Contents
■ Short circuit
■ Distance measurement (principle)
■ All you need is X
■ Load- and short circuit impedance
■ Pickup
■ Directional measurement
■ Guideline for zone 1 setting
■ Redundancy
■ Signal transmission
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 2
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit
Example
Single phase diagram of 3 phase system, only X considered
■ Source VN (L-L) = 20 kV, Ik = 5,77 kA
■ Line 1 4 km zu 0,5 Ω/km
■ Line 2 33% of 3km at 0,5 Ω/km
■ What is the short circuit current?
■ Which voltages can be measured at the busbars?
XSource Xline1 k·Xline2
ISC ISC
VSource
ISC = VS/(Xsource+Xline1+k·Xline2)
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 3
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 4
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance measurement (principle phase- phase)
IL1 ZL
ZL = RL + j XL
IL2
ZE = RE +j XE
IL3
IE ZE
Measured current
measured voltage
The same applies to the remaining loops
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 5
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance measurement (principle phase- ground)
IL1 ZL
ZL = RL + j XL
IL2
ZE = RE +j XE
IL3
Phase- ground- loop
IE ZE
UL1 = IL1 · ZL - IE · ZE
UL1 UL2 UL3
IL1, IE measured current
This equation cannot be solved! Measured voltage
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 6
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zero sequence impedance for cables
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 7
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
All you need is X
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 8
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Typical values for overhead lines and cables
R’L1 X’L1 jL1 R’L0 X’L0 jL0 R’LE X’LE R’LE/ X’LE/
R’L1 X’L1
W/km W/km o el. W/km W/km o el. W/km W/km
Overheadline 380 kV
earthing wire 0,018 0,25 86 0,17 0,94 80 0,053 0,23 2,94 0,92
4-times bundle
4´Al/St 435/55
Overheadline 220 kV
earthing wire 0,058 0,30 79 0,22 0,99 77 0,053 0,23 0,91 0,77
2-times bundle
2´Al/St 265/35
Overheadline 110 kV
earthing wire 0,071 0,38 79 0,22 1,10 79 0,050 0,24 0,70 0,63
Al/St 435/35
Overheadline 20 kV
Without earthing wire 0,31 0,37 50 0,53 1,58 71 0,073 0,40 0,24 1,08
95 mm2 Al
cable 400 kV
Single phase-oil isol. 0,020 0,22 85 0,049 0,11 66 0,01 -0,036 0,50 -0,16
Cable 3´1´1200 mm2 Cu
Cable110 kV
Gas pressure cablle 0,090 0,14 57 0,39 0,16 22 0,1 0,007 1,11 0,05
40 mm2 Cu
Cable 20 kV
3-phase lead isolated 0,16 0,12 37 1,4 0,25 10 0,41 0,043 3,42 0,36
3´120 mm2 Cu
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 9
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Electromechanicle Relay R1Z23a
(application for high voltage feeder)
Electromechanicle
relays only provides
circle diagrams
I> pickup
L1, L2, L3, M
Time
measurement Alarm
indications ZL
X
circle
direction
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 10
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Load and short circuit impedance
X
Short circuit range
ZL
Distance protection characteristic
ZLF2 RF ZF2
ZL
ZLoad ZLF1
ZLF2
ZLF1 RF
ZF1
RF RF ZLoad
jL
j F1 F2
jSC1 SC2
D
R
Short circuit
in
reverse
Load
direction range
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 11
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection: Adaptive measuring method
Z1
Estimator 1 (n=5)
Estimator 2 (n=6)
Estimator 3 (n=8)
Estimator 4 (n=10)
Estimator 5 (n=13)
Estimator 6 (n=15)
Normal 1 (n = 21)
Normal 2 (n = 26)
Normal 3
0 10 20 30 40 50 60 70 80
Jump detected ms
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 12
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection,
Typical operating time characteristic
30
25
Operating time (ms) 20
15
10
0
10 20 30 40 50 60 70 80 90 100
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 13
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zone 1 - Setting guidelines
X
Line characteristic
X1
Recommendation for Zone 1 settings:
X1 » 80...90% of line reactance
0,5 * X < R < 2*X important!
R1
● R
1, R1E = half load impedance (if possible)
t1 = 0 ms
R1E
R
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 14
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Redundancy
■ Locale redundancy
■ Z2 for faults of 80% … 100% of the line
■ Remote redundancy
■ Z2 … ZX für
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 15
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Fault detection techniques
U Voltage and
angle dependant
over- current
fault detection
R
Impedance
fault
detection
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 16
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Reach of overcurrent starter
ph-ph fault as an example
ISC(2) [kA]
110 kV
2,5 net SCC(3)" = 1500 MVA
40 MVA
uT = 15 %
2,0 20 kV
10 20 30 40 50 60 l [km]
reach of OC starter
ca. 35 km
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 17
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Determination of fault direction
ISC Z'SC
Current area for Impedance area for
reverse faults reverse faults
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 18
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Alternatives for the Directional Measurement
~ ~ ~
~ ~ ~
fault L1-E
~ ~ ~
Zgrid Relay Zline
VL1
Vf
VN If
VL3
VL3 VL2 VL2
fault-free VL1
faulty phase voltage
Vf
VN
If If
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 19
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection schemes
1 2
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 20
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme - Permissive Overreach
Z1 Z1B or Z2
A B
Z1B or Z2
Z1
Trip
Trip
& &
TS TS
& ³1 ³1 &
S S
R R
Z1B Z1B
T1B T1B
(A) (B)
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 21
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme
SIPROTEC 4 SIPROTEC 5
Zone Z1B must be used for Every zone (even more than one) can be
teleprotection schemes used for teleprotection schemes
Zone Z1B will trip only, in combination Each zone will trip with the set trip delay
with teleprotection schemes time
Therefore, typical trip time setting is Therefore, typical trip time setting for used
0ms for Z1B teleprotection zone should not be 0ms
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 22
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme
Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 23
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp