Distance protection principles


SIPROTEC5 - Application and exercises of system protection

21
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Contents

■ Short circuit
■ Distance measurement (principle)
■ All you need is X
■ Load- and short circuit impedance
■ Pickup
■ Directional measurement
■ Guideline for zone 1 setting
■ Redundancy
■ Signal transmission

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 2
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit

Example
Single phase diagram of 3 phase system, only X considered
■ Source VN (L-L) = 20 kV, Ik = 5,77 kA
■ Line 1 4 km zu 0,5 Ω/km
■ Line 2 33% of 3km at 0,5 Ω/km
■ What is the short circuit current?
■ Which voltages can be measured at the busbars?
XSource Xline1 k·Xline2

ISC ISC
VSource

ISC = VS/(Xsource+Xline1+k·Xline2)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 3
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit

VLG = 11.54kV 0kV


2Ω 2Ω 0.5Ω 1Ω

VLG = 2.56kA∙(2Ω +0.5Ω) VLG = 2.56kA∙0.5Ω 2.56kA


= 6.4kV = 1.28kV

Xmeas = 2.5Ω Xmeas = 0.5Ω

XSet = 2Ω XSet = 1.5Ω

=> No Trip => Trip

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 4
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance measurement (principle phase- phase)

IL1 ZL
ZL = RL + j XL
IL2
ZE = RE +j XE
IL3

IE ZE

UL1 UL2 UL3


6 loops: 3 phase- phase loops and
3 phase- ground loops

phase- phase- loop UL1-L2 = ZL ( IL1 - IL2)

Measured current
measured voltage
The same applies to the remaining loops

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 5
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance measurement (principle phase- ground)

IL1 ZL
ZL = RL + j XL
IL2
ZE = RE +j XE
IL3
Phase- ground- loop
IE ZE
UL1 = IL1 · ZL - IE · ZE
UL1 UL2 UL3
IL1, IE measured current
This equation cannot be solved! Measured voltage

Thus ZE/ZL is used as setting value

XE/XL = 1/3 * (X0/XL – 1) The same applies to the


remaining loops
RE/RL = 1/3 * (R0/RL – 1)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 6
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zero sequence impedance for cables

The zero sequence impedance for a cable is hardly to be calculated

• Z0 depends on enviroment conditions such as:


• Other parallel cables, pipelines, rails etc.

• At cables with steel band, Z0 depends on actual current flowing


• Magnatizing of steel band

For correct values:


Z0 should be measured on site at the cables!

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 7
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
All you need is X

■ The magnitude of the impedance is


simply calculated from the
magnitudes of current and voltage
X
■ Reaktance und resistance were then
calculated by angle measurement,
which can be critical
■ Errors in this angle measurement will
lead to big errors in R but only small
errors in X
■ Therefor only X is used for distance
measurement

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 8
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Typical values for overhead lines and cables

R’L1 X’L1 jL1 R’L0 X’L0 jL0 R’LE X’LE R’LE/ X’LE/
R’L1 X’L1
W/km W/km o el. W/km W/km o el. W/km W/km

Overheadline 380 kV
earthing wire 0,018 0,25 86 0,17 0,94 80 0,053 0,23 2,94 0,92
4-times bundle
4´Al/St 435/55
Overheadline 220 kV
earthing wire 0,058 0,30 79 0,22 0,99 77 0,053 0,23 0,91 0,77
2-times bundle
2´Al/St 265/35
Overheadline 110 kV
earthing wire 0,071 0,38 79 0,22 1,10 79 0,050 0,24 0,70 0,63
Al/St 435/35

Overheadline 20 kV
Without earthing wire 0,31 0,37 50 0,53 1,58 71 0,073 0,40 0,24 1,08
95 mm2 Al
cable 400 kV
Single phase-oil isol. 0,020 0,22 85 0,049 0,11 66 0,01 -0,036 0,50 -0,16
Cable 3´1´1200 mm2 Cu
Cable110 kV
Gas pressure cablle 0,090 0,14 57 0,39 0,16 22 0,1 0,007 1,11 0,05
40 mm2 Cu
Cable 20 kV
3-phase lead isolated 0,16 0,12 37 1,4 0,25 10 0,41 0,043 3,42 0,36
3´120 mm2 Cu

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 9
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Electromechanicle Relay R1Z23a
(application for high voltage feeder)

Electromechanicle
relays only provides
circle diagrams
I> pickup
L1, L2, L3, M

Time
measurement Alarm
indications ZL
X
circle

Moving coil relay RLB


D: Distance
N: Direction
R

direction

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 10
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Load and short circuit impedance

X
Short circuit range
ZL
Distance protection characteristic

ZLF2 RF ZF2
ZL
ZLoad ZLF1
ZLF2
ZLF1 RF
ZF1
RF RF ZLoad
jL
j F1 F2
jSC1 SC2
D
R

Short circuit
in
reverse
Load
direction range

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 11
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection: Adaptive measuring method

n Least Square estimator with


variance control
n Adaptive Zone reach

Z1

Estimator 1 (n=5)
Estimator 2 (n=6)
Estimator 3 (n=8)
Estimator 4 (n=10)
Estimator 5 (n=13)
Estimator 6 (n=15)
Normal 1 (n = 21)
Normal 2 (n = 26)
Normal 3

0 10 20 30 40 50 60 70 80
Jump detected ms

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 12
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection,
Typical operating time characteristic

30

25
Operating time (ms) 20

15

10

0
10 20 30 40 50 60 70 80 90 100

Short-circuit data: Fault location in % zone reach


SIR = 26
f = 50 Hz
Fault: L1-E
5 shots per fault case Information: Trip times with high speed contacts
Fault inception: 0° ... 90° approx. 5 ms shorter
extension module IO209 required

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 13
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zone 1 - Setting guidelines

X
Line characteristic

X1
Recommendation for Zone 1 settings:
X1 » 80...90% of line reactance
0,5 * X < R < 2*X important!
R1
● R
1, R1E = half load impedance (if possible)
t1 = 0 ms
R1E
R

If the measured impedance is within the set characteristic


and the set time has expired, a TRIP command is issued

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 14
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Redundancy

■ Locale redundancy
■ Z2 for faults of 80% … 100% of the line

■ Remote redundancy
■ Z2 … ZX für

breaker fail or protection fail

Zones can be added


in 7SA8
(function points needed!)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 15
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Fault detection techniques

Over- current fault detection


Voltage dependant X
over- current fault detection

U Voltage and
angle dependant
over- current
fault detection
R
Impedance
fault
detection

I> Ij> I >> I

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 16
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Reach of overcurrent starter
ph-ph fault as an example

ISC(2) [kA]
110 kV
2,5 net SCC(3)" = 1500 MVA

40 MVA
uT = 15 %
2,0 20 kV

400/1 A D I >start = 1,5 · IN = 600 A


1,5
UN · 1,1
ISC(2) = ISC
OH-line
2 · (ZS + ZS + ZL' · l) 95/15 Al/St
N T
1,0
Z'L = 0,483 W/km
I >start = 600 A
0,5

10 20 30 40 50 60 l [km]
reach of OC starter
ca. 35 km

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 17
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Determination of fault direction

Current area for Impedance area for


forward faults X forward faults
USC
ISC ZSC
jSC
jSC
R

ISC Z'SC
Current area for Impedance area for
reverse faults reverse faults

current / voltage diagram impedance diagram

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 18
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Alternatives for the Directional Measurement

~ ~ ~
~ ~ ~
fault L1-E
~ ~ ~
Zgrid Relay Zline
VL1
Vf

VN If
VL3
VL3 VL2 VL2
fault-free VL1
faulty phase voltage
Vf
VN
If If

VL3 VL2 VL3 VL2


Vdir
healthy-phase voltage voltage memory

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 19
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection schemes

Why use tele- protection?

1 2

Faults in this area Faults in this area Faults in this area


are cleared after t2 are cleared without additional are cleared after t2
at line end 2 time delay at both line ends at line end 1

Faults on approximately 70% of the line length are cleared


without delay at both line ends

Faults in the remaining 30% of the line length


are cleared with a time delay.

Remedy: Exchange of information between the two line ends

Required: Communication channel (PLC, microwave radio, fibre optic, etc.)


Tele- protection logic (dedicated device or internal
function in numerical protection devices)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 20
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme - Permissive Overreach

Z1 Z1B or Z2

A B

Z1B or Z2
Z1

Trip
Trip

Trip Z1 and ³1 ³1 Trip Z1 and


further zones further zones

& &
TS TS
& ³1 ³1 &
S S
R R
Z1B Z1B
T1B T1B
(A) (B)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 21
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme

What is different in setting of teleprotection system compared to SIPROTEC 4?

SIPROTEC 4 SIPROTEC 5

Zone Z1B must be used for Every zone (even more than one) can be
teleprotection schemes used for teleprotection schemes

Zone Z1B will trip only, in combination Each zone will trip with the set trip delay
with teleprotection schemes time

Therefore, typical trip time setting is Therefore, typical trip time setting for used
0ms for Z1B teleprotection zone should not be 0ms

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 22
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme

How to set setting of teleprotection system in SIPROTEC 5 similar to SIPROTEC 4?

•Add new stage


•Rename new stage to Z1B
•Use this zone Z1B for teleprotection scheme
•Set delay time for Z1B stage to oo (infinite)

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 23
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp