Ethanol 1 Product Stored Any other tank 2 Flash Point in o C 16.6 3 Product Classification Class A 4 Type of Product Petroleum Product 5 Tank Type Fixed Roof Tanks 6 Diameter (D) in m 13 7 Height in m 11 8 Volume in m3 1460 9 Maximum allowed volume in one dyke in m3 60000 10 From Storage Tanks Class-A 11 To Storage Tanks Class-A Table-1A: 12 Separate dyke required No 13 Average Inside grade level ( G ) in m 0.3 14 Freeboard in dyke height in m 0.2 15 Distance from Tank shell to dyke wall ( C ) in m 12.5 16 Dyke Height Required in m 1.31 17 Height of the dyke wall (F) in m 2.00 Separation distances between the nearest tanks 18 30.00 located in separate dykes ( E ) in m 19 Overall Width of Dyke wall (A) in m 68(2tanks), 111.5(3tanks) 20 Overall length of Dyke wall (B) in m 38.00