Академический Документы
Профессиональный Документы
Культура Документы
Sr. No Title
1.0 INTRODUCTION
2.0 BASIC DATA FOR THE DESIGN OF WATER SUPPLY
SYSTEM
3.0 SALIENT FEATURES OF WATER TREATMENT
PLANT
4.0 POPULATION FORECASTING
5.0 CALCULATION OF WATER DEMAND
5.1 Calculation of different drafts
5.2 Design capacity of various components
5.3 Physical and chemical standards of water
5.4 Comparison of given data and standard data
5.5 Suggested units of treatment plant
6.0 DESIGN OF UNITS
6.1 Collection units
6.1.1 Design of intake well
6.1.2 Design of pen stock
6.1.3 Design of gravity main
6.1.4 Design of jack well
6.1.5 Design of pumping system
6.1.6 Design of rising main
6.2 Treatment units
6.2.1 Design of aeration unit
6.2.2 Design of chemical house and calculation of chemical dose
6.2.3 Design of mechanical rapid mix unit
6.2.4 Design of clriflocculator
6.2.5 Design of rapid gravity filter
6.2.6 Disinfection unit
6.3 Storage tank
7.0 CONCLUSION
REFERENCES:
INTRODUCTION
Water, undubiously is a basic human need. Providing safe and adequate quantities of the
same for all rural and urban communities, is perhaps one of the most important
undertaking, for the public works Dept. Indeed, the well planned water supply scheme, is
a prime and vital element of a country’s social infrastructures as on this peg hangs the
health and wellbeing of it’s people
The populationin India is likely to be Hundred crores by the turn of this century, with an
estimated 40% of urban population. This goes on to say that a very large demand of water
supply; for Domestic, Industrial, Firefighting, Public uses, ect; will have to be in
accordance with the rising population. Hence, identification of sources of water supply,
there conservation and optimum utilization is of paramount importance. The water
supplied should be ‘Potable’ and ‘Wholesome’ . Absolute pure water is never found in
nature, but invariable contains certain suspended, colloidal, and dissolved impurities
(organic and inorganic in nature, generally called solids), in varying degree of
concentration depending upon the source. Hence treatment of water to mitigate and/or
absolute removal of these impurities (Which could be; solids, pathogenic microorganisms,
odour and taste generators, toxic substances, etc.) become indispensable. Untreated or
improperly treated water, becomes unfit for intended use proves to be detrimental for life.
The designed water treatment plant has a perennial river as the basic source of water the
type of treatment to be given depends upon the given quality of water available and the
quality of water to be served. However such an extensive survey being not possible in the
designed water treatment plant. It is assumed that all kinds of treatment processors are
necessary and an elaborate design.
The design of water treatment plant for Gadhinglaj situated in district Kolhapur Maharastra
has been done. Gadhinglaj located on the bank of river Hirankeshi. The latitude and
longitude of the town corresponding 21.61N, 73.118E respectively. The population of the
given year 2031 will be 61400. Treated water supply for domestic and industrial uses are
very essential.
SALIENT FEATURES OF
WATER TREATMENT PLANT
1. POPULATION OF THE TOWN (IN THOUSAND
YEAR 1991
1. Length (m) : 20
2. Breadth (m) : 12
3. Height (m) :3.0
1. No. of Tank :1
2. Length (m) :2
3. Breadth (m) :2
4. Depth (m) :1.5
Flash mixer
1. No. of units :1
2. Dia. (m) :1.6
3. Detentio time (min) :0.5
4. Height (m) :2.6
5. Depth of water (m) :2.37
Clariflocculator
Flocculator:
1. No. of units :1
2. Dia. (m) :10.16
3. Dia. Of inlet pipes (m) :0.45
4. Depth of water flow (M) :3.5
5. Velocity of flow (m/s) :1.0
Clarifie:
1. No. of units :1
2. Dia. (m) :23
3. Depth of water (m) :4.4
4. Overall depth of tank (m) :4.7
5. Slope of bo :8%
6.
Rapid Sand Filter
1. No. of units : 2
2. Surface area (Sq. M) : 58.48
3. Dimension of unit (m x m) :8.6 x6.8
4. Thickess of sand bed (m) :0.6
5. Thickess of gravel bad (m) :0.5
6. Dia. Of manifold (m) :1 7. Laterals : a. No’s : 86 b. Dia. (mm) : 90 c.
Length (cm) : 2..9 d. Spacing (cm) : 20
8. No. of orifices :16
9. Dia. Of orifice (mm) : 13
10. Wash water tank :1
Disinfection house
1. Chiorine required / day (kg) : 1.662
2. Cylinder required / day (no.) :2
3.4STORAGE UNITS
Undergound reservoir
1. No. of units :1
2. Length (m) : 14
3. Breadth (m) : 14
4. Depth (m) : 4.5
4.2population forecast
General considerations
The population to be served during such period will have to be estimated with due
regard to all the factors governing the future growth and development of the city in the
industrial, commercial, educational. Social and administrative spheres. Special factors
causing sudden immigration or influx of population should also be foreseen to the
extent possible.
Calculation of Population with different Methods
(Table No. 4.1)
Sr.no Year Population Increase Increase Increamental Decrease
(thousand (thousand) % Increase in %
increase
) (thousand)
1 2 3 4 5 6 7
1 1761 7.48 - - - -
2 1971 12 4.52 60.45 - -
3 1981 15 03 25 -1.52 35.45
4 1991 22 07 45.67 4.0 -21.67
Total 14.52 132.12 2.48 13.78
Average 4.84 44.04 1.24 6.89
Arithmetical increase method
Using the relation
Po = pn + nc
Where.
Po = initial population;
Pn = Population in nth decade;
N = no. of decades;
C = average increase ( refer table 2.1, cik. 4)
P 2031 = 36521 + 4840.33
= 41361.33
N = No. of decade
P 2031 = 65744.86+(44.04 / 100 x 65744.8)
= 94698.17
Incremental increase Method
Using the relation
Pn = Po + (r+i0n
Where, r = Average rate of increase in population per
Decade (Ref. Table 4.1, Col. 5);
I = Average rate of incremental increase per
Decade
(Ref. Table 4.1 Col. 6);
pO = population in any decade;
pn = population in n decade;
p 2031 = 40239.49+ (4840.33+12395)
= 46319.32
Decrease Rate Of Growth Method
Year Expected population
2001 2200+ 39.78/100 × 2200 = 30751
2011 30751+ 32.39/100 × 30751 = 40865
2021 40865 +26/100× 40865 = 51490
2031 51490 + 19.11/100 × 51490 =61330
Also this method is more suitable for very big and older cities whereas in our case it is
relatively smaller and new town.
So results by this method is although good but not as accurate as desired.
This method would apply to cities with unlimited scope for expansion.
This method would apply to cities, likely to grow with a progressively increasing or
decreasing rate rather than constant rate.
Thus this gives weightage to the previous date as well as the latest trends. Decrease in
percentage increase is worked out average thus giving importance to whole date.
The city shall grow as per the logistic curve, which will plot straight line on the arithmetic
paper with the time intervals plotted against population in percentage of solution.
Also this method gives very approximate results. Thus this method is useful only to verify
the date obtained by some other method.
The city shall grow as per the logistic curve, which will plot straight line on the arithmetic
paper with the time intervals plotted against population in percentage of solution.
Simple Graphical Method
Since the result obtained by this method is dependent upon the intelligence of the designer,
this method of empirical nature and not much reliable.
Also this method gives very approximate results. Thus this method is useful only to verify
the date obtained by some other method.
=5.4 MLD
Fire Requirement:
2) Treatment unit:
a) Aeration unit
b) Coagulant dose
c) Lime soda dose
d) Chemical dissolving tank
e) Chemical hose
f) Flash mixer
g) Clariflocculator
h) Rapid sand filter
i) Chlorination unit
3) Storage unit:
a) Underground storage tank
b) Elevated storage
A schematic diagram of each of the unit is shown.
DESIGN OF UNITS
6.1 collection Units 6.1.1 Design of Intake well
a) Intake well
Intake consists of opening, strainer or grating through which the water enters, and the
conduct conveying the water, usually by gravity to a well or sump. From the well, the water
is pumped to the mains or treatment plants. Intakes should also be so located and designed
that possibility of interference with the supply is minimized and where uncertainty of
continuous serviceability exists, intakes should be duplicated. The following must be
considered in designing and locating the intakes.
The source of supply, whether impounding reservoir, lake or river (including the possibility
of wide fluctuation in water level).
The character of the intake surrounding, depth of water, character of bottom, navigation
requirements, the effect of currents, floods and storms upon the structure and in scouring
the bottom.
The location with respect to the sources of pollution.
The prevalence of floating materials, such as ice, logs and vegetation.
Types of Intakes:
• Wet Intakes: Water is up to source of supply
• Dry Intakes: No water inside it other than in the intake pipe.
• Submerged Intake: Entirely under the water.
• Movable and Floating Intakes: Used where wide variation in surface elevation
with sloping blanks.
Location of Intakes:
• The location of the best quality of water available.
• Currents that might threaten the safety of the intake structure.
• Navigation channels should be avoided.
• Ice flows and other difficulties.
• Formation of shoals and bars.
• Fetch of the wing and other conditions affection the weight of waves.
• Ice storm.
• Floods.
• Power availability and reliability.
• Accessibility.
• Distance from Pumping station.
• Possibilities of damage by moving objects and hazards.
The intake structure used intake our design is wet- type.
b) Design Criteria
c) Design Assumptions
Given F.S.L = 27m
Minimum R.L =28m
Given invert level of gravity mina=24m
Detention time = 10 min.
Design Calculation
Flow of water required = 8.1 MLD/3600X24
Volume of well
B) Design Criteria
Velocity through pen stock = 0.6 to1.0 m/sec.
Diameter of each pen stock = less than 1 m
Number of pen stock for each intake well =2
C) Design Calculation
Number of intake well =1
Number of pen stocks at each level =2
Velocity = 0.75 m/sec (assumed)
C/s area of each pen stock = 0.0937/0.75x2
= 0.0624 m2
Diameter = 0.28m≅0.3
D) Summary
.S
S = 1: 862
Head loss = 10/862
= 0.116
R.L of gravity main = 27 – 3
= 24 m
R.L of gravity main at jack well = 24 – 0.116
= 23.88m
(d) Summary
1. Number of gravity intake 1 unit
2. Diameter of gravity intake 0.55 m
hf
= 0.448
Head loss = 0.45
Total head of pumping = hs + hd + hf + minor losses
= 2.12+4.88+0.45+1
8.45
Assuming two pumps in parallel
W.H.P. =
B.H.P = = 14.07 HP
(e) Summary
Provide 1 – 25 HP pump in parallel
(d) Summary
1. Diameter of pipe 0.35m
6.2 Treatment units
The aim of water treatment is to produce and maintain water that is hygienically safe,
aesthetically attractive and palatable, in an economical manner. Albeit the treatment of
water would achieve the desired quality, the evaluation of its quality should be extended
to the point of consumer’s use. The method of treatment to be employed depends on the
characteristics of the raw water and the desired standards of water quality. The unit
operation and units’ processes in water treatment constitute aeration flocculation, water
conditioning and disinfection and may take many different combinations to suit the above
requirements.
In the cases of ground water and surface water storage which are well protected where the
water has turbidity below 10 JTU (Jackson Candle Turbidity Units) and is free from odour
and color, only disinfection by chlorination is adopted before supply.
Where ground water contains excessive dissolved carbon dioxide and odorous gases,
aeration followed by flocculation and sedimentation, rapid gravity or pressure filtration
and chlorination may be necessary.
Conventional treatment including prechlorination, aeration. Flocculation and
sedimentation rapid gravity filtration and postchlorination are adopted for highly polluted
surface waters laden with algae or microscopic organisms.
Based on the data given in second chapter, the following treatment units and accessory
units are designed to meet the quality and requirement of project:
Aeration Unit
Coagulant dose
Lime soda dose
Chemical dissolving tank
Chemical house
Flash mixer
Clariflocculator
Rapid sand filter Chlorination unit
The detail design of the above units are discussed in subsequent sections.
The concentration of gases in a liquid generally obeys Henry’s Law which states that the
concentration of each gas in water is directly proportional to the partial pressure, or
concentration of gas in the atmosphere in contact with water. The saturation concentration
of a gas decreases with temperature and dissolved salts in water. Aeration tends to
accelerate the gas exchange.
The three types of aerators are:
Waterfall or multiple tray aerators.
Cascade aerators.
Diffused air aerators.
Design calculation
Qmax = 0.0937 m3 / sec
Provide area at tray = 17m2
Diameter of bottom most tray = 5m
Rise of each tray = 0.4 m
Trade of each tray = 50m
Summary
Sr.
Cascade Diameter of tray (m) R.L. (m)
No
1 First 1 31.00
2 Second 2 30.60
3 Third 3 30.20
4 Fourth 4 29.80
5 Fifth 5 29.40
R.L.of ground at site = 29.00 m
Design of Chemical House and Calculation of Chemical Dose
The space for storing the chemicals required for the subsequent treatment of water consist
of determining space required for storing the most commonly used coagulant alum, lime,
chlorine etc. for the minimum period of three month and generally for six months.
The size of units also depends upon the location, transport facilities, weather conditions,
and distance of production units and availability of chemicals. Chemical house should be
designed to be free from moisture, sap, etc. These should be sufficient space for handling
hand measuring chemicals and other related operations.
It should be located near to the treatment plant and chemicals should be stored in such size
of bags that can be handled easily. Alum Dose:
Coagulation
The terms coagulation and flocculation are used rather indiscriminately to describe the
process of removal of turbidity caused by fine suspension colloids and organic colors.
Coagulation describes the effect produced by the addition of a chemical to a colloidal
dispersion, resulting in particle destabilization. Operationally, this achieved by the addition
of appropriate chemical and rapid intense mixing for obtaining uniform dispersion of the
chemical.
The coagulant dose in the field should be judiciously controlled in the light of the values.
Alum is used as coagulant.
Design Criteria For Alum Dose
Alum required in particular season is given below:
Monsoon = 50 mg / L
Winter = 20 mg / L
Summer = 5 mg / L
Alum required
Let the average does of Alum required be 50 mg / L, 20 mg / L, 5 mg / L, in monsoon ,
winter and summer, respectively .
Per day Alum required for worst season for intermediate stage
= 50 x 10 - 6 x 337. 5 x 103 x 24
= 405 kg / day
For six months (180 days) = 405 x 180
= 72900 kg
Number of bags whence 1 bag is containing 50 kg = 1458
If 15 Days in each heap = 97.2 heap
If area of one heap be 0.2 m2, then total area required = 48.6 50 m2 Lime
- soda process:
Softening
A water is said to be hard, when it does not form leather readily with soap.
The hardness of water is due to the presence of calcium and magnesium ions in most of
the cases. The method generally used are lime- soda process. Softening with these
chemicals is used particularly water with high initial hardness (>500 mg / L) and suitable
for water containing turbidity, color and iron salts. Lime- soda softening cannot, however,
reduce the hardness to values less than 40 mg / L.
high turbulence in the water. The source of power for rapid mixing to create the desired
intense turbulence are gravitation and pneumatic.
The intensity of mixing is dependent upon temporal mean velocity gradient ‘G’. This is
defined as the rate of change of change of velocity per unit distance normal to a section.
The turbulence and resultant intensity of mixing is based on the rate of power input to the
water.
Flash mixture is one of the most popular methods in which the chemicals are dispersed.
They are mixed by the impeller rotating at high speeds.
1. Dimension of tank :
Volume = 2.813m3
D = 1.7m
Height = 1.24+ (0.26m free board)
Total height of tank = 1.5m
2. Power Requirement :
Power spend = 3.16 kW
Dimension of Paddles:
= G2 x u v x vol
= 302 x 0.89 x 103 x (𝜋/4 𝑥 82𝑥 3.5)
= 140.92
Power input = ½ (Cd x p x AP x (v-u) 3
Cd = 1.8
P = 995 kg/m3 (250c)
V= Velocity of tip of blade = 0.4 m/sec. V=
Velocity of water tip of blade = 0.25 x 0.4
= 0.1 m/sec.
140.92 = ½ x 1.8 x 995 x AP x (0.4-0. 1)3
AP = 5.79m2
Ratio of paddles to cs of flocculator
[5.79/ (8-0.75) 3.5] x 100 = 7.26% < 10 to 25%
Provide AP = 8 m2
AP = [8/ (8-0.75) 3.5] x 100 = 10.1% ….ok
Which is acceptable (within 10 to 25%)
Provide 5 no of paddies of 3 m height and 0.7 m width
One shaft will support 5 paddles
The paddles will rotate at an rpm of 4
V = 2 x 𝜋 x r x 𝜋/60
0.4 = 2x 𝜋 x r x 4/60 r
= 0.96m ≅ 1m
r = distance of paddle from C1. Of vertical shaft
Let velocity of water below the partition wall between the flocculator and clarifier be 0.3
m/sec.
Area = 337.5/0.3 x 60 x 60 = 0.3/m2
Depth below partition wall = 0.31/ 8
= 0.0123m
Provide 25% for storage of sludge = 0.25 x 3.5
= 0.875m
Provide 8% slope for bottom
Total depth of tank at partition wall = 0.3 + 3.5 + 0.012 + 0875
= 4.69m ≅ 4.7m
Design of Clarifier
Assuming a surface overflow rate of 40m3/m2/day
Surface of clariflocculator = 337.5 x 24/ 40
= 202.5m2
Dcf= Dia. Of clariflocculator
𝜋4[Dcf2 – (8)2] = 202.5m
Dcf = 17.94 ≅18m
Length of weir = 𝜋 x Dcf
= 𝜋 x 23 = 72.26m
Weir loading = 337.5 x 24/72.26
= 112.09m3 /day/m
According to manual of Govt of India. If it is a well clarifier it can exceed up to
1500m3/day/m
Summary (Clariflocculato)
1. Detention period 30min
4. Diameter of tank 8m
The intensity of mixing is dependent upon temporal mean velocity gradient ‘G’. This is
defined as the rate of change of change of velocity per unit distance normal to a section.
The turbulence and resultant intensity of mixing is based on the rate of power input to the
water.
Flash mixture is one of the most popular methods in which the chemicals are dispersed.
They are mixed by the impeller rotating at high speeds.
5. Dimension of tank :
Volume = 2.813m3
D = 1.7m
Height = 1.24+ (0.26m free board)
Total height of tank = 1.5m
Design of Clariflocculator
Clariflocculator
The coagulation and sedimentation processes are affectively incorporated in a single unit
in the clariflocculator. Sometimes clarifier and clariflocculator are designed as separate
units.
All these units consists of 2 or 4 flocculating paddles placed equidistantly. Theses paddles
rotate on their vertical axis. The flocculating paddles may be of rotor-stator type. Rotating
in opposite direction above the vertical axis. The clarification unit outside the flocculation
compartment is served by inwardly raking rotating blades. The water mixed with
chemical is fed in the flocculation compartment fitted with paddles rotating at low speeds
thus forming flocs.
The flocculated water passes out from the bottom of the flocculation tank to the clarifying
zone through a wide opening. The area of the opening being large enough to maintain a
very low velocity. Under quiescent conditions, in the annular setting zone the floc
embedding the suspended particles settle to the bottom and the clear effluent overflows
into the peripheral launder.
(c) Assumptions
Average outflow from clariflocculator = 337.5 m3/hr.
Water lost in desludging = 2%
Design average period = 344.25 m3/ hr.
Detention period = 30 min.
Average value of velocity gradient = 30 s-1
Dimension of Paddles:
= G2 x u v x vol
= 302 x 0.89 x 103 x (𝜋/4 𝑥 82𝑥 3.5)
= 140.92
Power input = ½ (Cd x p x AP x (v-u) 3
Cd = 1.8
P = 995 kg/m3 (250c)
V= Velocity of tip of blade = 0.4 m/sec. V=
Velocity of water tip of blade = 0.25 x 0.4
= 0.1 m/sec.
140.92 = ½ x 1.8 x 995 x AP x (0.4-0. 1)3
AP = 5.79m2
Design of Clarifier
Assuming a surface overflow rate of 40m3/m2/day
Surface of clariflocculator = 337.5 x 24/ 40
= 202.5m2
Dcf= Dia. Of clariflocculator
𝜋4[Dcf2 – (8)2] = 202.5m
Dcf = 17.94 ≅18m
Length of weir = 𝜋 x Dcf
= 𝜋 x 23 = 72.26m
Weir loading = 337.5 x 24/72.26
= 112.09m3 /day/m
According to manual of Govt of India. If it is a well clarifier it can exceed up to
1500m3/day/m
Summary (Clariflocculato)
1 Detention period 30min
2 Diameter of influent pipes 350mm
3 Overall depth of flocculator 3.5m
4 Diameter of tank 8m
5 No. of paddles (3m height and 0.7 m width) 5
6 Distance of shaft from C.L. of flocculater 1m
7 Paddles rotation (RPM) 4
8 Distance of paddle from C.L. of vertical shaft 1m
9 Slope of bottom (%) 8
10 Total depth of partition wall 4.7m
11 Diameter of clariflocculater 18m