27
59
81
87G
32
40
Cos Φ 80 DEG CT
Sec Current
657.02461 A 87T
InrushCurrent 6 x In 87TN
InrushCurrent 6 x In 87T
87TN
50/51
50N/51N
87T
87TN
InrushCurrent 6 x In 87T
87TN
50/51
50N/51N
87T
87TN
Setting Value Remark
Normal Inverse
Current
1200 Setting curent = DEG full load rating
Setting (A)
Time Dial 0.402
Setting instantaneous is based on Transformer
Definite Time (A) 11375 inrush current = 6 x In for min 6 cycle or (1/50 x 6 =
120 ms)
Definite Time (A) 100 A
Setting based on max current flow to NGR
Delay (S) 0.3 S
Value 10%
Delay (S) Based on Max allowable voltage variation
1
Value 10%
Delay (S) Based on Max allowable voltage variation
1
Under Freq Value 5%
Delay (S) 1
Over Freq Value Based on Max Freq Variation
5%
Delay (S) 1
Setting Diff (%) 20% CT accuracy = 5%, Measurement Error = 10%
Delay (S) 0.3 Protection Value = 10%, Total Setting = 20%
Directional Power
(Power Reverse) 2%
Delay Time (S) 0.3 S
Delay (S) 0.01
Normal Inverse
Current
656 Setting curent = DEG full load rating
Setting (A)
Time Dial 0.14
Setting instantaneous is based on Transformer
Definite Time (A) 5296 inrush current = 6 x In for min 6 cycle or (1/50 x 6 =
120 ms)
Delay (S) 0.25
Definite Time (A) 288 A Setting based on max current flow to NGR (40
Delay (S) 0.3 S Ohm, calculated by ETAP)
CT accuracy = 5%, Tap Deviation = 15%,
Ids 35% Measurement Error = 22.4%, Relay Error = 2%,
Protection Value = 10%, Ids = 35%
Idt/lt 28% CT accuracy = 5%, Tap Deviation = 15%,
Measurement Error = 21.3%, Relay error = 2%,
Protection Value = 5%, Ids = 28%
Primer Side
Extremely Inverse
Current
29
Setting (A)
Time Dial 0.28
Definite Time (A) 287
Delay (S) 0.2
Secondary Side
Normal Inverse
Current
1440 Setting curent = Transformer full load rating
Setting (A)
Time Dial 0.05
Setting instantaneous is based on Transformer
Definite Time (A) 10064 inrush current = 6 x In for min 6 cycle or (1/50 x 6 =
120 ms)
Delay (S) 0.15
Definite Time (A) 130 A
Delay (S) 0.3 S 20% from In
Primer Side
Extremely Inverse
Current
270 Setting curent = Transformer full load rating
Setting (A)
Time Dial 0.3
Definite Time (A) 1890 Coordination with secondary side of transformer
Delay (S) 0.1
Secondary Side
Normal Inverse
Current
2025 Setting curent = Transformer full load rating
Setting (A)
Time Dial 0.61
Setting instantaneous is based on Transformer
Definite Time (A) 17250 inrush current = 6 x In for min 6 cycle or (1/50 x 6 =
120 ms)
Delay (S) 0.13
Definite Time (A) 540 A
20% from In
Delay (S) 0.3 S
CT accuracy = 5%, Tap Deviation = 15%,
Ids 35% Measurement Error = 22.4%, Relay Error = 2%,
Protection Value = 10%, Ids = 35%
Idt/lt 28% CT accuracy = 5%, Tap Deviation = 15%,
Measurement Error = 21.3%, Relay error = 2%,
Protection Value = 5%, Ids = 28%