EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Condensate drain line (discharge piping) shall not be smaller than the SAES-K-100
A4
drain pan connection. (UMC Para 309.1). Section 1
Drain pans shall extend completely under the coil sections and shall
SAES-K-001
A5 have minimum 1-¼ inch threaded drain connections for AHUs with the
Para 4.8.8.9 (g)
total supply air equal to or greater than 5,000 cfm.
SAES-K-001
A6 Drain pan shall be sloped toward drain connection.
Para 4.8.8.9 (g)
Condensate drain line shall maintain a minimum horizontal slope in the SAES-K-100
A7
direction of discharge not less than 1%. (UMC para 309.1) Section 1
The drain pipe trap shall have a water seal height equal to or larger
than the fan's External Static Pressure (ESP) but not less than 50 mm
SAES-K-001
A8 (2").
Para 5.3.4.2 (d)
Note:ESP can be read from the Construction drawings or
Specifications
Drains pan shall be sealed, double wall steel construction with rigid SAES-K-001
A10
glass fiber insulation and Type 316 stainless steel inner pan. Para 4.8.8.9 (g)
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 05 Dec 2012
2-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 20 Oct, 2012
3-SAES-S-060 -- Saudi Aramco Plumbing Code, 28 March 2013
4-Uniform Mechanical Code (UMC), 2009
Page 1 of 2
QC Inspector PID Representative
Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:
Page 2 of 2