ANNEXURE VIII (1/10)

A. Generator data to be filled in the format given below


depending type of generator along with following data:
1. Generator capability curve.
2. Make of Generator.
3. Generator type: Gas/Steam/Hydro.
4. Machine MVA rating and p.u Source impedance on MVA Base.
5. Generator Transformer Details: Rating, %impedance, No of taps
Nominal tap, present tap etc
6. Contact person phone number in case of any clarification regarding
data
7. Generator Data to be filled:
a. Round Rotor Generator Model:

Note:Xd, Xq, X’d, X’q, X"d, X"q, X1, H, and D are in pu on machine MVA base.
ANNEXURE VIII (2/10)

b. Salient Pole Generator Model:

Note: Xd, Xq, X’d, X"d, X"q, X1, H, and D are in pu on machine MVA base.

Xd- Direct Axis Positive phase Sequence Synchronous Reactance


Xq- Quadrature Axis Positive phase Sequence Synchronous Reactance
X’d- Direct Axis Transient Reactance(unsaturated)
X’q- Quadrature Axis Transient Reactance(unsaturated)
X’d- Direct Axis Sub-Transient Reactance(unsaturated)
X’q- Quadrature Axis Sub-Transient Reactance
T’do –Direct axis transient open circuit time constant (Secs)
T’qo –Quadraturet axis transient open circuit time constant (Secs)
T”do –Direct axis Subtransient open circuit time constant (Secs)
T”qo –Quadrature axis Subtransient open circuit time constant (Secs)
H- Inertia of complete turbogenerator(MWs/MVA)
s- saturation factor
B. Excitation system:
Data for the type of excitation system in the generator along with block
diagram to be given. 2 Nos. Sample data/Block diagrams are given for IEEE type2
and simple model.
a. IEEE Type 2 Excitation System:

Note: for E1, SE(E1),E2, SE(E2) – Excitation curve i.e) Efd Vs If curve is required
b. Simple exciter model:

Set CSWITCH = 0 for bus fed. Set CSWITCH = 1 for solid fed.
Set CON (J+7) = 0 for exciter with negative field current capability.
Set CON (J+7) > 0 for exciter without negative field current capability. (Typical CON (J+7) = 10.)
C. Governor Data:
a. Hydro Turbine-Governor:
b. Steam Turbine-Governor:

Note: VMAX, VMIN, Dt are in per unit on generator base.


T2/T3 = high-pressure fraction.
T3 = reheater time constant.
c. Gas Turbine-Governor:
D. Power System Stabilizer Model(PSS):
ANNEXURE VIII (9/10)

E. HVDC Model:
a. DC Line Model:
ANNEXURE VIII (10/10)

b. DC Line auxiliary signal Model: