Вы находитесь на странице: 1из 53

Transmission Lines

We have obtained the following solutions for the steady-state


voltage and current phasors in a transmission line:

Loss-less line Lossy line


+ − jβ z − jβ z + −γz − γz
V (z) = V e +V e V (z) = V e +V e

I (z) =
1
Z0
(
V + e − jβ z − V − e jβ z ) I (z) =
1
Z0
(
V + e− γ z − V −e γ z )
Since V (z) and I (z) are the solutions of second order differential
+ −
(wave) equations, we must determine two unknowns, V and V ,
which represent the amplitudes of steady-state voltage waves,
travelling in the positive and in the negative direction, respectively.

Therefore, we need two boundary conditions to determine these


unknowns, by considering the effect of the load and of the
generator connected to the transmission line.

© Amanogawa, 2006 – Digital Maestro Series 65


Transmission Lines

Before we consider the boundary conditions, it is very convenient


to shift the reference of the space coordinate so that the zero
reference is at the location of the load instead of the generator.
Since the analysis of the transmission line normally starts from the
load itself, this will simplify considerably the problem later.

New Space Coordinate


ZR

z
d
0

We will also change the positive direction of the space coordinate,


so that it increases when moving from load to generator along the
transmission line.

© Amanogawa, 2006 – Digital Maestro Series 66


Transmission Lines

We adopt a new coordinate d = − z, with zero reference at the load


location. The new equations for voltage and current along the lossy
transmission line are

Loss-less line Lossy line


+ jβd − − jβ d + γd − −γ d
V (d) = V e +V e V (d) = V e +V e

I (d) =
Z0
1
( + jβd
V e −V e
− − jβ d
) I (d) =
1
Z0
( + γd
V e −V e
− −γd
)
At the load (d = 0) we have, for both cases,

V (0) = V + + V −

I (0) =
1
Z0
(
V + −V − )
© Amanogawa, 2006 – Digital Maestro Series 67
Transmission Lines

For a given load impedance ZR , the load boundary condition is

V (0) = Z R I (0)

Therefore, we have

+
V +V =
ZR
Z0

V + −V − ( )
from which we obtain the voltage load reflection coefficient

V−
Z R − Z0
ΓR = + =
V Z R + Z0

© Amanogawa, 2006 – Digital Maestro Series 68


Transmission Lines

We can introduce this result into the transmission line equations as


Loss-less line Lossy line

V (d) = V e
+ jβ d
( 1+ ΓR e
−2 jβ d
) V (d) = V e
+ γd
( 1+ ΓR e
−2 γ d
)
+ jβ d + γd
I (d) =
V e
Z0
( 1 − Γ Re
−2 jβ d
) I (d) =
V e
Z0
(
1 − Γ Re
−2 γ d
)
At each line location we define a Generalized Reflection Coefficient

Γ (d) = Γ R e−2 jβ d Γ (d) = Γ R e−2 γ d


and the line equations become

V (d) = V + e jβ d (1 + Γ (d) ) V (d) = V + e γ d (1 + Γ (d) )


V + e jβ d V +e γd
I (d) = (1 − Γ (d) ) I (d) = (1 − Γ (d) )
Z0 Z0

© Amanogawa, 2006 – Digital Maestro Series 69


Transmission Lines

We define the line impedance as

V (d) 1 + Γ(d)
Z (d) = = Z0
I (d) 1 − Γ(d)

A simple circuit diagram can illustrate the significance of line


impedance and generalized reflection coefficient:

ΓReq = Γ(d)
Zeq=Z(d) ZR

d 0
© Amanogawa, 2006 – Digital Maestro Series 70
Transmission Lines

If you imagine to cut the line at location d, the input impedance of


the portion of line terminated by the load is the same as the line
impedance at that location “before the cut”. The behavior of the line
on the left of location d is the same if an equivalent impedance with
value Z(d) replaces the cut out portion. The reflection coefficient of
the new load is equal to Γ(d)
Z Req − Z 0
Γ Req = Γ(d ) =
Z Req + Z 0
If the total length of the line is L, the input impedance is obtained
from the formula for the line impedance as

Vin V (L) 1 + Γ(L)


Z in = = = Z0
I in I (L) 1 − Γ(L)
The input impedance is the equivalent impedance representing the
entire line terminated by the load.

© Amanogawa, 2006 – Digital Maestro Series 71


Transmission Lines

An important practical case is the low-loss transmission line, where


the reactive elements still dominate but R and G cannot be
neglected as in a loss-less line. We have the following conditions:

ω L >> R ω C >> G
so that
γ = ( jω L + R )( jω C + G )
 R  G 
= jω L jω C  1 +  1+ 
 j ω L  j ω C 
R G RG
≈ jω LC 1 + + −
jω L jω C ω2 LC

The last term under the square root can be neglected, because it is
the product of two very small quantities.

© Amanogawa, 2006 – Digital Maestro Series 72


Transmission Lines

What remains of the square root can be expanded into a truncated


Taylor series

 1 R G 
γ ≈ jω LC 1 +  + 
 2  j ω L j ω C 
1 C L
= R +G  + jω LC
2 L C

so that

1 C L
α = R +G  β = ω LC
2 L C

© Amanogawa, 2006 – Digital Maestro Series 73


Transmission Lines

The characteristic impedance of the low-loss line is a real quantity


for all practical purposes and it is approximately the same as in a
corresponding loss-less line

R + jω L L
Z0 = ≈
G + jωC C
and the phase velocity associated to the wave propagation is

ω 1
vp = ≈
β LC

BUT NOTE:

In the case of the low-loss line, the equations for voltage and
current retain the same form obtained for general lossy lines.

© Amanogawa, 2006 – Digital Maestro Series 74


Transmission Lines

Again, we obtain the loss-less transmission line if we assume

R=0 G=0
This is often acceptable in relatively short transmission lines, where
the overall attenuation is small.

As shown earlier, the characteristic impedance in a loss-less line is


exactly real

L
Z0 =
C
while the propagation constant has no attenuation term

γ = ( jω L)( jω C ) = jω LC = jβ

The loss-less line does not dissipate power, because α = 0.

© Amanogawa, 2006 – Digital Maestro Series 75


Transmission Lines

For all cases, the line impedance was defined as

V (d) 1 + Γ (d)
Z (d) = = Z0
I (d) 1 − Γ (d)
By including the appropriate generalized reflection coefficient, we
can derive alternative expressions of the line impedance:

A) Loss-less line
1 + Γ R e−2 jβd
Z R + jZ 0 tan(β d)
Z (d) = Z 0 −2 jβd
= Z0
1 − Γ Re jZ R tan(β d) + Z 0

B) Lossy line (including low-loss)


1 + Γ R e −2 γ d
Z R + Z 0 tanh( γ d)
Z (d) = Z 0 −2 γ d
= Z0
1 − Γ Re Z R tanh( γ d) + Z 0

© Amanogawa, 2006 – Digital Maestro Series 76


Transmission Lines

Let’s now consider power flow in a transmission line, limiting the


discussion to the time-average power, which accounts for the
active power dissipated by the resistive elements in the circuit.

The time-average power at any transmission line location is

1
{
〈 P(d , t ) 〉 = Re V (d) I * (d)
2
}
This quantity indicates the time-average power that flows through
the line cross-section at location d. In other words, this is the
power that, given a certain input, is able to reach location d and
then flows into the remaining portion of the line beyond this point.

It is a common mistake to think that the quantity above is the power


dissipated at location d !

© Amanogawa, 2006 – Digital Maestro Series 77


Transmission Lines

The generator, the input impedance, the input voltage and the input
current determine the power injected at the transmission line input.

Iin
ZG Zin
Vin = VG
ZG + Zin
Zin 1
VG Vin Iin = VG
ZG + Zin

Generator Line
1
{ *
〈 Pin 〉 = Re Vin Iin
2
}

© Amanogawa, 2006 – Digital Maestro Series 78


Transmission Lines

The time-average power reaching the load of the transmission line


is given by the general expression
1
{
〈 P(d=0 , t ) 〉 = Re V (0) I * (0)
2
}
 + *
1
2 
1
(
= Re V (1 + Γ R ) * V + (1 − Γ R )
Z0
) 

This represents the power dissipated by the load.


The time-average power absorbed by the line is simply the
difference between the input power and the power absorbed by the
load
〈 P line 〉 = 〈 P in 〉 − 〈 P (d = 0 , t ) 〉
In a loss-less transmission line no power is absorbed by the line, so
the input time-average power is the same as the time-average
power absorbed by the load. Remember that the internal impedance
of the generator dissipates part of the total power generated.

© Amanogawa, 2006 – Digital Maestro Series 79


Transmission Lines

It is instructive to develop further the general expression for the


time-average power at the load, using Z0=R0+jX0 for the
characteristic impedance, so that

1 R0 + jX 0 R0 + jX 0
Z0
*
= * = 2
= 2
Z0 Z0 Z0 Z0 R0 + X 02

Alternatively, one may simplify the analysis by introducing the line


characteristic admittance

1
Y0 = = G0 + jB0
Z0
It may be more convenient to deal with the complex admittance at
the numerator of the power expression, rather than the complex
characteristic impedance at the denominator.

© Amanogawa, 2006 – Digital Maestro Series 80


Transmission Lines

 * 
   
〈 P(d=0, t ) 〉 = 1 Re V + 1+Γ R  1 V + 1−Γ

 
R  

 =
2   Z  * 


0 


2
V+  
+ j Im Γ
      
 
= 2
Re R0 + jX
 
0
1+ Re Γ + j Im Γ






R


R  


1− Re Γ 



R


R   
        
2 Z0 

2  
V+ 
 



 
2
 
2
 
= Re R0
+ jX

0 
1−   Re Γ   +  Im Γ    +
    j 2Im Γ R  
2      R     R      
    
2 Z0 
     

2 
V+  2 
  
   
= 2
Re R0
+ jX

0  1− Γ
R
+ j 2Im
 Γ


R   
=
   
 
2 Z0 
   

2
V+ 

2


= 2
 R0 − R0 Γ R − 2 X 0 Im Γ 

R 
 
2 Z0  

© Amanogawa, 2006 – Digital Maestro Series 81


Transmission Lines

Equivalently, using the complex characteristic admittance:


 * 
   
〈 P(d=0, t ) 〉 = 1 Re V + 1+Γ R  Y V + 1−Γ


*
R  

 =
2    0
  
 
 
2
V+  
+ j Im Γ
      
 
= Re G0 − jB
 
0
1+ Re Γ + j Im Γ
 



R


R  
1− Re Γ 



R


R   
2  
   

   

2  
V+  
 
 
2

2
  
= Re G0 − jB0 


1−   Re Γ
 R   +  Im Γ R    +
     
j 2Im Γ R  

2   

 

     

  

     

2 
V+  2 
  
 
= Re G0 − jB0  1− Γ R + j 2Im Γ

  
R   
=
2   
  
   

2
V+ 

2


= G0 − G0 Γ R + 2B0 Im Γ 

R 
2 




© Amanogawa, 2006 – Digital Maestro Series 82


Transmission Lines

The time-average power, injected into the input of the transmission


line, is maximized when the input impedance of the transmission
line and the internal generator impedance are complex conjugate of
each other.

Zin
Generator Load
ZG

VG Transmission line ZR

ZG = Z*in for maximum power transfer

© Amanogawa, 2006 – Digital Maestro Series 83


Transmission Lines

The characteristic impedance of the loss-less line is real and we


can express the power flow, anywhere on the line, as
1
〈 P (d , t ) 〉 = Re{ V (d) I * (d) }
2
1  + jβ d
= Re V e
2 
(
1 + Γ R e− j 2β d )
( ) 
1 *
(V + )* e− jβ d 1 − Γ R e− j 2β d
Z0
1 +2 1 +2
= V − V ΓR 2
2Z0 2Z0



Incident wave Reflected wave

This result is valid for any location, including the input and the load,
since the transmission line does not absorb any power.

© Amanogawa, 2006 – Digital Maestro Series 84


Transmission Lines

In the case of low-loss lines, the characteristic impedance is again


real, but the time-average power flow is position dependent
because the line absorbs power.

1
〈 P (d , t ) 〉 = Re V (d) I * (d)
2
{ }
1
{ (
= Re V + eα d e jβ d 1 + Γ R e−2 γ d
2
)
( ) 
1 *
(V + )* eα d e− jβ d 1 − Γ R e−2 γ d
Z0
1 + 2 2α d 1 + 2 −2α d
= V e − V e ΓR 2
2Z0 2Z0



Incident wave Reflected wave

© Amanogawa, 2006 – Digital Maestro Series 85


Transmission Lines

Note that in a lossy line the reference for the amplitude of the
incident voltage wave is at the load and that the amplitude grows
exponentially moving towards the input. The amplitude of the
incident wave behaves in the following way

V + eα L ⇔ V + eα d ⇔ V+




input inside the line load

The reflected voltage wave has maximum amplitude at the load, and
it decays exponentially moving back towards the generator. The
amplitude of the reflected wave behaves in the following way

V + Γ R e−α L ⇔ V + Γ R e−α d ⇔ V +ΓR






input inside the line load

© Amanogawa, 2006 – Digital Maestro Series 86


Transmission Lines

For a general lossy line the power flow is again position dependent.
Since the characteristic impedance is complex, the result has an
additional term involving the imaginary part of the characteristic
admittance, B0, as

1
〈 P (d , t ) 〉 = Re V (d) I * (d)
2
{ }
1
{
= Re V + eα d e jβ d (1 + Γ (d) )
2
Y0* (V + )* eα d e− jβ d (1 − Γ (d) )*}
G0 + 2 2α d G0 + 2 −2α d
= V e − V e ΓR 2
2 2
+2
+ B0 V e2α d Im(Γ (d))

© Amanogawa, 2006 – Digital Maestro Series 87


Transmission Lines

For the general lossy line, keep in mind that

1 Z 0* R0 − jX 0 R0 − jX 0
Y0 = = *
= 2
= 2 2
= G0 + jB0
Z0 Z0 Z0 Z0 R0 + X 0
R0 −X0
G0 = 2 B 0 =
R0 + X 02 R02 + X 02

Recall that for a low-loss transmission line the characteristic


impedance is approximately real, so that

B0 ≈ 0 and Z 0 ≈ 1 G0 ≈ R0 .
The previous result for the low-loss line can be readily recovered
from the time-average power for the general lossy line.

© Amanogawa, 2006 – Digital Maestro Series 88


Transmission Lines

To completely specify the transmission line problem, we still have


to determine the value of V+ from the input boundary condition.

¾ The load boundary condition imposes the shape of the


interference pattern of voltage and current along the line.

¾ The input boundary condition, linked to the generator, imposes


the scaling for the interference patterns.

We have
Zin 1 + Γ (L)
Vin = V (L) = VG with Zin = Z 0
ZG + Zin 1 − Γ (L)

 Z R + jZ 0 tan(β L)
or
 Zin = Z 0 loss - less line
jZ R tan(β L) + Z 0

 Z R + Z 0 tanh( γ L)
Zin = Z 0 lossy line
 Z R tanh( γ L) + Z 0

© Amanogawa, 2006 – Digital Maestro Series 89


Transmission Lines

For a loss-less transmission line:

V (L) = V + e jβ L [1 + Γ (L) ] = V + e jβ L (1 + Γ R e− j 2β L )
+ Zin 1
⇒ V = VG
ZG + Zin e jβ L (1 + Γ R e− j 2β L )

For a lossy transmission line:

(
V (L) = V + e γ L [1 + Γ (L) ] = V + e γ L 1 + Γ R e−2 γ d )
+ Zin 1
⇒ V = VG
ZG + Zin e γ L (1 + Γ R e−2 γ L )

© Amanogawa, 2006 – Digital Maestro Series 90


Transmission Lines

In order to have good control on the behavior of a high frequency


circuit, it is very important to realize transmission lines as uniform
as possible along their length, so that the impedance behavior of
the line does not vary and can be easily characterized.

A change in transmission line properties, wanted or unwanted,


entails a change in the characteristic impedance, which causes a
reflection. Example:

Z01 Z02 ZR

Γ1
Zin − Z01
Z01 Zin Γ1 =
Zin + Z01

© Amanogawa, 2006 – Digital Maestro Series 91


Transmission Lines

Special Cases

ZR → 0 (SHORT CIRCUIT)

Z0 ZR = 0

The load boundary condition due to the short circuit is V (0) = 0

⇒ V (d = 0) = V + e jβ 0 (1 + Γ R e− j 2β 0 )
= V + (1 + Γ R ) = 0
⇒ Γ R = −1

© Amanogawa, 2006 – Digital Maestro Series 92


Transmission Lines

Since
V−
ΓR =
V+
⇒ V − = −V +

We can write the line voltage phasor as

V (d) = V + e jβ d + V − e− jβ d
= V + e jβ d − V + e− jβ d
= V + ( e jβ d − e− jβ d )
= 2 jV + sin(β d)

© Amanogawa, 2006 – Digital Maestro Series 93


Transmission Lines

For the line current phasor we have


1
I (d) = (V + e jβ d − V − e− jβ d )
Z0
1
= (V + e jβ d + V + e− jβ d )
Z0
V + jβ d
= (e + e− jβ d )
Z0
2V +
= cos(β d)
Z0
The line impedance is given by

V (d) 2 jV + sin(β d)
Z(d) = = = jZ0 tan(β d)
+
I (d) 2V cos(β d) / Z0

© Amanogawa, 2006 – Digital Maestro Series 94


Transmission Lines

The time-dependent values of voltage and current are obtained as

V (d, t ) = Re[V (d) e jω t ] = Re[2 j | V + | e jθ sin(β d) e jω t ]


= 2| V + |sin(β d) ⋅ Re[ j e j (ω t +θ) ]
= 2| V + |sin(β d) ⋅ Re[ j cos(ω t + θ) − sin(ω t + θ)]
= −2| V + |sin(β d) sin(ω t + θ)

I (d, t ) = Re[ I (d) e jω t ] = Re[2 | V + | e jθ cos(β d) e jω t ] / Z0


= 2| V + |cos(β d) ⋅ Re[ e j (ω t +θ) ] / Z0
= 2| V + |cos(β d) ⋅ Re[ (cos(ω t + θ) + j sin(ω t + θ)] / Z0
| V+ |
=2 cos(β d) cos(ω t + θ)
Z0
© Amanogawa, 2006 – Digital Maestro Series 95
Transmission Lines

The time-dependent power is given by

P(d, t ) = V (d, t ) ⋅ I (d, t )


| V + |2
=−4 sin(β d) cos(β d) sin(ω t + θ) cos(ω t + θ)
Z0
| V + |2
=− sin(2β d) sin (2ω t + 2θ)
Z0
and the corresponding time-average power is

1 T
< P(d, t ) > = ∫ P(d, t ) dt
T 0
| V + |2 1 T
=− sin(2β d) ∫ sin (2ω t + 2θ) = 0
Z0 T 0

© Amanogawa, 2006 – Digital Maestro Series 96


Transmission Lines

ZR → ∞ (OPEN CIRCUIT)

Z0 ZR → ∞

The load boundary condition due to the open circuit is I (0) = 0

V + jβ 0
⇒ I (d = 0) = e (1 − Γ R e− j 2β 0 )
Z0
V+
= (1 − Γ R ) = 0
Z0
⇒ ΓR = 1

© Amanogawa, 2006 – Digital Maestro Series 97


Transmission Lines

Since
V−
ΓR =
V+
⇒ V− = V+
We can write the line current phasor as

1
I (d) = (V + e jβ d − V − e− jβ d )
Z0
1
= (V + e jβ d − V + e− jβ d )
Z0
V + jβ d − jβ d 2 jV +
= (e −e )= sin(β d)
Z0 Z0

© Amanogawa, 2006 – Digital Maestro Series 98


Transmission Lines

For the line voltage phasor we have

V (d) = (V + e jβ d + V − e− jβ d )
= (V + e jβ d + V + e− jβ d )
= V + ( e jβ d + e− jβ d )
= 2V + cos(β d)

The line impedance is given by

V (d) 2V + cos(β d) Z0
Z(d) = = =−j
I (d) 2 jV + sin(β d) / Z0 tan(β d)

© Amanogawa, 2006 – Digital Maestro Series 99


Transmission Lines

The time-dependent values of voltage and current are obtained as


V (d, t ) = Re[V (d) e jω t ] = Re[2 | V + | e jθ cos(β d) e jω t ]
= 2| V + |cos(β d) ⋅ Re[ e j(ω t +θ) ]
= 2| V + |cos(β d) ⋅ Re[ (cos(ω t + θ) + j sin(ω t + θ)]
= 2| V + |cos(β d) cos(ω t + θ)

I (d, t ) = Re[ I (d) e jω t ] = Re[2 j | V + | e jθ sin(β d) e jω t ] / Z0


= 2| V + |sin(β d) ⋅ Re[ j e j(ω t +θ) ] / Z0
= 2| V + |sin(β d) ⋅ Re[ j cos(ω t + θ) − sin(ω t + θ)] / Z0
| V+ |
= −2 sin(β d) sin(ω t + θ)
Z0

© Amanogawa, 2006 – Digital Maestro Series 100


Transmission Lines

The time-dependent power is given by

P(d, t ) = V (d, t ) ⋅ I (d, t ) =


| V + |2
=−4 cos(β d) sin(β d) cos(ω t + θ) sin(ω t + θ)
Z0
| V + |2
=− sin(2β d) sin (2ω t + 2θ)
Z0
and the corresponding time-average power is

1 T
< P(d, t ) > = ∫ P(d, t ) dt
T 0
| V + |2 1 T
=− sin(2β d) ∫ sin (2ω t + 2θ) = 0
Z0 T 0

© Amanogawa, 2006 – Digital Maestro Series 101


Transmission Lines

ZR = Z0 (MATCHED LOAD)

Z0 ZR = Z0

The reflection coefficient for a matched load is


ZR − Z0 Z0 − Z0
ΓR = = =0 no reflection!
ZR + Z0 Z0 + Z0
The line voltage and line current phasors are

V (d) = V + e jβ d (1 + Γ R e−2 jβ d ) = V + e jβ d
V + jβ d V +
I( d ) = e (1 − Γ R e−2 jβ d ) = e jβ d
Z0 Z0
© Amanogawa, 2006 – Digital Maestro Series 102
Transmission Lines

The line impedance is independent of position and equal to the


characteristic impedance of the line

V (d) V + e jβ d
Z(d) = = = Z0
+
I (d) V jβ d
e
Z0
The time-dependent voltage and current are

V (d, t ) = Re[| V + | e jθ e jβ d e jω t ]
= | V + | ⋅ Re[e j(ω t +β d +θ) ] =| V + | cos(ω t + β d + θ)
I (d, t ) = Re[| V + | e jθ e jβ d e jω t ] / Z0
| V+ | j (ω t +β d +θ) | V +
|
= ⋅ Re[e ]= cos(ω t + β d + θ)
Z0 Z0

© Amanogawa, 2006 – Digital Maestro Series 103


Transmission Lines

The time-dependent power is


+
| V |
P(d, t ) = | V + | cos(ω t + β d + θ) cos(ω t + β d + θ)
Z0
| V + |2
= cos2 (ω t + β d + θ)
Z0

and the time average power absorbed by the load is

1 t | V + |2
< P(d) > = ∫ cos2 (ω t + β d + θ) dt
T 0 Z0
| V + |2
=
2 Z0

© Amanogawa, 2006 – Digital Maestro Series 104


Transmission Lines

ZR = jX (PURE REACTANCE)

Z0 ZR = j X

The reflection coefficient for a purely reactive load is

ZR − Z0 jX − Z0
ΓR = = =
ZR + Z0 jX + Z0
( jX − Z0 )( jX − Z0 ) X 2 − Z02 XZ0
= = +2j
( jX + Z0 )( jX − Z0 ) Z02 + X 2 Z02 + X 2

© Amanogawa, 2006 – Digital Maestro Series 105


Transmission Lines

In polar form
Γ R = Γ R exp( jθ)
where

ΓR =
( 2
X − Z0 2 2
+
)
4 X 2 Z02
=
( 2
Z0 + X )
2 2
=1
( ) ( ) ( )
2 2 2
Z02 + X 2 Z02 + X 2 Z02 + X 2

−1  2 XZ0 
θ = tan 
 X 2 − Z2 
 0
The reflection coefficient has unitary magnitude, as in the case of
short and open circuit load, with zero time average power absorbed
by the load. Both voltage and current are finite at the load, and the
time-dependent power oscillates between positive and negative
values. This means that the load periodically stores power and
then returns it to the line without dissipation.

© Amanogawa, 2006 – Digital Maestro Series 106


Transmission Lines

Reactive impedances can be realized with transmission lines


terminated by a short or by an open circuit. The input impedance of
a loss-less transmission line of length L terminated by a short
circuit is purely imaginary
 2π   2π f 
Zin = j Z0 tan ( β L ) = j Z0 tan  L  = j Z0 tan  L
 λ   v 
 p 
For a specified frequency f, any reactance value (positive or
negative!) can be obtained by changing the length of the line from 0
to λ/2. An inductance is realized for L < λ/4 (positive tangent)
while a capacitance is realized for λ/4 < L < λ/2 (negative tangent).

When L = 0 and L = λ/2 the tangent is zero, and the input


impedance corresponds to a short circuit. However, when L = λ/4
the tangent is infinite and the input impedance corresponds to an
open circuit.

© Amarcord, 2006 – Digital Maestro Series 107


Transmission Lines

Since the tangent function is periodic, the same impedance


behavior of the impedance will repeat identically for each additional
line increment of length λ/2. A similar periodic behavior is also
obtained when the length of the line is fixed and the frequency of
operation is changed.

At zero frequency (infinite wavelength), the short circuited line


behaves as a short circuit for any line length. When the frequency
is increased, the wavelength shortens and one obtains an
inductance for L < λ/4 and a capacitance for λ/4 < L < λ/2, with
an open circuit at L = λ/4 and a short circuit again at L = λ/2.

Note that the frequency behavior of lumped elements is very


different. Consider an ideal inductor with inductance L assumed to
be constant with frequency, for simplicity. At zero frequency the
inductor also behaves as a short circuit, but the reactance varies
monotonically and linearly with frequency as

X = ωL (always an inductance)
© Amarcord, 2006 – Digital Maestro Series 108
Transmission Lines

Short circuited transmission line – Fixed frequency


L L= 0 Z in = 0 s h o rt c irc u it
λ
0< L<
4
k p
Im Z in > 0 in d u c ta n c e

λ
L= Z in → ∞ o p e n c irc u it
4
λ λ
4
< L<
2
k p
Im Z in < 0 c a p a c ita n c e

λ
L= Z in = 0 s h o rt c irc u it
2
λ 3λ
2
< L<
4
k p
Im Z in > 0 in d u c ta n c e


L= Z in → ∞ o p e n c irc u it
4

4
< L< λ k p
Im Z in < 0 c a p a c ita n c e

© Amarcord, 2006 – Digital Maestro Series 109


Transmission Lines

Z(L)/Zo = j tan(β L) Impedance of a short circuited transmission line


(fixed frequency, variable length)
40

30

20

inductive inductive inductive


10
Normalized Input Impedance

-10
capacitive cap.

-20

-30

-40
0 100 200 300 400 500 θ [deg]
π/(2β)= λ/4 π/β =λ/2 3π/(2β)= 3λ/4 2π/β= λ 5π/(2β)= 5λ/4 L
Line Length L

© Amarcord, 2006 – Digital Maestro Series 110


Transmission Lines

Z(L)/Zo = j tan(β L) Impedance of a short circuited transmission line


(fixed length, variable frequency)
40

30

20

inductive inductive inductive


10
Normalized Input Impedance

-10
capacitive cap.

-20

-30

-40
0 100 200 300 400 500 θ [deg]
vp / (4L) vp / (2L) 3vp / (4L) vp / L 5vp / (4L)
f
Frequency of operation

© Amarcord, 2006 – Digital Maestro Series 111


Transmission Lines

For a transmission line of length L terminated by an open circuit,


the input impedance is again purely imaginary

Z0 Z0 Z0
Zin = − j =−j =−j
tan ( β L )  2π   2π f 
tan  L  tan  L
 λ   v 
 p 
We can also use the open circuited line to realize any reactance, but
starting from a capacitive value when the line length is very short.

Note once again that the frequency behavior of a corresponding


lumped element is different. Consider an ideal capacitor with
capacitance C assumed to be constant with frequency. At zero
frequency the capacitor behaves as an open circuit, but the
reactance varies monotonically and linearly with frequency as
1
X= (always a capacitance)
ωC
© Amarcord, 2006 – Digital Maestro Series 112
Transmission Lines

Open circuit transmission line – Fixed frequency


L L= 0 Z in → ∞ o p e n c irc u it
λ
0< L<
4
k p
Im Z in < 0 c a p a c ita n c e

λ
L= Z in = 0 s h o rt c irc u it
4
λ λ
4
< L<
2
k p
Im Z in > 0 in d u c ta n c e

λ
L= Z in → ∞ o p e n c irc u it
2
λ 3λ
2
< L<
4
k p
Im Z in < 0 c a p a c ita n c e


L= Z in = 0 s h o rt c irc u it
4

4
< L< λ k p
Im Z in > 0 in d u c ta n c e

© Amarcord, 2006 – Digital Maestro Series 113


Transmission Lines

Impedance of an open circuited transmission line


(fixed frequency, variable length)
Z(L)/ Zo = - j cotan(β L)

40

30

20
inductive inductive inductive
10

0
Normalized Input Impedance

-10 capacitive
capacitive capacitive

-20

-30

-40
0 100 200 300 400 500 θ [deg]
0 π/(2β) = λ/4 π/β = λ/2 3π/(2β) = 3λ/4 2π/β = 2λ 5π/(2β) = 5λ/4 L
Line Length L
© Amarcord, 2006 – Digital Maestro Series 114
Transmission Lines

Impedance of an open circuited transmission line


(fixed length, variable frequency)
Z(L)/ Zo = - j cotan(β L)

40

30

20
inductive inductive inductive
10

0
Normalized Input Impedance

-10 capacitive
capacitive capacitive

-20

-30

-40
0 100 200 300 400 500 θ [deg]
vp / (4L) vp / (2L) 3vp / (4L) vp / L 5vp / (4L)
0 f
Frequency of operation
© Amarcord, 2006 – Digital Maestro Series 115
Transmission Lines

It is possible to realize resonant circuits by using transmission


lines as reactive elements. For instance, consider the circuit below
realized with lines having the same characteristic impedance:

I
L1 L2

short Z0 Z0 short
circuit V circuit

Zin1 Zin2

Zin1 = j Z0 tan ( β L 1 ) Zin2 = j Z0 tan ( β L 2 )

© Amarcord, 2006 – Digital Maestro Series 116


Transmission Lines

The circuit is resonant if L1 and L2 are chosen such that an


inductance and a capacitance are realized.
A resonance condition is established when the total input
impedance of the parallel circuit is infinite or, equivalently, when
the input admittance of the parallel circuit is zero
1 1
+ =0
j Z0 tan ( β r L1 ) j Z0 tan ( β r L 2 )
or

 ωr   ωr  2π ωr
tan  L1  = − tan  L 2  with βr = =
 vp   vp  λ r vp
   
Since the tangent is a periodic function, there is a multiplicity of
possible resonant angular frequencies ωr that satisfy the condition
above. The values can be found by using a numerical procedure to
solve the trascendental equation above.
© Amarcord, 2006 – Digital Maestro Series 117

Вам также может понравиться