Cortec

Information required with Order :

Variants Order Number


1-4 5 6 7
Model Type
Feeder Management Protection IED - Directional P14D

Application
Adapted to 20TE case A
Base B
Small Generator G
Load / Line Management L
HIF (SEF CT only) Z
PWH (Wattmetric Directional Earthfault) (Standard Earth CT only) H

Current/Voltage Transformers
Standard Earth CT 1
SEF CT 2

Hardware Options Case


EIA RS485/IRIG-B (demodulated) 20TE/30TE 1
EIA RS485/IRIG-B (demodulated) and Ethernet - Single channel Fibre/Copper (setting configurable as Failover*) 30TE 6
EIA RS485/IRIG-B (demodulated) and EIA RS485 30TE 8
EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as Failover) 30TE/40TE A
EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as Failover) 30TE/40TE B
EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as RSTP) 30TE/40TE C
EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as RSTP) 30TE/40TE D
EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as PRP or HSR) 30TE/40TE E
EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as PRP or HSR) 30TE/40TE F
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as Failover) 40TE G
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as Failover) 40TE H
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as RSTP) 40TE J
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as RSTP) 40TE K
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as PRP or HSR) 40TE L
40TE only - EIA RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as PRP or HSR) 40TE M

I/O Options Case


Standard (8 logic inputs + 8 relay outputs) 20TE/30TE
Total (11 logic inputs + 12 relay outputs) 30TE/40TE
Total (11 logic inputs + 12 relay outputs) suitable for trip circuit supervision 30TE/40TE
Total (13 logic inputs + 12 relay outputs) 30TE/40TE
Total (3 logic inputs + 4 relay outputs) 20TE
Total (6 logic inputs + 8 relay outputs) suitable for trip circuit supervision 30TE
Total (10 logic inputs + 12 relay outputs) suitable for trip circuit supervision 40TE
Total (12 logic inputs + 12 relay outputs) suitable for trip circuit supervision 40TE

Communication protocol
Courier
Modbus
IEC60870-5-103 (VDEW)
DNP3.0
IEC 61850 over Ethernet and Courier via rear RS485
IEC 61850 over Ethernet and IEC60870-5-103 via rear RS485
DNP3.0 over Ethernet and Courier via rear RS485
IEC 61850 over Ethernet and Modbus via rear RS485
IEC 61850 over Ethernet and DNP3.0 via rear RS485

Case
20TE Flush (no function keys, 4 programmable LEDs)
30TE Flush (3 function keys with LEDs, 8 programmable LEDs)
Software only
30TE Flush (Adapted field voltage for KCEG retrofit)
30TE Flush (without field voltage jumpering for KCEG retrofit)
30TE Flush (Additional shorting link)
40TE Flush (3 function keys with LEDs, 8 programmable LEDs)

Language
Multilingual (English, French, German, Spanish)
Multilingual (English, Russian, Italian, Portuguese)
Chinese, English or French via HMI, with English or French only via Communications port

Software Reference
Unless specified the latest version will be delivered

Customisation / Regionalisation
Default
Customer specific
With frequency function (Model P14DB in 20TE Case only)

Hardware design suffix


Initial release

Page 3 of 8 416002224.xls 04/10/2019


Cortec

8 9 10 11 12-13 14 15

A
B
C
D
E
F
H
J

1
2
3
4
6
7
8
9
A

B
C
0
3
5
6
D

0
6
C

**

0
A
F

Page 4 of 8 416002224.xls 04/10/2019


Configurator

1-4 5 6 7 8 9 10 11 12-13 14 15

P14D B 1 1 A 1 C 0 61 0 A
Model Type
P14D
Feeder Management Protection IED - Directional
Application Version

Adapted to 20TE case B


Base
Current/Voltage transformers
Small Generator
10P14D01-1 P14D DIRECTIONAL PHASE OVERCURRENT AND EARTH FAULT (8 I/P & 8 O/P)

1
Standard
LoadOptions
Hardware / Line Earth CT
Management
SEF
HIF CT CT only) 50Hz
(SEF
EIA RS485/IRIG-B Applications Only
(demodulated)
PWHRS485/IRIG-B
EIA (Wattmetric Directional Earthfault)
(demodulated) (Standard
and Ethernet Earthchannel
- Single CT only)Fibre/Copper (setting configurable as Failover)
EIA RS485/IRIG-B (demodulated) and EIA RS485 1

EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as Failover)
EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as Failover)
EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as RSTP)
I/O Options

Standard
EIA RS485/IRIG-B (8 logic inputs + 8 relay and
(demodulated) outputs)
Dual Redundant Fibre A
Ethernet - 2x multimode fibre (setting configurable as RSTP)
Total (11 logic inputs
EIA RS485/IRIG-B
Communications Protocol
+ 12 relay outputs)
(demodulated) and Dualsuitable for trip
Redundant circuitEthernet
Copper supervision
- 2x RJ45 Copper (setting configurable as PRP or HSR)
Total
EIA
Courier (13 logic inputs
RS485/IRIG-B + 12 relay outputs)
(demodulated) and Dual Redundant Fibre 1 Ethernet - 2x multimode fibre (setting configurable as PRP or HSR)
Total
EIA RS485,
Modbus
Case
(6 logic EIA inputs + 8 relay outputs)
RS485/IRIG-B suitableand
(demodulated) forDual
trip circuit supervision
Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as Failover)
EIA RS485, EIA RS485/IRIG-B
IEC60870-5-103 (VDEW)keys, 4(demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as Failover)
20TE
EIA Flush (no function programmable LEDs)
RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Copper Ethernet - 2x RJ45 Copper (setting configurable as RSTP)
C
DNP3.0
30TE Flush (3
EIA RS485,
Language EIAfunction keys with
RS485/IRIG-B LEDs, 8 programmable
(demodulated) LEDs)
and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as RSTP)
Software
EIA RS485, onlyEIA RS485/IRIG-B (demodulated) and Dual Redundant 0 Copper Ethernet - 2x RJ45 Copper (setting configurable as PRP or HSR)
Multilingual
30TE (English,
Flush (Adapted French, German,
field voltage Spanish)
for KCEG retrofit)
EIA Version
Software
RS485, EIA RS485/IRIG-B (demodulated) and Dual Redundant Fibre Ethernet - 2x multimode fibre (setting configurable as PRP or HSR)
Multilingual
30TE Flush (without (English, field
Russian, Italian,
voltage Portuguese)
jumpering for KCEG retrofit)
61: TEFDEnglish
Chinese, (P14DZ), or SW Enhancements
French via HMI,
30TE Flush (Additional shorting link)with English or French only via Communications port
60: VVS (P14DG/L/Z), Switch Control, SW Enhancements 61
57: RSTP and software enhancement
56: Redundancy Ethernet protocol options
Customisation / Regionalisation
55: Software enhancement, mixed protocol options 0
Default
54:
Design
Russian optos included
Suffix

Customer
53:
InitialPWH specific
(Wattmetric
release Directional Earthfault)
A

52: Chinese language support


51: 30TE voltage model, 20TE directional model and neutral admittance
50: Initial release
59: For SEC only

Page 5 of 8 416002224.xls 04/10/2019


Software Upgrade

REQUEST FOR SOFTWARE UPGRADE

ALL SOFTWARE UPGRADES ARE DEDICATED TO SPECIFIC RELAY SERIAL NUMBERS SO ALL REQUIREMENTS
MUST BE SUBMITTED BY EMAIL QUOTING E14D-SOFTWARE, WITH THIS DOCUMENT AS AN ATTACHMENT, TO
automationrepair.uk@alstom.com., WHO WILL DEAL WITH YOUR REQUEST.

Character/digit # 1 2 3 4 5 6 7 8 9 10 11 12 &13 14 15
Cortec Code of existing model variant : P 1 4 D

Cortec Code of required model variant : Derived by


option selection from the 'Configurator' worksheet in P 1 4 D B 1 1 A 1 C 0 61 0 A
this workbook

Note: P14DA cannot be upgraded for other application based software models

Character/digit # 1 2 3 4 5 6 7 8
Serial number(s) of existing model variant(s) : 3
3
3
3
3
3
3
3
3
3
3

If more than 10 relays (by serial number) are to be updated, please submit a supplementary list of the additional
serial numbers

Version : A1 15/08/12

Page 6 of 8 416002224.xls 04/10/2019


Documents

P14DB11A1C0610A

External Connection Diagram : 10P14D01-1


P14D DIRECTIONAL PHASE OVERCURRENT AND EARTH FAULT (8 I/P & 8 O/P)

Page 7 of 8 416002224.xls 04/10/2019


Master Text

P14DB11A1C0610A
Feeder Management Protection IED - Directional
Application Version :
Base
In/Vn Rating :
Standard Earth CT
Hardware Options :
EIA RS485/IRIG-B (demodulated)
I/O Options :
Standard (8 logic inputs + 8 relay outputs)
Communication protocol :
Courier
Case :
30TE Flush (3 function keys with LEDs, 8 programmable LEDs)
Languages :
Multilingual (English, French, German, Spanish)
Software Version :
61
Setting Files :
Default
Design Suffix
Initial release

Issue :
Version : A Final Release, see CID SKEL-8ZBBRF - 22/10/2012
B Correction to document lookup - was referencing 10P14N - 20/12/2012
C SEF & Ethernet options released by CID SKEL-94EDHZ - 29/01/2013
D '51' Software released by CID ISTE-9BVEP5 - 30/09/2013
E Reinstatement of Retrofit option without field voltage jumpering - 23/10/2013
F '52' released by CID CWUU-9DV43R - 02/12/2013
G '53' released by CID FPAO-9HXJ82 - 12/04/2014
H Correction to current/voltage transformers cell - 17/04/2014
I P14DB 20TE model released by CID FPA9KDJX3 - 30/05/2014
J Correction to case lookup listbox - 02/07/2014
K '54' released by CID FPAO-9R9KZX - 04/12/2014
L Further corrections to case lookup listbox - 11/09/2015
M '55' software released by CID FPAO-A3YN65 - 23/11/2015
N Master text correction on Cell A4 above - 11/01/2016
O '56' software released by CID OBUN-A7AEGW - 23/02/2016
P Protocol descriptions updated - 09/03/2016
Q 57' software released by CID FPAO-A9MJPZ - 12/05/2016
Q '57' software released by CID FPAO-A9MJPZ - 12/05/2016
R '60' software released by CID FPAO-AGUD36 - 04/01/2017
S P14DH now has additional protocol options - see CID GBER-AK4M34 - 06/05/2017
T 61' software released by CID GBER-ALKLW2 - 12/05/2017
U 40TE models released by CID005146, '59' software released by CID005125 - 11/07/2017
V Lookup error corrected in 20TE model - 31/08/2017

Page 8 of 8 416002224.xls 04/10/2019