Вы находитесь на странице: 1из 34

PROYECTO DE LINEAS

DE TRANSMISIÓN
ANCASH - HUAYAN

Ingeniería Eléctrica.
Ingeniería Eléctrica. 2

UNIVERSIDAD NACIONAL DE SAN


AGUSTÍN DE AREQUIPA
FACULTAD DE INGENIERÍA DE
PRODUCCIÓN Y SERVICIOS
ESCUELA PROFESIONAL DE INGENIERÍA
ELÉCTRICA

CURSO:
LÍNEAS DE TRANSMISIÓN

TEMA:
“PROYECTO DE LINEAS DE TRANSMISIÓN ANCASH -
HUAYAN”

DOCENTE:
Ing. Harry Carrasco.

PRESENTADO POR:
Ayque Cabana Franklin Samuel
Ccama Llallacachi Américo Emerson
Ccama Llallacachi Marco Antonio
Huancahuire Sequeiros Olmer
Roque Gutierrez Brayan

AREQUIPA- PERÚ
2018

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 3

PROYECTO DE LINEAS DE TRANSMISIOÓ N ANCASH - HUAYAN

Contenido
ANTECEDENTES..........................................................................................................5

CARACTERISTICAS GENERALES DEL ÁREA DE INFLUENCIA DEL PROYECTO....6

RESUMEN..................................................................................................................... 7

INTRODUCCIÓN........................................................................................................... 8

OBJETIVOS DEL PROYECTO......................................................................................8

CAPITULO I...................................................................................................................9

PARAMETROS AMBIENTALES DE LA ZONA...............................................................9

1.1 Temperatura....................................................................................................9

1.2 Lluvia............................................................................................................. 13

1.3 Viento............................................................................................................ 13

1.4 Humedad relativa...........................................................................................14

CAPITULO II................................................................................................................ 15

TRAZO DE LA RUTA...................................................................................................15

CAPITULO III............................................................................................................... 19

NIVEL DE TENSIÓN DE LA LINEA..............................................................................19

MATERIAL DEL CONDUCTOR................................................................................20

CALCULOS DEL DISEÑO PARA EL CALIBRE DEL CONDUCTOR............................20

2.1 Capacidad De Corriente..................................................................................20

2.2 Gradiente Crítico................................................................................................21

SELECCIONAMOS EL TIPO DE AISLADOR...........................................................22

CALCULO DEL NUMERO DE AISLADORES..........................................................22

Cálculo de la geometría de la Estructura..................................................................24

CÁLCULO MECANICO DE LOS CONDUCOTRES DE LA LINEA DE TRANSMISION


HUAYAN 220KV........................................................................................................... 26

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 4

Sección del conductor:.............................................................................................26

Módulo de elasticidad del conductor.........................................................................26

Coeficiente de dilatación del conductor....................................................................26

A CONTINUACIÓN, SE MUESTRA EL CÁLCULO DE LAS HIPÓTESIS PARA UN


VANO PROMEDIO DE 300m DE LA LINEA DE TRANSMISIÓN HUAYAN 220KV.. 27

HIPOTESIS II........................................................................................................... 27

A. CALCULO DEL ESFUERZO MAXIMO.................................................................27

B. CALCULO DEL PESO DEL CONDUCTOR............................................................27

C. CALCULO DE LA FLECHA..................................................................................28

HIPOTESIS I............................................................................................................ 28

A. CALCULO DEL ESFUERZO EN ELCONDUCTOR..................................................28

B. CALCULO DEL PESO DEL CONDUCTOR............................................................29

C. CALCULO DE LA FLECHA..................................................................................29

HIPOTESIS III.......................................................................................................... 29

A. CALCULO DEL ESFUERZO EN ELCONDUCTOR..................................................29

B. CALCULO DEL PESO DEL CONDUCTOR............................................................30

C. CÁLCULO DE LA FLECHA..................................................................................30

TABLA DE REGULACIÓN........................................................................................31

CALCULO DE LOS PARAMETROS AYB........................................................................31

ARMAMOS LA TABLA DE REGULACIÓN PARA TEMPERATURAS DE 15 °C A


50°C, CON INTERVALOS DE 10 °C........................................................................32

ARMAMOS LA TABLA DE FLECHAS USANDO LOS VANOS DADOS


ANTERIORMENTE PARA TEMPERATURAS VARIABLES, USANDO LA SIGUIENTE
FORMULA:............................................................................................................... 33

ESFUERZOS PARA DIFERENTES TIPOS DE VANO.............................................33

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 5

ANTECEDENTES

En la elaboración del presente proyecto “HUAYAN” se debe considerar una revisión


previa de las normas que se deben tener en cuenta, así como también la influencia del
clima (precipitaciones, velocidad del viento, temperatura máxima y mínima etc.) en el
proyecto. Consideramos que enfocarnos en estos puntos era fundamental para iniciar
nuestro proyecto. A continuación se mostrara las normas que consideramos en nuestro
proyecto sobre todo al momento de plantear la ruta.
Normas de Referencia.
Para la elaboración del proyecto se ha tomado como referencia las siguientes normas:
 Código Nacional de Electricidad – Suministro 2011.
 Ley de Concesiones eléctricas DL N° 25844.
 Reglamento de la ley de Concesiones Eléctricas, DS N° 009-93-EM.
 Norma RD 018-2003 EM/DGE
 RD N° 031-2003-EM-DGE, Bases para el diseño de líneas y redes secundarias
con conductores autoportantes para electrificación rural.
 RD N° 028-2003-EM/DGE, Especificaciones técnicas para el suministro de
materiales y equipos de líneas de transmisión para electrificación rural.
 RD N° 501- 2003-EM/DGE, bases para el diseño de líneas y redes primarias.

Uno de nuestros enfoques como se mencionó al inicio era poder contar con toda la
información climatológica esta fue obtenida atreves del “servicio nacional de
meteorología e hidrología del Perú” SENAMHI.
Para poder obtener los datos de la velocidad del viento buscamos la información que
brinda la NASA para lo cual utilizamos las coordenadas de nuestro proyecto.

CARACTERISTICAS GENERALES DEL ÁREA DE


INFLUENCIA DEL PROYECTO

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 6

Figura 1: Terreno donde se ubicará la línea de transmisión 220 kv en Google earth.

El área de trabajo del proyecto es “HUAYAN” la cual está ubicada en el departamento


de Ancash que se encuentra a 2706 msnm como se puede observar el terreno es
, lo cual deberán ser consideradas para el diseño.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 7

RESUMEN

En el siguiente informe se describe minuciosamente el procedimiento que se llevara a


cabo en el diseño de una línea de transmisión 220 KV “HUAYAN” la cual está ubicada
en el departamento de Ancash, con una longitud: -77.20125 y latitud: -9.95182, el
largo de la línea de transmisión es de: Km, en el diseño y elaboración de este
proyecto se basó en las normas ya mencionadas.
Este informe presenta los siguientes pasos: nivel de tensión, ruta del proyecto, cálculo
del conductor, cálculo del soporte, en el estudio de la ruta se empleó el programa
Google Earth, la cual se debe tener en cuenta aspectos económicos, aspectos de
ingeniería, accesibilidad a la zona del proyecto, y aspectos ambientales. Una vez
finalizada esta etapa se elaboraron los planos. Seguido a esto se realizó un cálculo de
los conductores tanto el material como el calibre y finalmente la elección de los
soportes.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 8

INTRODUCCIÓN

Este proyecto “HUAYAN” presenta el diseño de una nueva línea de transmisión a


220KV de una longitud aproximada de Km que enlaza las coordenadas descritas en
los planos correspondientes.
El terreno donde se sitúa el proyecto es una zona agreste, accidentada.
La elección del conductor se basa es cálculos de la gradiente superficial en un
conductor simple (efecto corona), caídas de tensión no mayores al 5%, capacitancia
del conductor, los factores ambientales como el viento la humedad que se deben
considerar para la elaboración del proyecto.
El material del conductor utilizado es ACSR por su resistencia a esfuerzos mecánicos
como el peso del cable fuerzas externas como vientos.

OBJETIVOS DEL PROYECTO

Objetivo General
Diseño y elaboración en detalle de una línea de transmisión de 220KV, usando para
ello los cálculos expuestos en el curso de Líneas de Transmisión
Objetivos específicos
 Parámetros ambientales de la zona
Consideraciones sobre parámetros ambientales que pueden afectar en el
diseño de la línea de transmisión en la zona correspondiente.
 Trazo de la ruta
Definir la ruta optima que satisfaga aspectos económicos, aspectos de
ingeniería, y de accesibilidad a la zona
 Calculo del nivel de tensión
Se va a seguir el criterio empírico que define los niveles de tensión en líneas de
transmisión
 Calculo del conductor
Establecer los materiales a ser usados en el diseño y que cumplan con los
requerimientos térmicos, de topología y capacidad de corriente.
 Estructuras de soporte
Seguir criterios y condiciones para determinar el tipo y material de las
estructuras a emplear

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 9

CAPITULO I

PARAMETROS AMBIENTALES DE LA ZONA

1.1 Temperatura
Los valores de temperatura fueron registrados siguiendo los datos suministrados por
SENAMHI según estos datos los valores los valores más altos y más bajos que se
alcanzaron en dicha zona fueron:

Figura 2: Territorio donde se obtuvo los datos climatológicos

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 10

DEPARTAMENTO: ANCASH PROVINCIA: HUARMEY DISTRITO: MALVAS


Temperatura Temperatura Temperatura Bulbo Temperatura Bulbo Precipitacion
(mm)
Max (°c) Min (°c) Seco (°c) Humedo (°c)
Día/mes/año

7 13 19 7 13 19 7 19

1-Abr-18 11.8 6.4 9.6 10.8 11.2 8.4 10.2 10.8 1.4 5.8

2-Abr-18 11 6.6 10 10.8 10.6 8 10 10.2 0 4.2

3-Abr-18 14 4.5 7.2 13 11 5 11 9 0 0.5

4-Abr-18 15 4 9.2 11.4 11 8 10.2 9.2 0 3

5-Abr-18 11 5.5 9 9.2 9 8.2 8 8 1 7.5

6-Abr-18 14.8 5 8.4 11 10.8 7.2 9.8 10 1.4 0

7-Abr-18 14 5.4 8.6 11.6 9.8 6.2 10.8 9.4 0 0.6

8-Abr-18 14.8 6.5 9.2 10.8 9.6 8 10.4 9.2 0 6.8

9-Abr-18 12.5 5.4 9.8 11.2 9.2 9.4 10 8.4 1 1.2

10-Abr-18 15 4.4 9 14 12.2 7.4 10.4 11 1 0

11-Abr-18 14 5.5 8.4 12.8 12 6.2 11.2 11.4 0 0.8

12-Abr-18 11.2 6.4 9.4 10.8 10.2 8 9.4 9.6 0 0.6

13-Abr-18 12.6 5.6 10 11.4 10.4 8 10.6 10 2.6 1.6

14-Abr-18 14.8 5.8 11.4 12.4 11.2 9 11.2 10.4 0 0

15-Abr-18 16.8 5 8.4 15.6 12 6.4 11.8 10.2 0 0

16-Abr-18 17.4 6 9.2 16.8 11.2 4.4 13.4 10.4 0 0

17-Abr-18 15.2 5 9.2 14.2 12 8.4 11.2 11 0 0

18-Abr-18 17.5 6 9.4 17 13.2 7.2 13.2 11.4 0 0

19-Abr-18 17.5 5 9 14.8 12.6 7.2 11.8 11 0 0

20-Abr-18 16.4 6.5 10 15.4 11.6 8 12.6 10.4 0 0

21-Abr-18 16.4 7.4 11.8 15 12.6 8.4 13.6 10 0 0

22-Abr-18 17 6 10.2 15.4 11.4 7.6 11 9.4 0 0

23-Abr-18 16.2 5 8.6 15.4 11.4 5.8 11.4 10.2 0 0.2

24-Abr-18 16 6.5 11.2 14.4 12.6 9 12 11.2 0.9 0

25-Abr-18 16.6 6.6 11.2 14.2 13 10 12.6 9 3.5 0.5

26-Abr-18 16.6 8.2 11.8 12.8 13 8 12.2 11 1.7 1

27-Abr-18 16.6 6.4 10 14.6 11.8 8 13 11 0 0.4

28-Abr-18 14.6 5.6 10 14.4 12.4 8.6 13 11 0 1.3

29-Abr-18 15.6 6.4 9.6 13 11.2 7.2 12.2 10.6 0 0.4

30-Abr-18 18 6.4 12 16.4 12.4 9.2 14 12 1.2 0

Tabla 1: Datos climatológicos del SENAMHI mes de ABRIL 2018 ESTACION MALVAS

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 11

PROVINCIA:
DEPARTAMENTO: ANCASH AIJA DISTRITO: AIJA
Direccio
Temperatura Temperatura Temperatura Bulbo Temperatura Bulbo Precipitacio Velocidad
n
n (mm)
Día/mes/año Max (°c) Min (°c) Seco (°c) Humedo (°c) del del
Viento Viento
7 13 19 7 13 19 7 19
13h 13h (m/s)
7. 6.
1-Abr-18 15.1 3.9 6.4 14.8 5.6 13.9 0 0.3 NW 4
2 4
6. 6.
2-Abr-18 14.5 4 7.3 14.2 5.6 13.4 0 2.7 NW 2
8 6
7. 6.
3-Abr-18 14.6 1.4 7.5 14.2 3.9 12.8 0 3.4 NW 2
2 8
6. 6.
4-Abr-18 14.3 3.9 6.6 13.8 5.7 13.4 5 4.2 C
8 5
6. 5.
5-Abr-18 13.2 3 5.4 12.9 5.2 12.6 0 7.9 C
1 6
6.
6-Abr-18 15.1 3.4 7 14.5 5.9 13 6 2.8 0 NW 2
8
6. 6.
7-Abr-18 16.2 3.7 7.5 15.8 6.9 13.6 0 4.1 NW 6
8 5
6. 5.
8-Abr-18 14.7 2.1 7 14.3 4.6 13.7 0 2.6 NW 2
4 9
6. 5.
9-Abr-18 14.1 2.9 6.7 13.8 4.6 13.1 0 5.3 C
1 9
6. 5.
10-Abr-18 14.2 1.8 5.9 13.9 3.6 13.2 0 0 C
4 8
6. 6.
11-Abr-18 16 2.6 5.8 15.7 4.4 13.9 0 2.9 NW 2
8 4
6. 5.
12-Abr-18 14.5 2 5.5 14.2 3.1 13.5 0 4.8 NW 2
3 9
6. 5.
13-Abr-18 14 3.6 6.1 13.7 4.9 13.3 5.2 0 NW 2
4 8
6. 4.
14-Abr-18 14.3 2.6 5.8 13.9 5.1 13.4 0 0 NW 4
1 5
6. 4.
15-Abr-18 15.7 1.3 5 15.3 3.4 13.6 0 0 NW 8
8 5
6. 4.
16-Abr-18 16.1 1.3 5.2 15.6 2.8 13.5 0 0 NW 4
2 7
5. 4.
17-Abr-18 16.4 0.8 4.7 15.9 2.3 13.8 0 0 NW 2
8 3
5. 4.
18-Abr-18 16.7 0.3 4.5 16.4 2 13.9 0 0 NW 6
8 6
7. 5.
19-Abr-18 17 0.9 6.1 16.5 2.5 13.7 0 0 NW 4
2 8
6.
20-Abr-18 16.5 0.5 5.3 16.1 2.9 13.4 5 0 0 NW 2
4
6. 5.
21-Abr-18 16.8 2 6.1 16.4 4.9 13.7 0 0 NW 4
7 5
6.
22-Abr-18 15.3 3.7 6.9 15.1 7 5.6 13.5 4.1 2.3 NW 2
2
6. 5.
23-Abr-18 15.4 1.3 6 14.8 3.9 13.6 0 0 NW 6
3 1
6. 5.
24-Abr-18 14.3 1.7 6.5 14.1 4.2 13.6 0 4.9 NW 2
1 8
5. 5.
25-Abr-18 14 2.8 5.2 13.8 4.7 13.4 6.1 2.7 C
6 2
6. 4.
26-Abr-18 15.4 3.1 6.3 14.9 5.7 13 4.3 0 NW 4
8 6
6. 5.
27-Abr-18 15.6 1.8 5.7 15.3 3.4 12.9 0 1.7 NW 4
5 8
7. 6.
28-Abr-18 14.5 2.4 6 13.8 5.3 13.5 0 1.8 C
1 3
6. 6.
29-Abr-18 15.8 3.1 6.7 15.4 4.5 13.7 0 1.2 NW 6
5 2
5. 5.
30-Abr-18 15.3 2.3 6.1 15.1 3.8 13.9 0 2.5 NW 4
8 4

Tabla 2: Datos climatológicos del SENAMHI mes de ABRIL 2018 ESTACION AIJA

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 12

DEPARTAMENTO: ANCASH PROVINCIA: HUARAZ DISTRITO: LA LIBERTAD


Temperatura Temperatura Temperatura Bulbo Temperatura Bulbo
Precipitacion
(mm)
Max (°c) Min (°c) Seco (°c) Humedo (°c)
Día/mes/año

7 13 19 7 13 19 7 19

1-Abr-18 22.4 6.6 12.2 19.4 12.8 10.8 17.6 11.2 0 0

2-Abr-18 20.6 6.2 11.4 18.6 12.6 10.4 17.2 11.4 0 0

3-Abr-18 21.4 6.6 10.8 19.4 11.8 10.2 17.2 10.8 0 0

4-Abr-18 20.4 6.2 10.6 18.2 11.2 9.8 16.6 10.6 0 0

5-Abr-18 18.4 5.4 10.2 17.2 10.6 9.4 15.6 9.8 0 7.2

6-Abr-18 18.2 5.2 9.8 16.4 10 9.2 14.2 9.6 0 9.4

7-Abr-18 17.2 4.6 9.4 14.2 9.8 7.6 13.6 8.6 7.6 10.2

8-Abr-18 18.6 5.2 9.8 16.2 10.2 8.6 14.4 9.6 0 12.4

9-Abr-18 17.6 5.6 9.6 17.4 9.8 9.2 14.6 9.4 0 10.6

10-Abr-18 18.4 5.8 9.8 16.6 10.2 8.2 14.2 9.6 0 7.6

11-Abr-18 20.2 6.2 10.4 17.2 10.8 9.6 15.4 10 0 0

12-Abr-18 19.4 5.6 9.4 17.4 10 8.6 15.6 9.4 0 0

13-Abr-18 18.6 5.2 9.8 16.2 10.2 9.2 14.4 9.8 0 0

14-Abr-18 19.4 5.6 10.2 17.4 10.6 8.6 15.6 9.6 0 0

15-Abr-18 20.4 6.2 10.6 18.4 11.4 9.8 15.6 10.2 0 0

16-Abr-18 21.4 6.6 11.6 19.6 11.8 10.4 18.2 10.6 0 0

17-Abr-18 19.4 5.4 10.8 18.2 11.4 9.6 17.4 11.4 0 0

18-Abr-18 21.8 6.2 11.4 19.2 11.8 10.2 17.6 10.6 0 0

19-Abr-18 20.4 5.8 10.8 18.2 11 9.6 16.4 10.2 0 0

20-Abr-18 22.6 6.2 11.2 19.2 11.6 10.2 17.4 10.6 0 0

21-Abr-18 21.4 5.8 10.6 18.2 10.8 9.8 16.6 10.2 0 0

22-Abr-18 17.2 5.6 10 16.8 10.6 8.6 14.6 9.4 0 0

23-Abr-18 19.6 5.8 10.6 17.4 10.8 9.2 15.6 9.6 0 0

24-Abr-18 18.2 4.4 9.6 16.4 9.8 9.2 14.8 9.6 0 0

25-Abr-18 20.2 5.4 10.2 17.2 10.6 9.4 15.4 9.8 0 0

26-Abr-18 19.2 5 9.8 16.2 10 8.8 14.2 9.4 0 8.6

27-Abr-18 18.2 5.2 9.6 15.6 10.2 9.2 14.4 9.6 0 10.6

28-Abr-18 19.6 4.2 9.8 16.4 10.2 9.2 14.2 9.6 9.6 0

29-Abr-18 17.4 4.4 9.6 15.4 9.8 8.2 14.4 9.6 9.8 10.4

30-Abr-18 18.6 4.6 9.8 16.4 10.2 9.2 15.6 9.6 0 12.6

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 13

Tabla 3: Datos climatológicos del SENAMHI mes de ABRIL 2018 ESTACION CAJAMARQUILLA

Así mismo presentamos a continuación:

- La temperatura media mínima: 6 °C


- La temperatura media: 19 °C
- La temperatura media máxima: 22 °C

Podemos observar:
Que las temperaturas promedio no afectan los parámetros de las líneas de transmisión
por lo tanto es un factor que no se tendrá en cuenta

1.2 Lluvia
Según los valores de precipitación obtenidos del: SENAMHI se tiene una tasa anual
de 64 mm al año, los meses de mayor precipitación son enero y
diciembre y el resto del año no llueve, en conclusión este factor es despreciable.

1.3 Viento
Según los valores obtenidos usando: datos de la NASA y las coordenadas del
proyecto:
- velocidad del viento promedio anual es: 9.1 Km/h
- un mínimo de : 8.0 Km/h
- un máximo de : 10.2 Km/h

Tabla 4: Velocidad del viento_NASA

1.4 Humedad relativa

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 14

Tabla 5: GRAFICO DE HUMEDAD RELATIVA

- La humedad relativa media mínima: 0%

- La humedad relativa media: 0%


- La humedad relativa máxima: 0%

La humedad relativa es un factor importante a tomar en cuenta, ya que esta afecta la


línea de transmisión:

- Oxidación
- Corrosión
- Aumento del efecto corona
- Disminución del aislamiento(rigidez dieléctrica del aire)

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 15

CAPITULO II

TRAZO DE LA RUTA

Esta es la etapa más importante del proyecto. Y por ello se tomó dos opciones de ruta,
y se debió aplicar un análisis para determinar cuál era la mejor opción
En esta etapa se siguieron las siguientes fases:
- Elección del software a emplear (Google Earth)
- Trazado de ruta
- Análisis de la ruta
- Selección de la ruta

Figura 2: Trazo de referencia en línea recta de los puntos Po, Pm y Pf

Elección del software a emplear


Google Earth, programa informático que muestra un globo virtual que permite
visualizar múltiple cartografía, con base en la fotografía satelital.
Por motivos de accesibilidad se empleó el Programa Google Earth, de donde se pudo
obtener la información necesaria del lugar exacto del proyecto “HUAYAN”, así como
también la longitud de la línea de transmisión, y la situación del terreno.
Los datos obtenidos, así como el trazado se presentan en el anexo A

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 16

Trazado de rutas alternativas


Al estar la ruta de la línea sujeta a puntos fijos por los cuales debe seguir, se procedió
a realizar el trazado manejando dos opciones, dichas alternativas se diferenciaban en
la longitud de la línea.
El área del proyecto se muestra en la siguiente figura
Distancia en línea recta entre punto inicial y final (km)
Po – Pm 13.70
Pm – Pf 11.70
Total (Po – Pf) 25.4

Distancia de la ruta entre punto inicial y final (km)


Opción A
Po – Pm 14.00
Pm – Pf 11.60
Total (Po – Pf) 25.60
Opción B
Po – Pm 13.80
Pm – Pf 11.70
Total (Po - Pf) 25.50

Opción A

Figura 4: Trazo de ruta opción A


Opción B

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 17

Figura 5: Trazo de ruta opción B

Se puede apreciar que la zona en general tienes muchas quebradas y empinadas


montañas, para la Opcion A del punto Po al Pob la zona tiene muchas quebradas, la
primera opción fue la de rodear estas montañas evitar lo picos, e ir por la zona baja,
nos permitía tener un perfil de bajas altitudes y evitar futuras fallas por descargas
atmosféricas, o esfuerzos por vientos y bajas temperaturas pero también aumentan el
número de vértices y la longitud es más larga. En la segunda opción es la de atravesar
las zonas montañosas, asi tomar un camino recto, esta nos permitirá reducir costos,
reducir vértices por lo tanto evitar ángulos.

Análisis de las alternativas


Para dicho análisis consideramos los siguientes factores:
- Se trató en lo posible hacer que la línea sea recta.
- Se evitó pasar por terrenos agrícolas, como casas.
- Se evitó en lo posible ángulos mayores al permitido
- Se trató de minimizar en lo posible la longitud de la línea de transmisión
- Ubicamos los puntos de vértice en las partes altas de los cerros y montañas
- Procuramos ubicar la línea de transmisión cerca de carreteras y/o accesos
- Los ríos, lagos deben ser lo más paralelos posibles a la línea de transmisión
- Tratar de compensar los vanos con la altura de los soportes en subida a los
cerros y montañas

De este análisis finalmente nos inclinamos por la Opción B no solo por la menor
longitud que esta ofrecía sino también por el acceso a esta zona, y la simplicidad.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 18

CAPITULO III

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 19

NIVEL DE TENSIÓN DE LA LINEA

a) Criterio inicial – perfil del proyecto

V =0.1∗√ P∗L(kV )

V =0.1∗√ 250000∗26.00 (kV )

V =254.95(kV )

b) Formula de Still

V =5.5∗(√ 1.609
L
)+( 100P )(kV )
√ 1.609 100 )(kV )
V =5.5∗ (
26.00
) +(
250000

V =275.89(kV )

c) Producto KW – Km
250000∗26.00=6500000
kV KW∗Km
2.3 400-4000
10 1000-30000
30 10000-300000
60 100000-2,000000
138 1,000000-5,500000
220 5,500000-20,000000

De acuerdo a tablas la tensión elegida es: 220 KV


Como resultado del análisis de los valores obtenidos se hará el proyecto para un nivel
de tensión de:

V ≈220 (kV )

MATERIAL DEL CONDUCTOR

Se eligira el conductor de tipo “ASCR” debido a que en la topografía del terreno


existen:
- Quebradas

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 20

- Cerros, montañas
- Pendientes pronunciadas

CALCULOS DEL DISEÑO PARA EL CALIBRE DEL


CONDUCTOR

2.1 Capacidad De Corriente

I =P/ √3 x V x cos( phi )( A )

250000
I= (A)
√ 3 220∗0.90
I =728.98
¿=1.25 x 728.98
¿=911.22( A)
Como resultado realizando la intercepción de las curvas del fabricante obtenemos un
diámetro del conductor tipo ACSR:
D=25.15 mm
Datos del conductor:
Descripción: ACSR
Diámetro del conductor: 25.15mm

2.2 Gradiente Crítico

Para realizar este cálculo tenemos que cumplir la condición de la gradiente


dada que es:
g=15 Kv / cm .

V
g=
√3
D
r × ln
r
Caso 1:

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 21

220
g=
√3 =15.87 kv /cm
730
1.2575 ×ln
1.2575

En este caso podemos se observa que 15.87 kv/cm > 15kv/cm por lo cual
tenemos que seleccionar otro diámetro del conductor para que cumpla con la
condición del gradiente de tensión:

Para un D=28.14 mm
Caso 2:
220
g=
√3 =14.44 kv /cm
730
1.407 × ln
1.407
En este caso se observa que 14.44 kv/cm < 15kv/cm por lo cual emplearemos
este diámetro del conductor para que cumpla con la condición del gradiente de
tensión.

DATOS DEL CONDUCTOR:

Descripción: ASCR
Diámetro del conductor: 28.14mm
Resistencia AC del conductor a 25°C: 0.0728 (Ohms/Km)
Resistencia AC del conductor a 75°C: 0.0869 (Ohms/Km)
Emisividad del conductor: 0.5
Peso total: 1.528(Kg/Km)
Carga de rotura: 14.359(Kg)

SELECCIONAMOS EL TIPO DE AISLADOR

Caracteristicas

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 22

-Distancia de fuga: 11.5’’


-Carga electromecánica: 15000lb
-Resistencia mecánica al impacto: 55 pulg-lib
-Tensión de flameo a baja frecuencia en seco: 80kV
-Altura del aislador: 5.75’’

CALCULO DEL NUMERO DE AISLADORES

a) Longitud de fuga de un aislador

Lf aislador =11.5∗2.54=29.21 cm=292.1mm

b) Longitud de fuga total


Vmax . K
Lf =
δ

K: Nivel de contaminación
Nivel de contaminacion mm/Kv
Limpia 16
Poco sucia(Media) 20
Sucia 25
Contaminada 31

δ : Densidad relativa del aire


Altura(m) δ
1000 0.9
1600 0.83
2300 0.77
3000 0.72
3300 0.69
3600 0.66
4000 0.64
4150 0.60
5000 0.56

Para altura (m) : 4200


1
δ= h
e 8150

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 23

1
δ= 4200
8150
e

δ=0.597

220∗1.1∗16
Lf =
0.597

Lf =6485.76 mm

c) Numero de aisladores

Lf 6485.76
N aisladores= = =22.2 ≅ 23 aisladores
Lf aislador 292.1

Cálculo de la geometría de la Estructura

d1: distancia de conductor a tierra


Con h=4200msnm
1
δ= h
e 8150
1
δ= 4200
8150
e

δ=0 . 597

Vmax
d 1=5.3+
150 δ
242
d 1=5.3+
150 δ

d 1=8 . 002 m

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 24

d2: flecha máxima


Para un vano = 300m
8
a2
f= ¿
¿
¿=0.13∗Tiro de rotura
¿=1.867 Kg
f =9 . 21m

d3: longitud de la cadena


d3=d5

Lc=Naisladores∗Haislador

Lc=23∗(5.75∗2.54)

Lc=3 .36 m

d4: distancia conductor a estructura


d4=d7

Vmax
d 4=0.1+
150 δ

d 4=2 . 80 m

d6: ubicación del cable de guarda

dH=d 7+ d 5∗senα

dH =5. 71 m

dH + x /2
d 6= −d 5
tanθ

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 25

x=[ 1−1.5 ]

d 6=7 . 40 m

d8: separación horizontal a medio vano

d 8=2∗dH + x

d 8=12 . 42 m

CÁLCULO MECANICO DE LOS CONDUCOTRES


DE LA LINEA DE TRANSMISION HUAYAN 220KV.

Sección del conductor:


A=468 mm2

Módulo de elasticidad del conductor.


E=6000 kg/mm

Coeficiente de dilatación del conductor.


∝=0.0000231/℃
Peso del conductor.
w=1.628 kg /m

Diámetro del conductor.


D=28.14 mm

Vano medio.
a=300 m

Tiro de ruptura.
Tr=14359 kg

Factor de seguridad.
fs=3

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 26

constante para el tipo de conductor cilíndrico.


k =0.0042

Espesor del hielo en el conductor.


e=0 mm
velocidad del viento.
v =75 km/h

Temperatura mínima
Tmin=13.2 ℃
Temperatura ambiente
Tmed=19.68 ℃
Temperatura máxima
Tmax=31.6 ℃

A CONTINUACIÓN, SE MUESTRA EL CÁLCULO DE LAS HIPÓTESIS PARA


UN VANO PROMEDIO DE 300m DE LA LINEA DE TRANSMISIÓN HUAYAN
220KV.

HIPOTESIS II.
Empezamos con la hipótesis 2 debido a que se cuenta son el dato de factor de
seguridad de
fs=3

A. CALCULO DEL ESFUERZO MAXIMO.


Tr
σ max =
fsxA

Donde:
2
A=468 mm
fs=3
Tr=14359 kg

14359 kg
σ max =
3 x 468 mm 2
2
σ max 2=10.2272 kg/mm

B. CALCULO DEL PESO DEL CONDUCTOR.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 27

√ 2
W r = ( W c +Wh ) +W v
2

Donde:
W h : Peso del hielo
W h=0 kg/m

W v : Peso del viento


0.00481 × v 2 ×(∅ c +2× e)
Wv=
1000

2
0.00481 ×75 × ( 28.14+ 2× 0 )
Wv= =0.7614 kg/ m
1000
W c : Peso delconductor ( Dato de catalogo )
W c =1.628 kg /m
W r : Peso resultante

W r =√ ( 1.628+ 0 ) +0.76142
2

W r 2 =1.7972kg /m

C. CALCULO DE LA FLECHA.
wr 2 x a 2
flecha=
8 x σ max xA

1.7972 x 300 2
flecha=
8 x 10.2272 x 468

flecha 2=4.2243 m

HIPOTESIS I.

Condiciones de templado condiciones normales de operación.

A. CALCULO DEL ESFUERZO EN ELCONDUCTOR.


a2 W r 2 E
A 1=αE ( Tmed−Tmin ) + −σ 2
24 A σ 22

DONDE:

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 28

∝=0.0000231/℃
E=6000 kg/mm
Tmed=19.68 ℃
Tmin=13.2 ℃
W r 2 =1.7972kg /m
σ 2 =10.2272kg /mm2
a=300 m
2 2
300 (1.7972 )(6000)
A 1=0.0000231 X 6000 (19.68−13.2 ) + −10.2272
24(4682)10.22722

A 1=−6.1606

2 2
aW E
B 1= 2
24 A
1.628
648
24 (¿¿ 2)
( ¿¿ 2)( 6000)
3002 ¿
B 1=¿
B 1=272.2699
DE LA SIGUIENTE ECUACION.
σ 2 ( σ + A 1 )=B 1
2
σ 1=9.3051 Kg/mm

B. CALCULO DEL PESO DEL CONDUCTOR.


W r 1=W

W r 1=1.628 kg/m

C. CALCULO DE LA FLECHA.
2
wr 1 x a
flecha=
8 x σ 1 xA

flecha 1=4.2057 m

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 29

HIPOTESIS III.

A. CALCULO DEL ESFUERZO EN ELCONDUCTOR.


a2W r 2 E
A 3=αE ( Tmax−Tmin )+ −σ 2
24 A σ 22

DONDE:
∝=0.0000231/℃
E=6000 kg/mm
Tmax=31.6 ℃
Tmin=13.2 ℃
W r 2 =1.7972kg /m
σ 2 =10.2272kg /mm2
a=300 m
300 2( 1.79722 )(6000)
A 3=0.0000231( 6000) ( 31 .6−13.2 ) + −10.2272
24( 4682)10.22722

A 3=−4.5156
a2 W 2 E
B 3=
24 A2
1.628
648
24 (¿¿ 2)
2 ( ¿¿ 2)( 6000)
300 ¿
B 3=¿
B 3=272.2699
DE LA SIGUIENTE ECUACION.
σ 2 ( σ + A 3 )=B 3
σ 3=8.3866 Kg/mm2

B. CALCULO DEL PESO DEL CONDUCTOR.


W r 1=W

W r 3 =1.628 kg/m

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 30

C. CÁLCULO DE LA FLECHA.
wr 1 x a2
flecha=
8 x σ 1 xA

flecha 3=5.1514 m

TABLA DE REGULACIÓN.
DATOS:
DATOS

Ar: Vano de regulaci’0n 300.0000 m


Modulo de Elasticidad 6000.0000 kg/mm2
Coef de expansion termica: 0.0000230 1/°C
Temperatura promedio: 20 °C
S: Seccion Real 468 mm2
Wr: De hipotesis 1 1.6280 kg/m
Wr: De hipotesis 3 1.6280 kg/m
σ2 10.22720798 kg/m2

CALCULO DE LOS PARAMETROS AYB.


DONDE:
a2r W r 21 E
A=[αE ( θ 2−θ1 ) + −σ EDS ]
24 S2 σ 2EDS
a2 W r 23 E
B=
24 S2

σ2^3+A*σ2^2-B A B
-32.6792214 -8.26998043 167.241946
-20.9801566 -7.57998043 167.241946
-10.3658227 -6.88998043 167.241946
-0.7758909 -6.19998043 167.241946
7.8631078 -5.50998043 167.241946
15.6441887 -4.81998043 167.241946

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 31

22.6422209 -4.12998043 167.241946


28.9093312 -3.43998043 167.241946
34.5432169 -2.74998043 167.241946
39.5957654 -2.05998043 167.241946
44.1317101 -1.36998043 167.241946

ARMAMOS LA TABLA DE REGULACIÓN PARA TEMPERATURAS DE 15 °C


A 50°C, CON INTERVALOS DE 10 °C.

T o=σ variable × S
T o :Tiro
σ variale : Esfuerzo hallado en el paso anterior
S : Secci ó n del Conductor ( Dato de catalogo )

To
C=
W r3
W r 3 : Peso resultante de la hipotesis3
T o :Tiro
C : ParametroC

a2r
f r=
8C
f r : flecha de regulaci ó n
ar :Vano de regulació n
C : ParametroC

σ2
TEMPERATURA TIRO To PARAMETR FLECHA
(T) (Kg) O C (m) (m)
kg/mm2
4539.6468
15 9.7001 0 2788.48084 4.03445
4342.4784
20 9.2788 0 2667.37002 4.21764
4155.6528
25 8.8796 0 2552.61229 4.40725
3979.2168
30 8.5026 0 2444.23636 4.60266

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 32

3813.1236
35 8.1477 0 2342.21351 4.80315
3657.2796
40 7.8147 0 2246.48624 5.00782
3511.4040
45 7.503 0 2156.88206 5.21586
3375.0288
50 7.2116 0 2073.11351 5.42662
3247.8264
55 6.9398 0 1994.97936 5.63916
3129.2352
60 6.6864 0 1922.13464 5.85287
3018.7404
65 6.4503 0 1854.26314 6.06710

ARMAMOS LA TABLA DE FLECHAS USANDO LOS VANOS DADOS


ANTERIORMENTE PARA TEMPERATURAS VARIABLES, USANDO LA
SIGUIENTE FORMULA:
2
a
f =f r ( )
ar

Donde:
f r : flecha de regulación
a :Vanos variables
ar :Vano de regulación

Ilustración 3: Anexamos el Excel al final del proyecto.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 33

ESFUERZOS PARA DIFERENTES TIPOS DE VANO


Datos:
DATOS DEL CONDUCTOR
Sección Real: 468 mm2
Módulo de elasticidad: 6000 kg/mm2
Tiro de Rotura: 14359.00 kg
Diametro Exterior: 28.14 mm
Coef. De expansion Termica: 0.000023 1/°C
Factor de Seguridad: 3
Masa Total: 1.628 kg/m

Ilustración 4: Anexamos el documento excel al final del proyecto.

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN
Ingeniería Eléctrica. 34

PROYECTO DE LINEAS DE
TRANSMISIÓN ANCASH - HUAYAN