Академический Документы
Профессиональный Документы
Культура Документы
Vapour Absorption
Refrigeration Systems
1
8.1. Introduction
Vapour Absorption Refrigeration Systems (VARS) belong to the class of
vapour cycles similar to vapour compression refrigeration systems. However, unlike
vapour compression refrigeration systems, the required input to absorption systems is
in the form of heat. Hence these systems are also called as heat operated or thermal
energy driven systems. Since conventional absorption systems use liquids for
absorption of refrigerant, these are also sometimes called as wet absorption systems.
Similar to vapour compression refrigeration systems, vapour absorption refrigeration
systems have also been commercialized and are widely used in various refrigeration
and air conditioning applications. Since these systems run on low-grade thermal
energy, they are preferred when low-grade energy such as waste heat or solar energy
is available. Since conventional absorption systems use natural refrigerants such as
water or ammonia they are environment friendly.
In this chapter, the basic working principle of absorption systems, the maximum
COP of ideal absorption refrigeration systems, basics of properties of mixtures and
simple absorption refrigeration systems will be discussed.
3
a) Initial condition
U
Valve closed
b) Refrigeration A
Water vapour
30oC 30oC
Valve open
Qe A B Qc
Water vapour
c) Regeneration
Valve open
Qc Qg
30oC
Tg > To > Te
4
The temperature of water in vessel A will be the saturation temperature
corresponding to 1.22 kPa, which is equal to about 10oC, as shown in the
figure. Since the water temperature in A is lower than the surroundings, a
refrigeration effect (Qe) can produced by transferring heat from the surroundings to
water at 10oC. Due to this heat transfer, water vaporizes in A, flows to B and is
absorbed by the solution in B. The exothermic heat of absorption (Qa) is rejected to
the surroundings.
Now for the above process to continue, there should always be pure water in
vessel A, and vessel B must be maintained always at 50 percent concentration and
30oC. This is not possible in a closed system such as the one shown in Fig.(8.1). In
a closed system with finite sized reservoirs, gradually the amount of water in
A decreases and the solution in B becomes diluted with water. As a result, the
system pressure and temperature of water in A increase with time. Hence the
refrigeration effect at A reduces gradually due to the reduced temperature
difference between the surroundings and water. Thus refrigeration produced by
systems using only two vessels is intermittent in nature. In these systems, after
a period, the refrigeration process has to be stopped and both the vessels A and B
have to be brought back to their original condition. This requires removal of water
absorbed in B and adding it back to vessel A in liquid form, i.e., a process of
regeneration as shown in Fig.8.1(c).
Assume that before regeneration is carried out, the valve between A and B is
closed and both A and B are brought in thermal equilibrium with the surroundings
(30oC), then during the regeneration process, heat at high temperature Tg is supplied
to the dilute LiBr solution in B, as a result water vapour is generated in B. The vapour
generated in B is condensed into pure water in A by rejecting heat of condensation to
the surroundings. This process has to be continued till all the water absorbed during
the refrigeration process (8.1(b)) is transferred back to A. Then to bring the system
back to its original condition, the valve has to be closed and solution in vessel B has
to be cooled to 30oC. If we assume a steady-flow process of regeneration and neglect
temperature difference for heat transfer, then the temperature of water in A will be
30oC and pressure inside the system will be 4.24 kPa. Then the temperature in vessel
B, Tg depends on the concentration of solution in B. The amount of heat transferred
during refrigeration and regeneration depends on the properties of solution and the
operating conditions. It can be seen that the output from this system is the
refrigeration obtained Qe and the input is heat supplied to vessel B during vapour
regeneration process, Qg.
5
Qg at Tg
Qc at To Qc at To
Condenser Wc Condenser Generator
Pc
Pc Wp
Qe at Te Qe
Mechanical Thermal Qa at To
compression compression
a) VCRS b) VARS
It can be seen from Fig.(8.2), that as far as the condenser, expansion valve
and evaporators are concerned both compression and absorption systems are
identical. However, the difference lies in the way the refrigerant is compressed to
condenser pressure. In vapour compression refrigeration systems the vapour is
compressed mechanically using the compressor, where as in absorption system the
vapour is first
6
converted into a liquid and then the liquid is pumped to condenser pressure using the
solution pump. Since for the same pressure difference, work input required to pump a
liquid (solution) is much less than the work required for compressing a vapour due to
Pc
very small specific volume of liquid ( w = − ∫ v.dP ), the mechanical energy required to
Pe
operate vapour absorption refrigeration system is much less than that required to
operate a compression system. However, the absorption system requires a relatively
large amount of low-grade thermal energy at generator temperature to generate
refrigerant vapour from the solution in generator. Thus while the energy input is in the
form of mechanical energy in vapour compression refrigeration systems, it is mainly
in the form of thermal energy in case of absorption systems. The solution pump work
is often negligible compared to the generator heat input. Thus the COPs for
compression and absorption systems are given by:
Qe
COPVCRS = (8.1)
Wc
Qe Q
COPVARS = ≈ e (8.2)
Q g + Wp Q g
Te
COPCarnot = (8.3)
Tc − Te
If we assume that heat rejection at the absorber and condenser takes place at
same external heat sink temperature To, then a vapour absorption refrigeration system
operates between three temperature levels, Tg, To and Te. The maximum possible COP
of a refrigeration system operating between three temperature levels can be obtained
by applying first and second laws of thermodynamics to the system. Figure
(8.3) shows the various energy transfers and the corresponding temperatures
in an absorption refrigeration system.
7
Tg
Pump
Wp
Qg
Cycle
System
Qa + Qc
Qe
Te TT
o∞
Q e + Q g − Q c + a + Wp = 0 (8.4)
where Qe is the heat transferred to the absorption system at evaporator temperature Te,
Qg is the heat transferred to the generator of the absorption system at temperature Tg,
Qa+c is the heat transferred from the absorber and condenser of the absorption system
at temperature To and Wp is the work input to the solution pump.
where ΔStotal is the total entropy change which is equal to the sum of entropy change
of the system ΔSsys and entropy change of the surroundings ΔSsurr. Since the
refrigeration system operates in a closed cycle, the entropy change of the working
fluid of the system undergoing the cycle is zero, i.e., ΔS sys = 0 . The entropy change
of the surroundings is given by:
Q e Q g Q a +c
ΔS surr = − − + ≥0 (8.6)
Te Tg To
Substituting the expression for first law of thermodynamics in the above equation
⎛ Tg − To ⎞ ⎛ ⎞
Qg ⎜ ⎟ ≥ Q e ⎜ To − Te ⎟⎟ − Wp (8.7)
⎜ Tg ⎟ ⎜ T
⎝ ⎠ ⎝ e ⎠
Neglecting solution pump work, Wp; the COP of VARS is given by:
Qe ⎛ Te ⎞⎛ Tg − To ⎞
COPVARS = ≤ ⎜⎜ ⎟⎟⎜ ⎟
⎜ ⎟
Qg ⎝ To − Te ⎠⎝ Tg ⎠ (8.8)
8
An ideal vapour absorption refrigeration system is totally reversible (i.e., both
internally and externally reversible). For a completely reversible system the total
entropy change (system+surroundings) is zero according to second law, hence for an
ideal VARS ΔS total, rev = 0 ⇒ ΔS surr , rev = 0 . Hence:
Q e Q g Q a +c
ΔS surr , rev = − − + =0 (8.9)
Te Tg To
Hence combining first and second laws and neglecting pump work, the maximum
possible COP of an ideal VARS system is given by:
Q ⎛ Te ⎞⎛ Tg − To ⎞
COPideal VARS = e = ⎜⎜ ⎟⎟⎜ ⎟ (8.10)
⎜ ⎟
Qg ⎝ To − Te ⎠⎝ Tg ⎠
Thus the ideal COP is only a function of operating temperatures similar to Carnot
system. It can be seen from the above expression that the ideal COP of VARS system
is equal to the product of efficiency of a Carnot heat engine operating between Tg and
To and COP of a Carnot refrigeration system operating between To and Te, i.e.,
Qe ⎛ Te ⎞⎛ Tg − To ⎞
COPideal VARS = = ⎜⎜ ⎟⎟⎜ ⎟ = COPCarnot .η Carnot (8.11)
⎜ ⎟
Qg ⎝ To − Te ⎠⎝ Tg ⎠
Tg
Qg
E WE
Qa
TT∞o
Qc
WE R
Qe
Te
9
8.4. Properties of refrigerant-absorbent mixtures
The solution used in absorption refrigeration systems may be considered as a
homogeneous binary mixture of refrigerant and absorbent. Depending upon the
boiling point difference between refrigerant and absorbent and the operating
temperatures, one may encounter a pure refrigerant vapour or a mixture of refrigerant
and absorbent vapour in generator of the absorption system. Unlike pure substances,
the thermodynamic state of a binary mixture (in liquid or vapour phase) cannot be
fixed by pressure and temperature alone. According to Gibbs’ phase rule, one more
parameter in addition to temperature and pressure is required to completely fix the
thermodynamic state. Generally, the composition of the mixture is taken as the third
independent parameter. The composition of a mixture can be expressed either in mass
fraction or in mole fraction. The mass fraction of components 1 and 2 in a binary
mixture are given by:
m1 m2
ξ1 = ; ξ2 = (8.12)
m1 + m 2 m1 + m 2
The mole fraction of components 1 and 2 in a binary mixture are given by:
n1 n2
x1 = ; x2 = (8.13)
n1 + n 2 n1 + n 2
where n1 and n2 are the number of moles of components 1 and 2, respectively
Condition 1: The volume of the mixture is equal to the sum of the volumes of its
constituents, i.e., upon mixing there is neither contraction nor expansion. Thus the
specific volume of the mixture, v is given by:
v = ξ1 .v1 + ξ 2 .v 2 (8.14)
where ξ1 and ξ2 are the mass fractions of components 1 and 2. For a binary mixture,
ξ1 and ξ2 are related by:
ξ1 + ξ 2 = 1 ⇒ ξ 2 = 1 − ξ1 (8.15)
10
Condition 2: Neither heat is generated nor absorbed upon mixing, i.e., the heat of
solution is zero. Then the specific enthalpy of the mixture, h is given by:
h = ξ1 .h 1 + ξ 2 .h 2 = ξ1 .h 1 + (1 − ξ1 )h 2 (8.16)
Condition 3: The mixture obeys Raoult’s law in liquid phase, i.e., the vapour pressure
exerted by components 1 and 2 (Pv,1 and Pv,2) at a temperature T are given by:
where x1 and x2 are the mole fractions of components 1 and 2 in solution, and P1,sat
and P2, sat are the saturation pressures of pure components 1 and 2 at temperature T.
The mole fractions x1 and x2 are related by:
x 1 + x 2 =1⇒ x 2 =1 − x 1 (8.19)
Condition 4: The mixture obeys Dalton’s law in vapour phase; i.e., the vapour
pressure exerted by components 1 and 2 (Pv,1 and Pv,2) in vapour phase at a
temperature T are given by:
where y1 and y2 are the vapour phase mole fractions of components 1 and 2 and
Ptotal is the total pressure exerted at temperature T.
The vapour phase mole fractions y1 and y2 are related by:
y1 + y 2 = 1 ⇒ y 2 = 1 − y1 (8.22)
and the total pressure Ptotal is given by:
Ptotal = Pv ,1 + Pv , 2 (8.23)
If one of the components, say component 2 is non-volatile compared to component
1(e.g. component 1 is water and component 2 is lithium bromide salt), then y1 ≈ 1 and
y2 ≈ 0, Pv,2 ≈ 0, then from Raoult’s and to Dalton’s laws:
Ptotal ≈ Pv,1 = x1.P1,sat
(8.24)
11
2. Either heat is evolved (exothermic) or heat is absorbed upon mixing;
h = ξ1 .h 1 + (1 − ξ1 )h 2 + Δh mix (8.26)
where Δhmix is the heat of mixing, which is taken as negative when heat is evolved
and positive when heat is absorbed.
The above two differences between ideal and real mixtures can be attributed to
the deviation of real mixtures from Raoult’s law. Real mixtures approach ideal
mixtures as the mole fraction of the component contributing to vapour
pressure approaches unity, i.e., for very dilute solutions. Figure (8.5) shows the
equilibrium pressure variation with liquid phase mole fraction (x) of ideal and real
binary mixtures with positive (+ve) and negative deviations (-ve) from Raoult’s
law at a constant temperature. It can be seen that when the deviation from
Raoult’s law is positive (+ve), the equilibrium vapour pressure will be higher than
that predicted by Raoult’s law, consequently at a given pressure and composition, the
equilibrium temperature of solution will be lower than that predicted by Raoult’s
law. The converse is true for solutions with –ve deviation from Raoult’s law, i.e.,
the equilibrium temperature at a given pressure and composition will be higher than
that predicted by Raoult’s law for solution with negative deviation. This
behaviour can also be shown on specific enthalpy-composition diagram as
shown in Fig. (8.6) for a solution with negative deviation from Raoult’s law.
Refrigerant-absorbent mixtures used in vapour absorption refrigeration systems
exhibit a negative deviation from Raoult’s law, i.e., the process of absorption is
exothermic with a negative heat of mixing.
T = Constant
P1,sat
+ve
P Ideal
-ve P2,sat
0 1
x2
12
T = Constant
h1
Ideal solution
h
Δhmix
h2
Real solution
0 ξ2 1
13
P
Pg 5
Condenser Generator
Qg
6
Qc
9 4
Heat exchanger
7
10 3
8
Pe Evaporator Absorber
1
Qe 2
Qa Solution pump
Te T∞ Tg T
Fig.8.7 Basic vapour absorption refrigeration sy: Basic vapour absorption refrigeration syststem with
solution heat exchanger on a pressure vs temperature diagram
i. The refrigerant should exhibit high solubility with solution in the absorber.
This is to say that it should exhibit negative deviation from Raoult’s law at
absorber.
ii. There should be large difference in the boiling points of refrigerant and
absorbent (greater than 200oC), so that only refrigerant is boiled-off in the
generator. This ensures that only pure refrigerant circulates through
refrigerant circuit (condenser-expansion valve-evaporator) leading to
isothermal heat transfer in evaporator and condenser.
14
iii. It should exhibit small heat of mixing so that a high COP can be achieved.
However, this requirement contradicts the first requirement. Hence, in
practice a trade-off is required between solubility and heat of mixing.
iv. The refrigerant-absorbent mixture should have high thermal conductivity
and low viscosity for high performance.
v. It should not undergo crystallization or solidification inside the system.
vi. The mixture should be safe, chemically stable, non-corrosive, inexpensive
and should be available easily.
15
Chapter 9
1
9.1. Introduction
Vapour absorption refrigeration systems using water-lithium bromide pair are
extensively used in large capacity air conditioning systems. In these systems water is
used as refrigerant and a solution of lithium bromide in water is used as absorbent.
Since water is used as refrigerant, using these systems it is not possible to provide
refrigeration at sub-zero temperatures. Hence it is used only in applications requiring
refrigeration at temperatures above 0oC. Hence these systems are used for air
conditioning applications. The analysis of this system is relatively easy as the vapour
generated in the generator is almost pure refrigerant (water), unlike ammonia-water
systems where both ammonia and water vapour are generated in the generator.
mL
ξ= (9.1)
mL + mW
where mL and mW are the mass of anhydrous lithium bromide and water in solution,
respectively.
nL
x= (9.2)
nL + nW
where nL and nW are the number of moles of anhydrous lithium bromide and water in
solution, respectively. The number moles of lithium bromide and water can easily be
obtained from their respective masses in solution and molecular weights, thus;
mL m
nL = ; and n W = W (9.3)
ML MW
where ML (= 86.8 kg/kmol) and MW (= 18.0 kg/kmol) are the molecular weights of
anhydrous lithium bromide and water respectively.
9.2.2. Vapour pressure of water-lithium bromide solutions
Applying Raoult’s law, the vapour pressure of water-lithium bromide solution
with the vapour pressure exerted by lithium bromide being negligibly small is given
by:
P = (1− x)PW (9 .4)
2
where PW is the saturation pressure of pure water at the same temperature as
that of the solution and x is the mole fraction of lithium bromide in solution. It is
observed that Raoult’s law is only approximately correct for very dilute solutions of
water lithium bromide (i.e., as x → 0). Strong aqueous solutions of water-lithium
bromide are found to deviate strongly from Raoult’s law in a negative manner.
For example, at 50 percent mass fraction of lithium bromide and 25oC, Raoult’s law
predicts a vapour pressure of 26.2 mbar, whereas actual measurements show that it is
only 8.5 mbar.
The ratio of actual vapour pressure to that predicted by Raoult’s law is known as
activity coefficient. For the above example, the activity coefficient is 0.324.
Solution Temperature, oC
3
P
Pg 5
Condenser Generator
Qg
6
Qc
9 4
Heat exchanger
7
10 3
8
Pe Evaporator Absorber
1
Qe 2
Qa Solution pump
Te T∞ Tg T
Fig.9.2: Basic vapor absorption refrigeration H2O-LiBr system with solution heat exchanger heat
exchanger on Dühring plot
4
where hL and hW are the specific enthalpies of pure lithium bromide and
water, respectively at the same temperature. Figure (9.4) shows a chart giving the
specific enthalpy-temperature-mass fraction data for water-lithium bromide
solutions. The chart is drawn by taking reference enthalpy of 0 kJ/kg for liquid
water at 0oC and solid anhydrous lithium bromide salt at 25oC.
The enthalpy of pure water vapour and liquid at different temperatures and
pressures can be obtained from pure water property data. For all practical purposes,
liquid water enthalpy, hW,liquid at any temperature T can be obtained from the equation:
5
The water vapour generated in the generator of water-lithium bromide system
is in super heated condition as the generator temperature is much higher than the
saturation water temperature at that pressure. The enthalpy of superheated water
vapour, hW,sup at low pressures and temperature T can be obtained approximately by
the equation:
9.2.5. Crystallization
6
1
C G
Qc Qg
8
2
SHX
7
ER
9
3 ES
10
4
Qe A 6
E Qa
P
Fig.9.5: Schematic of a H2O-LiBr system
A: Absorber; C: Condenser; E: Evaporator; G: Generator; P: Solution Pump
SHX: Solution HX; ER: Refrigerant Expansion valve; ES: Solution Expansion valve
The circulation ratio (λ) is defined as the ratio of strong solution flow rate to
refrigerant flow rate. It is given by:
.
m ss
λ= .
(9.7)
m
this implies that the strong solution flow rate is given by:
. .
m ss = λ m (9.8)
The analysis is carried out by applying mass and energy balance across each
component.
Condenser:
. . .
m1 = m 2 = m (9.9)
.
Q c = m( h 1 − h 2 ) (9.10)
Pc = Psat (Tc ) (9.11)
7
Expansion valve (refrigerant):
. . .
m2 = m3 = m (9.12)
h 2 = h3 (9.13)
Evaporator:
. . .
m3 = m 4 = m (9.14)
.
Q e = m( h 4 − h 3 ) (9.15)
Pe = Psat (Te ) (9.16)
Absorber:
. . .
m + (1− ξ )mss = (1− ξ )m ws
ss ws
(9.18)
ξ
⇒ λ= ws
ξss − ξ
ws
. . .
Q a = m h 4 + λ m h 10 − (1 + λ) m h 5 (9.19)
.
or, Q a = m[(h 4 − h 5 ) + λ(h 10 − h 5 )] (9.20)
.
The first term in the above equation m(h 4 − h 5 ) represents the enthalpy change of
water as changes its state from vapour at state 4 to liquid at state 5. The second term
.
m λ(h 10 − h 5 ) represents the sensible heat transferred as solution at state 10 is cooled
to solution at state 5.
Solution pump:
. . .
m 5 = m 6 = m ws (9.21)
. .
WP = m ws (h 6 − h 5 ) = (1 + λ) m(h 6 − h 5 ) (9.22)
8
. .
WP = (1+ λ) m vsol (P6 − P 5) = (1+ λ) m vsol (Pc − Pe ) (9.23)
where vsol is the specific volume of the solution which can be taken to be
approximately equal to 0.00055 m3/kg. Even though the solution pump work is small
it is still required in the selection of suitable pump.
. . .
m 6 = m 7 = m ws
. . .
(9.24)
m 8 = m 9 = m ss
heat transfer rate in the solution heat exchanger, QHX is given by:
. .
Q HX = (1 + λ) m(h 7 − h 6 ) = λ m(h 8 − h 9 ) (9.25)
Generator:
. . .
m 7 = m 8 + m1 (9.26)
. . .
Q g = m h 1 + λ m h 8 − (1 + λ ) m h 7 (9.27)
.
or, Q g = m[(h 1 − h 7 ) + λ(h 8 − h 7 )] (9.28)
.
in the above equation the 1st term on the RHS m(h 1 − h 7 ) represents energy required
to generate water vapour at state 1 from solution at state 7 and the 2nd term
.
m λ(h 8 − h 7 ) represents the sensible heat required to heat the solution from state 7 to
state 8.
. . .
m 9 = m 10 = m ws (9.29)
h 9 = h 10 (9.30)
Qe Q
COP = ≈ e (9.31)
Q g + WP Q g
9
The second law (exergetic) efficiency of the system ηII is given by:
COP ⎛ Q ⎞⎛ Tg ⎞⎛ Tc − Te ⎞
η II = = ⎜ e ⎟⎜ ⎟⎜ ⎟⎟ (9.32)
COPmax ⎜⎝ Q g ⎟⎠⎜⎝ Tg − Tc ⎟⎜ Te
⎠⎝ ⎠
In order to find the steady-state performance of the system from the above set
of equations, one needs to know the operating temperatures, weak and strong solution
concentrations, effectiveness of solution heat exchanger and the refrigeration
capacity. It is generally assumed that the solution at the exit of absorber and generator
is at equilibrium so that the equilibrium P-T-ξ and h-T-ξ charts can be used for
evaluating solution property data. The effectiveness of solution heat exchanger, εHX is
given by:
(T7 − T6 )
ε HX = (9.33)
(T8 − T6 )
From the above equation the temperature of the weak solution entering the
generator (T7) can be obtained since T6 is almost equal to T5 and T8 is equal to the
generator temperature Tg. The temperature of superheated water vapour at state 1 may
be assumed to be equal to the strong solution temperature T8.
1. Crystallization
2. Air leakage, and
3. Pressure drops
10
9.5.1. Single Stage/ Effect system
Single stage systems operate under two pressures – one corresponding to the
condenser-generator (high pressure side) and the other corresponding to evaporator-
absorber. Single stage systems can be either:
Since evaporator and absorber operate at the same pressure they can be housed in
a single vessel, similarly generator and condenser can be placed in another vessel as
these two components operate under a single pressure. Thus a twin drum
system consists of two vessels operating at high and low pressures. Figure (9.6)
shows a commercial, single stage, twin drum system.
11
As shown in the figure, the cooling water (which acts as heat sink) flows first to
absorber, extracts heat from absorber and then flows to the condenser for condenser
heat extraction. This is known as series arrangement. This arrangement is
advantageous as the required cooling water flow rate will be small and also by
sending the cooling water first to the absorber, the condenser can be operated at a
higher pressure to prevent crystallization. It is also possible to have cooling water
flowing parallelly to condenser and absorber, however, the cooling water requirement
in this case will be high. A refrigerant pump circulates liquid water in evaporator and
the water is sprayed onto evaporator tubes for good heat and mass transfer. Heater
tubes (steam or hot water or hot oil) are immersed in the strong solution pool of
generator for vapour generation. Pressure drops between evaporator and absorber and
between generator and condenser are minimized, large sized vapour lines are
eliminated and air leakages can also be reduced due to less number of joints.
Figure (9.7) shows a single stage system of single drum type in which all the
four components are housed in the same vessel. The vessel is divided into high
and low pressure sides by using a diaphragm.
12
9.5.2. Multi Stage/ Effect System
In multi-effect systems a series of generators operating at progressively reducing
pressures are used. Heat is supplied to the highest stage generator operating at the highest
pressure. The enthalpy of the steam generated from this generator is used to generate
some more refrigerant vapour in the lower stage generator and so on. In this manner the
heat input to the system is used efficiently by generating more refrigerant vapour
leading to higher COPs. However, these systems are more complex in construction and
require a much higher heat source temperatures in the highest stage generator. Figures
(9.8) and (9.9) show commercial double-effect systems. Figure (9.10) shows the
double effect cycle on Dühring plot.
Qg,in
Ph,g
Qc,out
Pc=Pl,g
Pe=Pa
Qe,in Qa,out
Te Tc = Ta Tl,g h,gT
14
9.6. Heat sources for water-lithium bromide systems
Water-lithium bromide systems can be driven using a wide variety of heat
sources. Large capacity systems are usually driven by steam or hot water. Small
capacity systems are usually driven directly by oil or gas. A typical single effect
system requires a heat source at a temperature of about 120oC to produce chilled
water at 7oC when the condenser operates at about 46oC and the absorber operates
at about 40oC. The COPs obtained are in the range of 0.6 to 0.8 for single effect
systems while it can be as high as 1.2 to 1.4 for multi-effect systems.
The above values are simulated values, which were validated on actual
commercial systems with very efficient heat and mass transfer design. If the heat and
mass transfer is not very efficient, then the actual required heat source temperatures
will be higher than the reported values. For a given cooling water temperature, if the
heat source temperature drops below the minimum temperature given above, then the
COP drops significantly. For a given cooling water temperature, if the heat source
temperature drops below a certain temperature (minimum generation temperature),
then the system will not function. Minimum generation temperature is typically 10 to
15oC lower than the minimum heat source temperature. If air cooled condensers and
absorbers are used, then the required minimum heat source temperatures will be much
higher (≈ 150oC). The COP of the system can be increased significantly by multi-
effect (or mult-stage) systems. However, addition of each stage increases the required
heat source temperature by approximately 50oC.
15
1. Regulating the flow rate of weak solution pumped to the generator through the
solution pump
2. Reducing the generator temperature by throttling the supply steam, or by
reducing the flow rate of hot water
3. Increasing the condenser temperature by bypassing some of the cooling water
supplied to the condenser
Method 1 does not affect the COP significantly as the required heat input reduces
with reduction in weak solution flow rate, however, since this may lead to the
problem of crystallization, many a time a combination of the above three methods are
used in commercial systems to control the capacity.
16