Static Pressure Calculator

L = CENTER DISTANCE INCHES 34


DUCT DIA 18

VELOCITY 1500
Q = Air Flow Rate, CFM 2650.725 1. Enter number for L in inches
D = DUCT DIA IN FEET 1.5 2. Enter Duct Diameter
A = AREA, Feet Squared 1.76715 3. Enter Velocity
V = AIR VELOCITY, Feet Per Minute 1500 4. Enter C - dynamic loss coefficient
VP = VELOCITY PRESSURE 0.1402741 5. Then get SP for each piece of duct
L = CENTER LINE DISTANCE, Feet 2.83333333 6. Do this for each duct piece to get Total SP for system
C = DYNAMIC LOSS COEFFICIENT 1.25

DUCT STATIC PRESURE = FRICTION LOSS + DYNAMIC LOSS

SPF = FRICTION LOSS 0.00516676


SPD = DYNAMIC LOSS 0.17534262

SP = STATIC PRESSURE 0.18051


PART L Center Distance in Inches
Factory Installed Riser 4
Field Installed Riser 4
Straight Duct Depends on Length
Adjustable Duct Depends on Length minus Minimum Overlap
Adaptor (all sizes) 13
90 Elbow (8" diameter) 15
90 Elbow (10" diameter) 16
90 Elbow (12" diameter) 17.5
90 Elbow (14" diameter) 18.7
90 Elbow (16" diameter) 21
90 Elbow (18" diameter) 22
90 Elbow (20" diameter) 23.5
90 Elbow (24" diameter) 26.5
45 Elbow (8" diameter) 8.8
45 Elbow (10" diameter) 9.5
45 Elbow (12" diameter) 10.2
45 Elbow (14" diameter) 10.9
45 Elbow (16" diameter) 11.6
45 Elbow (18" diameter) 12.3
45 Elbow (20" diameter) 13
45 Elbow (24" diameter) 14.4
Duct Tee (8" diameter) 15
Duct Tee (10" diameter) 17
Duct Tee (12" diameter) 19
Duct Tee (14" diameter) 21
Duct Tee (16" diameter) 23
Duct Tee (18" diameter) 25
Duct Tee (20" diameter) 27
Duct Tee (24" diameter) 31
Y Tee (12" diameter) 28
Y Tee (14" diameter) 30
Y Tee (18" diameter) 33.5
Y Tee (20" diameter) 35.5
Y Tee (24" diameter) 54
Off Set Collar 4 when matched with horizontal run
8" Duct Diameter Str
Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.017
STRAIGHT/ADJ See Design Guide
ADAPTOR (8 TO 12) 0.797
90 ELBOW 0.400
45 ELBOW 0.150
DUCT TEE 1.250

10" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.013
STRAIGHT/ADJ See Design Guide
ADAPTOR (10 TO 14) 0.470
90 ELBOW 0.420
45 ELBOW 0.150
DUCT TEE 1.250

12" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.011
STRAIGHT/ADJ See Design Guide
ADAPTOR (12 TO 18) 0.797
90 ELBOW 0.440
45 ELBOW 0.150
DUCT TEE 1.250
Y TEE 0.600

14" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.010
STRAIGHT/ADJ See Design Guide
ADAPTOR (14 TO 20) 0.522
90 ELBOW 0.460
45 ELBOW 0.150
DUCT TEE 1.250
Y TEE 0.600

16" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.008
STRAIGHT/ADJ See Design Guide
ADAPTOR (16 TO 24) 0.797
90 ELBOW 0.480
45 ELBOW 0.150
DUCT TEE 1.250

18" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.006
STRAIGHT/ADJ See Design Guide
90 ELBOW 0.500
45 ELBOW 0.150
DUCT TEE 1.250
Y TEE 0.600

20" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.005
STRAIGHT/ADJ See Design Guide
90 ELBOW 0.520
45 ELBOW 0.150
DUCT TEE 1.250
Y TEE 0.600

24" Duct Diameter


Duct Component Dynamic Loss Coefficient
RISER/FRISER 0.004
STRAIGHT/ADJ See Design Guide
90 ELBOW 0.540
45 ELBOW 0.150
DUCT TEE 1.250
Y TEE 0.600
Straight and Adjustable Dynamic Loss Coefficient Table
Duct Velocity (V) = CFM/Area (in ft sq) = FPM
Round Area
8" = 50.24 in sq or 0.348 ft sq
10" = 78.5 in sq or 0.545 ft sq
12" = 113.04 in sq or 0.79 ft sq
14" = 153.86 in sq or 1.07 ft sq
16" = 200.96 in sq or 1.40 ft sq
18" = 254.34 in sq or 1.77 ft sq
20" = 314.00 in sq or 2.18 ft sq
24" = 452.16 in sq or 3.14 ft sq

Square Area
12" = 144 in sq or 1.00 ft sq
14" = 196 in sq or 1.36 ft sq
16" = 256 in sq or 1.78 ft sq
18" = 324 in sq or 2.25 ft sq
20" = 400 in sq or 2.78 ft sq
22" = 484 sq in or 3.36 ft sq
24" = 576 sq in or 2.00 ft sq