SPECIFICATION OF REVERSE OSMOSIS (RO) PLANT:

General features:

i) The system shall be completely assembled, pre-piped with CPVC Piping


in suitable fixable diameters, pre Electrical wired and preferably skid
mounted.

ii) The System shall have microprocessor based control panel for ease of
operating and inbuilt process logic.

iii) The system shall be auto start/stop based on water level in the supply
tank.

iv) The system shall be equipped with Electrical panel/MCB for plant
protection and shall have integrated raw water pump with the unit.

v) The system shall have integrated pre-treatment modules for removal of


suspended solids along with pressure gauge.

vi) The System shall have inbuilt protection to high pressure pump by way
of low/high pressure switch.

vii) The System shall have the membrane of General Electric (GE) or
Hydranutics make. Glycerine filled Stainless Steel pressure gauge shall
be provided for durability. Online rotometer shall be provided for
measuring flow. Blending cartridge shall be provided to adjust tests/TDS
and followed by UV disinfection for total safety. System should have
automatic backwashing of filters.

viii) The system shall be capable of working 24 Hrsx365 days by using the
semi treated water provided through Bore Well / Municipal water Supply.

ix) Recovery of water (i.e component of treated water) shall be in range of


40%-60%. If desired. The waste/rejected water may be separately
stored by using suitable pump. This water may be used for cleaning
gardening or toilet purpose.
TECHNICAL FEATURES:

Sl. RO Plant RO Plant


No Specifications Specifications
Description Capacity: 500 LPH. Capacity: 1000
LPH.

1 RAW WATER
Type Centrifugal Centrifugal
FEED PUMP
Flow rate 1500 Litres/Hour 2000 Litres/Hour
Discharge
2.50 Kg/Cm² (Min) 2.50 Kg/Cm² (Min)
Capacity
Motor Rating 0.50 HP (Min) 1.00 HP (Min)
Electricity 220 V Single Phase 220 V Single Phase
Quantity 1 1
CRI,KSB or equivalent CRI,KSB or
Make
to BIS equivalent to BIS
2 SAND FILTER -
Capacity 1500 Litres/Hour
Min. Operating -
1.50Kg/ Cm²
Pressure
Media - Support Sand Filter
-
Quantity 1
- Pressure range 0-
Pressure Switch
10 Bar
2A DUAL MEDIA -
FILTER (DMF)
Capacity (min) 2000 Litres/Hour
(For capacity
above 500LPH)
Operating -
3.50 Kg/Cm² (Min)
Pressure (min)
Type of Value Single Multiport -

Media -
Anthracite+ Support
(SAND+CARBO
bed
N)
-
Bed depth (min) 800mm
-
Quantity 1
Penlair,Wave or -
Vessel Make
Equivalent
Pressure range -
Pressure Switch
0-10 Bar
3 ACTIVATED
CARBON Capacity - 2000 Litres/Hour
FILTER (ACF)
Min Operating
- 1.50 kg/ Cm²
pressure
Media - Activated Carbon
Quantity - 1
Pentair, Wave lon
Vessel make - Exchange or
equivalent to BIS

Sl. RO Plant RO Plant


No Specifications Specifications
Description Capacity: 500 LPH. Capacity: 1000
LPH.

4 Anti scalant
Dosing Pump
Dosing System
Type Electro magnetic Electro magnetic
Capacity 1.50 Litre / Hour 1.50 Litre / Hour
Discharge 4 KG/ Cm² 4 KG/ Cm²
pressure
Quantity 1 1
Make E dose, Hydracell, E dose, Hydracell,
Sandur or Equivalent Sandur or Equivalent
to BIS. to BIS.
Dosing Tank

Capacity 100 Liters 100 Liters


Materials of HDPE HDPE
Const.
Quantity 1 1
Micron
Cartridge Filter
(for removing
5 Capacity 1200 Litres /Hour 2000 Litres /Hour
suspended
particles>5
micron)
Material of
Polypropylene Polypropylene
Cartridge
Filter Rating 5 Micron 5 Micron
Length 20” 20”
Quantity 1 1
Pratham, Aquapure or Pratham, Aquapuro
Make
Equivalent to BIS or Equivalent to BIS
High Pressure Vertical Multistage Vertical Multistage
6 Type of Pump
Pump Centrifugal Centrifugal
Capacity 1200 Litres/Hour 2000 Litres/Hour
Discharge
13 Kg/ Cm² 13 Kg/ Cm²
Pressure (Max)
Material of
SS 304 SS 304
Constructions
Electricity 220 V Single Phase 220 V Single Phase
Quantity 1 1
LUBI, CRI,LEO or LUBI, CRI, LEO or
Make
Equivalent to BIS. Equivalent to BIS.

Sl. RO Plant RO Plant


No Specifications Specifications
Capacity: 500 LPH. Capacity: 1000
Description
LPH.

Reverse
Permeate
7 Osmosis 500 Litres /Hour 1000 Litres /Hour
Capacity
Membrane
Spiral Wound TFC- Spiral Wound TFC-
Membrane type
Polyamide Polyamide
Size Dia 4”x 40” long Dia 80”x 40” long
No.of
2 1
Membrane
No.of
Membrane 2 1
Housing
Skid Material of Mild Steel powder Mild Steel powder
Construction Coated Coated
HITECH/ HITECH/
Make of
Hydronautics or Hydronautics or
Membrane
Equivalent to BIS Equivalent to BIS
8 UV System Capacity 500 Litres/Hour 1000 Litres/Hour
Quantity 1 1
Make Sukrut or Equivalent Sukrut or Equivalent
Instrument list A) Pressure
9 2 Nos. 2 Nos.
gauges
Range
0-21 bar 0-21 bar
Dail Size
4 inches 4 inches
Type
Bourdon Bourdon
B) Pressure
2 Nos. 2 Nos.
Switches
Range 0-450 psl 0-450 psl
A) Starters
over load Should be provided of Should be provided of
Electrical
single/three adequate capacity adequate capacity
10 Control Panel
phase Havells /Anchor Havells /Anchor
controller for /Equivalent to BIS /Equivalent to BIS
pump
B) Voltmeter, Should be provided of Should be provided of
Ammeter,
adequate capacity adequate capacity
MCB’s
C) PLC & Touch
Should be provided Should be provided
panel
D) Feed/produc
t water
Should be provided Should be provided
conductivity
meter/TDS
Sl. RO Plant RO Plant
No Specifications Specifications
Capacity: 500 LPH. Capacity: 1000
Description
LPH.

Raw Water
Capacity
11 Tank 1000 Litres 2000 Litres

Type
3 Layers 3 Layers

Make Sintex /Sudhakar Sintex /Sudhakar


Equivalent Equivalent
SS Tank for
Drinking
Capacity
12 Water and 1000 Litres 2000 Litres
Storage

Type
Stainless Steel Stainless Steel
OTHER CONDITONS:

1 The RO Plants should be supplied, Installed and Commissioned as per


the General features, and technical specifications as mentioned above.

2. The installation of total consignment of (92) units should be within


(60) days.

3. In case failure to install and commence all the RO plants within the
stipulated time order shall be cancelled and action will be taken against the firm
as deemed fit.

4. The unit cost should be quoted inclusive of all cost and conveyance
of materials, Equipment, transportation, labour charges for installation and
commencement including all internal taxes and GST.

5. The participating firm should submit their firm Registration details


PAN, GST/TIN Registration etc., invariably.

6. The Firm should demonstrate free service, maintenance training of


cleaning the RO Plant and technical guidelines to the Institution
officers at the time of connections, Installation of the RO Plant.

7. The Maintenance period shall be (12) Months from the date of


commencement of the RO Plant including all spares.

8. All the items as per the specification should be supplied with (2)
years warranty and maintenance.

9. The firm should get the sample of drinking water and get tested in
the reputed quality testing laboratories and the produce the test report. The
drinking water should be as per BIS standards.

10 A) In case of any break downs or failure of functioning of RO system


during the maintenance period ie., (12) months of AMC the firm has to attend
within (48) Hours.

10 B) Failed to attend the AMC within (48) Hours penalty shall be imposed
at 1% of cost per day up to (3) days, 3% up to (10) days. If the firm not attended
the AMC beyond (10) days penal action shall be initiated to recover the EMD as
deemed fit.
11. The contact number for AMC offering should be affixed on the RO
Plant When ever need to call for attending break down.

12. Payment shall be made by the Executing Engineer, Tribal Welfare,


concerned after the verification and testing of RO Plants by the HWO/ATDO of the
concerned institution in regard to quality specification and test reports of
Drinking water etc.,

13. To impose and recover penalty for delay in supplies as specified


below.

Sl.No. Delay Penalty (in percentage of the


value of store not supplied
within time )
1 Upto 15 days 1%
2 16-30 Days 2%
3 31-60 Days 3%
4 61-90 Days 4%
5 91 to 120 Days 5%
6 Beyond 120 days 6%