Вы находитесь на странице: 1из 1

SINGLE PANTHER ACSR SINGLE PANTHER ACSR

MAIN BUS SINGLE MOOSE ACSR


C1 (SINGLE MOOSE ACSR)

4
SINGLE PANTHER ACSR SINGLE MOOSE ACSR R3

8
9

5
R3.5

3.1
.5

0.6
FGL:1131 C2 9

5
0.8

0.6
3.18
3
4.5 3.75 2 C3 LINE SIDE EARTH WIRE SINGLE MOOSE ACSR

C.L. OF 66KV LA
C.L. OF ROAD

C.L. OF 66/11KV TRAFO

FGL:1128 3.5 ( NOT IN EMC SCOPE)


9

6T1S

6T1S
2.5
3.59

4
C4 LINE SIDE CONDUCTOR FGL:1125

6T1

6T1

8
0.7

3.1
1.5 4 ( NOT IN EMC SCOPE)
FGL:1125
C.L. OF 66KV CT

C.L. OF 66KV RETAINING WALL


3.75 2.5 2.25

4
0.8

C.L. OF 66KV TOWER & ISO

C.L. OF 66KV CB

C.L. OF 66KV CT

C.L. OF 66KV TOWER & ISO


8
3
4.5 2 3 1.2 2.6 3.8 0.5

3.1
C.L. OF 66KV CB

C.L. OF 66KV TOWER


C.L. OF 66KV ISO

C.L. OF 66KV BPI

C.L. OF 66KV TOWER


C.L. OF 66KV RCC RETAINING WALL

C.L. OF 66KV HIGH BPI (6 MTR.)


FGL:1122

4
3 1.5 4 2

6T1P

0.3
C.L. OF 66KV CB
C.L. OF 66KV ISO

C.L. OF 66KV BPI


FGL:1118
SL
O
1.5 3.5 2 2 PE

C.L. OF 66KV CT

C.L. OF 66KV ISO

C.L. OF 66KV LA
C.L. OF SLOPE
C.L. OF 66KV TOWER
C1 SL. DESCRIPTION OF
66 kV SYSTEM 11 kV SYSTEM
NO. PARAMETERS
FOR 1200 FOR <1000 FOR 1200
SECTION : A----A 1 MINIMUM CLEARANCES FOR <1000 Mtr.
Mtr. Mtr. Mtr.
i) PHASE TO PHASE 630 mm 646 mm 280 mm 287 mm
ii) PHASE TO EARTH 630 mm 646 mm 140 mm 144 mm

iii) SECTIONAL CLEARANCES 3500 mm 3588 mm 3000 mm 3075 mm


18
3.

SAFETY WORKING
iv) 3100 mm 3178 mm 2600 mm 2665 mm
CLEARANCE
2 RATED INSULATION LEVEL
FULL WAVE IMPULSE
i) WITHSTAND VOLTAGE 325 kVp 334 kVp 75 kVp 77 kVp
(1.2/50 microsec.)
C4
ONE MINUTE POWER
FREQUENCY DRY AND
ii) WET WITHSTAND VOLTAGE
140 kV 144 kV 28 kV 29 kV
(r.m.s.)
SAFETY WORKING CLEARANCE

C2 C3 2 THIRD SUBMISSION B.A. U.S. P.K.M 20.09.2017


1 SECOND SUBMISSION B.A. U.S. P.K.M 05.06.2017

0 FIRST SUBMISSION B.A. U.S. P.K.M 20-04-2017

2.5
3.59 PREP. CHKD. APPD.
5

REV. DESCRIPTION DATE


0.6

3.5 DESCRIPTION
9
CUSTOMER Power Grid Corporation of India Limited
(A Government of India Enterprises)
5
0.6

THIS DRAWING IS THE


PROPERTY OF M/S
EMC Limited
EMC LIMITED AND NOT
TO BE COPIED OR Constantia Office Complex, 11, Dr.U.N.Brahmachari
8
3.1

USED WITHOUT THEIR


Street, 8th Floor (South Block) Kolkata - 700 017,INDIA
3.18

PRIOR PERMISSION

SUPPLY CC-CS/93-ER2/SS-3239/3/G4/NOA-I/5849 dated 08.07.16


NOA NO.
SERVICE CC-CS/93-ER2/SS-3239/3/G4/NOA-II/5850 dated 08.07.16
8
3.1

Substation Package SIK-SS01 for (i) 132/66/11kV Dikchu Pool (New) S/s (ii)
220/132kV Legship Pool (New) S/S (iii) 66/11kV Makha (New) S/S (iv) 66/11kV
Temi (New) S/S (v) 66/11kV Khamdong (New) S/S (vi) 66/11kV Kumrek (New) S/S
PROJECT (vii) 66/11kV Namthang (New) S/S (viii) 66/11kV Rorathang (New) S/S (ix)
66/11kV Mamring (Extension) S/S under Comprehensive Scheme for
Strengthening of Transmission & Distribution System in Sikkim Spec. No.:
CC-CS/93-ER2/SS-3239/3/G4.
6T1P

SUBSTATION 66/11 KV TEMI NEW SUBSTATION


SAFETY WORKING & PH TO EARTH CLEARANCE DRG. TITLE ELECTRICAL CLEARANCE DIAGRAM
SAFETY WORKING & SECTIONAL CLEARANCE SAFETY WORKING & SECTIONAL CLEARANCE
DRG. NO. : EMC 670 TEMI E LAY DRG 007
SCALE N.T.S JOB NO. 670 SHEET 1 OF 1

Вам также может понравиться