Академический Документы
Профессиональный Документы
Культура Документы
Peripheral Expansion
Network Node
Up to 4 Loop Panel
Touch Control
Annunciator
Peripheral Expansion Network Node
8 Zone 10 Input
Monitored
4 Output
PSE
6 Fan
Control Display
Junction Box
ModBus BacNet
Redundancy IP/Web
AX-LPD
Two Additional
Signaling Line
Circuits (SLC’s)
Axis Ax – Board (2)
Two Signaling Line Circuits (SLC’s) Two Notification Appliance Circuits (NAC)
USB Port
Battery
RS232 Port 24 VDC @ 48 Ah (max.)
(temperature compensated)
Internal Panel Bus
(RS485) Battery
Start Button
24 VDC @ 0.5 Amp, Resettable Power
24 VDC @ 0.5 Amp Non-resettable Power Auxiliary PSU 24 VDC @ 5 Amp
Power Input/Supervision Contact
Signalling Line Circuit - SLC
▪ 100% Digital Protocol STYLE 6/7 STYLE 4
LOOP LOOP
▪ 24 VDC @ 0.5 Amp OUT RET OUT
ALARM SUPERVISORY
PRE-ALARM
R ESET
! ACK
ABC DEF
DISABLE RESOUND F1
TEST
F ire System
R e m o t e A n n u n c ia t o r
GHI JKL MNO
POWER
ESC MENU
D R IL L F3
HOLD 2 SEC
▪ Remote Control Terminal/Repeater
▪ 10” HD Touchscreen
▪ Active Map display
▪ Network node
▪ Easy two-part, slide-in, installation
▪ All the control & indication features of Advanced RCT/repeater
▪ Does not include programmable buttons or key switches – it’s a
touchscreen!
▪ Dedicated LED indication
▪ Works with or without gloved hands
▪ Programmed on screen or via Config Tool
▪ Active Maps easily created and added with Map Tool from any drawing/pic
▪ Standard Advanced 3-level access
▪ Via Advanced 3-level controls users can:
▪ Evacuate, Mute, Silence & Reset
▪ View
▪ Enable/disable outputs by type
▪ Enable Walk Test Mode
▪ Test display/zones/outputs/buzzer and
LEDs
▪ Quickly access all zones in
fire/fault/disablement/test via ‘instant
filters’ and where allowed change status
▪ View 1000 event General and 500 event
Fire log
▪ Set network time & date
▪ Dedicated status indicators
Active
Maps
The PENN (Peripheral Expansion Network Node) from
Advanced is your key to unlocking greater power and versatility
for your fire system.
The PENN :
• Allows you to expand/reconfigure your fire system without affecting the
existing installation
• Helps you to reduce costs and disruption by allowing remote inputs and
outputs to be connected directly to the network instead of having to wire
them back to a panel, which may be distantly located
Two Signaling Line Circuits (SLC’s)
TB TB TB
A B
Last Module – FIT EOL to
spare terminals
To External Modules B A B A B A B A B A B A
8 Conventional Zone 10 Input Zone
6 Fan Control
8 Relay Output
ExGo – Control Panel Specification
▪ Backlit 128x64 LCD Display
▪ Large Countdown timer on LCD screen
▪ 1,000 event log entries which can be downloaded to a PC
▪ 3 conventional detection zones (inc support for I.S. barrier)
▪ 1 Flooding/extinguishing zone
▪ 4 relay outputs (Fire, Fault and 2x programmable) rated 30V DC at 1A max
▪ 3 sounder circuits 21-28VDC rated at 700mA max
▪ 2 aux supply outputs (1 switched), 21-28 VDC each rated at 500mA
▪ 11 monitored inputs. 4 programmable, 1 manual trigger, 6 Release related
(Mode, Valve Monitor, Pressure Monitor, Hold, Abort, Flow)
▪ Support for monitoring status of a manual isolate valve/ abort input
▪ RS-485 link to remote status indicators (maximum of 7)