Firefighting System Design – Oil Installation

Calculations for Foam:

Flammable Liquids

Flammable liquids shall be or shall include any liquids having a flash point below 100°F (37.8°C) and having a vapor pressure not
exceeding 40 psi (276 kPa) (absolute) at 100°F (37.8°C).

Flammable liquids shall be subdivided as follows:

(a) Class I liquids shall include those having flash points below 100°F (37.8°C) and shall be subdivided as follows:

1. Class IA liquids shall include those having flash points below 73°F (22.8°C) and having a boiling point below 100°F
(37.8°C).
2. Class IB liquids shall include those having flash points below 73°F (22.8°C) and having a boiling point above 100°F
(37.8°C).
3. Class IC liquids shall include those having flash points at or above 73°F (22.8°C) and below 100°F (37.8°C).

Combustible Liquids

Combustible liquids shall be or shall include any liquids having a flash point at or above 100°F (37.8°C). They shall be subdivided as
follows:

(a) Class II liquids shall include those having flash points at or above 100°F (37.8°C) and below 140°F (60°C).
(b) Class IIIA liquids shall include those having flash points at or above 140°F (60°C) and below 200°F (93.3°C).
(c) Class IIIB liquids shall include those having flash points at or above 200°F (93.3°C).

Minimum discharge times and application rates for sub-surface application

NOTE: The maximum application rate shall be 0.20 gpm / ft. (8.1 L/min./m).
The number of Foam Chambers required for the protection of a flammable liquid contained in a vertical cone roof
atmospheric storage tank where the discharge device is attached to the tank.

Tank Fire Calculations

Tank/ Tank Dia./ Product Foam Foam No. of Total Foam Water Water
Gantry/ Pool Dia. Solution Application pourer Foam Concentration Flow Rate Required
Pump Application Time (Minimum) Solution Required (@ for Foam
(Liters)
House Rate (Min.) (Nos.) Required 3% Foam) (LPM)
(LPM/m2) (LPM) (Liters)
Foam Calculation for Pool Fire

Tank/ Tank Dia./ Product Foam Foam - - Total Foam Water


Gantry/ Pool Dia. Solution Application Foam Concentration Flow Rate
Pump Application Time Solution Required (@ for Foam
House Rate (Min.) Required 3% Foam) (LPM)
(LPM/m2) (LPM) (Liters)
Foam Calculation for Supplementary Requirements

The number of SUPPLEMENTARY hose streams required for various size tanks. Each hose stream must be capable of a minimum
flow rate of 50 gpm of foam solution.

The minimum operating time of the supplementary hose stream(s) for various size tanks.

No. Of Minimum Foam Water Water


hose operating solution Requirement Required
stream time of requirement
(Liters)
required hose/monitor (usgpm)
@50 gpm (min.)/(hour)
(no.)
Adjacent Tank Cooling Requirements

The area of the adjacent tank used in the water provision calculation is as follows:

(Shell Area x 0.25) + (Roof Area x 0.4) m2

Shell Area = 2 x pi x radius x height

Roof Area = 2 x pi x (radius)2

Adjacent tank = T – 302

Shell Area = x 0.25 = m2

Roof Area = x 0.4 = m2

Total Area = m2

Adjacent Minimum Total Water Application Water


Tank application Rate Time Required
Area Rate (LPM) (Min.) (Liters)
(m2) (LPM/m2)
Total Water Required (Liters)

Total USGPM

LPM of Tank fire + LPM of Supplementary water + LPM of Adjacent tank fire water