6.1.1 SCOPE OF WORKS

Design, Supply, installation, Testing and Commissioning of 05 (Five) 132/33/11 kV Gas Insulated Switchgear
(GIS) and 132/33 kV (80/120MVA) & 33/11kV (20/28MVA) power transformer, indoor 132 kV, 33 kV and
11KV GIS, control, protection and civil works at Uttara 3rd Phase, Purbachal, Dumni, Gulshan/ Banani and
Aftabnagar on turnkey Basis.
The works covered by the Bid is design, supply, installation of 132/33/11KV Grid substations (132/33
KV plus 33/11KV) at Uttara 3rd Phase, Purbahal, Aftabnagar, Dumni and Gulshan/Banani under the
jurisdiction of DESCO on Turn Key basis.

The scope of plant and services include design, manufacture, quality assurance, inspection & testing,
packing for export, insurance & shipment to site, complete construction & installation, jointing,
terminating, bonding, earthing, painting, setting to work, site testing & commissioning, warranty for a
period of 365 days for all equipment, including all civil works.

The detail requirement is listed in the technical particulars and guarantee schedules in the technical
specification.

The scope also includes imparting training to DESCO Engineers on offered system.

The contractor is responsible for ensuring that all and any items of work required for the safe, efficient
and satisfactory completion and functioning of the works is included in the bid price whether they will
be described in the specification or not and this shall be called balance of plant.

The detailed scope of works for all new 132/33/11 kV grid substations are given below:
Installation of a new 132/33/11 kV GIS Sub-Station at Uttara 3rd Phase.
The scope of work under this turnkey bid is design, supply, delivery, installation, testing &
commissioning of a complete new 132/33/11kV Gas Insulated Switchgear (GIS) substation
at Uttara 3rd Phase, Dhaka.
The scope of work but not limited to; comprise with the following: -
• Design, supply, delivery, installation, testing and commission of a new indoor type
132kV GIS substation at Uttara 3rd Phase for two new line bays.
• Design, supply, delivery, installation, testing & commissioning of two 132/33 kV,
80/120 MVA three phase power transformers in Uttara 3rd Phase substation.
• Design, supply, delivery, installation, testing & commissioning of three 33/11 kV, 20/28
MVA three phase power transformers in Uttara 3rd Phase substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33 kV Air
insulated surge arresters for new power transformers.
• Design, supply, installation, testing & commissioning of associated local control panel,
metering panel, protection equipment for132 KV side of new 132/33kV power
transformers, line bays & bus-coupler bay, as above.
• Design, supply, installation and commission of substation automation system.
• Design, supply, installation and commission of CCTV with 6 cameras at 6 strategic
locations in the GIS building and substation area.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-5

• Design, supply, installation and commission of three new 132kV bus bar protection
equipment and synchronizing schemes for complete substation.
• Design, supply, installation, testing & commissioning of associated local control,
metering panel , protection equipment and substation automation system for 33kVside
of new 132/33kV power transformers, line bays & bus coupler bay.
• Design, supply, installation, testing & commissioning of 132 kV cable including 132kV
cable termination for two new power transformers at Uttara 3rd Phase (both GIS and
transformer ends).
• Design, supply, delivery, installation, testing & commissioning of three 33/11kV, 20/28
MVA three phase power transformers in at Uttara 3rd Phase substation.
• 33kV cable termination at transformer & 33 kV GIS end for two new power
transformers at Uttara 3rd Phase.
• Design, supply, delivery, installation, testing & commissioning of 11KV Air Insulated
Switchgear for at Uttara 3rd Phase substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV,33kV and 11
kV XLPE(Cu) cables with necessary cable sealing ends including one spare cable with
cable sealing ends (for each 132kV & 33kV) for connecting the 132/33kV transformer
at 132kV and 33kV GIS substation.
• Two sets indoor type Fibre Optic Multiplexer Equipment shall be installed for
protection & communication at Uttara 3rd Phase substation.
• One set new digital type telephone exchanges shall be installed at Uttara 3rd Phase
substation (24 subscribers and 24 trunks).
• Complete new set of DC and LVAC system with all necessary materials required for
the plant being installed with 50% spares for future use of 110V DC battery & battery
charger, 48V DC battery & battery charger, DC distribution board and LVAC
distribution board for new New Ramna substation.
• Design, supply, installation, testing & commissioning of fire fighting equipment for
power transformers & 132kV GIS Substation.
• Complete design, supply and construction of all civil items required for the outdoor
works suitable for switchyard foundations, transformer foundations, fire walls, oil pit,
access roads, cable trenches, septic tank, surfacing, drainage including switchyard
earthing & lightning protection, switchyard lighting etc.
• Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; fittings and flooring & finishes; air-
conditioning; emergency exit (staircase) and lighting for six storied GIS building
including control room and basement.
• The basement of control room building shall be used for power & control cables. The
ground floor shall be used for GIS equipment and the 1st floor shall be used for control
& protection panels; AC/DC distribution panels; battery and battery charger and office
room.
• Breaking of foundation/pucca structures, repair, fabrications etc. wherever necessary
and cleaning of the debris etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-6

BILL OF MATERIALS/ WORKS


Uttara 3rd Phase, 132/33/11 kV GIS Substation
Item
Description Quantity Remarks
No.
Design, manufacture, factory testing, carrying and handling up to the site of:
1 Power Transformers & Auxiliary Transformers
1.1 132/33 kV, 80/120 MVA Transformer with Network Equipment including 2 Nos.
1.2 33/0.4 kV 200 KVA Auxiliary Transformer with 33 kV surge Arresters and
2 Nos.
connection.
1.3 33/11 kV 20/28 MVA Transformer with Network Equipment. 3 Nos.
2 132 kV GIS Indoor Switchgear with Relay Control Panel
(Double Bus scheme to be fully equipped for termination of 132 kV 02 Line
Bays,132 kV 02 Transformer Bays, 03 additional spare Bay, 132 kV 01 Bus Coupler)
2.1 132 kV Underground line Circuit Bay. 2 Nos.
2.2 132 kV Transfromer Circuit Bay. 2 Nos.
2.3 132 kV Bus Coupler Circuit Bay. 1 Nos.
2.4 132 kV Underground Circuit Bay (Spare). 3 Nos.
2.5 132 kV Transfromer Circuit Bay. (Spare) 1 No.
3 33 kV GIS Indoor Switchgear with Relay Control Panel.
33 kV 1250A GIS indoor Breaker with 2500A Bus, 2500A Bus Section Breaker and
2500A incoming Breaker having (2 incoming, 1 Bus Section, 3 Transformer Feeder, 1 set
8 outgoing feeder & cubicles for 2 nos. 33 kV Bus PT and 2 nos. 33 kV incomer line
PT and 2 nos. spare Breaker)
3.1 33 kV, 2500A Incoming feeder. 2Nos.
3.2 33 kV Bus coupler. 1Nos.
3.3 33 kV Transformer Feeder. 3Nos.
3.4 33 kV, Outgoing feeder. 8Nos.
3.5 33 kV, 2500A Incoming feeder. (Spare) 1 No.
3.6 33 kV Bus PT. 2Nos.
3.7 33 kV Line PT. 2Nos.
4 11 kV Switchgear with CT & PT
11 kV Switchgear Panel for 3000 Amps. Bus with 23 nos. of Breaker (3 incoming, 2
1 set
Bus -section, 18 Feeder Breaker) together with 3 set of 11 kV Bus PT (s) and 3 Set of
Line PT.
4.1 11 kV, 2000 Amps, Incoming feeder from Transformer Feeder. 3 Nos
4.2 11kV, 3000 Amps, Bus coupler. 2Nos.
4.3 11 kV, 630 Amps, Outgoing feeder. 18Nos.
4.4 11 kV Bus PT. 3 Nos.
4.5 11 kV Line PT. 3 Nos.
4.6 11 kV Circuit Breaker (Spare). 2 Nos.
5 132 kV Underground Cable & Termination
132 kV Cable 1c x 800 mm² XLPE (Cu) for connection from 132kV GIS Breaker to
Transformer
5.1 132 kV cable, 1Cx 800 mm² XLPE (Cu) 0.5 KM
5.2 132 kV Cable Termination for above and Straight through joint. Lot
6 33 kV Underground Cable & Termination
6.1 33 kV Cable 1c x 800 mm² XLPE (Cu) for connection from grid transformer to
1.0 KM
33 kV Bus.
6.2 33 kV Cable 1c x 800 (500) mm² XLPE (Cu) for connection from 33 kV Bus to
0.5 KM
33/11 kV transformer.
6.3 33 kV Cable 3c x 95 mm² XLPE (Cu) for connection from 132/33 kV
1.0 km
Transformer to 33/0.4 kV auxiliary transformer.
6.4 33 kV Cable Termination for above and Straight through joint. 1 Lot
7 11 kV Underground Cable & Termination
1.5 KM
11 kV Cable 1x500 mm², XLPE (Cu ) for connection from power transformer to
Switch Gear (3 runs per phase) including termination (Indoor & Outdoor).

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-7

Item
Description Quantity Remarks
No.
8 Battery/Charger & AC/DC Distribution Panel
8.1 110 V Battery & Battery Charger with accessories 2 sets
8.2 48 V Battery & Battery Charger with accessories 2 sets
8.3 LV AC Distribution Panel 1 set
8.4 LV DC Distribution Panel 1 set
9 Control, Protection, Substation Automation & Metering
9.1 132 kV Underground line Circuit 2 Nos.
9.2 2 Nos.
132 kV Transformer Circuit
9.3 1 No.
132 kV Bus Coupler Circuit
9.4 3 Nos.
132 kV Spare Bay
9.5 1 No.
132 kV Busbar Protection Panel
9.6 33 kV Switchgear Panels 1 Set.
9.7 11 kV Switchgear Panels 1 Set.
9.8 Tariff Metering Panel 1 No.
10 Multicore Cable
Multicore Cable for control, protection, metering & power 1Lot
10.1
circuits.
11 Earthing & Lighting Protection.
Earthing & Lighting Protection System including grounding cable 1Lot
11.1
& accessories.
12 Surge Arrester & Connections
16.1132 kV single phase surge arresters and accessories. 24 Nos.
16.2 33 kV single phase surge arresters and accessories 42 Nos.
13 Communication Equipments/UHF 2 Sets
UHF Radio Equipment including antenna and base equipment
14 Fire Extinguishing Equipment
14.1 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 1 Set
fire (15 kg.)
14.2 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire 3 Set
(5 kg.)
14.3 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 3 Set
fire (2 kg.)
15 Steel Structure, Conductor, Insulator, Connector of 132KV, 33 KV & 11 KV L.S.
16 Air Conditioning Equipment (3 Tones Each) 3 Nos.
17 Solar System for grid Substation 4Kw
18 Lighting,Small power and ventilation
18.1 Lighting,Small power, and ventilation and emergency DC lighting for GIS & 1 No.
Control building
18.2 Lighting for outside building for security, roadway, switchyard and emergency 1 No.
DC lighting.
19 Fibre Optic cable along with each 132 kV circuit with Multiplexer Equipment 2 sets.
20 Civil Works, Building and foundation
20.1 To release the equipment and material from L.S.
port,rent,Charges,handling,carrying to thesite store ptior to installation
20.2 To Construct 3 Storied 132KV GIS Control room building with four storied Sq.m
foundation and Basement floor along with the facilities to electricity,lift,water
supply sewerage etc.
20.3 To Construct the foundation of the 05 (Five) power Transformer, 02(Two) L.S.
Station Transformers, Fire wall and the foundation of the supporting structrure
for cables (132KV, 33KV and 11KV) terminations on both side of the
transformers.
20.4 Installation of the grounding mesh including welding of conductors,connection
between mesh and different earthing points of equipments,construction of pit
with cover etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-8

Item
Description Quantity Remarks
No.
20.5 Security boundary wall Meter
20.6 Barbed Wire Fencing Meter
20.7 Approach/Internal road Meter
20.8 Surface Drain Meter
20.9 Construction of Cable trench (132kv,33kv,11kv) Meter
20.10 Covered Store & Godown Meter
20.11 Laying of gravel’s in the switchyard with associate works Cu.m
20.12 Switchyard electrification and boundary lighting L.S.
20.13 Security and Sentry Post Nos.
20.14 Transformer Blast Wall Sq.m
20.15 Septic Tank, Soak way Nos.
20.16 Rain water Rerserver Sq.m
21 Installation of the of the following equipment to the HV connections, LV connections
and grounding as required including relocations and transportation as indicated in the
bid:
21.1 132KV GIS(Indoor) Panel
21.2 33KV GIS (Indoor) Panel
21.3 11KV VCB Panel (23Panels) 1set
21.4 Power Transformer 132/33 kV 80/120 MVA 2 Nos.
21.5 Power Transformer 33/11 kV 20/28 MVA 3 Nos.
21.6 Auxiliary Transformer 33/0.4 kV 200 KVA and the supporting structures. 2 Nos.
21.7 132 kV, 33 kV and 11 kV Cable termination with the supporting structures. L.S
21.8 LV AC Distribution Panel 1 set
21.9 LV DC Distribution Panel 1 set
21.10 Battery and battery charger (110V and 48V) 4 sets
21.11 Surge Arrester (132KV,33KV) 1 set
21.12 Laying of 132KV, 33KV and11KV cables as required and their jointing
L.S.
(Inside substation).
21.13 Laying of LV cables, Control cables and their terminations. L.S.
21.14 Laying of Fiber Optic cables and their connections.
22 Installation of panel with Necessary equipment and other accessories for integrated
automotion system.
23 Others
23.1 To Perform Pre-commissioning test of all the equipments under the scope of
works indivisually and in conjuction and to commission them.
23.2 Submission of 05 (Five) sets as built drawing together with operation and
maintenance manual of installed equipment.
23.3 Miscellaneous necessary equipments/ works to complete the project
L.S.
successfully in all respect.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-9

Purbachal, 132/33/11 kV GIS Substation


The scope of work under this turnkey bid is design, supply, delivery, installation, testing &
commissioning of a complete new 132/33kV Gas Insulated Switchgear (GIS) substation at
Purbachal, Dhaka.
The scope of work but not limited to; comprise with the following: -
• Design, supply, delivery, installation, testing and commission of a new indoor type
132kV GIS substation at Purbachal.
• Design, supply, delivery, installation, testing & commissioning of two 132/33 kV,
80/120 MVA three phase power transformers in Purbachal substation.
• Design, supply, delivery, installation, testing & commissioning of three 33/11 kV, 20/28
MVA three phase power transformers in Purbachal substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33 kV Air
insulated surge arresters for new power transformers.
• Design, supply, installation, testing & commissioning of associated local control panel,
metering panel, protection equipment for132 KV side of new 132/33kV power
transformers, line bays & bus-coupler bay, as above.
• Design, supply, installation and commission of substation automation system.
• Design, supply, installation and commission of CCTV with 6 cameras at 6 strategic
locations in the GIS building and substation area.
• Design, supply, installation and commission of three new 132kV bus bar protection
equipment and synchronizing schemes for complete substation.
• Design, supply, installation, testing & commissioning of associated local control,
metering panel , protection equipment and substation automation system for 33kV side
of new 132/33kV power transformers, line bays & bus coupler bay.
• Design, supply, installation, testing & commissioning of 132 kV cable including 132kV
cable termination for two new power transformers at Purbachal (both GIS and
transformer ends) .
• 33kV cable termination at transformer & 33 kV GIS end for two new power
transformers at Purbachal.
• Design, supply, delivery, installation, testing & commissioning of 132kV,33kV and 11
kV XLPE(Cu) cables with necessary cable sealing ends including one spare cable with
cable sealing ends (for each 132kV & 33kV) for connecting the 132/33kV transformer
at 132kV and 33kV GIS substation.
• Two sets indoor type Fibre Optic Multiplexer Equipment shall be installed for
protection & communication at Purbachal substation.
• One set new digital type telephone exchanges shall be installed at Purbachal substation
(24 subscribers and 24 trunks).
• Complete new set of DC and LVAC system with all necessary materials required for
the plant being installed with 50% spares for future use of 110V DC battery & battery
charger, 48V DC battery & battery charger, DC distribution board and LVAC
distribution board for new Purbachal substation.
• Design, supply, installation, testing & commissioning of fire fighting equipment for
power transformers & 132kV GIS Substation.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-10

• Complete design, supply and construction of all civil items required for the outdoor
works suitable for switchyard foundations, transformer foundations, fire walls, oil pit,
access roads, cable trenches, septic tank, surfacing, drainage including switchyard
earthing & lightning protection, switchyard lighting etc.
• Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; fittings and flooring & finishes; air-
conditioning; emergency exit (staircase) and lighting for six storied GIS building
including control room and basement.
• The basement of control room building shall be used for power & control cables. The
ground floor shall be used for GIS equipment and the 1st floor shall be used for control
& protection panels; AC/DC distribution panels; battery and battery charger and office
room.
• Breaking of foundation/pucca structures, repair, fabrications etc. wherever necessary
and cleaning of the debris etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-11

BILL OF MATERIALS/ WORKS


Purbachal, 132/33/11 kV GIS Substation
Item
Description Quantity Remarks
No.
Design, manufacture, factory testing, carrying and handling up to the site of:
1 Power Transformers & Auxiliary Transformers
1.1 132/33 kV, 80/120 MVA Transformer with Network Equipment including 2 Nos.
1.2 33/0.4 kV 200 KVA Auxiliary Transformer with 33 kV surge Arresters and
2 Nos.
connection.
1.3 33/11 kV 20/28 MVA Transformer with Network Equipment. 3 Nos.
2 132 kV GIS Indoor Switchgear with Relay Control Panel
(Double Bus scheme to be fully equipped for termination of 132 kV 02 Line
Bays,132 kV 02 Transformer Bays, 03 additional spare Bay, 132 kV 01 Bus Coupler)
2.1 132 kV Underground line Circuit Bay. 2 Nos.
2.2 132 kV Transfromer Circuit Bay. 2 Nos.
2.3 132 kV Bus Coupler Circuit Bay. 1 Nos.
2.4 132 kV Underground Circuit Bay (For Spare). 3 Nos.
2.5 132 kV Transfromer Circuit Bay. (Spare) 1 No.
3 33 kV GIS Indoor Switchgear with Relay Control Panel.
33 kV 1250A GIS indoor Breaker with 2500A Bus, 2500A Bus Section Breaker and
2500A incoming Breaker having (2 incoming, 1 Bus Section, 3 Transformer Feeder, 1 set
8 outgoing feeder & cubicles for 2 nos. 33 kV Bus PT and 2 nos. 33 kV incomer line
PT and 2 nos. spare Breaker)
3.1 33 kV, 2500A Incoming feeder. 2Nos.
3.2 33 kV Bus coupler. 1Nos.
3.3 33 kV Transformer Feeder. 3Nos.
3.4 33 kV, Outgoing feeder. 8Nos.
3.5 33 kV, 2500A Incoming feeder. (Spare) 1 No.
3.6 33 kV Bus PT. 2Nos.
3.7 33 kV Line PT. 2Nos.
4 11 kV Switchgear with CT & PT
11 kV Switchgear Panel for 3000 Amps. Bus with 23 nos. of Breaker (3 incoming, 2
1 set
Bus -section, 18 Feeder Breaker) together with 3 set of 11 kV Bus PT (s) and 3 Set of
Line PT.
4.1 11 kV, 2000 Amps, Incoming feeder from Transformer Feeder. 3 Nos
4.2 11kV, 3000 Amps, Bus coupler. 2Nos.
4.3 11 kV, 630 Amps, Outgoing feeder. 18Nos.
4.4 11 kV Bus PT. 3 Nos.
4.5 11 kV Line PT. 3 Nos.
4.6 11 kV Circuit Breaker (Spare). 2 Nos.
5 132 kV Underground Cable & Termination
132 kV Cable 1c x 800 mm² XLPE (Cu) for connection from 132kV GIS Breaker to
Transformer.
5.1 132 kV cable, 1Cx 800 mm² XLPE (Cu) 0.5 KM
5.2 132 kV Cable Termination for above and Straight through joint. Lot
6 33 kV Underground Cable & Termination
6.1 33 kV Cable 1c x 800 mm² XLPE (Cu) for connection from grid transformer to
1.0 KM
33 kV Bus.
6.2 33 kV Cable 1c x 800 (500) mm² XLPE (Cu) for connection from 33 kV Bus to
0.5 KM
33/11 kV transformer.
6.3 33 kV Cable 3c x 95 mm² XLPE (Cu) for connection from 132/33 kV
1.0 km
Transformer to 33/0.4 kV auxiliary transformer.
6.4 33 kV Cable Termination for above and Straight through joint. 1 Lot
7 11 kV Underground Cable & Termination
1.5 KM
11 kV Cable 1x500 mm², XLPE (Cu ) for connection from power transformer to
Switch Gear (3 runs per phase) including termination (Indoor & Outdoor).

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-12

Item
Description Quantity Remarks
No.
8 Battery/Charger & AC/DC Distribution Panel
8.1 110 V Battery & Battery Charger with accessories 2 sets
8.2 48 V Battery & Battery Charger with accessories 2 sets
8.3 LV AC Distribution Panel 1 set
8.4 LV DC Distribution Panel 1 set
9 Control, Protection, Substation Automation & Metering
9.1 132 kV Underground line Circuit 2 Nos.
9.2 132 kV Transformer Circuit 2 Nos.
9.3 132 kV Bus Coupler Circuit 1 No.
9.4 132 kV Spare Bay 3 Nos.
9.5 132 kV Busbar Protection Panel 1 No.
9.6 33 kV Switchgear Panels 1 Set.
9.7 11 kV Switchgear Panels 1 Set.
9.8 Tariff Metering Panel 1 No.
10 Multicore Cable
10.1 Multicore Cable for control, protection, metering & power circuits. 1Lot
11 Earthing & Lighting Protection.
11.1
Earthing & Lighting Protection System including grounding cable & 1Lot
accessories.
12 Surge Arrester & Connections
16.1 132 kV single phase surge arresters and accessories. 24 Nos.
16.2 33 kV single phase surge arresters and accessories 42 Nos.
13 Communication Equipments/UHF 2 Sets
UHF Radio Equipment including antenna and base equipment
14 Fire Extinguishing Equipment
14.1 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 1 Set
fire (15 kg.)
14.2 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire 3 Set
(5 kg.)
14.3 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 3 Set
fire (2 kg.)
15 Steel Structure, Conductor, Insulator, Connector of 132KV, 33 KV & 11 KV L.S.
16 Air Conditioning Equipment (3 Tones Each) 3 Nos.
17 Solar System for grid Substation 4Kw
18 Lighting,Small power and ventilation
18.1 Lighting,Small power, and ventilation and emergency DC lighting for GIS & 1 No.
Control building
18.2 Lighting for outside building for security, roadway, switchyard and emergency 1 No.
DC lighting.
19 Fibre Optic cable along with each 132 kV circuit with Multiplexer Equipment 2 sets.
20 Civil Works, Building and foundation
20.1 To release the equipment and material from L.S.
port,rent,Charges,handling,carrying to thesite store ptior to installation
20.2 To Construct 3 Storied 132KV GIS Control room building with four storied Sq.m
foundation and Basement floor along with the facilities to electricity,lift,water
supply sewerage etc.
20.3 To Construct the foundation of the 05 (Five) power Transformer, 02(Two) L.S.
Station Transformers, Fire wall and the foundation of the supporting structrure
for cables (132KV, 33KV and 11KV) terminations on both side of the
transformers.
20.4 Installation of the grounding mesh including welding of conductors,connection
between mesh and different earthing points of equipments,construction of pit
with cover etc.
20.5 Security boundary wall Meter
20.6 Barbed Wire Fencing Meter

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-13

Item
Description Quantity Remarks
No.
20.7 Approach/Internal road Meter
20.8 Surface Drain Meter
20.9 Construction of Cable trench (132kv,33kv,11kv) Meter
20.10 Covered Store & Godown Meter
20.11 Laying of gravel’s in the switchyard with associate works Cu.m
20.12 Switchyard electrification and boundary lighting L.S.
20.13 Security and Sentry Post Nos.
20.14 Transformer Blast Wall Sq.m
20.15 Septic Tank, Soak way Nos.
20.16 Rain water Rerserver Sq.m
21 Installation of the of the following equipment to the HV connections, LV connections
and grounding as required including relocations and transportation as indicated in the
bid:
21.1 132KV GIS(Indoor) Panel
21.2 33KV GIS (Indoor) Panel
21.3 11KV VCB Panel (23Panels) 1set
21.4 Power Transformer 132/33 kV 80/120 MVA 2 Nos.
21.5 Power Transformer 33/11 kV 20/28 MVA 3 Nos.
21.6 Auxiliary Transformer 33/0.4 kV 200 KVA and the supporting structures. 2 Nos.
21.7 132 kV, 33 kV and 11 kV Cable termination with the supporting structures. L.S
21.8 LV AC Distribution Panel 1 set
21.9 LV DC Distribution Panel 1 set
21.10 Battery and battery charger (110V and 48V) 4 sets
21.11 Surge Arrester (132KV,33KV) 1 set
21.12 Laying of 132KV, 33KV and11KV cables as required and their jointing
L.S.
(Inside substation).
21.13 Laying of LV cables, Control cables and their terminations. L.S.
21.14 Laying of Fiber Optic cables and their connections.
22 Installation of panel with Necessary equipment and other accessories for integrated
automotion system.
23 Others
23.1 To Perform Pre-commissioning test of all the equipments under the scope of
works indivisually and in conjuction and to commission them.
23.2 Submission of 05 (Five) sets as built drawing together with operation and
maintenance manual of installed equipment.
23.3 Miscellaneous necessary equipments/ works to complete the project
L.S.
successfully in all respect.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-14

Aftabnagar, 132/33/11 kV GIS Substation


The scope of work under this turnkey bid is design, supply, delivery, installation, testing &
commissioning of a complete new 132/33/11kV Gas Insulated Switchgear (GIS) substation at
Aftabnagar, Dhaka.
The scope of work but not limited to; comprise with the following: -
• Design, supply, delivery, installation, testing and commission of a new indoor type 132kV
GIS substation at Aftabnagar for two new line bays.
• Design, supply, delivery, installation, testing & commissioning of two 132/33 kV, 80/120
MVA three phase power transformers in Aftabnagar substation.
• Design, supply, delivery, installation, testing & commissioning of three 33/11 kV, 20/28
MVA three phase power transformers in Aftabnagar substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33 kV Air
insulated surge arresters for new power transformers.
• Design, supply, installation, testing & commissioning of associated local control panel,
metering panel, protection equipment for 132 KV side of new 132/33kV power
transformers, line bays & bus-coupler bay, as above.
• Design, supply, installation and commission of substation automation system.
• Design, supply, installation and commission of CCTV with 6 cameras at 6 strategic
locations in the GIS building and substation area.
• Design, supply, installation and commission of three new 132kV bus bar protection
equipment and synchronizing schemes for complete substation.
• Design, supply, installation, testing & commissioning of associated local control, metering
panel , protection equipment and substation automation system for 33kVside of new
132/33kV power transformers, line bays & bus coupler bay.
• Design, supply, installation, testing & commissioning of 132 kV cable including 132kV
cable termination for two new power transformers at Motijheel (both GIS and transformer
ends).
• 33kV cable termination at transformer & 33 kV GIS end for two new power transformers at
Aftabnagar.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33kV
XLPE(Cu) cables with necessary cable sealing ends including one spare cable with cable
sealing ends (for each 132kV & 33kV) for connecting the 132/33kV transformer at 132kV
and 33kV GIS substation.
• Two sets indoor type Fibre Optic Multiplexer Equipment shall be installed for protection &
communication at Aftabnagar substation.
• One set new digital type telephone exchanges shall be installed at Aftabnagar substation
(24 subscribers and 24 trunks).
• Complete new set of DC and LVAC system with all necessary materials required for the
plant being installed with 50% spares for future use of 110V DC battery & battery charger,
48V DC battery & battery charger, DC distribution board and LVAC distribution board for
new Aftabnagar substation.
• Design, supply, installation, testing & commissioning of fire fighting equipment for power
transformers & 132kV GIS Substation.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-15

• Complete design, supply and construction of all civil items required for the outdoor works
suitable for switchyard foundations, transformer foundations, fire walls, oil pit, access
roads, cable trenches, septic tank, surfacing, drainage including switchyard earthing &
lightning protection, switchyard lighting etc.
• Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; fittings and flooring & finishes; air-conditioning;
emergency exit (staircase) and lighting for six storied GIS building including control room
and basement.
• The basement of control room building shall be used for power & control cables. The
ground floor shall be used for GIS equipment and the 1st floor shall be used for control &
protection panels; AC/DC distribution panels; battery and battery charger and office room.
• Breaking of foundation/pucca structures, repair, fabrications etc. wherever necessary and
cleaning of the debris etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-16

BILL OF MATERIALS/ WORKS


Aftabnagar, 132/33/11 kV GIS Substation
Item
Description Quantity Remarks
No.
Design, manufacture, factory testing, carrying and handling up to the site of:
1 Power Transformers & Auxiliary Transformers
1.1 132/33 kV, 80/120 MVA Transformer with Network Equipment including 2 Nos.
1.2 33/0.4 kV 200 KVA Auxiliary Transformer with 33 kV surge Arresters and
2 Nos.
connection.
1.3 33/11 kV 20/28 MVA Transformer with Network Equipment. 3 Nos.
2 132 kV GIS Indoor Switchgear with Relay Control Panel
(Double Bus scheme to be fully equipped for termination of 132 kV 02 Line
Bays,132 kV 02 Transformer Bays, 03 additional spare Bay, 132 kV 01 Bus Coupler)
2.1 132 kV Underground line Circuit Bay. 2 Nos.
2.2 132 kV Transfromer Circuit Bay. 2 Nos.
2.3 132 kV Bus Coupler Circuit Bay. 1 Nos.
2.4 132 kV Underground Circuit Bay (For Spare). 3 Nos.
2.5 132 kV Transfromer Circuit Bay. (Spare) 1 No.
3 33 kV GIS Indoor Switchgear with Relay Control Panel.
33 kV 1250A GIS indoor Breaker with 2500A Bus, 2500A Bus Section Breaker and
2500A incoming Breaker having (2 incoming, 1 Bus Section, 3 Transformer Feeder, 1 set
8 outgoing feeder & cubicles for 2 nos. 33 kV Bus PT and 2 nos. 33 kV incomer line
PT and 2 nos. spare Breaker)
3.1 33 kV, 2500A Incoming feeder. 2Nos.
3.2 33 kV Bus coupler. 1Nos.
3.3 33 kV Transformer Feeder. 3Nos.
3.4 33 kV, Outgoing feeder. 8Nos.
3.5 33 kV, 2500A Incoming feeder. (Spare) 1 No.
3.6 33 kV Bus PT. 2Nos.
3.7 33 kV Line PT. 2Nos.
4 11 kV Switchgear with CT & PT
11 kV Switchgear Panel for 3000 Amps. Bus with 23 nos. of Breaker (3 incoming, 2
1 set
Bus -section, 18 Feeder Breaker) together with 3 set of 11 kV Bus PT (s) and 3 Set of
Line PT.
4.1 11 kV, 2000 Amps, Incoming feeder from Transformer Feeder. 3 Nos
4.2 11kV, 3000 Amps, Bus coupler. 2Nos.
4.3 11 kV, 630 Amps, Outgoing feeder. 18Nos.
4.4 11 kV Bus PT. 3 Nos.
4.5 11 kV Line PT. 3 Nos.
4.6 11 kV Circuit Breaker (Spare). 2 Nos.
5 132 kV Underground Cable & Termination
132 kV Cable 1c x 800 mm² XLPE (Cu) for connection from 132 KV GIS breaker to
Power Transformer
5.1 132 kV cable, 1Cx 800 mm² XLPE (Cu) 0.5 KM
5.2 132 kV Cable Termination for above and Straight through joint. Lot
6 33 kV Underground Cable & Termination
6.1 33 kV Cable 1c x 800 mm² XLPE (Cu) for connection from grid transformer to
1.0 KM
33 kV Bus.
6.2 33 kV Cable 1c x 800 (500) mm² XLPE (Cu) for connection from 33 kV Bus to
0.5 KM
33/11 kV transformer.
6.3 33 kV Cable 3c x 95 mm² XLPE (Cu) for connection from 132/33 kV
1.0 km
Transformer to 33/0.4 kV auxiliary transformer.
6.4 33 kV Cable Termination for above and Straight through joint. 1 Lot
7 11 kV Underground Cable & Termination 1.5 KM

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-17

Item
Description Quantity Remarks
No.
11 kV Cable 1x500 mm², XLPE (Cu ) for connection from power transformer to
Switch Gear (3 runs per phase) including termination (Indoor & Outdoor).
8 Battery/Charger & AC/DC Distribution Panel
8.1 110 V Battery & Battery Charger with accessories 2 sets
8.2 48 V Battery & Battery Charger with accessories 2 sets
8.3 LV AC Distribution Panel 1 set
8.4 LV DC Distribution Panel 1 set
9 Control, Protection, Substation Automation & Metering
9.1 132 kV Underground line Circuit 2 Nos.
9.2 132 kV Transformer Circuit 2 Nos.
9.3 132 kV Bus Coupler Circuit 1 No.
9.4 132 kV Spare Bay 3 Nos.
9.5 132 kV Busbar Protection Panel 1 No.
9.6 33 kV Switchgear Panels 1 Set.
9.7 11 kV Switchgear Panels 1 Set.
9.8 Tariff Metering Panel 1 No.
10 Multicore Cable
10.1 Multicore Cable for control, protection, metering & power circuits. 1Lot
11 Earthing & Lighting Protection.
11.1
Earthing & Lighting Protection System including grounding cable & 1Lot
accessories.
12 Surge Arrester & Connections
16.1 132 kV single phase surge arresters and accessories. 24 Nos.
16.2 33 kV single phase surge arresters and accessories 42 Nos.
13 Communication Equipments/UHF 2 Sets
UHF Radio Equipment including antenna and base equipment
14 Fire Extinguishing Equipment
14.1 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 1 Set
fire (15 kg.)
14.2 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire 3 Set
(5 kg.)
14.3 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 3 Set
fire (2 kg.)
15 Steel Structure, Conductor, Insulator, Connector of 132KV, 33 KV & 11 KV L.S.
16 Air Conditioning Equipment (3 Tones Each) 3 Nos.
17 Solar System for grid Substation 4Kw
18 Lighting,Small power and ventilation
18.1 Lighting,Small power, and ventilation and emergency DC lighting for GIS & 1 No.
Control building
18.2 Lighting for outside building for security, roadway, switchyard and emergency 1 No.
DC lighting.
19 Fibre Optic cable along with each 132 kV circuit with Multiplexer Equipment 2 sets.
20 Civil Works, Building and foundation
20.1 To release the equipment and material from port, rent, Charges, handling, L.S.
carrying to thesite store ptior to installation
20.2 To Construct 3 Storied 132KV GIS Control room building with four storied Sq.m
foundation and Basement floor along with the facilities to electricity,lift,water
supply sewerage etc.
20.3 To Construct the foundation of the 05 (Five) power Transformer, 02(Two) L.S.
Station Transformers, Fire wall and the foundation of the supporting structrure
for cables (132KV, 33KV and 11KV) terminations on both side of the
transformers.
20.4 Installation of the grounding mesh including welding of conductors,connection
between mesh and different earthing points of equipments,construction of pit
with cover etc.
20.5 Security boundary wall Meter

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-18

Item
Description Quantity Remarks
No.
20.6 Barbed Wire Fencing Meter
20.7 Approach/Internal road Meter
20.8 Surface Drain Meter
20.9 Construction of Cable trench (132kv,33kv,11kv) Meter
20.10 Covered Store & Godown Meter
20.11 Laying of gravel’s in the switchyard with associate works Cu.m
20.12 Switchyard electrification and boundary lighting L.S.
20.13 Security and Sentry Post Nos.
20.14 Transformer Blast Wall Sq.m
20.15 Septic Tank, Soak way Nos.
20.16 Rain water Rerserver Sq.m
21 Installation of the of the following equipment to the HV connections, LV connections
and grounding as required including relocations and transportation as indicated in the
bid:
21.1 132KV GIS(Indoor) Panel
21.2 33KV GIS (Indoor) Panel
21.3 11KV VCB Panel (23Panels) 1set
21.4 Power Transformer 132/33 kV 80/120 MVA 2 Nos.
21.5 Power Transformer 33/11 kV 20/28 MVA 3 Nos.
21.6 Auxiliary Transformer 33/0.4 kV 200 KVA and the supporting structures. 2 Nos.
21.7 132 kV, 33 kV and 11 kV Cable termination with the supporting structures. L.S
21.8 LV AC Distribution Panel 1 set
21.9 LV DC Distribution Panel 1 set
21.10 Battery and battery charger (110V and 48V) 4 sets
21.11 Surge Arrester (132KV,33KV) 1 set
21.12 Laying of 132KV, 33KV and11KV cables as required and their jointing
L.S.
(Inside substation).
21.13 Laying of LV cables, Control cables and their terminations. L.S.
21.14 Laying of Fiber Optic cables and their connections.
22 Installation of panel with Necessary equipment and other accessories for integrated
automotion system.
23 Others
23.1 To Perform Pre-commissioning test of all the equipments under the scope of
works indivisually and in conjuction and to commission them.
23.2 Submission of 05 (Five) sets as built drawing together with operation and
maintenance manual of installed equipment.
23.3 Miscellaneous necessary equipments/ works to complete the project
L.S.
successfully in all respect.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-19

Dumni, 132/33/11 kV GIS Substation:


The scope of work under this turnkey bid is design, supply, delivery, installation, testing &
commissioning of a complete new 132/33kV Gas Insulated Switchgear (GIS) substation at
Dumni,Dhaka.
The scope of work but not limited to; comprise with the following: -
• Design, supply, delivery, installation, testing and commission of a new indoor type
132kV GIS substation at Dumni for two new line bays.
• Design, supply, delivery, installation, testing & commissioning of two 132/33 kV,
80/120 MVA three phase power transformers in Dumni substation.
• Design, supply, delivery, installation, testing & commissioning of three 33/11 kV, 20/28
MVA three phase power transformers in Dumni substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33 kV Air
insulated surge arresters for new power transformers.
• Design, supply, installation, testing & commissioning of associated local control panel,
metering panel, protection equipment and substation automation system for132 KV side
of new 132/33kV power transformers, line bays & bus-coupler bay, as above.
• Design, supply, installation and commission of CCTV with 6 cameras at 6 strategic
locations in the GIS building and substation area.
• Design, supply, installation and commission of three new 132kV bus bar protection
equipment and synchronizing schemes for complete substation.
• Design, supply, installation, testing & commissioning of associated local control,
metering panel , protection equipment and substation automation system for33kVside
of new 132/33kV power transformers, line bays & bus coupler bay.
• Design, supply, installation, testing & commissioning of 132 kV cable including 132kV
cable termination for two new power transformers at Dumni (both GIS and transformer
ends) .
• 33kV cable termination at transformer & 33 kV GIS end for two new power
transformers at Dumni.
• Design, supply, delivery, installation, testing & commissioning of 132kV,33kV and 11
kV XLPE(Cu) cables with necessary cable sealing ends including one spare cable with
cable sealing ends (for each 132kV & 33kV) for connecting the 132/33kV transformer
at 132kV and 33kV GIS substation.
• Two sets indoor type Fibre Optic Multiplexer Equipment shall be installed for
protection & communication at Dumni substation.
• One set new digital type telephone exchanges shall be installed at Dumni substation (8
subscribers and 8 trunks).
• Complete new set of DC and LVAC system with all necessary materials required for
the plant being installed with 50% spares for future use of 110V DC battery & battery
charger, 48V DC battery & battery charger, DC distribution board and LVAC
distribution board for new Dumni substation.
• Design, supply, installation, testing & commissioning of fire fighting equipment for
power transformers & 132kV GIS Substation.
• Complete design, supply and construction of all civil items required for the outdoor

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-20

works suitable for switchyard foundations, transformer foundations, fire walls, oil pit,
access roads, cable trenches, septic tank, surfacing, drainage including switchyard
earthing & lightning protection, switchyard lighting etc.
• Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; fittings and flooring & finishes; air-
conditioning; emergency exit (staircase) and lighting for six storied GIS building
including control room and basement.
• The basement of control room building shall be used for power & control cables. The
ground floor shall be used for GIS equipment and the 1st floor shall be used for control
& protection panels; AC/DC distribution panels; battery and battery charger and office
room.
• Breaking of foundation/pucca structures, repair, fabrications etc. wherever necessary
and cleaning of the debris etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-21

BILL OF MATERIALS/ WORKS


Dumni, 132/33/11 kV GIS Substation
Item
Description Quantity Remarks
No.
Design, manufacture, factory testing, carrying and handling up to the site of:
1 Power Transformers & Auxiliary Transformers
1.1 132/33 kV, 80/120 MVA Transformer with Network Equipment including 2 Nos.
1.2 33/0.4 kV 200 KVA Auxiliary Transformer with 33 kV surge Arresters and
2 Nos.
connection.
1.3 33/11 kV 20/28 MVA Transformer with Network Equipment. 3 Nos.
2 132 kV GIS Indoor Switchgear with Relay Control Panel
(Double Bus scheme to be fully equipped for termination of 132 kV 02 Line
Bays,132 kV 02 Transformer Bays, 03 additional spare Bay, 132 kV 01 Bus Coupler)
2.1 132 kV Underground line Circuit Bay. 2 Nos.
2.2 132 kV Transfromer Circuit Bay. 2 Nos.
2.3 132 kV Bus Coupler Circuit Bay. 1 Nos.
2.4 132 kV Underground Circuit Bay (For Spare). 3 Nos.
2.5 132 kV Transfromer Circuit Bay. (Spare) 1 No.
3 33 kV GIS Indoor Switchgear with Relay Control Panel.
33 kV 1250A GIS indoor Breaker with 2500A Bus, 2500A Bus Section Breaker and
2500A incoming Breaker having (2 incoming, 1 Bus Section, 3 Transformer Feeder, 1 set
8 outgoing feeder & cubicles for 2 nos. 33 kV Bus PT and 2 nos. 33 kV incomer line
PT and 2 nos. spare Breaker)
3.1 33 kV, 2500A Incoming feeder. 2Nos.
3.2 33 kV Bus coupler. 1Nos.
3.3 33 kV Transformer Feeder. 3Nos.
3.4 33 kV, Outgoing feeder. 8Nos.
3.5 33 kV, 2500A Incoming feeder. (Spare) 1 No.
3.6 33 kV Bus PT. 2Nos.
3.7 33 kV Line PT. 2Nos.
4 11 kV Switchgear with CT & PT
11 kV Switchgear Panel for 3000 Amps. Bus with 23 nos. of Breaker (3 incoming, 2
1 set
Bus -section, 18 Feeder Breaker) together with 3 set of 11 kV Bus PT (s) and 3 Set of
Line PT.
4.1 11 kV, 2000 Amps, Incoming feeder from Transformer Feeder. 3 Nos
4.2 11kV, 3000 Amps, Bus coupler. 2Nos.
4.3 11 kV, 630 Amps, Outgoing feeder. 18Nos.
4.4 11 kV Bus PT. 3 Nos.
4.5 11 kV Line PT. 3 Nos.
4.6 11 kV Circuit Breaker (Spare). 2 Nos.
5 132 kV Underground Cable & Termination
132 kV Cable 1c x 800 mm² XLPE (Cu) for connection from 132 KV GIS breaker to
Power Transformer.
5.1 132 kV cable, 1Cx 800 mm² XLPE (Cu) 0.5 KM
5.2 132 kV Cable Termination for above and Straight through joint. Lot
6 33 kV Underground Cable & Termination
6.1 33 kV Cable 1c x 800 mm² XLPE (Cu) for connection from grid transformer to
1.0 KM
33 kV Bus.
6.2 33 kV Cable 1c x 800 (500) mm² XLPE (Cu) for connection from 33 kV Bus to
0.5 KM
33/11 kV transformer.
6.3 33 kV Cable 3c x 95 mm² XLPE (Cu) for connection from 132/33 kV
1.0 km
Transformer to 33/0.4 kV auxiliary transformer.
6.4 33 kV Cable Termination for above and Straight through joint. 1 Lot
7 11 kV Underground Cable & Termination
1.5 KM
11 kV Cable 1x500 mm², XLPE (Cu ) for connection from power transformer to
Switch Gear (3 runs per phase) including termination (Indoor & Outdoor).

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-22

Item
Description Quantity Remarks
No.
8 Battery/Charger & AC/DC Distribution Panel
8.1 110 V Battery & Battery Charger with accessories 2 sets
8.2 48 V Battery & Battery Charger with accessories 2 sets
8.3 LV AC Distribution Panel 1 set
8.4 LV DC Distribution Panel 1 set
9 Control, Protection, Substation Automation & Metering
9.1 132 kV Underground line Circuit 2 Nos.
9.2 132 kV Transformer Circuit 2 Nos.
9.3 132 kV Bus Coupler Circuit 1 No.
9.4 132 kV Spare Bay 3 Nos.
9.5 132 kV Busbar Protection Panel 1 No.
9.6 33 kV Switchgear Panels 1 Set.
9.7 11 kV Switchgear Panels 1 Set.
9.8 Tariff Metering Panel 1 No.
10 Multicore Cable
10.1 Multicore Cable for control, protection, metering & power circuits. 1Lot
11 Earthing & Lighting Protection.
11.1
Earthing & Lighting Protection System including grounding cable & 1Lot
accessories.
12 Surge Arrester & Connections
16.1 132 kV single phase surge arresters and accessories. 24 Nos.
16.2 33 kV single phase surge arresters and accessories 42 Nos.
13 Communication Equipments/UHF 2 Sets
UHF Radio Equipment including antenna and base equipment
14 Fire Extinguishing Equipment
14.1 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 1 Set
fire (15 kg.)
14.2 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire 3 Set
(5 kg.)
14.3 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 3 Set
fire (2 kg.)
15 Steel Structure, Conductor, Insulator, Connector of 132KV, 33 KV & 11 KV L.S.
16 Air Conditioning Equipment (3 Tones Each) 3 Nos.
17 Solar System for grid Substation 4Kw
18 Lighting,Small power and ventilation
18.1 Lighting,Small power, and ventilation and emergency DC lighting for GIS & 1 No.
Control building
18.2 Lighting for outside building for security, roadway, switchyard and emergency 1 No.
DC lighting.
19 Fibre Optic cable along with each 132 kV circuit with Multiplexer Equipment 2 sets.
20 Civil Works, Building and foundation
20.1 To release the equipment and material from port, rent, Charges, handling, L.S.
carrying to thesite store ptior to installation
20.2 To Construct 3 Storied 132KV GIS Control room building with four storied Sq.m
foundation and Basement floor along with the facilities to electricity,lift,water
supply sewerage etc.
20.3 To Construct the foundation of the 05 (Five) power Transformer, 02(Two) L.S.
Station Transformers, Fire wall and the foundation of the supporting structrure
for cables (132KV, 33KV and 11KV) terminations on both side of the
transformers.
20.4 Installation of the grounding mesh including welding of conductors,connection
between mesh and different earthing points of equipments,construction of pit
with cover etc.
20.5 Security boundary wall Meter
20.6 Barbed Wire Fencing Meter

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-23

Item
Description Quantity Remarks
No.
20.7 Approach/Internal road Meter
20.8 Surface Drain Meter
20.9 Construction of Cable trench (132kv,33kv,11kv) Meter
20.10 Covered Store & Godown Meter
20.11 Laying of gravel’s in the switchyard with associate works Cu.m
20.12 Switchyard electrification and boundary lighting L.S.
20.13 Security and Sentry Post Nos.
20.14 Transformer Blast Wall Sq.m
20.15 Septic Tank, Soak way Nos.
20.16 Rain water Rerserver Sq.m
21 Installation of the of the following equipment to the HV connections, LV connections
and grounding as required including relocations and transportation as indicated in the
bid:
21.1 132KV GIS(Indoor) Panel
21.2 33KV GIS (Indoor) Panel
21.3 11KV VCB Panel (23Panels) 1set
21.4 Power Transformer 132/33 kV 80/120 MVA 2 Nos.
21.5 Power Transformer 33/11 kV 20/28 MVA 3 Nos.
21.6 Auxiliary Transformer 33/0.4 kV 200 KVA and the supporting structures. 2 Nos.
21.7 132 kV, 33 kV and 11 kV Cable termination with the supporting structures. L.S
21.8 LV AC Distribution Panel 1 set
21.9 LV DC Distribution Panel 1 set
21.10 Battery and battery charger (110V and 48V) 4 sets
21.11 Surge Arrester (132KV,33KV) 1 set
21.12 Laying of 132KV, 33KV and11KV cables as required and their jointing
L.S.
(Inside substation).
21.13 Laying of LV cables, Control cables and their terminations. L.S.
21.14 Laying of Fiber Optic cables and their connections.
22 Installation of panel with Necessary equipment and other accessories for integrated
automotion system.
23 Others
23.1 To Perform Pre-commissioning test of all the equipments under the scope of
works indivisually and in conjuction and to commission them.
23.2 Submission of 05 (Five) sets as built drawing together with operation and
maintenance manual of installed equipment.
23.3 Miscellaneous necessary equipments/ works to complete the project
L.S.
successfully in all respect.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-24

Gulshan/Banani, 132/33/11 kV GIS Substation


The scope of work under this turnkey bid is design, supply, delivery, installation, testing &
commissioning of a complete new 132/33kV Gas Insulated Switchgear (GIS) substation at
Gulshan/Banani, Dhaka.
The scope of work but not limited to; comprise with the following: -
• Design, supply, delivery, installation, testing and commission of a new indoor type
132kV GIS substation at Gulshan/Banani for two new line bays.
• Design, supply, delivery, installation, testing & commissioning of two 132/33 kV,
80/120 MVA three phase power transformers in Gulshan/Banani substation.
• Design, supply, delivery, installation, testing & commissioning of three 33/11 kV, 20/28
MVA three phase power transformers in Gulshan/Banani substation.
• Design, supply, delivery, installation, testing & commissioning of 132kV and 33 kV Air
insulated surge arresters for new power transformers.
• Design, supply, installation, testing & commissioning of associated local control panel,
metering panel, protection equipment and substation automation system for132 KV side
of new 132/33kV power transformers, line bays & bus-coupler bay, as above.
• Design, supply, installation and commission of CCTV with 6 cameras at 6 strategic
locations in the GIS building and substation area.
• Design, supply, installation and commission of three new 132kV bus bar protection
equipment and synchronizing schemes for complete substation.
• Design, supply, installation, testing & commissioning of associated local control,
metering panel , protection equipment and substation automation system for 33kVside
of new 132/33kV power transformers, line bays & bus coupler bay.
• Design, supply, installation, testing & commissioning of 132 kV cable including 132kV
cable termination for two new power transformers at Gulshan/Banani (both GIS and
transformer ends) .
• 33kV cable termination at transformer & 33 kV GIS end for two new power
transformers at Gulshan/Banani.
• Design, supply, delivery, installation, testing & commissioning of 132kV,33kV and 11
kV XLPE(Cu) cables with necessary cable sealing ends including one spare cable with
cable sealing ends (for each 132kV & 33kV) for connecting the 132/33kV transformer
at 132kV and 33kV GIS substation.
• Two sets indoor type Fibre Optic Multiplexer Equipment shall be installed for
protection & communication at Gulshan/Banani substation.
• One set new digital type telephone exchanges shall be installed at Gulshan/Banani
substation (8 subscribers and 8 trunks).
• Complete new set of DC and LVAC system with all necessary materials required for
the plant being installed with 50% spares for future use of 110V DC battery & battery
charger, 48V DC battery & battery charger, DC distribution board and LVAC
distribution board for new Gulshan/Banani substation.
• Design, supply, installation, testing & commissioning of fire fighting equipment for
power transformers & 132kV GIS Substation.
• Complete design, supply and construction of all civil items required for the outdoor

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-25

works suitable for switchyard foundations, transformer foundations, fire walls, oil pit,
access roads, cable trenches, septic tank, surfacing, drainage including switchyard
earthing & lightning protection, switchyard lighting etc.
• Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; fittings and flooring & finishes; air-
conditioning; emergency exit (staircase) and lighting for six storied GIS building
including control room and basement.
• The basement of control room building shall be used for power & control cables. The
ground floor shall be used for GIS equipment and the 1st floor shall be used for control
& protection panels; AC/DC distribution panels; battery and battery charger and office
room.
• Breaking of foundation/pucca structures, repair, fabrications etc. wherever necessary
and cleaning of the debris etc.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-26

BILL OF MATERIALS/ WORKS


Gulshan/Banani, 132/33/11 kV GIS Substation
Item
Description Quantity Remarks
No.
Design, manufacture, factory testing, carrying and handling up to the site of:
1 Power Transformers & Auxiliary Transformers
1.1 132/33 kV, 80/120 MVA Transformer with Network Equipment including 2 Nos.
1.2 33/0.4 kV 200 KVA Auxiliary Transformer with 33 kV surge Arresters and
2 Nos.
connection.
1.3 33/11 kV 20/28 MVA Transformer with Network Equipment. 3 Nos.
2 132 kV GIS Indoor Switchgear with Relay Control Panel
(Double Bus scheme to be fully equipped for termination of 132 kV 02 Line
Bays,132 kV 02 Transformer Bays, 03 additional spare Bay, 132 kV 01 Bus Coupler)
2.1 132 kV Underground line Circuit Bay. 2 Nos.
2.2 132 kV Transfromer Circuit Bay. 2 Nos.
2.3 132 kV Bus Coupler Circuit Bay. 1 Nos.
2.4 132 kV Underground Circuit Bay (For Spare). 3 Nos.
2.5 132 kV Transfromer Circuit Bay. (Spare) 1 No.
3 33 kV GIS Indoor Switchgear with Relay Control Panel.
33 kV 1250A GIS indoor Breaker with 2500A Bus, 2500A Bus Section Breaker and
2500A incoming Breaker having (2 incoming, 1 Bus Section, 3 Transformer Feeder, 1 set
8 outgoing feeder & cubicles for 2 nos. 33 kV Bus PT and 2 nos. 33 kV incomer line
PT and 2 nos. spare Breaker)
3.1 33 kV, 2500A Incoming feeder. 2Nos.
3.2 33 kV Bus coupler. 1Nos.
3.3 33 kV Transformer Feeder. 3Nos.
3.4 33 kV, Outgoing feeder. 8Nos.
3.5 33 kV, 2500A Incoming feeder. (Spare) 1 No.
3.6 33 kV Bus PT. 2Nos.
3.7 33 kV Line PT. 2Nos.
4 11 kV Switchgear with CT & PT
11 kV Switchgear Panel for 3000 Amps. Bus with 23 nos. of Breaker (3 incoming, 2
1 set
Bus -section, 18 Feeder Breaker) together with 3 set of 11 kV Bus PT (s) and 3 Set of
Line PT.
4.1 11 kV, 2000 Amps, Incoming feeder from Transformer Feeder. 3 Nos
4.2 11kV, 3000 Amps, Bus coupler. 2Nos.
4.3 11 kV, 630 Amps, Outgoing feeder. 18Nos.
4.4 11 kV Bus PT. 3 Nos.
4.5 11 kV Line PT. 3 Nos.
4.6 11 kV Circuit Breaker (Spare). 2 Nos.
5 132 kV Underground Cable & Termination
132 kV Cable 1c x 800 mm² XLPE (Cu) for connection from 132 KV GIS breaker to
power transformer.
5.1 132 kV cable, 1Cx 800 mm² XLPE (Cu) 0.5 KM
5.2 132 kV Cable Termination for above and Straight through joint. Lot
6 33 kV Underground Cable & Termination
6.1 33 kV Cable 1c x 800 mm² XLPE (Cu) for connection from grid transformer to
1.0 KM
33 kV Bus.
6.2 33 kV Cable 1c x 800 (500) mm² XLPE (Cu) for connection from 33 kV Bus to
0.5 KM
33/11 kV transformer.
6.3 33 kV Cable 3c x 95 mm² XLPE (Cu) for connection from 132/33 kV
1.0 km
Transformer to 33/0.4 kV auxiliary transformer.
6.4 33 kV Cable Termination for above and Straight through joint. 1 Lot
7 11 kV Underground Cable & Termination
1.5 KM
11 kV Cable 1x500 mm², XLPE (Cu ) for connection from power transformer to
Switch Gear (3 runs per phase) including termination (Indoor & Outdoor).

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-27

Item
Description Quantity Remarks
No.
8 Battery/Charger & AC/DC Distribution Panel
8.1 110 V Battery & Battery Charger with accessories 2 sets
8.2 48 V Battery & Battery Charger with accessories 2 sets
8.3 LV AC Distribution Panel 1 set
8.4 LV DC Distribution Panel 1 set
9 Control, Protection, Substation Automation & Metering
9.1 132 kV Underground line Circuit 2 Nos.
9.2 132 kV Transformer Circuit 2 Nos.
9.3 132 kV Bus Coupler Circuit 1 No.
9.4 132 kV Spare Bay 3 Nos.
9.5 132 kV Busbar Protection Panel 1 No.
9.6 33 kV Switchgear Panels 1 Set.
9.7 11 kV Switchgear Panels 1 Set.
9.8 Tariff Metering Panel 1 No.
10 Multicore Cable
10.1 Multicore Cable for control, protection, metering & power circuits. 1Lot
11 Earthing & Lighting Protection.
11.1
Earthing & Lighting Protection System including grounding cable & 1Lot
accessories.
12 Surge Arrester & Connections
16.1 132 kV single phase surge arresters and accessories. 24 Nos.
16.2 33 kV single phase surge arresters and accessories 42 Nos.
13 Communication Equipments/UHF 2 Sets
UHF Radio Equipment including antenna and base equipment
14 Fire Extinguishing Equipment
14.1 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 1 Set
fire (15 kg.)
14.2 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire 3 Set
(5 kg.)
14.3 Trolley mounted fire extinguisher with dry type chemical for A, B and C type 3 Set
fire (2 kg.)
15 Steel Structure, Conductor, Insulator, Connector of 132KV, 33 KV & 11 KV L.S.
16 Air Conditioning Equipment (3 Tones Each) 3 Nos.
17 Solar System for grid Substation 4Kw
18 Lighting,Small power and ventilation
18.1 Lighting,Small power, and ventilation and emergency DC lighting for GIS & 1 No.
Control building
18.2 Lighting for outside building for security, roadway, switchyard and emergency 1 No.
DC lighting.
19 Fibre Optic cable along with each 132 kV circuit with Multiplexer Equipment 2 sets.
20 Civil Works, Building and foundation
20.1 To release the equipment and material from port, rent, Charges, handling, L.S.
carrying to thesite store ptior to installation
20.2 To Construct 3 Storied 132KV GIS Control room building with four storied Sq.m
foundation and Basement floor along with the facilities to electricity,lift,water
supply sewerage etc.
20.3 To Construct the foundation of the 05 (Five) power Transformer, 02(Two) L.S.
Station Transformers, Fire wall and the foundation of the supporting structrure
for cables (132KV, 33KV and 11KV) terminations on both side of the
transformers.
20.4 Installation of the grounding mesh including welding of conductors,connection
between mesh and different earthing points of equipments,construction of pit
with cover etc.
20.5 Security boundary wall Meter
20.6 Barbed Wire Fencing Meter

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-28

Item
Description Quantity Remarks
No.
20.7 Approach/Internal road Meter
20.8 Surface Drain Meter
20.9 Construction of Cable trench (132kv,33kv,11kv) Meter
20.10 Covered Store & Godown Meter
20.11 Laying of gravel’s in the switchyard with associate works Cu.m
20.12 Switchyard electrification and boundary lighting L.S.
20.13 Security and Sentry Post Nos.
20.14 Transformer Blast Wall Sq.m
20.15 Septic Tank, Soak way Nos.
20.16 Rain water Rerserver Sq.m
21 Installation of the of the following equipment to the HV connections, LV connections
and grounding as required including relocations and transportation as indicated in the
bid:
21.1 132KV GIS(Indoor) Panel
21.2 33KV GIS (Indoor) Panel
21.3 11KV VCB Panel (23Panels) 1set
21.4 Power Transformer 132/33 kV 80/120 MVA 2 Nos.
21.5 Power Transformer 33/11 kV 20/28 MVA 3 Nos.
21.6 Auxiliary Transformer 33/0.4 kV 200 KVA and the supporting structures. 2 Nos.
21.7 132 kV, 33 kV and 11 kV Cable termination with the supporting structures. L.S
21.8 LV AC Distribution Panel 1 set
21.9 LV DC Distribution Panel 1 set
21.10 Battery and battery charger (110V and 48V) 4 sets
21.11 Surge Arrester (132KV,33KV) 1 set
21.12 Laying of 132KV, 33KV and11KV cables as required and their jointing
L.S.
(Inside substation).
21.13 Laying of LV cables, Control cables and their terminations. L.S.
21.14 Laying of Fiber Optic cables and their connections.
22 Installation of panel with Necessary equipment and other accessories for integrated
automotion system.
23 Others
23.1 To Perform Pre-commissioning test of all the equipments under the scope of
works indivisually and in conjuction and to commission them.
23.2 Submission of 05 (Five) sets as built drawing together with operation and
maintenance manual of installed equipment.
23.3 Miscellaneous necessary equipments/ works to complete the project
L.S.
successfully in all respect.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-29

6.1.2 TRAINING & ORIENTATION FOR EMPLOYER’S STAFF ON THE MAJOR EQUIPMENTS
The Contractor shall provide all facilities for the Engineers, nominated by the Employer, to be Trained & Oriented
with all necessary operational and maintenance works for the offered major equipments (Power Transformers,
SF6 & GIS Switchgears (132 & 33kV), Substation Automation System and AIS breaker). All costs relating to
the training/supervision program shall be within the contract price. The training shall be conducted before
erection and commissioning of the plant or equpments. Course notes and handbooks as appropriate are to be
issued to attendees, and full reference is to be made to the Operation and Maintenance manuals issued by the
Contractor.

Importance shall be emphasized on the following particulars but not limited to during training:-

Routine Operation, Maintenance, Testing and Repair of:-

GIS Switchgear
Power Transformers, including use of oil treatment plant
Control equipment, metering and alarm equipment
Protection equipment
Underground cables, sheaths, etc
Earthing
Substation Automation System
Building Services
DC and LV AC systems.

In addition full instruction is required in the stripping down, repair or replacement of components, reassembly,
operation testing and re-commissioning of switchgears and transformers. This training is required to ensure that
the Employers staffs are made fully familiar with the plant operational design, maintenance procedures, etc.

The Contractor is to arrange training on offered items for (i) 15 (fifteen) Employer’s engineers on GIS (132kV &
33kV) operation & maintenance at GIS manufacturer’s premises/factory (ii) 8 (eight) Employer’s engineers on
Protection Scheme for 132kV and 33kV as well as offered Protective devices at manufacturer’s premises/factory
(iii) 8 (eight) Employer’s engineers on operation & maintenance of offered Power Transformers (132/33kV and
33/11kV) at manufacturer’s premises/factory, (iv) 8 (eight) Employer’s engineers on offered Substation
Automation System (SAS) at Automation system manufacturer’s premises/factory for a period of three (03) weeks
for each and (v) 4 (four) Employer’s engineers on offered Fibre Optic Multiplexer Equipment for Operation and
maintenance for a period of two (02) weeks. The training shall also include the field visit during training for
practical operation. The training program on Substation Automation System (SAS) also includes the installation &
configuration of automation software. The full training programme is to be approved by the employer prior to
commencement.

Four (06) teams of senior engineers of DESCO each consisting of two (02) members will also visit the
manufacturer’s works during manufacturing of major equipments like Power Transformers (132/33kV and
33/11kV), GIS (132kV & 33kV), 11 kV VCBs and Substation Automation System (SAS) for a period of 10 (ten)
days for each team.

The Contractor will be responsible for bearing all costs for the trainees and supervisors, including visa fees, air
fares, accommodation, fooding, laundry, transportation etc plus a daily allowance (not less than DESCO standard)
for each of the trainees and supervisors.
The contractor is also to arrange a local training program on Substation Automation System for twenty (20)
operators for ten (10) days. This should include training on operation & control of the automation software. The
Contractor is to report on the capability and progress of each trainee at completion of their training periods.

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-30

6.1.3 SYSTEM ELECTRICAL PARAMETERS


6.1.3.1 System Conditions
Equipment supplied under this Contract shall be suitable for the following system conditions.

Nominal system voltage between phases kV 132 33 11


System frequency Hz 50
Rated voltage between phases kV 145 36 12
Lightning impulse withstand kV 650 170 75
50 Hz withstand 1 minute kV 275 70 28
Symmetrical short-circuit current (3 sec) kA 63.5 40 31.5
6.1.3.2 System Earthing
The 132/33kV and 33/11 kV transformers shall be solidly earthed
The 132 kV system is solidly earthed at the power station transformer 132 kV neutrals and
132/33kV transformer neutrals but not earthed at the 132kV Grid supply points.

6.1.3.3 Minimum Substation Clearances


Air insulated busbars and connections shall have electrical clearances as listed in the following
table:-
Nominal system voltage between phases kV 132 33
Minimum clearance between live metal and earth mm 1300 380
Minimum clearance between live metal mm 1500 430
Minimum safety clearance between ground and the
nearest point not at earth potential of an insulator mm 2500 500
Minimum safety clearance between ground and the mm 3500 2740
nearest live unscreened conductor (BS 7354 ‘Safety
Working Clearance’)
Minimum insulator creepage distance (at rated mm/kV 25 25
voltage between phases)

6.1.3.4 Low Voltage AC System


Rated service voltage 400/230 volts
(3 phase, 4 wire 50 Hz)
Tolerance on rated voltage +15%, -15%
Switchgear symmetrical breaking capacity 15 kA, 3 sec
System earthing Solid

6.1.3.5 D.C. System


For d.c. motor driven auxiliaries, relays, tripping, indicating lamps and controls.
Normal battery voltage 110 V nominal
Tolerance on rated voltage + 10%, -15%

Bidding Document for Package-1 (Lot-1) Construction of 132kV GIS S/S DESCO
Section 6-Employer’s Requirements 6-31

6.1.4 CLIMATIC CONDITIONS


All plant and equipment supplied under the Contract shall be entirely suitable for the climatic
conditions prevailing at site.
The project area and vicinity is close to sea level and is in a tropical climate. The ambient
shade temperature variation is between 4°C and 42°C with periods of high humidity.
Between May and November low lying areas are subject to flooding.
The flooding can be taken advantage of at certain Sites in that the heavy loads may be floated
on barges to close proximity to the Sites.
The project area is designated a zone of moderate intensity for earthquakes.
The seismic factor is 0.05 g to 0.1 g.
Atmospheric pollution is moderate and special insulator design or washing is not required.
The area is subject to high winds of typhoon strength.
Maximum ambient shade temperature 450C
Minimum ambient shade temperature 40 C
Maximum daily average temperature 350C
Maximum annual average temperature 250C
Maximum wind velocity 160 Km/h
Minimum wind velocity for line rating purposes 3.2 Km/h (132kV)
Solar radiation 100mW/sq.cm
Rainfall 2.5 m/annum
Relative humidity, maximum 100%
Relative humidity, average 80%
Altitude less than 150 m
Atmospheric Pollution light
(No ice or snow expected)
Soil type alluvial
Soil temperature (at 1.1m) 30OC
Soil thermal resistivity 1.5 °C m/W
Isokeraunic Level (Thunderstorm days/year) 80
The information in this Clause is given solely for the general assistance of Bidders and no
responsibility for it will be accepted nor will any claim based on this Clause be considered.