VENDOR TECHNICAL CLARIFICATION FOR FLOATING ROOF STORAGE TANKS

PLANT LOCATION: NORTH JEDDAH BULK PLANT REV.: A

PROJECT TITLE: YANBU DISTRIBUTION HUB AND NORTH JIDDAH BULK PLANT EXPANSION VENDOR NAME: METSCCO

PACKAGE TITLE: FLOATING ROOF STORAGE TANKS VENDOR REFERENCE: 3919R3

MECHANICAL - JZ Clarification / Confirmation items Vendor's Response JZ Response Vendor's Response JZ Response Clarification Status
Sr.
Rev.
No.
Date Offer Reference Description Date Description Date Description Date Description Date Open/ Closed

MECHANICAL

All structural steels (Stairways, Platforms, Ladders, etc) shall


A M1 10-Dec-2017 be galvanized and coated per SAES-H-001. 13-Dec-2017 Noted Closed

Fixed Foam chambers shall be spaced equally with intervals


less than or equal 80 ft. Confirmed, however fixed foam chambers are excluded
A M2 10-Dec-2017 13-Dec-2017 17-Dec-17 Noted Closed
from Metscco scope.

Vendor shall comply to SAES-B-018 for Fixed Foam System.


A M3 10-Dec-2017 13-Dec-2017 Excluded from Metscco scope. 17-Dec-17 Noted Closed

Linear Seal Rim Fire Detection is required as per SAES-B-005


Section 5.1.5 (b).
A M4 10-Dec-2017 VENDOR shall provide clips for cable. 13-Dec-2017 Metscco will only provide clips for cable. 17-Dec-17 Noted Closed

Vendor to confirm determining the design wind pressure in


accordance with the procedures detailed in ASCE 7 (2005
A M5 10-Dec-2017 Edition). Occupancy Category IV shall be used and the 13-Dec-2017 Noted Closed
corresponding Importance Factor shall be I WIND=1.15.

The Tank Manufacturer shall submit a complete material


specification complete material details will be indicated in general
A M6 10-Dec-2017 13-Dec-2017 17-Dec-17 Noted Closed
arrangement drawing and calculation sheet.

Vendor shall submit all calculations related to design,


A M7 10-Dec-2017 construction, testing etc. for review and approval. 13-Dec-2017 It will be submitted with NMR 601. 17-Dec-17 Noted Closed

Vendor shall provide nozzles for RTG along with stilling well as
A M8 10-Dec-2017 per Saudi Aramco Standard Drawing AA-036256.001 13-Dec-2017 Noted Closed

Vendor to comply the datasheet and Technical Specification


A M9 10-Dec-2017 (attached). 13-Dec-2017 Noted as applicable Closed

Vendor shall submit all calculations related to design,


A M10 10-Dec-2017 construction, testing etc. attached to NMR-601 for review and 13-Dec-2017 Noted as applicable Closed
approval.
Vendor to submit native files for compliance form and deviation
A M11 10-Dec-2017 list. 13-Dec-2017 Submitted on 12 Dec. 17 to SSEM 17-Dec-17 Noted Closed

PROCESS

A P01 10-Dec-2017 Vendor to consider for X07-D-0335, Emptying rate is = 69 m3/h. 13-Dec-2017 Noted Closed

specific gravity range (0.737-0.870),


Noted.

As per datasheet doc. No. VE-086484_Rev.B and VE- Please note that as per SAES-H-001,
086485_Rev.B For painting system, APCS-2D, the
specific gravity range is : (0.757-0.870). Revise the whole tank must be 100% coated from
datasheet. Vendor shall comply and consider inside. Now, as per datasheet for
Vendor to X07-D-0335 and X07-D-0336 Surge tank shall contain:
specific gravity range (0.737-0.870). internal floating roof tanks (VE-
Diesel / Kerosene / Gasoline PG91/PG95 as alternative product.
A P02 10-Dec-2017 13-Dec-2017 As per the datasheet for internal floating roof tanks (VE- 17-Dec-17 18-Dec-17 086484, 086485, 086483) it is Open
Specific gravity range for these prducts are between : (0.737 -
086484, 086485, 086483) multiple product is mentioned For painting system, APCS-2D is mentioned as supported cone roof.
0.870)
including kerosene and internal painting spec. is APCS accepted. This has to be revised to self
2A. However as per SAES-H-001, for kerosene product, it supported roof as per cl. 5.10.2.10 of
shall be APCA-2D. we have followed your datasheet for 32-SAMSS-005. We would suggest to
painting spec. APCS 2A. revise your datasheets considering
above comments and others (if any).

This will have price impact.

As per datasheet doc. No. VE-086485_Rev.B


Vendor shall comply and consider
Vendor to consider for X07-D-0336, Emptying rate is = 69 m3/h. Emptying rate is = 69 m3/h
A P03 10-Dec-2017 13-Dec-2017 17-Dec-17 Emptying rate is = 69 m3/h. and Filling 18-Dec-17 Noted Open
and Filling rate is : 2252 m3/h Filling rate is = 1556.8 m3/h
rate is : 2252 m3/h
Revise the datasheet.

Page 1 of 3
PLANT LOCATION: NORTH JEDDAH BULK PLANT REV.: A

PROJECT TITLE: YANBU DISTRIBUTION HUB AND NORTH JIDDAH BULK PLANT EXPANSION VENDOR NAME: METSCCO

PACKAGE TITLE: FLOATING ROOF STORAGE TANKS VENDOR REFERENCE: 3919R3

MECHANICAL - JZ Clarification / Confirmation items Vendor's Response JZ Response Vendor's Response JZ Response Clarification Status
Sr.
Rev.
No.
Date Offer Reference Description Date Description Date Description Date Description Date Open/ Closed

As per datasheet doc. No. VE-086485_Rev.B Vendor shall comply and consider Filling
Vendor to consider for X07-D-0336, Filling rate is : 2292 m3/h Filling rate is = 1556.8 m3/h rate is : 2292 m3/h
A P04 10-Dec-2017 13-Dec-2017 17-Dec-17 18-Dec-17 Noted Open
and specific gravity range is : (0.775-0.870) specific gravity range is : (0.757-0.870). Revise the and specific gravity range is : (0.737-
datasheet. 0.870)

INTERNAL FLOATING ROOF OVER PRESSURE/VACUMM


TYPE VENTS SHALL BE SIZED AND PROVIDED BY TANK
A P05 10-Dec-2017 13-Dec-2017 Noted Closed
VENDOR ACCORDANCE WITH API STD 2000, 32-SAMSS-005
(Annex H) and SAES-D-100.

EXTERNAL FLOATING ROOF OVER PRESSURE/VACUUM


BLEEDER TYPE VENTS SHALL BE SIZED AND PROVIDED BY
A P06 10-Dec-2017 13-Dec-2017 Noted Closed
TANK VENDOR ACCORDANCE WITH API STD 2000, 32-
SAMSS-005 (Annex C) and SAES-D-100.

X07-D-0329/0331, Critical High level shall be considered as per


A P07 10-Dec-2017 13-Dec-2017 Noted Closed
API 2350 and will be 18002 mm.

X07-D-0334 A/B, Critical High level shall be considered as per


A P08 10-Dec-2017 13-Dec-2017 Noted Closed
API 2350 and will be 12408 mm.

X07-D-0335, Critical High level shall be considered as per API


A P09 10-Dec-2017 2350 and will be 11414 mm. Based on this vendor to confirm the 13-Dec-2017 Noted Closed
tank height.

X07-D-0336, Critical High level shall be considered as per API


A P10 10-Dec-2017 2350 and will be 11647 mm. Based on this vendor to confirm the 13-Dec-2017 Noted Closed
tank height.

PIPING

Vendor shall consider the access/ladder (and additional Noted, however sampling jar, valves and pipings are
provisions for mounting them) for the elevated valves part of 13-Dec-2017 excluded from Metscco scope. Metscco scope is upto first 17-Dec-17 Noted Closed
sampling piping; The details in this regard will be provided later. flange only.

ELECTRICAL

No Comment Closed

INSTRUMENTATION

No Comment Closed

CIVIL

No Comment Closed

CMP

Vendor to revsie the coating selection according to the revised


tank data sheets. All surface preparation and coating application 13-Dec-2017 Noted Closed
shall follow the requirment of SAES-H-001&101V.

FIRE PROTECTION

noted,
The Foam Water piping system associated with external floating METSCCO scope interface ~1.5m The foam system along with piping is
Excluded from Metscco scope. Metscco scope is upto first
tanks X07-D-0329 & 0331 and the provisions required for 13-Dec-2017 17-Dec-17 above grade. Exact location/orientation 18-Dec-17 excluded from Metscco scope. Closed
flange only.
mounting them shall be considered by Vendor. details will be provided on the nozzle Metscco scope is upto first flange only.
projection drawings.

Page 2 of 3
PLANT LOCATION: NORTH JEDDAH BULK PLANT REV.: A

PROJECT TITLE: YANBU DISTRIBUTION HUB AND NORTH JIDDAH BULK PLANT EXPANSION VENDOR NAME: METSCCO

PACKAGE TITLE: FLOATING ROOF STORAGE TANKS VENDOR REFERENCE: 3919R3

MECHANICAL - JZ Clarification / Confirmation items Vendor's Response JZ Response Vendor's Response JZ Response Clarification Status
Sr.
Rev.
No.
Date Offer Reference Description Date Description Date Description Date Description Date Open/ Closed

noted, Metscco scope is upto first flange only.


The piping material selection shall be based on SAES-L-105 & Excluded from Metscco scope. Metscco scope is upto first
13-Dec-2017 17-Dec-17 however, piping scope of METSCCO 18-Dec-17 Pipings and its supports outside the Closed
SAES-L-132. flange only.
shall comply with SAES-L-105 / L-132. tank is SSEM scope.