Location
Company: AIR LIQUID Country:
Station: Tablero 13.8 Feeder:
Phase: IEC-ID:
CT Nameplate
Manufacturer: tab.13.8-unit-03-ta1 Tap:
Type: Core Number:
Serial Number: Optional 1:
Equipment
Test Device: CT-Analyzer Software Version: 4.40 (14-06-24 09:36)
Serial Number: MB169K Hardware Version: 01/01/08/05/00/11
Test Settings:
Rated burdens < 1VA: Enable
Primary Current I-pn: 2000.0A Nominal Burden: 30.0VA ?* cos φ: 0.8
Secondary Current I-sn: 5.0A Operating Burden: 30.0VA ? cos φ: 0.8 ?
Frequency: 60.0Hz
ALF: -1.0
Resistance
Secondary Winding:
R-meas: 147.8mΩ T-meas: 25.0°C
R-ref: 176.2mΩ T-ref: 75.0°C
Ratio:
1.0 5.0
VA / cos φ 10 % 20 % 50 % 100 % 120 % 200 %
% %
100%
30.00 / 0.8 897 898 899 899 ! 899 ! 899 (Failed) ! 899 ! 899
Nom.Burden
50%
15.00 / 0.8 898 899 899 899 ! 899 ! 899 ! 899 ! 900
Nom.Burden
25%
7.50 / 0.8 898 899 899 899 900 ! 900 ! 900 ! 900
Nom.Burden
12.5%
3.75 / 1.0 899 900 900 900 900 ! 900 ! 900 ! 900
Nom.Burden
1.0 5.0
VA / cos φ 10 % 20 % 50 % 100 % 120 % 200 %
% %
100%
30.00 / 0.8 3.29 0.97 0.60 0.34 ! 0.09 ! -0.35 ! -0.45 ! -0.52
Nom.Burden
50%
15.00 / 0.8 3.37 1.06 0.68 0.46 ! 0.27 ! 0.12 ! 0.06 ! -0.13
Nom.Burden
25%
7.50 / 0.8 3.53 1.14 0.74 0.51 0.34 ! 0.26 ! 0.25 ! 0.13
Nom.Burden
12.5%
3.75 / 1.0 4.88 1.85 1.32 0.98 0.71 ! 0.58 ! 0.56 ! 0.48
Nom.Burden
NOTE: Measurements with '!' have reduced accuracy. Accuracy only guaranteed on non-
gapped cores.
Excitation:
Knee Points:
Standard V I
Results: