PRICE INDUSTRIES

SINGLE DUCT TERMINAL UNITS

Manufactured in Kuwait by
Air Movement Products Division
Bader Al Mulla & Bros. Co. W.L.L.
Under license from E.H. Price Limited, Canada
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Product Information

General Information
Model SDV
Price has, as a primary component of its
terminal unit line, the SPV (pneumatic
controls), SDV (digital controls) single duct
VAV assemblies. These units are designed
to control the air flow rate of conditioned
air into an occupied space in response to
a control signal, usually a thermostat. The
clean and efficient design of these single
duct terminal units result in a system
component which has minimal pressure
drop reducing fan horsepower require-
ments, and low noise generation for quiet
operation. A compact configuration makes
this unit easier to use in today‘s crowded
mechanical spaces or in retrofitting existing
systems.
Control options for this product line are
wide and varied with pneumatic, analog
electronic and state of the art direct
digital control available to suit most any
application. Most of the control options
utilize the exclusive Price SP300 multipoint
sensor for accurate duct air velocity pressure
measurement. This allows the terminals to
monitor the desired flow rate, as dictated by
the thermostat, and compensate instantly
for any changes in supply air pressure that
might tend to alter the supply volume. In BMB
other words, the net result is a pressure
independent variable air volume system.
In addition to the basic volume ✓ Product Selection Checklist
control assembly, a complete line of 1] Select Unit Inlet Size based on control and acoustic parameters.
accessories is offered to meet specific job 2] Select Control type (Pneumatic, Digital) based on system design.
requirements. Sound attenuators, multi- 3] Select Accessories (Multi-Outlet Adaptor, Attenuator) as required.
outlet adaptors and heating coils are all 4] Select Reheat Coil, if required.
available. These are factory assembled 5] Select Control Sequence based on system design.
to the basic assembly for shipment as an
integrated unit. • Full range of accessories available (i.e. as option. Stainless steel shaft for
Features: coils, attenuators, etc.). dampers available as option.
• Capacities ranging from 50 – 8000 cfm • Protective metal shrouds for digital
in 11 sizes. controls. Protective metal cover optional
for pneumatic controls.
• Pressure independent operation.
• Compact, lightweight design for ease of
• Can be used for VAV or constant volume
installation.
applications.
• 22 gauge zinc-coated steel housing (optional
• Available with pneumatic, or direct
20 gauge available).
digital controls.
• 1/2 in. [13] thick, min. 1.5 lb density fiberglass
• Factory calibrated to job requirements.
internal insulation – meets requirements for
• Individually adjustable minimum and NFPA90A and UL181. 3/4 in. [19] and 1 in.
maximum air volumes – easily field [25] insulation also available as an option.
adjusted.
• Special liners and insulations available
• SP300 multipoint sensor designed as options.
to maintain control accuracy indepen-
• Damper blade constructed of two layers
dent of field installation conditions.
of heavy gauge galvanized steel with a
• Gauge taps for measurement sandwiched peripheral gasket of cross
and balancing supplied with factory linked polyurethane foam to ensure
mounted pneumatic controls (optional tight seal and no damper deflection.
for digital controls by others).
Alternate material for damper seal
• Conveniently accessible externally available as option subject to
mounted controls.
manufacturer’s recommendation.
• Inlet connection bead offers a means for
secure flex duct connections. • Plated damper shaft with position indicator
• A full 2 in. inlet connection to secure is mounted in self-lubricating bearings.
flex and hard duct connections. Bronze bushings are also available
All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Dimensional Data

SPV8 Size 4 -16


5 3/16” (132)
4 3/8” 6 3/8”
(111) (162)

5”
(127) Size 4 & 5 have 6”ø duct with inlet and
Optional Bottom Access Door (AD) dischage reducer as shown.

SDV8 Size 4 – 16 • 1/2 in. [13] thick, min. 1.5 lb density internal
insulation which meets requirements of NFPA 90A
and UL181. Optional 3/4 in. [19] and 1 in. [25] also
available.
• 22 gauge zinc-coated steel housing. Mechanically
sealed and gasketed, leak resistant construction.
• Rectangular discharge opening with slip and drive
cleat duct connection.
• Control assembly will be supplied as illustrated on
right hand side unless otherwise.
• Gauge taps are standard on units with pneumatic
Optional Bottom Access Door (AD) controls (optional with digital controls by others).
• Clean, dry, 20 psi [138 KPa] for pneumatic unit .
SDV5 Size 4 – 16 Optional NEMAT Controls Enclosure • Optional insulated access door 4 x 63/4" ( 102 x 171)
attached with 4 screws or optional latches.
Multi-Point Sensor 18 1/2” (470)
(Gauge Taps Optional) • Alternate material for damper seal available as option
subject to manufacturer’s recommendation.
• Bronze bushings are also available as options.
• Stainless steel shaft for damper available as option

4 3/4” (121)
Optional Bottom Access Door (AD)
Optional Access Door

Bottom Access Door AD - Access Door w/Screws


4” x 63/4” (102 x 171) 4” (102) x 63/4”(171)

ADL - Access Door w/Snap Latches


4” (102) x 63/4”(171)

ADQ - Access Door w/Quarter Turn Sash Latches


4” (102) x 63/4”(171)

Note: Optional top and bottom access door available (TB)

IP Units (in.] SI Units [mm]


Unit L/s cfm Outlet Inlet Length Outlet Inlet Length
Size Range Range B C A L B C A L
4 0 – 106 0 – 225 12 8 4 22 1/8 305 203 102 562
5 0 – 165 0 – 350 12 8 5 22 1/8 305 203 127 562
6 0 – 212 0 – 450 12 8 6 20 1/8 305 203 152 511
7 0 – 307 0 – 650 12 10 7 20 1/8 305 254 178 511
8 0 – 378 0 – 800 12 10 8 20 1/8 305 254 203 511
9 0 – 496 0 – 1050 14 12 1/2 9 20 1/8 356 318 229 511
10 0 – 637 0 – 1350 14 12 1/2 10 20 1/8 356 318 254 511
12 0 – 991 0 – 2100 16 15 12 20 1/8 406 381 305 511
14 0– 1416 0 – 3000 20 17 1/2 14 23 5/8 508 445 356 600
16 0– 1888 0 – 4000 24 18 16 23 5/8 610 457 406 600
All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Dimensional Data

SPV8 Size 24 x 16
3 89
5 3/16” (132)

Optional Bottom
5” (127) Access Door (AD)

• 1/2 in. [13] thick, min. 1.5 lb density internal insulation which
SDV5 and SDV8 Size 24 x 16 meets requirements of NFPA 90A and UL181. Optional 3/4 in. [19] and 1
in. [25] also available.
Multi-Point Sensor • 22 gauge zinc-coated steel housing. Mechanically sealed and gasketed,
3 89
(Gauge Taps Optional) leak resistant construction.
• Rectangular discharge opening with slip and drive cleat duct connection.
• Control assembly will be supplied as illustrated on right hand side unless
otherwise.
• Gauge taps are standard on units with pneumatic controls (optional with
digital controls by others).
• Clean, dry, 20 psi [138 KPa] control air required for pneumatic unit .
• Optional insulated access door 4 x 63/4" ( 102 x 171) attached with 4 screws
or optional latches
Optional Bottom
Access Door (AD) • Alternate material for damper seal available as option
subject to manufacturer’s recommendation.
• Bronze bushings are also available as options.
• Stainless steel shaft for damper available as option
IP Units (in.] SI Units[mm]
Unit L/s cfm Outlet Inlet Length Outlet Inlet Length
Size Range Range B C D E L B C D E L
24 x 16 0 – 3776 0 – 8000 38 18 23 7/8 15 7/8 19 965 457 603 403 483

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Accessories

Water Coil Section Coil Connections Dimensional Data – IP (in.)/SI [mm ]


Size 4 – 8 1 Row 1/2- in. [13] OD
7/8-in. [22] OD Unit Size B C
Size 9 – 24x16 1 Row
Size 4 – 24x16 2, 3, 4 Row 7/8 in. [22]
- OD 4, 5, 6 12 [305 ] 8 [203 ]
Dimension 'L' 7, 8 12 [305 ] 10 [254 ]
For 1 row or 2 row Coils 9, 10 14 [356 ] 121/2 [318 ]
L = 5 in. [127] 12 16 [406 ] 15 [381 ]
For 3 and 4Row Coils 14 20 [508 ] 171/2 [445 ]
L = 71/4 in. [184] 16 24 [610 ] 18 [457 ]
Note: 1 and 2 row High Capacity (HC) coils available with 12 per inch – see performance tables 24 x 16 38[905 ] 18 [457 ]

Not Insulated
Not Insulated AD - Access Door w/Screws
AD - Access Door w/Screws
Not Insulated 4” (102) 3/4”(171)3
x- 6Access
Not Insulated
Not Insulated AD4” (102) x 6Door w/Screws
/4”(171)
Not Insulated 4” (102) x 63/4”(171)
ADL - Access Door w/Snap
ADL - Access LatchesLatches
Door w/Snap
4” (102) 3/4”(171)3
x 6-(102)
ADL 4” Access
x 6 Door
/4”(171)w/Snap Latches
4” (102) x 63/4”(171)
ADQ - Access Door w/Quarter
ADQ - Access Turn Sash
Door w/Quarter Latches
Turn Sash Latches
Insulated Bottom Bottom
Insulated 3/4”(171)3
Access Door 4” (102)
ADQ x 6-(102)
4” Access
x 6 Door
/ 4 w/Quarter
”(171) Turn Sash Latches
Access
Insulated Door
Bottom Insulated Bottom Bottom
Insulated Downstream
Downstream
Access Door Access Door
Access Door Access Door (ADD) 4” (102) x 63/4”(171)
Insulated Bottom Access
Downstream Note: Optional
Door (ADD) top and bottom access door available (TB)
Note: Optional top and bottom access door available (TB)
61/2”(165)
61/2”(165) (Not Insulated)
Access Door Access Door (ADD)
(Not Insulated) Note: Optional top and bottom access door available (TB)
61/2”(165) (Not Insulated)

Electric Duct Heater Size 4-16


Unit Outlet Inlet Control Box
Size B C D E
4 12 in. [305mm] 8 in. [203mm] 4 in. [102mm] 12 in. [305]
18” (457)* 5 12 in. [305mm] 8 in. [203mm] 5 in. [127mm] 12 in. [305]
6 12 in. [305mm] 8 in. [203mm] 6 in. [152mm] 12 in. [305]
7 12 in. [305mm] 10 in. [254mm] 7 in. [178mm] 12 in. [305]
8 12 in. [305mm] 10 in. [254mm] 8 in. [203mm] 12 in. [305]
9 14 in. [356mm] 12½ in.[318mm] 9 in. [229mm] 12 in. [305]
** 10 14 in. [356mm] 12½ in.[318mm] 10 in. [254mm] 12 in. [305]
35 13/16” (910) 12 16 in. [406mm] 15 in. [381mm] 12 in. [305mm] 17 in. [432]
14 20 in. [508mm] 17½ in.[445mm] 14 in. [356mm] 17 in. [432]
16 24 in. [610mm] 18 in. [447mm] 16 in. [406mm] 17 in. [432]
* Consult submittal drawing for actual and dimensions.
** Heater section not insulated. Insulation option available.

Electric Duct Heater Size 24 x 16 IP Units [in.]

Unit Max Max Outlet Inlet Length


Size L/s cfm B C D E L
3 89
24 x 16 3776 8000 38 18 237/8 157/8 381/2

SI Units [mm]

Unit Max Max Outlet Inlet Length


Size L/s cfm B C D E L
**
24 x 16 3776 8000 965 457 603 403 978

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Accessories

RDC Round Discharge Collar IP Units (in.) SI Units [mm]


Unit RDC RDC
Size Outlet Outlet
4, 5, 6 4, 5, 6 102, 127, 152
7, 8 7, 8 178, 203
9, 10 9, 10 229, 254
12 12 305
14 14 355
16 16 406

HSG Oversized Casing

4 3/8”
(111) 6 3/8”
(162)

Size 4 & 5 have 6”ø duct with inlet and


dischage reducer as shown.
IP Units [mm] SI Units [mm]
Inlet Casing Max Max
Model Outlet Inlet Length Outlet Inlet Length
Size Size L/s cfm
B C A L B C A L
4 8 106 225 12 10 4 221/8 305 254 102 562
HSG8 5 8 165 350 12 10 5 221/8 305 254 127 562
6 8 212 450 12 10 6 201/8 305 254 152 511
7 10 307 650 14 121/2 7 201/8 356 318 178 511
HSG10
8 10 378 800 14 121/2 8 201/8 356 318 203 511
9 12 496 1050 16 15 9 201/8 406 381 229 511
HSG12
10 12 637 1350 16 15 10 201/8 406 381 254 511
HSG14 12 14 991 2100 20 171/2 12 235/8 508 445 305 600
HSG16 14 16 1416 3000 24 18 14 235/8 610 457 356 600
• The oversized casing option utilizes a casing one unit size larger than the standard unit.
• Accessories such as water coils, attenuators, and MOA will correspond to the larger casing size.
• For sound performance, use:
- discharge sound data for standard SDV unit corresponding to inlet size.
- radiated sound data for standard SDV unit corresonding to larger casing size.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Accessories

ATT Attenuator Section IP SI


Unit Units Units
Size B C B C
4, 5, 6 12 8 305 203
7, 8 12 10 305 254
9, 10 14 12 1/2 356 318
12 16 15 406 381
14 20 17 1/2 508 445
Discharge attenuator section is provided as integral extension to the single Duct Terminals size 4-16. Separate 16 24 18 610 457
attenuators are also available. Note that water coil is attached to the end of integral construction unit and between
terminal and for separate construction coded ATTSP. See typical accessories example below.

Typical Accessories Configurations PKIT – Pneumatic Controls Kit


SDV c/w separate Attenuator 143/8” (365)
SDV c/w Integral Attenuator ATTSP, ATT5SP 73/4” (197) 1/2” (13)

311/16”
(94)
SDV c/w Integral Attenuator SDV c/w separate Attenuator
and R.H. Water Coil ATTSP, ATT5SP and R.H. Water Coil 73/8”
(187)

SDV c/w Integral Attenuator and Electric Coil 1/2” (13)


Gauge Taps
Damper Normally Open - PKIT-NO
SDV c/w R.H. Water Coil SDV c/w R.H. Electric Coil
22 gauge zinc-coated mounting plate with
pneumatic controls for
installation.
SDV c/w MOA

SDV c/w MOA and R.H. Water Coil

Damper Normally Closed - PKIT-NC

MOA Multi-Outlet Attenuator Section M.O.A. Outlets


Standard outlet sizes are listed below.

Unit MOA
SDV c/w separate Attenuator 143/8” (365)
Size 1/2” (13) Outlets
SDV c/w Integral Attenuator ATTSP, ATT5SP 73/4” (197)
4, 5, 6 6 in. [152]
7, 8 311/16” 8 in. [203]
SDV c/w Integral Attenuator SDV c/w separate Attenuator 9,10,12 (94) 10 in. [254]
and R.H. Water Coil ATTSP, ATT5SP and R.H. Water Coil 12 73/812
” in. [305]
All outlets c/w manual dampers. 14, 16 (187)
16 in. [406]
Standard MOA Outlet Arrangements
SDV c/w Integral Attenuator and Electric Coil ACS Adaptor Coupling Section*
1/2” (13)
Gauge Taps
Damper Normally Open - PKIT-NO
SDV c/w R.H. Water Coil SDV c/w R.H. Electric Coil

SDV c/w MOA

SDV c/w MOA and R.H. Water Coil


* Used to attach a size 8 MOA to a size 4,5, or 6 terminal,
Damper Normally Closed - PKIT-NC
allowing larger outlet sizes.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Liners – Terminal Casing (Optional)

Price offers an extensive Terminal Unit Liner


System to address the issue of terminal unit SM AFPM
insulation fibers entering the air stream. Each
liner system offers benefits that are designed
to meet applications with various lining and
insulation requirements.
SM
Solid Metal Liner System
This system integrates a fiberglass insulating
material with a solid sheet metal liner
constructed from zinc-coated steel.
The solid metal liner system complies with the
following industry standards and tests:
PM WFPM
• UL 181 (Air Erosion)
• UL 181 (Mold Growth and Humidity)
• UL 723 (25/50) (Flame and Smoke)
• ASTM E 84 (25/50) (Flame and Smoke)
• ASTM C 665 (Fungi Resistance)
• ASTM C 1071 (Physical Properties)
Solid metal liners offer the ultimate protection
against exposure of fiberglass particles to the air
stream. The fiberglass insulation is completely
enclosed in metal eliminating the possibility
of punctures exposing the fiberglass particles. AFPM WFPM
This system is also resistant to moisture. The Aluminum Foil with Woven Fabric with
encased insulation provides thermal resistance, Perforated Metal Liner System Perforated Metal Liner System
however, acoustic absorption of discharge This system integrates foil-faced fiberglass This system integrates a fiberglass insulating
noise is significantly reduced. insulating material with a perforated metal material with woven fabric facing to prevent
The following thicknesses are available liner. The edges are sealed with metal end particles from entering the air stream. Perforated
caps to prevent particles from entering the air metal liner, covers the insulation and the edges
• SM - 3/4 in. [19] thick, R value=3.2
stream.The double liner system (aluminum foil/ are sealed with metal caps.
• SM1 - 1 in. [25] thick, R value = 4.1 perforated metal) complies with the following The double liner system (woven fabric/
PM industry standards and tests: perforated metal) complies with the following
Perforated Metal Liner System • UL 181 (Air Erosion) industry standards and tests:
This system integrates a fiberglass insulating • UL 181 (Mold Growth and Humidity) • UL 181 (Air Erosion)
material with a perforated metal liner • UL 723 (25/50) (Flame and Smoke)
constructed from coated steel. The edges are • UL 181 (Mold Growth and Humidity)
sealed with metal caps. • ASTM E 84 (25/50) (Flame and Smoke) • UL 723 (25/50) (Flame and Smoke)
• ASTM C 665 (Fungi Resistance) • ASTM E 84 (25/50) (Flame and Smoke)
The perforated metal liner system complies
with the following industry standards and tests: • ASTM C 1071 (Physical Properties) • ASTM C 665 (Fungi Resistance)
• UL 181 (Air Erosion) The aluminum foil with perforated metal liner The woven fabric with perforated metal liner
system provides effective protection against system provides effective protection against
• UL 181 (Mold Growth and Humidity) damage of the liner while maintaining some damage of the liner and/or insulation, while
• UL 723 (25/50) (Flame and Smoke) acoustic value. The aluminum foil prevents maintaining some acoustic value. The woven
• ASTM E 84 (25/50) (Flame and Smoke) fiberglass particles from escaping through the fabric prevents fiberglass particles from
• ASTM C 665 (Fungi Resistance) perforations as well as resistance to moisture escaping through the perforations. Since
• ASTM C 1071 (Physical Properties) penetration. the fabric is porous, the system is not totally
• AFPM - 5/8 in. [16] thick, R value=2.6 impervious to moisture R value=3.2.
The metal perforated liner system provides
effective protection against damage of • AFPM1 - 1 in. [25] thick, R value = 4.1
the insulation while maintaining some
acoustic value. Small fiberglass particles
could conceivably still escape through the
perforations and moisture can also be exposed
to the insulation.
The following thicknesses are available
• PM - 3/4 in. [19] thicks, R value = 3.2
• PM1 - 1 in. [25] thick, R value = 4.1

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Liners – Terminal Casing

FB
Foil Board Liner System FB
This system integrates 4 lb. density rigid insulating material
with an aluminum foil facing. Exposed edges are coated with NFPA-90A
approved sealant.
The fiberglass insulation and aluminum foil liner complies with the
following industry standards and tests:
• UL 181 (Air Erosion)
• UL 181 (Mold Growth and Humidity)
• UL 723 (25/50) (Flame and Smoke)
• ASTM E 84 (25/50) (Flame and Smoke)
• ASTM C 665 (Fungi Resistance)
• ASTM C 1071 (Physical Properties)
Acoustic absorption of aluminum foil lined insulation is reduced compared
to standard unlined units. The aluminum foil liner is non porous, thereby
protecting the insulation from moisture. Damage to the liner can expose
fiberglass particles to the air stream.
The following thicknesses are available
• FB - 5/8 in. [16] thicks, R-value =2.6
• FB1 - 1 in. [25] thick, R-value = 4.2
FG
Fiberglass Line FG
This system integrates 1.5 lb. density insulating material to
provide lining and insulation characteristics.
Fiberglass insulation meets NFPA 90A requirements and complies with
the following industry standards and tests:
• ASTM C 1071 3/4” (19)
• UL 181 (Air Erosion)
• UL 181 (Mold Growth and Humidity)
• UL 723 (25/50) (Flame and Smoke)
• ASTM E 84 (25/50) (Flame and Smoke)
• ASTM C 665 (Fungi Resistance)
The following thicknesses are available
• FG50 - 1/2 in. [13] thicks, R-value = 2.1
• FG75 - 3/4 in. [19] thicks, R-value = 3.2
• FG1 - 1 in. [25] thick, R-value = 4.1

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Cleanroom Construction

General Information fibrous particles from entering the primary airstream as air flows
Price single duct terminal units with cleanroom construction are through the unit. The proven design of the Price standard single
designed for those applications where indoor air quality (IAQ) duct terminal unit incorporates unique design features to provide
is critical. These units are ideally suited to hospital applications these benefits.
such as patient rooms, burn wards, operating rooms and Attenuators and multi-outlet attenuator sections are available and
laboratories as well as cleanrooms and other areas where are specifically designed to match these terminals with cleanroom
airborne particles are of concern. Today, when IAQ is a growing construction. These sections are shipped as an integral part of the
concern, the Price line of cleanroom terminals can be successfully terminal unit.
applied to regular commercial construction. Three options of cleanroon construction are offered to meet the
Terminals with cleanroom construction are designed to reduce the specific needs of various applications. The options are designated
risk of micro-organism growth within the terminal as well as prevent CRAF, CRWF, and FF.

FF
Fiber Free Foam Insulation System FF
This system integrates an engineered foam which provides excellent
insulating characteristics. The foam edges are self sealing due to
the material’s composition.
The engineered foam meets requirement of NFPA 90A and complies
with the following industry standards and tests:
• UL 181 (Air Erosion)
• UL 181 (Mold Growth & Humidity) (FF50) 1/2” (13)
or
• UL 723 (25/50) (Flame & Smoke) (FF) 3/4” (19)
• ASTM E 84 (25/50) (Flame & Smoke)
• CAN/ULC-102.2-M88 (Flame and Smoke)
Fiber free foam insulation totally eliminates the risk of
particles entering the airstream while maintaining thermal resistance
and acoustic absorption. An important advantage over other liner
systems is that even scrapes or punctures will not expose fibers
to the airstream. The foam also will not absorb water, reducing the
likelihood of mold or bacterial growth. Acoustic absorption of the
foam insulation is equivalent to aluminum foil faced insulation.
The following thicknesses are available
• FF50 - 1/2" (13) thick, R value =2
• FF - 3/4" (19) thick, R value =3
• FF1 - 1" (25) thick, R value =4

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Cleanroom Construction

CRAF CRWF
Cleanroom Aluminum Foil System Cleanroom Woven Fabric System CRAF
This system integrates a rigid 4 lb. density This system integrates fiberglass insulating
fiberglass insulating material with an material with a woven fabric facing. All
aluminum foil facing. All edges are sealed edges are sealed with metal end caps and
with metal endcaps and corner angles corner angles to prevent particles from
to prevent particles from entering the air entering the air stream.
stream. The liner’s integrity is maintained where the
The liner’s integrity is maintained where the damper shaft penetrates the insulation by a
damper shaft penetrates the insulation by a flanged nylon bushing.To reduce risk of liner
flanged nylon bushing.To reduce risk of liner damage during installation, sealed-in-place
damage during installation, sealed-in-place s-cleats are provided at the discharge collar.
s-cleats are provided at the discharge collar. The fiberglass insulation and fabric liner
The fiberglass insulation and aluminum foil complies with the following industry
liner complies with the following industry standards and tests:
standards and tests: • UL 181 (Air Erosion)
• UL 181 (Air Erosion) • UL 181 (Mold Growth and Humidity) CRWF
• UL 181 (Mold Growth and Humidity) • UL 723 (25/50) (Flame and Smoke)
• UL 723 (25/50) (Flame and Smoke) • ASTM E 84 (25/50) (Flame and Smoke)
• ASTM E 84 (25/50) (Flame and Smoke) • ASTM C 665 (Fungi Resistance)
• ASTM C 665 (Fungi Resistance) • ASTM C 1071 (Physical Properties)
• ASTM C 1071 (Physical Properties) The woven fabric liner provides acoustic
Acoustic absorption of aluminum foil lined absorption equivalent to aluminum foil
insulation is reduced compared to standard faced insulation with slightly improved
unlined units.The aluminum foil liner is non- attenuation at high frequencies. The Fiberglass with
woven fabric facing
porous, thereby protecting the insulation fabric is more porous than aluminum foil,
from moisture. The smooth surface of the therefore moisture can be absorbed into
liner reduces the risk of micro-organisms the insulation. If the liner is damaged,
being trapped in the material and also fiberglass particles can be exposed to the
facilitates cleaning. Damage to the liner can air stream. The woven fabric liner has been
expose fiberglass particles to the air stream. specified in certain areas for many years
The following thicknesses are available and has a proven track record in health care
• CRAF - 5/8 in. [16] thick, R-value=2.6 applications, R value = 2.6.
• CRAF1 - 1 in. [25] thick, R-value =4.2 The following thicknesses are available
• CRWF - 3/4 in. [19] thick, R-value=3.2
• CRWF1 - 1 in. [25] thick, R-value =4.1

Metal Flange Zinc-Coated Metal Angles


• Captures and seals insulation ends • Encloses seams to further reduce risk of micro-organism growth

Reinforced, Non-Porous, Smooth Foil or


Fabric Faced Insulation
• Reduces risk of moisture formation and micro-organism growth
• Smooth surface facilitates cleaning
• ASTM C665, UL 181, NFPA 90A

Nylon Flanged Bushing


• Seals insulation

S–Cleats
• Sealed in place to reduce risk of damage
to liner during installation

Insulated Inlet Panel Caulking Seal Inside


• Covered with sheet metal Inlet Panel
• Mold-resistant caulking seals
CRAF and CRWF Construction Features Internal Insulation to Inlet Duct

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
Electric Coils for
Single Duct Terminals
Return to product page

Product Information

General Information
Price offers factory supplied and mounted
electric coils for single duct terminal units.
The electric coils come standard as a
side-mounted unit (slide-in type) and are
specifically designed to suit Price terminal
units. The heating elements are low watt
density and designed to minimize hot spots
and thermal cutout. This allows for a more
compact assembly making field installation
much easier and reducing shipping costs.
Price heaters offer a full range of options
and accessories to meet all customers'
needs. SCR (Silicon Controlled Rectifier) and
the Price exclusive 'Electronic Modulating
Control' are also available, offering numer-
ous benefits over conventional duct heater
control.
Benefits of Electric Reheat
Electric coils offer an alternative to water
reheat coils as an optional accessory for
single duct terminal units.
Some of the benefits include:
• No requirement for water lines.
• Low pressure drop across the coil
elements, which reduces central fan
horsepower requirements.
• Operate using standard building
electrical power.
Features
• Extremely compact design – 35 in.
housing length.
• Specially designed elements allow
for installation with minimal clearance
between the terminal and coil, resulting • All heaters come with an Automatic • An air switch is provided as
in an extremely compact assembly. This Reset thermal cutout to protect from standard to ensure air is passing over
allows for easier field installation and overheating in case the minimum air the coil before it will energize. This
reduced shipping costs. flow requirements are not met. ensures that the coil will not energize
• A Manual Reset thermal cutout is when the system fan is shut-down or
• Heaters are factory wired and tested
standard on all heaters. fails.
ensuring a high level of quality.
• Terminal housing is lined with 1/2 in. • A unique pressure sensing tap
• The heater controls can be
compatible with pneumatic, electronic, [13] thick, min. 1.5 lb density fiberglass strategically located to ensure
internal insulation which meets positive operation of the heater at low
or direct digital control.
requirements for NFPA90A and UL181. downstream static pressure.
• Heavy gauge zinc-coated steel electrical
Optional 3/4 in. [19] and 1 in. [25] also
enclosure and frame. • For stable operation of heater controls
available. Heater section in not insulated minimum discharge static pressure of
• Electric coil and air is
unless requested. 0.2 in. w.g. is recommended
matched to eliminate hot spots, provide
• Magnetic contactors or Pneumatic-
efficient heat transfer, and to maintain
Electric switches are provided as
element life.
standard on staged heaters for de-
• Hinged access door for the electrical
energizing or disconnecting power to
enclosure.
the heating element.
• Heaters are provided with Low Watt
Density elements to prevent overheating
and nuisance tripping of the thermal
overload protectors.
• High grade nickel chrome elements
provide maximum corrosion resistance
and extended element life.
• When needed, a Class II (24VAC) control
transformer is provided as standard
with heater controls.
All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
Single Duct – Controller Type

Typical Selection Guide

Discharge NC Discharge NC c/w Radiated NC


Basic Unit 36 in. Attenuator Basic Unit
Minimum ∆Ps ∆Ps Across Unit ∆Ps Across Unit ∆Ps Across Unit
Across Assembly Min. ∆Pt. 0.5 in. 1.5 in. 3.0 in. 0.5 in. 1.5 in. 3.0 in. 0.5 in. 1.5 in. 3.0 in.
Unit Air Flow Basic Unit w/Atten. 1 Row Coil 2 Row Coil Basic Unit in.w.g in.w.g in.w.g in.w.g in.w.g in.w.g in.w.g in.w.g in.w.g
Size cfm L/s in.w.g Pa in.w.g Pa in.w.g Pa in.w.g Pa in.w.g Pa 125Pa 375Pa 750Pa 125Pa 375Pa 750Pa 125Pa 375Pa 750Pa
4 75 35 0.01 2 0.01 2 0.02 5 0.03 7 0.06 14 -- -- -- -- -- -- -- -- --
125 59 0.01 2 0.01 2 0.03 7 0.05 12 0.14 34 -- 23 24 -- 21 23 -- -- --
150 71 0.01 2 0.01 2 0.04 10 0.08 20 0.19 48 23 26 28 21 24 26 -- -- --
225 106 0.01 2 0.01 2 0.05 12 0.11 27 0.42 104 31 34 36 28 31 33 -- 22 26
5 125 59 0.01 2 0.01 2 0.03 7 0.05 12 0.06 15 -- -- 20 -- -- -- -- -- --
200 94 0.01 2 0.01 2 0.05 12 0.09 22 0.14 35 -- 25 28 -- 21 24 -- 21 24
250 118 0.01 2 0.01 2 0.06 15 0.13 32 0.21 53 23 28 32 -- 25 28 21 25 28
350 165 0.01 2 0.01 2 0.11 27 0.22 55 0.41 101 25 30 34 21 26 29 27 31 34
6 150 71 0.02 5 0.02 5 0.04 10 0.07 17 0.05 13 -- -- 22 -- -- -- -- -- --
225 106 0.05 12 0.05 12 0.09 22 0.15 37 0.13 31 -- 22 27 -- -- 24 -- -- 21
300 142 0.08 20 0.08 20 0.15 37 0.24 60 0.21 53 -- 23 29 -- -- 24 -- 20 24
400 189 0.14 35 0.14 35 0.26 65 0.40 100 0.38 94 -- 27 33 -- 23 27 -- 24 28
450 212 0.18 45 0.18 45 0.33 82 0.50 124 0.48 119 -- 29 35 -- 25 29 -- 25 29
7 250 118 0.02 5 0.02 5 0.05 12 0.09 22 0.07 17 -- 20 27 -- -- -- -- -- --
350 165 0.03 7 0.03 7 0.09 22 0.16 40 0.13 31 -- 23 30 -- -- 21 -- -- 23
450 212 0.05 12 0.05 12 0.14 35 0.24 60 0.21 52 -- 26 33 -- 21 25 -- 22 26
550 260 0.07 17 0.07 17 0.20 50 0.34 85 0.31 76 -- 29 35 -- 24 28 -- 24 28
650 307 0.10 25 0.10 25 0.27 67 0.46 114 0.43 107 21 31 38 -- 26 30 22 27 29
8 400 189 0.01 2 0.01 2 0.08 20 0.17 42 0.08 19 -- 21 29 -- -- 21 -- 21 25
500 236 0.01 2 0.01 2 0.12 30 0.24 60 0.12 29 -- 24 31 -- -- 24 -- 24 28
600 283 0.01 2 0.01 2 0.16 40 0.33 82 0.16 40 -- 26 33 -- 22 26 -- 26 30
700 330 0.01 2 0.01 2 0.2 50 0.42 105 0.22 54 -- 28 35 -- 24 28 21 28 32
800 378 0.01 2 0.01 2 0.25 62 0.52 129 0.28 70 -- 28 35 -- 23 28 22 29 33
9 450 212 0.01 2 0.01 2 0.06 15 0.11 27 0.07 16 -- 25 34 -- -- 25 -- -- 24
650 307 0.01 2 0.01 2 0.10 25 0.20 50 0.13 32 -- 27 36 -- 22 27 -- -- 27
900 425 0.01 2 0.01 2 0.16 40 0.34 85 0.23 58 -- 28 37 -- 22 29 -- 22 30
1050 496 0.01 2 0.01 2 0.21 52 0.44 109 0.32 78 -- 29 38 -- 24 30 -- 23 32
10 550 260 0.01 2 0.01 2 0.08 20 0.16 40 0.06 15 -- 21 29 -- -- 23 -- -- 26
750 354 0.01 2 0.01 2 0.12 30 0.25 62 0.10 26 -- 25 32 -- 21 27 -- 21 29
950 448 0.01 2 0.01 2 0.18 45 0.37 92 0.16 40 -- 25 33 -- 21 27 -- 23 31
1100 519 0.01 2 0.01 2 0.23 57 0.47 117 0.21 53 -- 26 34 -- 23 28 -- 24 32
1350 637 0.01 2 0.01 2 0.32 80 0.66 164 0.32 79 -- 28 36 -- 25 31 -- 26 34
12 900 425 0.01 2 0.01 2 0.10 25 0.20 50 0.07 18 -- 27 35 -- -- 27 -- 21 28
1200 566 0.01 2 0.01 2 0.16 40 0.33 82 0.12 31 -- 27 35 -- 22 28 -- 23 30
1600 755 0.01 2 0.01 2 0.25 62 0.52 129 0.21 53 -- 29 36 -- 24 31 -- 25 32
1800 850 0.01 2 0.01 2 0.31 77 0.63 157 0.27 66 20 31 37 -- 25 32 -- 26 33
2100 991 0.01 2 0.01 2 0.4 100 0.82 204 0.36 89 22 33 39 -- 27 34 -- 28 34
14 1000 472 0.01 2 0.01 2 0.07 17 0.13 32 0.05 13 -- 23 32 -- 23 30 -- 21 28
1500 708 0.01 2 0.01 2 0.12 30 0.25 62 0.11 27 -- 26 35 -- 25 32 -- 26 32
2100 991 0.01 2 0.01 2 0.21 52 0.44 109 0.20 51 -- 29 37 -- 28 35 23 31 36
2500 1180 0.01 2 0.01 2 0.28 70 0.58 144 0.28 71 -- 31 39 -- 29 36 26 33 38
3000 1416 0.01 2 0.01 2 0.38 95 0.79 197 0.41 101 20 33 41 -- 30 37 28 36 41
16 1500 708 0.01 2 0.01 2 0.09 22 0.19 47 0.07 17 -- 23 31 -- 21 29 -- 25 31
2000 944 0.01 2 0.01 2 0.15 37 0.3 75 0.11 27 -- 26 34 -- 24 32 -- 28 34
2500 1180 0.01 2 0.01 2 0.21 52 0.43 107 0.17 41 -- 28 36 -- 26 33 23 31 36
2800 1321 0.01 2 0.01 2 0.25 62 0.52 129 0.21 51 -- 30 38 -- 27 34 25 33 38
3500 1652 0.01 2 0.01 2 0.37 92 0.75 187 0.32 79 -- 33 41 -- 29 37 29 37 42
4000 1888 0.01 2 0.01 2 0.46 114 0.94 234 0.41 102 22 35 43 -- 31 38 32 40 45
24x16 3000 1416 0.01 2 0.01 2 0.13 32 0.28 70 0.06 16 23 32 37 -- 27 32 24 31 35
4000 1888 0.01 2 0.01 2 0.21 52 0.44 109 0.11 26 27 35 41 23 31 36 29 35 39
5300 2501 0.01 2 0.01 2 0.34 85 0.70 174 0.18 44 30 39 44 27 35 40 34 39 43
6000 2832 0.01 2 0.01 2 0.42 105 0.86 214 0.23 56 32 41 46 28 37 42 36 41 45
7000 3304 0.01 2 0.01 2 0.54 134 1.11 276 0.30 76 34 42 48 30 39 44 38 43 47
8000 3776 0.01 2 0.01 2 0.68 169 1.39 346 0.39 98 35 44 50 32 40 46 40 46 49

Performance Notes:
1. NCs are derived from sound power levels, which are 7. ∆Ps for terminal units with electric coil is equal to basic Typical Attenuation Values:
obtained in accordance with AHRI Standard 880-2011 unit. Resistance of the coil elements is negligible. Radiated Sound
and ASHRAE Standard 130-2008. 8. ∆Pt is the difference in total pressure from inlet to discharge Total Deduction Octave Band Mid Frequency, Hz.
2. NCs are derived from sound power levels which include of the unit.
125 250 500 1000 2000 4000
duct end corrections per AHRI Standard 880 -2011. 9. Pressure is given in Pa and in. w.g.
All Sizes 18 19 20 26 3 1 36
10. NC values are calculated based on typical attenuation
3. Blank spaces (--) indicate NCs less than 20. values outlined in Appendix E, AHRI Standard 885-2008, Discharge Sound
4. Asterisks (*) indicate minimum static pressure of the unit “A Procedure for Estimating Occupied Space Sound Levels Total Deduction Octave Band Mid Frequency, Hz.
exceeds the minimum operating pressure across the unit. in the Application of Air Terminals and Air Outlets.” 125 250 500 1000 2000 4000
5. Air flow is given in L/s and cfm. < 300 cfm 24 28 39 53 59 4 0
6. ∆Ps is the difference in static pressure from inlet to 300 – 700 cfm 27 29 40 51 53 39
discharge of the unit. > 700 cfm 29 30 41 51 52 3 9

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct - Controller Type
SPV-K, SEV-K, SDV-K Series

Radiated Sound Power Levels, Basic Assembly

Sound Power Levels Lw, dB, RE 10-12 Watts


125 Pa (0.5" W.G.) 250 Pa (1.0" W.G.) 375 Pa (1.5" W.G.) 750 Pa (3.0" W.G.)
Unit Air Flow Octave Band Octave Band Octave Band Octave Band
Size cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
4 75 35 46 35 26 22 24 29 46 35 28 23 25 30 45 36 30 24 26 31 45 36 32 26 28 32
125 59 54 43 33 26 27 30 53 44 36 29 28 31 53 44 37 30 29 32 53 45 40 32 31 33
150 71 57 46 36 28 28 31 56 47 38 31 30 32 56 47 40 32 30 32 55 48 43 34 32 33
225 106 63 53 41 33 31 32 62 53 44 35 32 33 62 54 46 37 33 34 61 54 49 39 34 35
5 125 59 46 38 28 22 20 29 47 40 32 25 23 29 48 42 35 27 24 29 50 44 39 31 27 29
200 94 53 45 35 27 25 31 55 47 39 31 27 31 55 49 42 34 29 31 57 51 46 38 32 31
250 118 56 48 39 30 27 32 58 51 43 34 30 32 59 52 45 37 31 32 60 55 49 40 34 32
350 165 62 54 44 35 31 33 63 56 48 39 33 33 64 58 50 41 35 33 65 60 54 45 38 33
6 150 71 49 39 30 22 20 29 51 42 34 25 23 30 52 44 37 28 25 30 54 47 41 32 28 31
225 106 54 45 36 26 24 31 56 48 40 31 27 32 57 50 43 33 29 32 59 53 47 38 32 33
300 142 58 49 40 31 27 32 60 52 44 35 31 33 61 54 47 38 32 33 63 57 51 42 35 34
400 189 61 53 44 35 31 33 63 56 49 39 34 34 64 58 51 42 35 34 66 61 56 46 39 35
450 212 63 55 46 36 32 34 65 58 50 41 35 34 66 60 53 43 37 35 68 63 57 48 40 35
7 250 118 52 42 33 26 22 28 54 47 38 29 25 30 56 49 40 31 27 31 58 53 45 35 30 32
350 165 55 47 38 30 25 30 58 51 42 33 29 31 59 53 45 35 31 32 62 57 49 39 34 33
450 212 58 50 41 33 28 31 61 54 46 37 31 32 62 56 48 39 33 33 65 61 53 42 36 34
550 260 61 52 44 36 30 31 63 57 48 39 34 33 65 59 51 41 35 34 67 63 55 45 39 35
650 307 62 54 46 38 32 32 65 59 51 41 35 34 66 61 53 43 37 34 69 65 58 47 41 36
8 400 189 54 44 36 28 24 30 57 48 40 33 28 32 58 51 43 36 30 33 60 55 47 40 34 34
500 236 57 47 39 31 27 31 59 51 43 36 31 32 60 54 46 38 33 33 63 58 51 43 37 35
600 283 59 49 41 33 29 31 61 54 46 38 33 33 62 56 49 41 35 34 65 60 53 45 39 36
700 330 60 51 44 35 30 32 63 56 48 40 34 33 64 58 51 43 37 34 67 62 55 47 40 36
800 378 62 53 46 37 32 32 64 57 50 42 36 34 66 60 53 44 38 35 68 64 57 49 42 37
9 450 212 49 41 35 28 24 25 52 47 41 33 29 30 54 50 44 36 32 32 57 56 50 40 37 37
650 307 53 45 40 33 28 28 56 51 45 38 33 32 58 54 49 40 36 35 61 60 54 45 41 39
900 425 56 49 44 37 32 30 59 55 49 42 37 34 61 58 53 45 40 37 64 64 58 49 45 41
1050 496 58 51 45 39 34 31 61 57 51 44 39 35 63 60 55 47 42 38 66 66 60 51 47 42
10 550 260 50 44 36 28 25 28 54 49 41 33 29 30 56 52 45 36 31 32 59 58 50 41 35 34
750 354 53 47 40 32 29 29 57 53 45 37 32 32 59 56 49 40 35 33 62 61 54 45 38 35
950 448 56 50 43 35 31 30 59 56 48 40 35 33 61 59 52 43 37 34 65 64 57 48 41 36
1100 519 57 52 44 37 33 31 61 57 50 42 37 33 63 60 53 45 39 35 66 66 59 50 43 37
1350 637 59 54 47 39 35 32 63 60 53 44 39 34 65 63 56 47 41 35 68 68 62 53 45 38
12 900 425 52 48 40 30 26 28 55 53 45 35 30 30 57 56 48 38 32 31 61 60 53 43 36 34
1200 566 54 51 43 34 29 30 58 56 48 38 33 32 60 58 51 41 35 33 64 63 56 46 39 35
1600 755 57 54 46 37 33 31 61 58 51 42 36 33 63 61 54 45 38 34 66 66 59 49 42 36
1800 850 58 55 47 38 34 32 62 60 53 43 38 34 64 62 55 46 40 35 67 67 61 51 43 37
2100 991 60 56 49 40 36 32 63 61 54 45 39 34 65 64 57 48 42 36 69 68 62 53 45 38
14 1000 472 51 50 41 32 27 24 55 55 46 36 31 27 57 57 49 39 33 29 60 62 54 44 37 33
1500 708 55 53 45 36 32 28 58 58 50 41 36 31 60 61 53 44 38 33 64 66 58 49 42 37
2100 991 58 55 48 40 36 31 61 60 54 45 40 34 63 63 57 48 42 37 67 68 62 53 46 40
2500 1180 60 57 50 42 38 33 63 62 55 47 42 36 65 65 58 50 44 38 68 70 64 55 48 42
3000 1416 61 58 52 45 40 34 65 63 57 49 44 38 67 66 60 52 47 40 70 71 65 57 51 44
16 1500 708 51 49 40 32 26 23 55 54 45 36 30 27 57 57 48 39 33 29 61 63 53 43 37 33
2000 944 54 52 43 35 31 27 58 57 48 40 35 31 60 60 51 43 37 33 65 65 56 47 41 37
2500 1180 56 54 46 38 34 30 60 59 51 43 38 34 63 62 54 46 40 36 67 67 59 50 44 40
2800 1321 58 55 47 40 35 31 62 60 52 44 39 35 64 63 55 47 42 38 68 68 61 52 46 42
3500 1652 60 57 50 43 39 34 64 62 55 47 43 38 67 65 58 50 45 41 71 70 63 55 49 45
4000 1888 61 58 52 45 40 36 66 63 57 49 45 40 68 66 60 52 47 43 72 72 65 56 51 47

Performance Notes:
1. Test obtained in accordance with ARI Standard 880-2008 3. Pressure given in Pascals, Pa; and inches water gauge.
and Ashrae Standard 130-2008
2. Airflow given in litres/second, L/s; and cubic feet/minute,
CFM
Single Duct - Controller Type
SPV-K, SEV-K, SDV-K Series

Discharge Sound Power Levels, Basic Assembly

Sound Power Levels Lw, dB, RE 10-12 Watts


125 Pa (0.5" W.G.) 250 Pa (1.0" W.G.) 375 Pa (1.5" W.G.) 750 Pa (3.0" W.G.)
Unit Air Flow Octave Band Octave Band Octave Band Octave Band
Size cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
4 75 35 61 50 43 36 35 35 61 53 47 41 40 40 62 54 50 43 42 43 63 57 54 48 47 48
125 59 67 57 50 42 40 40 68 60 54 47 45 45 68 61 56 49 48 47 69 64 60 54 53 52
150 71 69 60 52 44 42 41 70 62 56 49 47 46 70 64 58 52 49 49 71 66 62 56 54 54
225 106 74 65 57 49 46 45 75 68 61 53 51 50 75 69 63 56 54 53 76 72 67 61 59 58
5 125 59 62 52 45 38 36 36 64 56 51 45 43 42 66 59 54 49 47 46 68 63 60 55 53 52
200 94 69 58 51 44 40 40 71 63 57 50 47 46 72 66 60 54 51 49 75 70 66 60 57 56
250 118 72 62 54 46 42 41 74 66 60 53 49 48 75 69 63 57 53 51 78 73 69 63 59 57
350 165 77 66 58 50 45 44 79 71 64 57 52 50 80 74 67 61 56 54 82 78 73 67 62 60
6 150 71 65 54 46 39 38 37 68 58 52 46 44 44 69 61 55 50 48 48 71 65 61 57 55 54
225 106 70 59 51 43 41 39 73 64 56 50 47 46 74 66 60 54 51 50 77 71 65 60 58 57
300 142 74 63 54 46 43 41 76 67 60 52 49 48 78 70 63 56 53 51 80 75 69 63 60 58
400 189 78 67 57 48 45 43 80 71 63 55 51 49 81 74 66 59 55 53 84 78 72 66 62 60
450 212 79 68 59 49 45 43 82 73 64 56 52 50 83 75 68 60 56 54 85 80 73 67 62 60
7 250 118 65 57 50 45 42 39 69 63 56 51 48 46 71 66 60 54 52 50 76 72 66 61 58 57
350 165 68 61 53 47 44 41 72 67 59 53 50 48 75 70 63 57 54 52 79 76 69 63 60 59
450 212 70 64 55 49 46 43 75 69 61 55 52 50 77 73 65 59 56 54 81 78 71 65 62 60
550 260 72 66 57 51 47 44 76 71 63 57 53 51 79 75 67 61 57 55 83 80 73 67 63 62
650 307 74 67 59 52 48 45 78 73 65 58 54 52 80 76 68 62 58 56 85 82 75 68 64 63
8 400 189 66 57 51 45 41 38 71 63 57 52 48 45 74 66 60 56 53 50 79 72 66 63 60 57
500 236 68 60 53 46 42 40 73 65 59 54 50 47 76 69 62 58 54 51 81 74 68 65 62 58
600 283 70 62 54 48 44 41 75 68 60 55 51 48 78 71 64 59 55 52 83 77 70 66 63 59
700 330 72 64 56 49 45 42 77 70 62 56 52 49 79 73 65 60 56 53 84 79 72 68 64 60
800 378 73 66 57 50 45 43 78 71 63 57 53 50 81 75 67 61 57 54 86 80 73 69 65 61
9 450 212 66 58 51 47 44 40 70 65 58 53 50 47 72 69 62 57 54 52 76 76 69 63 61 59
650 307 69 60 53 49 46 42 72 67 60 56 53 50 75 71 64 59 56 54 79 78 71 66 63 61
900 425 71 62 55 51 48 44 75 69 62 58 54 52 77 73 66 62 58 56 81 80 73 68 65 63
1050 496 72 63 56 52 49 45 76 70 63 59 55 53 78 74 67 62 59 57 82 81 74 69 66 64
10 550 260 67 58 53 47 44 40 72 65 60 54 50 47 74 69 64 58 54 51 79 76 71 64 60 57
750 354 69 60 54 49 45 42 73 67 61 56 52 49 76 71 65 60 56 53 81 78 72 66 62 59
950 448 70 62 56 51 47 43 75 69 63 57 53 50 78 73 67 61 57 54 82 79 74 68 64 61
1100 519 71 63 57 52 48 44 76 70 64 58 54 51 78 74 68 62 58 55 83 80 75 69 64 62
1350 637 72 64 58 53 49 46 77 71 65 60 55 52 80 75 69 63 59 56 84 82 76 70 66 63
12 900 425 67 60 54 48 45 42 72 67 60 55 52 49 75 71 64 59 55 53 80 78 71 65 62 59
1200 566 68 62 56 51 48 44 74 69 63 57 54 51 77 73 67 61 58 55 82 79 73 67 64 62
1600 755 70 64 58 53 50 46 75 70 65 59 56 53 78 74 69 63 60 57 83 81 76 70 66 64
1800 850 71 64 59 54 51 47 76 71 66 60 57 54 79 75 70 64 61 58 84 82 76 71 67 65
2100 991 72 65 60 55 52 48 77 72 67 61 59 55 80 76 71 65 62 59 85 82 78 72 69 66
14 1000 472 64 60 54 49 47 44 69 66 61 57 53 51 72 70 65 61 57 54 78 76 72 69 64 61
1500 708 66 62 56 51 49 46 72 68 63 59 56 53 75 72 67 63 60 57 80 78 74 71 66 63
2100 991 68 63 58 53 51 48 74 70 65 61 58 55 77 73 70 65 62 59 83 80 77 73 68 65
2500 1180 69 64 60 54 52 49 75 70 67 61 59 56 78 74 71 66 63 60 84 81 78 74 69 66
3000 1416 70 65 61 55 53 50 76 71 68 62 60 57 79 75 72 67 64 61 85 81 79 75 70 67
16 1500 708 61 56 52 49 47 45 68 64 60 56 54 52 72 68 64 60 58 56 78 75 71 67 65 62
2000 944 63 58 55 51 49 47 70 65 62 58 56 54 73 69 66 62 60 58 80 77 73 69 66 64
2500 1180 64 59 56 53 51 49 71 67 63 60 58 55 75 71 67 64 61 59 81 78 75 71 68 66
2800 1321 65 60 57 53 52 49 72 67 64 60 58 56 75 71 68 64 62 60 82 79 75 71 69 66
3500 1652 67 61 59 55 53 51 73 69 66 62 60 57 77 73 70 66 64 61 83 80 77 73 70 68
4000 1888 67 62 60 56 54 52 74 69 67 63 61 58 78 74 71 67 65 62 84 81 78 74 71 69

Performance Notes:
1. Test obtained in accordance with ARI Standard 880-2008 3. Pressure given in Pascals, Pa; and inches water gauge.
and Ashrae Standard 130-2008
2. Airflow given in litres/second, L/s; and cubic feet/minute,
CFM
Bader Al Mulla & Bros. Co. W.L.L.
Air Movement Products Division
Post Box 177, Safat, 13002, Kuwait
Fax: 2483 9725 Tel: 2481 5077 Ext. 721
e-mail: ampsales@almullagroup.com