1.000 .1390
_______ _______
4.7318 4.7318
WIND LOAD
= 1.0x207.000x1.00x4.7318
= 979 kg

___________________________________________________________________________
TRAN WIND ON tw08 (0 Deg. Wind)
___________________________________________________________________________
Drag Exposed No. of Area Shape Area x Drag x
Part coeff. Dimension Pieces (A) Factor Shape Factor
___________________________________________________________________________

Panel between LU0,BA0,jU0,BAA :- Solidity Ratio : .1118


^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
Main Legs
^^^^^^^^^^^^
M1 :1.000 3.017 x .100 x 2 = .6034 1.000 .6034
M23 :1.000 7.542 x .110 x 2 = 1.6593 1.000 1.6593

26
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

Diagonals
^^^^^^^^^^^^
D1 :1.000 4.905 x .050 x 2 = .4905 1.000 .4905
D56 :1.000 8.040 x .065 x 2 = 1.0452 1.000 1.0452
Horizontals
^^^^^^^^^^^^
H12 :1.000 4.200 x .045 x 1 = .1890 1.000 .1890
Redundants
^^^^^^^^^^^^
R1 :1.000 1.126 x .045 x 2 = .1013 1.000 .1013
R2 :1.000 1.327 x .045 x 2 = .1194 1.000 .1194
R3 :1.000 1.508 x .045 x 2 = .1358 1.000 .1358
R93 :1.000 .420 x .045 x 2 = .0378 1.000 .0378
R94 :1.000 1.522 x .045 x 2 = .1370 1.000 .1370
R95 :1.000 .840 x .045 x 2 = .0756 1.000 .0756
R96 :1.000 1.647 x .045 x 2 = .1482 1.000 .1482
R97 :1.000 1.260 x .045 x 2 = .1134 1.000 .1134
R98 :1.000 1.860 x .045 x 2 = .1674 1.000 .1674
R99 :1.000 1.680 x .045 x 2 = .1512 1.000 .1512
R100 :1.000 1.927 x .045 x 2 = .1734 1.000 .1734
R101 :1.000 1.572 x .045 x 2 = .1415 1.000 .1415
_______ _______
5.4896 5.4894
WIND LOAD
= 1.0x207.000x1.00x5.4894
= 1136 kg

NOTE: WIND LOAD ON THE TOWER BODY IS CONVERTED TO NODAL LOADS AND APPLIED AT INTERMEDIATE
BODY LEVELS, CROSS ARM AND PEAK LEVELS.

27
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

DESIGN CALCULATIONS

28
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

6.DESIGN CALCULATIONS
_______________________________________________________________________________________________________________________

-: Main Legs :-
___________________________________________________________________________________________________________________
D E T A I L S M1 M2 M3 M4

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X002 case-X002
(TENSION) case-X009 case-X009 case-X009 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 26097. 24533. 24365. 22122.
TOTAL TENSION(kg) 24696. 23402. 23392. 21452.
_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 100x100x8.00 100x100x8.00 100x100x7.00 90x90x7.00
RADIUS OF GYRATION(cm) 1.95 1.95 1.97 1.77
UNSUPPORTED LENGTH(cm) 151.69 136.52 126.40 111.24
CURVE NUMBER 1 1 1 1
SLENDERNESS RATIO KL/R 77.79 70.01 64.16 62.85
SECTIONAL AREA (GROSS)(sq.cm) 15.39 15.39 13.62 12.22
ULTIMATE COMPRESSION STRENGTH 40555.08 43434.86 38402.63 36381.10
(kg)
FACTOR OF SAFETY 1.55 1.77 1.58 1.64

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 12.59 12.59 11.17 9.77
ULTIMATE TENSILE STRENGTH 45575.80 45575.80 40435.39 35367.39
(kg)
FACTOR OF SAFETY 1.85 1.95 1.73 1.65

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 6.D.S. 6.D.S. 6.D.S. 6.D.S.
ULTIMATE SHEARING STRENGTH 76266.81 76266.81 76266.81 76266.81
(kg)
ULTIMATE BEARING STRENGTH 48552.96 48552.96 42483.84 42483.84
(kg)
FACTOR OF SAFETY 1.86 1.98 1.74 1.92

___________________________________________________________________________________________________________________

29
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S M5 M6 M7 M8

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X002 case-X009
(TENSION) case-X009 case-X009 case-X009 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 22161. 19070. 11358. 6030.
TOTAL TENSION(kg) 21589. 18860. 10258. 6312.
_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 90x90x7.00 90x90x6.00 65x65x6.00 60x60x6.00
RADIUS OF GYRATION(cm) 1.77 1.75 1.26 1.15
UNSUPPORTED LENGTH(cm) 78.37 78.37 108.21 108.41
CURVE NUMBER 1 1 1 1
SLENDERNESS RATIO KL/R 44.28 44.78 85.88 94.27
SECTIONAL AREA (GROSS)(sq.cm) 12.22 10.47 7.44 6.84
ULTIMATE COMPRESSION STRENGTH 40337.15 31744.75 18002.31 14867.63
(kg)
FACTOR OF SAFETY 1.82 1.66 1.59 2.47

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 9.77 8.37 5.34 4.74
ULTIMATE TENSILE STRENGTH 35367.39 30299.40 19330.80 17158.80
(kg)
FACTOR OF SAFETY 1.64 1.61 1.88 2.72

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 6.D.S. 6.D.S. 4.D.S. 2.D.S.
ULTIMATE SHEARING STRENGTH 76266.81 76266.81 50844.54 25422.27
(kg)
ULTIMATE BEARING STRENGTH 42483.84 36414.72 24276.48 12138.24
(kg)
FACTOR OF SAFETY 1.92 1.91 2.14 1.92

___________________________________________________________________________________________________________________

30
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S M9 M10 M11 M12

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X004 case-X004 case-X002 case-X002
(TENSION) case-X009 case-X009 case-X009 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 5374. 4807. 26497. 26707.
TOTAL TENSION(kg) 5728. 4994. 24664. 24729.

_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 50x50x6.00 50x50x6.00 110x110x8.00 110x110x8.00
RADIUS OF GYRATION(cm) .96 .96 2.14 2.14
UNSUPPORTED LENGTH(cm) 100.03 100.03 151.69 151.69
CURVE NUMBER 1 1 1 1
SLENDERNESS RATIO KL/R 104.20 104.20 70.88 70.88
SECTIONAL AREA (GROSS)(sq.cm) 5.68 5.68 17.02 17.02
ULTIMATE COMPRESSION STRENGTH 10523.47 10523.47 46961.20 46961.20
(kg)
FACTOR OF SAFETY 1.96 2.19 1.77 1.76

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.58 3.58 14.22 14.22
ULTIMATE TENSILE STRENGTH 12959.60 12959.60 51476.40 51476.40
(kg)
FACTOR OF SAFETY 2.26 2.60 2.09 2.08

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.D.S. 2.D.S. 6.D.S. 6.D.S.
ULTIMATE SHEARING STRENGTH 25422.27 25422.27 76266.81 76266.81
(kg)
ULTIMATE BEARING STRENGTH 12138.24 12138.24 48552.96 48552.96
(kg)
FACTOR OF SAFETY 2.12 2.43 1.83 1.82

___________________________________________________________________________________________________________________

31
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S M13 M14 M15 M16

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X002 case-X002
(TENSION) case-X009 case-X009 case-X009 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 25979. 26616. 26213. 27709.
TOTAL TENSION(kg) 24354. 24731. 24521. 25676.

_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 100x100x8.00 110x110x8.00 100x100x8.00 110x110x8.00
RADIUS OF GYRATION(cm) 1.95 2.14 1.95 2.14
UNSUPPORTED LENGTH(cm) 151.69 151.69 151.69 151.69
CURVE NUMBER 1 1 1 1
SLENDERNESS RATIO KL/R 77.79 70.88 77.79 70.88
SECTIONAL AREA (GROSS)(sq.cm) 15.39 17.02 15.39 17.02
ULTIMATE COMPRESSION STRENGTH 40555.09 46961.20 40555.08 46961.20
(kg)
FACTOR OF SAFETY 1.56 1.76 1.55 1.69

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 12.59 14.22 12.59 14.22
ULTIMATE TENSILE STRENGTH 45575.80 51476.40 45575.80 51476.40
(kg)
FACTOR OF SAFETY 1.87 2.08 1.86 2.00

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 6.D.S. 6.D.S. 6.D.S. 6.D.S.
ULTIMATE SHEARING STRENGTH 76266.81 76266.81 76266.81 76266.81
(kg)
ULTIMATE BEARING STRENGTH 48552.96 48552.96 48552.96 48552.96
(kg)
FACTOR OF SAFETY 1.87 1.82 1.85 1.75

___________________________________________________________________________________________________________________

32
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S M17 M18 M19 M20

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X002 case-X002
(TENSION) case-X010 case-X010 case-X010 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 28072. 28062. 28163. 26204.
TOTAL TENSION(kg) 25883. 25718. 25672. 24449.

_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 110x110x8.00 110x110x8.00 110x110x8.00 100x100x8.00
RADIUS OF GYRATION(cm) 2.14 2.14 2.14 1.95
UNSUPPORTED LENGTH(cm) 151.69 151.69 151.69 151.69
CURVE NUMBER 1 1 1 1
SLENDERNESS RATIO KL/R 70.88 70.88 70.88 77.79
SECTIONAL AREA (GROSS)(sq.cm) 17.02 17.02 17.02 15.39
ULTIMATE COMPRESSION STRENGTH 46961.20 46961.20 46961.20 40555.09
(kg)
FACTOR OF SAFETY 1.67 1.67 1.67 1.55

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 14.22 14.22 14.22 12.59
ULTIMATE TENSILE STRENGTH 51476.40 51476.40 51476.40 45575.80
(kg)
FACTOR OF SAFETY 1.99 2.00 2.01 1.86

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 6.D.S. 6.D.S. 6.D.S. 6.D.S.
ULTIMATE SHEARING STRENGTH 76266.81 76266.81 76266.81 76266.81
(kg)
ULTIMATE BEARING STRENGTH 48552.96 48552.96 48552.96 48552.96
(kg)
FACTOR OF SAFETY 1.73 1.73 1.72 1.85

___________________________________________________________________________________________________________________

33
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S M21 M22 M23

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X002
(TENSION) case-X009 case-X009 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 26259. 26323. 26277.
TOTAL TENSION(kg) 24461. 24477. 24397.

_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE H:---SINGLE H:---SINGLE
SECTION 110x110x8.00 110x110x8.00 110x110x8.00
RADIUS OF GYRATION(cm) 2.14 2.14 2.14
UNSUPPORTED LENGTH(cm) 151.69 151.69 151.69
CURVE NUMBER 1 1 1
SLENDERNESS RATIO KL/R 70.88 70.88 70.88
SECTIONAL AREA (GROSS)(sq.cm) 17.02 17.02 17.02
ULTIMATE COMPRESSION STRENGTH 46961.20 46961.20 46961.20
(kg)
FACTOR OF SAFETY 1.79 1.78 1.79

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 14.22 14.22 14.22
ULTIMATE TENSILE STRENGTH 51476.40 51476.40 51476.40
(kg)
FACTOR OF SAFETY 2.10 2.10 2.11

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 6.D.S. 6.D.S. 6.D.S.
ULTIMATE SHEARING STRENGTH 76266.81 76266.81 76266.81
(kg)
ULTIMATE BEARING STRENGTH 48552.96 48552.96 48552.96
(kg)
FACTOR OF SAFETY 1.85 1.84 1.85

___________________________________________________________________________________________________________________

34
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

_______________________________________________________________________________________________________________________

-: Diagonals :-

___________________________________________________________________________________________________________________
D E T A I L S D1 D2 D3 D4

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2305. 2805. 2269. 2733.
TOTAL TENSION(kg) 2445. 2235. 2734. 3381.
_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 50x50x4.00 65x65x5.00 65x65x5.00 65x65x4.00
RADIUS OF GYRATION(cm) .97 1.26 1.26 1.26
UNSUPPORTED LENGTH(cm) 132.99 231.36 231.36 203.37
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 133.07 168.52 168.52 151.59
SECTIONAL AREA (GROSS)(sq.cm) 3.88 6.25 6.25 5.00
ULTIMATE COMPRESSION STRENGTH 4410.17 4430.03 4430.03 4379.51
(kg)
FACTOR OF SAFETY 1.91 1.58 1.95 1.60

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.18 5.38 5.38 4.30
ULTIMATE TENSILE STRENGTH 7294.92 12330.25 12330.25 9864.20
(kg)
FACTOR OF SAFETY 2.98 5.52 4.51 2.92

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 7340.80 7340.80 5872.64
(kg)
FACTOR OF SAFETY 2.40 2.62 2.68 1.74

___________________________________________________________________________________________________________________

35
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D5 D6 D7 D8

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 3444. 4224. 3566. 3717.
TOTAL TENSION(kg) 2818. 3330. 4329. 4714.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 65x65x5.00 65x65x5.00 65x65x4.00 60x60x4.00
RADIUS OF GYRATION(cm) 1.26 1.26 1.26 1.18
UNSUPPORTED LENGTH(cm) 203.37 173.31 173.31 130.81
CURVE NUMBER 5 5 5 3
SLENDERNESS RATIO KL/R 151.59 133.41 133.41 115.43
SECTIONAL AREA (GROSS)(sq.cm) 6.25 6.25 5.00 4.71
ULTIMATE COMPRESSION STRENGTH 5474.39 7068.24 5654.59 6941.53
(kg)
FACTOR OF SAFETY 1.59 1.67 1.59 1.87

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 5.38 5.38 4.30 4.01
ULTIMATE TENSILE STRENGTH 12330.25 12330.25 9864.20 9198.94
(kg)
FACTOR OF SAFETY 4.37 3.70 2.28 1.95

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 3.S.S. 3.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 19066.70 19066.70
(kg)
ULTIMATE BEARING STRENGTH 7340.80 7340.80 8808.96 8808.96
(kg)
FACTOR OF SAFETY 2.13 1.74 2.03 1.87

___________________________________________________________________________________________________________________

36
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D9 D10 D11 D12

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 4900. 6308. 5392. 1567.
TOTAL TENSION(kg) 4017. 4888. 6571. 1370.
_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 60x60x5.00 65x65x5.00 60x60x5.00 55x55x4.00
RADIUS OF GYRATION(cm) 1.16 1.26 1.16 1.06
UNSUPPORTED LENGTH(cm) 130.81 119.88 119.88 188.09
CURVE NUMBER 3 3 3 5
SLENDERNESS RATIO KL/R 116.38 107.57 111.67 163.81
SECTIONAL AREA (GROSS)(sq.cm) 5.75 6.25 5.75 4.22
ULTIMATE COMPRESSION STRENGTH 8371.47 10094.72 8869.92 3165.40
(kg)
FACTOR OF SAFETY 1.71 1.60 1.64 2.02

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.88 5.38 4.88 3.52
ULTIMATE TENSILE STRENGTH 11183.25 12330.25 11183.25 8074.88
(kg)
FACTOR OF SAFETY 2.78 2.52 1.70 5.89

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 3.S.S. 3.S.S. 3.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 19066.70 19066.70 19066.70 12711.14
(kg)
ULTIMATE BEARING STRENGTH 11011.20 11011.20 11011.20 5872.64
(kg)
FACTOR OF SAFETY 2.25 1.75 1.68 3.75

___________________________________________________________________________________________________________________

37
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D13 D14 D15 D16

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X003 case-X003 case-X002
(TENSION) case-X003 case-X006 case-X003 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 9821. 7063. 958. 8605.
TOTAL TENSION(kg) 8512. 7325. 1129. 5869.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE H:---SINGLE M:---SINGLE
SECTION 80x80x6.00 75x75x5.00 45x45x4.00 75x75x6.00
RADIUS OF GYRATION(cm) 1.56 1.46 .87 1.46
UNSUPPORTED LENGTH(cm) 119.55 126.99 177.07 125.17
CURVE NUMBER 3 3 5 3
SLENDERNESS RATIO KL/R 98.32 103.49 183.69 102.87
SECTIONAL AREA (GROSS)(sq.cm) 9.29 7.27 3.47 8.66
ULTIMATE COMPRESSION STRENGTH 16433.31 12247.74 2069.95 14679.34
(kg)
FACTOR OF SAFETY 1.67 1.73 2.16 1.71

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 8.24 6.39 2.77 7.61
ULTIMATE TENSILE STRENGTH 18902.56 14670.13 9024.66 17457.34
(kg)
FACTOR OF SAFETY 2.22 2.00 7.99 2.97

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 4.S.S. 3.S.S. 2.S.S. 3.S.S.
ULTIMATE SHEARING STRENGTH 25422.27 19066.70 12711.14 19066.70
(kg)
ULTIMATE BEARING STRENGTH 17617.92 11011.20 8092.16 13213.44
(kg)
FACTOR OF SAFETY 1.79 1.50 7.16 1.54

___________________________________________________________________________________________________________________

38
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D17 D18 D19 D20

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X002 case-X011 case-X002
(TENSION) case-X009 case-X009 case-X011 case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 4990. 907. 2228. 1550.
TOTAL TENSION(kg) 6323. 746. 1916. 1860.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE H:---SINGLE M:---SINGLE M:---SINGLE
SECTION 60x60x5.00 45x45x4.00 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) 1.16 .87 .87 .87
UNSUPPORTED LENGTH(cm) 125.17 166.06 77.64 77.64
CURVE NUMBER 3 5 3 3
SLENDERNESS RATIO KL/R 113.95 174.04 104.62 104.62
SECTIONAL AREA (GROSS)(sq.cm) 5.75 3.47 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 8631.30 2305.84 5779.86 5779.86
(kg)
FACTOR OF SAFETY 1.73 2.54 2.59 3.73

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.88 2.77 2.77 2.77
ULTIMATE TENSILE STRENGTH 11183.25 9024.66 6354.38 6354.38
(kg)
FACTOR OF SAFETY 1.77 12.10 3.32 3.42

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 3.S.S. 2.S.S. 2.S.S. 1.S.S.
ULTIMATE SHEARING STRENGTH 19066.70 12711.14 12711.14 6355.57
(kg)
ULTIMATE BEARING STRENGTH 11011.20 8092.16 5872.64 2936.32
(kg)
FACTOR OF SAFETY 1.74 8.92 2.64 1.58

___________________________________________________________________________________________________________________

39
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D21 D22 D23 D24

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X009 case-X009 case-X004 case-X010
(TENSION) case-X002 case-X002 case-X009 case-X005

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 592. 736. 874. 139.
TOTAL TENSION(kg) 739. 989. 852. 145.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 50x50x4.00 45x45x4.00 45x45x4.00 50x50x4.00
RADIUS OF GYRATION(cm) .97 .87 .87 .97
UNSUPPORTED LENGTH(cm) 160.81 76.27 76.27 155.56
CURVE NUMBER 5 3 3 5
SLENDERNESS RATIO KL/R 154.93 103.83 103.83 150.81
SECTIONAL AREA (GROSS)(sq.cm) 3.88 3.47 3.47 3.88
ULTIMATE COMPRESSION STRENGTH 3253.77 5825.99 5825.99 3434.05
(kg)
FACTOR OF SAFETY 5.50 7.92 6.66 24.66

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.18 2.77 2.77 3.18
ULTIMATE TENSILE STRENGTH 7294.92 6354.38 6354.38 7294.92
(kg)
FACTOR OF SAFETY 9.87 6.43 7.46 50.29

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 1.S.S. 1.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 6355.57 6355.57 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 2936.32 2936.32 5872.64
(kg)
FACTOR OF SAFETY 7.94 2.97 3.36 40.49

___________________________________________________________________________________________________________________

40
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D25 D26 D27 D28

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 1510. 1405. 1945. 1771.
TOTAL TENSION(kg) 1602. 1489. 1888. 1708.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 50x50x4.00 50x50x4.00
RADIUS OF GYRATION(cm) .87 .87 .97 .97
UNSUPPORTED LENGTH(cm) 122.89 122.89 151.69 151.69
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 136.24 136.24 147.76 147.76
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.88 3.88
ULTIMATE COMPRESSION STRENGTH 3763.05 3763.05 3577.11 3577.11
(kg)
FACTOR OF SAFETY 2.49 2.68 1.84 2.02

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 3.18 3.18
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 7294.92 7294.92
(kg)
FACTOR OF SAFETY 3.97 4.27 3.86 4.27

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 3.67 3.94 3.02 3.32

___________________________________________________________________________________________________________________

41
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D29 D30 D31 D32

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X003 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2091. 1601. 2723. 1735.
TOTAL TENSION(kg) 1744. 1703. 1915. 2522.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 50x50x4.00 45x45x4.00 60x60x4.00 55x55x4.00
RADIUS OF GYRATION(cm) .97 .87 1.18 1.06
UNSUPPORTED LENGTH(cm) 135.84 135.84 183.79 183.79
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 135.31 147.57 147.29 160.72
SECTIONAL AREA (GROSS)(sq.cm) 3.88 3.47 4.71 4.22
ULTIMATE COMPRESSION STRENGTH 4265.74 3207.18 4370.28 3288.31
(kg)
FACTOR OF SAFETY 2.04 2.00 1.61 1.90

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.18 2.77 4.01 3.52
ULTIMATE TENSILE STRENGTH 7294.92 6354.38 9198.94 8074.88
(kg)
FACTOR OF SAFETY 4.18 3.73 4.80 3.20

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 2.81 3.45 2.16 2.33

___________________________________________________________________________________________________________________

42
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D33 D34 D35 D36

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X003 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X003 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 964. 1181. 2036. 1261.
TOTAL TENSION(kg) 1413. 896. 1428. 1699.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 50x50x4.00 45x45x4.00
RADIUS OF GYRATION(cm) .87 .87 .97 .87
UNSUPPORTED LENGTH(cm) 122.89 122.89 158.25 158.25
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 136.24 136.24 152.91 167.20
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.88 3.47
ULTIMATE COMPRESSION STRENGTH 3763.06 3763.06 3340.00 2498.33
(kg)
FACTOR OF SAFETY 3.90 3.19 1.64 1.98

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 3.18 2.77
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 7294.92 6354.38
(kg)
FACTOR OF SAFETY 4.50 7.09 5.11 3.74

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 4.16 4.97 2.88 3.46

___________________________________________________________________________________________________________________

43
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D37 D38 D39 D40

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 1952. 1371. 1506. 1725.
TOTAL TENSION(kg) 1473. 1784. 1990. 1260.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 50x50x4.00 45x45x4.00 50x50x4.00 55x55x4.00
RADIUS OF GYRATION(cm) .97 .87 .97 1.06
UNSUPPORTED LENGTH(cm) 145.42 145.42 190.24 190.24
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 142.84 155.97 178.05 165.36
SECTIONAL AREA (GROSS)(sq.cm) 3.88 3.47 3.88 4.22
ULTIMATE COMPRESSION STRENGTH 3827.83 2871.20 2463.65 3106.54
(kg)
FACTOR OF SAFETY 1.96 2.09 1.64 1.80

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.18 2.77 3.18 3.52
ULTIMATE TENSILE STRENGTH 7294.92 6354.38 7294.92 8074.88
(kg)
FACTOR OF SAFETY 4.95 3.56 3.67 6.41

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 3.01 3.29 2.95 3.41

___________________________________________________________________________________________________________________

44
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D41 D42 D43 D44

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X003
(TENSION) case-X006 case-X006 case-X001 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 1969. 1089. 113. 24.
TOTAL TENSION(kg) 1474. 1546. 106. 71.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 60x60x4.00 50x50x4.00 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) 1.18 .97 .87 .87
UNSUPPORTED LENGTH(cm) 209.14 209.14 122.89 122.89
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 163.65 192.89 136.24 136.24
SECTIONAL AREA (GROSS)(sq.cm) 4.71 3.88 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 3539.79 2098.99 3763.06 3763.06
(kg)
FACTOR OF SAFETY 1.80 1.93 33.31 157.10

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.01 3.18 2.77 2.77
ULTIMATE TENSILE STRENGTH 9198.94 7294.92 6354.38 6354.38
(kg)
FACTOR OF SAFETY 6.24 4.72 59.78 89.19

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 2.98 3.80 51.99 82.43

___________________________________________________________________________________________________________________

45
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D45 D46 D47 D48

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2351. 1256. 2430. 1262.
TOTAL TENSION(kg) 1804. 1645. 1838. 1660.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 60x60x4.00 50x50x4.00 60x60x4.00 50x50x4.00
RADIUS OF GYRATION(cm) 1.18 .97 1.18 .97
UNSUPPORTED LENGTH(cm) 197.55 197.55 193.34 193.34
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 156.17 183.79 153.45 180.48
SECTIONAL AREA (GROSS)(sq.cm) 4.71 3.88 4.71 3.88
ULTIMATE COMPRESSION STRENGTH 3887.27 2312.15 4025.99 2397.51
(kg)
FACTOR OF SAFETY 1.65 1.84 1.66 1.90

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.01 3.18 4.01 3.18
ULTIMATE TENSILE STRENGTH 9198.94 7294.92 9198.94 7294.92
(kg)
FACTOR OF SAFETY 5.10 4.44 5.01 4.39

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 2.50 3.57 2.42 3.54

___________________________________________________________________________________________________________________

46
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D49 D50 D51 D52

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2446. 2265. 3133. 2836.
TOTAL TENSION(kg) 2361. 2206. 3024. 2811.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 60x60x4.00 60x60x4.00 65x65x4.00 60x60x4.00
RADIUS OF GYRATION(cm) 1.18 1.18 1.26 1.18
UNSUPPORTED LENGTH(cm) 193.34 193.34 173.61 173.61
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 153.45 153.45 133.59 140.71
SECTIONAL AREA (GROSS)(sq.cm) 4.71 4.71 5.00 4.71
ULTIMATE COMPRESSION STRENGTH 4025.99 4025.99 5639.11 4788.20
(kg)
FACTOR OF SAFETY 1.65 1.78 1.80 1.69

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.01 4.01 4.30 4.01
ULTIMATE TENSILE STRENGTH 9198.94 9198.94 9864.20 9198.94
(kg)
FACTOR OF SAFETY 3.90 4.17 3.26 3.27

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 2.40 2.59 1.87 2.07

___________________________________________________________________________________________________________________

47
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S D53 D54 D55 D56

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 3777. 3393. 4559. 3713.
TOTAL TENSION(kg) 3666. 3388. 4397. 3883.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 65x65x4.00 65x65x4.00 65x65x5.00 65x65x4.00
RADIUS OF GYRATION(cm) 1.26 1.26 1.26 1.26
UNSUPPORTED LENGTH(cm) 165.65 165.65 161.59 161.59
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 128.78 128.78 126.32 126.32
SECTIONAL AREA (GROSS)(sq.cm) 5.00 5.00 6.25 5.00
ULTIMATE COMPRESSION STRENGTH 6068.81 6068.81 7883.43 6306.41
(kg)
FACTOR OF SAFETY 1.61 1.79 1.73 1.70

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 4.30 4.30 5.38 4.30
ULTIMATE TENSILE STRENGTH 9864.20 9864.20 12330.25 9864.20
(kg)
FACTOR OF SAFETY 2.69 2.91 2.80 2.54

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 7340.80 5872.64
(kg)
FACTOR OF SAFETY 1.55 1.73 1.61 1.51

___________________________________________________________________________________________________________________

48
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

_______________________________________________________________________________________________________________________

-: Horizontals :-
___________________________________________________________________________________________________________________
D E T A I L S H1 H2 H3 H4

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X003 case-X008 case-X002 case-X008
(TENSION) case-X006 case-X001 case-X009 case-X001

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2596. 1144. 3718. 2461.
TOTAL TENSION(kg) 1412. 1553. 4378. 2209.
_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 50x50x4.00 50x50x4.00 55x55x4.00 55x55x4.00
RADIUS OF GYRATION(cm) .97 .97 1.06 1.06
UNSUPPORTED LENGTH(cm) 133.00 133.00 125.21 125.21
CURVE NUMBER 5 5 3 3
SLENDERNESS RATIO KL/R 133.08 133.08 119.06 119.06
SECTIONAL AREA (GROSS)(sq.cm) 3.88 3.88 4.22 4.22
ULTIMATE COMPRESSION STRENGTH 4409.73 4409.73 5929.27 5929.27
(kg)
FACTOR OF SAFETY 1.70 3.85 1.59 2.41

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.18 3.18 3.52 3.52
ULTIMATE TENSILE STRENGTH 7294.92 7294.92 8074.88 8074.88
(kg)
FACTOR OF SAFETY 5.17 4.70 1.84 3.65

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 3.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 19066.70 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 8808.96 5872.64
(kg)
FACTOR OF SAFETY 2.26 3.78 2.01 2.39

___________________________________________________________________________________________________________________

49
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S H5 H6 H7 H8

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X003 case-X008 case-X010 case-X011
(TENSION) case-X010 case-X011 case-X011 case-X008

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 2265. 1000. 405. 889.
TOTAL TENSION(kg) 1401. 1405. 1338. 520.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) .87 .87 .87 .87
UNSUPPORTED LENGTH(cm) 117.42 117.42 113.71 113.71
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 131.44 131.44 128.19 128.19
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 4042.62 4042.62 4250.14 4250.14
(kg)
FACTOR OF SAFETY 1.78 4.04 10.50 4.78

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 2.77 2.77
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 6354.38 6354.38
(kg)
FACTOR OF SAFETY 4.54 4.52 4.75 12.22

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 2.59 4.18 4.39 6.61

___________________________________________________________________________________________________________________

50
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S H9 H10 H11 H12

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002 case-X008 case-X006 case-X006
(TENSION) case-X009 case-X001 case-X006 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 944. 583. 1658. 1388.
TOTAL TENSION(kg) 897. 634. 1451. 1462.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) .87 .87 .87 .87
UNSUPPORTED LENGTH(cm) 110.00 110.00 105.00 105.00
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 124.94 124.94 120.57 120.57
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 4473.47 4473.47 4774.54 4774.54
(kg)
FACTOR OF SAFETY 4.74 7.67 2.88 3.44

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 2.77 2.77
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 6354.38 6354.38
(kg)
FACTOR OF SAFETY 7.09 10.02 4.38 4.35

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 6.22 9.26 3.54 4.02

___________________________________________________________________________________________________________________

51
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S H13 H14 H15 H16

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X006 case-X006
(TENSION) case-X006 case-X006 case-X003 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 63. 72. 1055. 729.
TOTAL TENSION(kg) 57. 65. 675. 957.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) .87 .87 .87 .87
UNSUPPORTED LENGTH(cm) 105.00 105.00 120.94 120.94
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 120.57 120.57 134.53 134.53
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 4774.54 4774.54 3859.19 3859.19
(kg)
FACTOR OF SAFETY 76.26 66.54 3.66 5.29

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 2.77 2.77
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 6354.38 6354.38
(kg)
FACTOR OF SAFETY 111.32 97.61 9.41 6.64

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 93.80 81.84 5.57 6.13

___________________________________________________________________________________________________________________

52
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S H17 H18 H19 H20

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X006 case-X001 case-X006
(TENSION) case-X006 case-X006 case-X001 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 97. 99. 169. 64.
TOTAL TENSION(kg) 69. 128. 127. 21.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00 50x50x4.00 50x50x4.00
RADIUS OF GYRATION(cm) .87 .87 .97 .97
UNSUPPORTED LENGTH(cm) 105.00 105.00 160.81 160.81
CURVE NUMBER 5 5 5 5
SLENDERNESS RATIO KL/R 120.57 120.57 154.92 154.92
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47 3.88 3.88
ULTIMATE COMPRESSION STRENGTH 4774.54 4774.54 3253.91 3253.91
(kg)
FACTOR OF SAFETY 49.04 48.25 19.31 50.92

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77 3.18 3.18
ULTIMATE TENSILE STRENGTH 6354.38 6354.38 7294.92 7294.92
(kg)
FACTOR OF SAFETY 91.63 49.79 57.64 346.68

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S. 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64 5872.64 5872.64
(kg)
FACTOR OF SAFETY 60.32 46.02 34.85 91.91

___________________________________________________________________________________________________________________

53
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

___________________________________________________________________________________________________________________
D E T A I L S H21 H22

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X008 case-X008
(TENSION) case-X001 case-X006

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 86. 18.
TOTAL TENSION(kg) 81. 21.

_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE
SECTION 45x45x4.00 45x45x4.00
RADIUS OF GYRATION(cm) .87 .87
UNSUPPORTED LENGTH(cm) 105.00 105.00
CURVE NUMBER 5 5
SLENDERNESS RATIO KL/R 120.57 120.57
SECTIONAL AREA (GROSS)(sq.cm) 3.47 3.47
ULTIMATE COMPRESSION STRENGTH 4774.54 4774.54
(kg)
FACTOR OF SAFETY 55.39 259.18

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 2.77 2.77
ULTIMATE TENSILE STRENGTH 6354.38 6354.38
(kg)
FACTOR OF SAFETY 78.83 299.48

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S. 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14 12711.14
(kg)
ULTIMATE BEARING STRENGTH 5872.64 5872.64
(kg)
FACTOR OF SAFETY 68.13 276.77

___________________________________________________________________________________________________________________

54
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

_______________________________________________________________________________________________________________________

-: Main Arms :-
___________________________________________________________________________________________________________________
D E T A I L S B1 B2 B3

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X006 case-X003 case-X005
(TENSION) case-X006 case-X010 case-X010

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 6764. 5181. 6195.
TOTAL TENSION(kg) 3737. 4394. 4114.
_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 65x65x6.00 60x60x6.00 60x60x6.00
RADIUS OF GYRATION(cm) 1.26 1.15 1.15
UNSUPPORTED LENGTH(cm) 145.60 142.19 138.79
CURVE NUMBER 2 6 6
SLENDERNESS RATIO KL/R 116.67 122.24 120.42
SECTIONAL AREA (GROSS)(sq.cm) 7.44 6.84 6.84
ULTIMATE COMPRESSION STRENGTH 10792.60 9187.26 9430.86
(kg)
FACTOR OF SAFETY 1.60 1.77 1.52

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 5.34 4.74 4.74
ULTIMATE TENSILE STRENGTH 13611.66 12082.26 12082.26
(kg)
FACTOR OF SAFETY 3.64 2.75 2.94

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 4.S.S. 2.S.S. 4.S.S.
ULTIMATE SHEARING STRENGTH 25422.27 12711.14 25422.27
(kg)
ULTIMATE BEARING STRENGTH 17617.92 8808.96 17617.92
(kg)
FACTOR OF SAFETY 2.60 1.70 2.84

___________________________________________________________________________________________________________________

55
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

_______________________________________________________________________________________________________________________

-: Arm Tops :-
___________________________________________________________________________________________________________________
D E T A I L S T1 T2 T3

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X007 case-X010 case-X009
(TENSION) case-X011 case-X011 case-X011

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 1303. 2605. 2055.
TOTAL TENSION(kg) 3772. 3688. 3874.
_________________________________________________________________________________________________________________
SECTION TYPE M:---SINGLE M:---SINGLE M:---SINGLE
SECTION 55x55x4.00 55x55x4.00 55x55x4.00
RADIUS OF GYRATION(cm) 1.06 1.06 1.06
UNSUPPORTED LENGTH(cm) 154.93 151.78 147.18
CURVE NUMBER 6 6 6
SLENDERNESS RATIO KL/R 136.09 134.26 131.59
SECTIONAL AREA (GROSS)(sq.cm) 4.22 4.22 4.22
ULTIMATE COMPRESSION STRENGTH 4586.57 4712.36 4905.11
(kg)
FACTOR OF SAFETY 3.52 1.81 2.39

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.52 3.52 3.52
ULTIMATE TENSILE STRENGTH 8074.88 8074.88 8074.88
(kg)
FACTOR OF SAFETY 2.14 2.19 2.08

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 3.S.S. 3.S.S. 3.S.S.
ULTIMATE SHEARING STRENGTH 19066.70 19066.70 19066.70
(kg)
ULTIMATE BEARING STRENGTH 8808.96 8808.96 8808.96
(kg)
FACTOR OF SAFETY 2.34 2.39 2.27

___________________________________________________________________________________________________________________

56
ASTER
Client SANIMA HYDRO AND ENGINEERING (P.) LIMITED Tower Type C Sreedhar
Designed by
MAI HYDROPOWER 132 KV_SC TRANSMISSION LINE Date 08/06/13
Project Name PROJECT Approved by Muthukrishnan
Rev 01

_______________________________________________________________________________________________________________________

-: Peak Memb :-
___________________________________________________________________________________________________________________
D E T A I L S P1

___________________________________________________________________________________________________________________
DESIGN CRITERIA (COMPRESSION) case-X002
(TENSION) case-X009

_________________________________________________________________________________________________________________
TOTAL COMPRESSION(kg) 5103.
TOTAL TENSION(kg) 4894.
_________________________________________________________________________________________________________________
SECTION TYPE H:---SINGLE
SECTION 50x50x6.00
RADIUS OF GYRATION(cm) .96
UNSUPPORTED LENGTH(cm) 95.01
CURVE NUMBER 1
SLENDERNESS RATIO KL/R 98.97
SECTIONAL AREA (GROSS)(sq.cm) 5.68
ULTIMATE COMPRESSION STRENGTH 11506.28
(kg)
FACTOR OF SAFETY 2.25

___________________________________________________________________________________________________________________
SECTIONAL AREA (NET)(sq.cm) 3.58
ULTIMATE TENSILE STRENGTH 12959.60
(kg)
FACTOR OF SAFETY 2.65

___________________________________________________________________________________________________________________
NO OF BOLTS 16.00 mm 2.S.S.
ULTIMATE SHEARING STRENGTH 12711.14
(kg)
ULTIMATE BEARING STRENGTH 12138.24
(kg)
FACTOR OF SAFETY 2.38

___________________________________________________________________________________________________________________

57
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

LOAD TREE DRAWINGS

58
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

7. LOAD TREE DRAWINGS

59
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

60
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

61
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

62
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

FOUNDATION FORCES

63
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

8. FOUNDATION FORCES:
NORMAL TOWER -3m BE:-

NORMAL CONDITION BROKEN WIRE CONDITION


TYPE OF FORCE UNIT(kgs) UNIT(kgs)
COMPRESSION 18240 26055
UPLIFT 16801 24430
LONGITUDINAL SHEAR 486 1513
TRANSVERSE SHEAR 50 1434

NORMAL TOWER +0m BE:-

NORMAL CONDITION BROKEN WIRE CONDITION


TYPE OF FORCE UNIT(kgs) UNIT(kgs)
COMPRESSION 19209 26989
UPLIFT 17328 24947
LONGITUDINAL SHEAR 578 1437
TRANSVERSE SHEAR 32 1238

NORMAL TOWER +3m BE:-

NORMAL CONDITION BROKEN WIRE CONDITION


TYPE OF FORCE UNIT(kgs) UNIT(kgs)
COMPRESSION 19845 27610
UPLIFT 17840 25442
LONGITUDINAL SHEAR 642 1644
TRANSVERSE SHEAR 423 1323

NORMAL TOWER +12m BE:-

NORMAL CONDITION BROKEN WIRE CONDITION


TYPE OF FORCE UNIT(kgs) UNIT(kgs)
COMPRESSION 21827 29644
UPLIFT 19074 26849
LONGITUDINAL SHEAR 687 1361
TRANSVERSE SHEAR 213 905

NOTE: 1) ALL THE ABOVE FORCES ARE IN KGS WITHOUT FOS.


2) COMPRESSION AND UPLIFT ARE ALONG THE TOWER SLOPE.
3) F.O.S: 1.8 (NORMAL & BROKEN CONDITION).

64
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

LINE DIAGRAM

65
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

9. LINE DIAGRAM

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
SINGLE LINE DRAWING (NT-3 M BE) AST/IBO/TL/132KV/C 0

66
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
SINGLE LINE DRAWING (+/-0M BE & +3 M BE) AST/IBO/TL/132KV/C 0

67
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
SINGLE LINE DRAWING (+12 M BE) AST/IBO/TL/132KV/C 0

68
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
SINGLE LINE DRAWING (+3 M LE & +4.5M LE) AST/IBO/TL/132KV/C 0

69
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
SINGLE LINE DRAWING (+6 M LE & +7.5M LE) AST/IBO/TL/132KV/C 0

70
ASTER
SANIMA HYDRO AND ENGINEERING (P.)
Client Tower Type C Sreedhar
LIMITED Designed by
MAI HYDROPOWER 132 KV_SC Date 08/06/13
Project Name TRANSMISSION LINE PROJECT Approved by Muthukrishnan
Rev 01

10. CLEARANCE DIAGRAM

NAME SIGN DATE FL. NAME


DESIGNED SREEDHAR 27.03.13
CAD SREEDHAR 27.03.13 132kV
PROJECT CHECKED MUTHU 27.03.13
MHP 132KV TRANSMISSION LINE ALL DIMENSIONS ARE IN MM SCALE
(TYPE-C TOWER) PATH = NTS
TITLE DWG NO REV
CLEARANCE DRAWING AST/IBO/TL/132KV/C 0

71

Вам также может понравиться