Вы находитесь на странице: 1из 1

ANNEXURE - IV

3-4 Public health and plumbing engineering

should be given to increasing the stack diameter


from that calculated in order to allow air move-
ment within the core of the stack, or using a
secondary ventilated stack instead of a primary
ventilated stack.
— The height of the building: the height of the building
and associated stack height will determine the
velocity of the waste water in the stack and the 2
likely positive and negative pressure created.
— The types of fitting that are to be used: this will have a
bearing of the flow of the waste water within the
stack with particular regard to the radius of any 3
offsets and turbulence from any adjoining
branches.
— Any changes in direction: changes in direction 4
should be avoided wherever practicable as they 5
generate back-pressure leading to loss of trap seal
as air is blown through the trap or, in extreme
cases, foul water being pushed back into the
building through the lowest connected appliances 6
on that floor.
— How the stack is to be ventilated: all discharge stacks Legend:
ideally should be ventilated to atmosphere BS EN 1 Open to atmosphere
12056-2(27). This is the designer’s most effective 2 Negative pressure
tool in balancing pressures within a discharge 3 Induced siphonage related to suction (negative pressure)
stack as it will allow air out under positive in the stack
pressure situations and entrain air under negative 4 Back pressure related to positive pressure in stack
pressure situations. Air admittance valves will 5 Positive pressure
only entrain air to relieve negative pressures and 6 Typical air pressure distribution in stack with two branches
therefore cannot be used for positive pressure discharging
applications. The designer should also give Note: Connection close to base of stack is not recommended but
consideration to the location of the vent is shown here to illustrate pressure effects.
termination so as not to be affected by the wind. Figure 3.1 Pressure effects and seal losses due to water flow in a
discharge stack (reproduced from BS EN 12056-2(27) by permission of the
— Surcharging of the underground drain: if it is antici- British Standards Institution)
pated that the underground drainage system is
liable to surcharge, measures must be taken to
prevent foul water entering the building. This is
achieved by ensuring that there are no low-level When calculating the discharge stack diameter the
appliances connected and, in addition, relieving designer must first establish the waste water flow rate (Q)
the positive pressures generated whilst the system by selecting the most appropriate value(s) for the
is still in use during the surcharge period by appliance(s) connected to the stack from the table. Once
means of adequate venting. each connected appliance has been allocated an
appropriate value, the total number of discharge units for
Figure 3.1 gives an indication of the pressures generated each stack can then be calculated by totalling the number
with a discharge stack under normal operation and the of discharge units from all the connected appliances.
effect on the traps connected for a multi-storey building.
When the sum of the discharge units (∑ DU) has been
calculated, the designer selects an appropriate frequency
3.4.4.3 Discharge stack sizing factor (K) for the type of building/development using BS
EN 12056-2, Table 3. Some values, drawn from this table,
Discharge stack sizing is achieved using the ‘discharge are given in Table 3.2.
unit’ method set down in BS EN 12056-2(27) for all gravity
drainage systems using the following formula: Having selected a value for the frequency factor (K) and
determined the sum of the discharge units (∑ DU), these
values can then be substituted into equation 3.1 to give the
Q ww = K ∑ (DU ) (3.1) waste water flow rate (Q) for each discharge stack.

where Qww is the waste water design flow rate (l·s–1), K is Example
the frequency factor and ∑ DU is the sum of the discharge
units. Determine the waste water flow rate for 8 apartments each
with a WC, wash basin, bath, kitchen sink and domestic
Table 2 of BS EN 12056-2 (27) gives discharge units for a washing machine.
wide range of appliances and sanitary fittings in common
use for all four system types. Some values, drawn from this From Table 2 of BS EN 12056-2(27), a discharge unit (DU)
table, are given in Table 3.1. value appropriate to each appliance is selected:

Вам также может понравиться