STRUCTURAL CALCULATIONS FOR GROUND FLOOR CURTAIN WALL

CITY LAND MALL


DUBAI, UAE,

Email us on interna.archi.systems@gmail.com
1
International Architectural Systems Fze
INTRODUCTION:
The following report contains the Structural Calculations for the Curtain Wall for
Ground Floor to 13.7 m Height for City Land Mall , Dubai, UAE . This structural
calculation is assessed as per BS 5950: Part 1:2000. (Structural use of Steel) with
required support paper at latest of this report. Referring to Drawing Number AVIC-CLM-
ME-SD-AL-SEC-904 , Section B-B , is the Most Critical of all types of Curtain Walls. Hence
forth this following designs will be typical for All types of Curtain walls.

GLASS DETAILS :
It consists of 6 mm outer glass + 12 mm air space + 6 mm inner pane.

DEFLECTION

Maximum deflection of framing members in direction normal to wall plane is limited to


1/175 of clear span as per AAMA TIR A11 04 upto height 4110 mm

Deflection Criteria

For Span 4110 mm = 1/175

For Span > 4110 mm but < 12 m = 1/240 + 6.35 mm

Email us on interna.archi.systems@gmail.com
2
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
3
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
4
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
5
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
6
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
7
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
8
International Architectural Systems Fze
ALUMINIUM PROPERTIES:
Density = 2710 kg/m3
Modulus of elasticity = 70000 N/mm2
Modulus of rigidity = 26600 N/mm2

LOAD COMBINATION ( BS 8118: Part 1:1991)

WIND LOAD FROM LEVEL TO HEIGHT 14.80 M (CURTAIN WALL LEVEL)


BS 6399-2:1997 was a technical revision of CP3: Chapter V: Part 2 (now

Withdrawn) which incorporated the considerable advances made and experience

Gained in wind engineering since that time. The design wind load is assessed as per

BS: 6399: Part 2:1997, by standard method.

Basic wind speed(Vg) = 45 m/sec


(3 sec gust)

Email us on interna.archi.systems@gmail.com
9
International Architectural Systems Fze
(As per the Dubai Muncipality)

The basic 3 sec wind speed is converted to mean hourly wind speed.

Basic wind speed = 45 m/sec


(3 sec gust)

Considering a Distance of 10 km from Sea(Country)


Terrain Building factor at 14 m height (CW Level) (Sb)
(Interpolation) =1.82

Hourly Wind Speed (Vb) =24.72 m/s

Email us on interna.archi.systems@gmail.com
10
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
11
International Architectural Systems Fze
Maximum Wind load is 1.325 kpa

Critical Design ( 1.5 m W and 14.10 H m)

Design wind load = 1.325 kN/m2

Mullion spacing (maximum) = 1500 mm

Intensity of wind load / m length = 1.325 x 1.50 m

= 1.9875 kN/m

DESIGN CRITERIA:

• Design Wind Pressure for = 1.325 kN/m2

Email us on interna.archi.systems@gmail.com
12
International Architectural Systems Fze
200 X100X5 MM PROFILE PROPERTIES :
z

Steel Grade S 275


Geometric properties of the cross-section
Parameter Value
A Sectional area 28.3546 cm^2
Av,y Conventional shearing area along Y-axis 6.4118 cm^2
Av,z Conventional shearing area along Z-axis 17.9751 cm^2
a Angle between Y-Z and U-V axes 0 deg
Iy Moment of inertia about axis parallel to Y passing 1459.1075 cm^4
through centroid
Iz Moment of inertia about axis parallel to Z passing 496.9005 cm^4
through centroid
It Torsional moment of inertia (St. Venant) 1208.7942 cm^4
Iw Warping constant 2533.8655 cm^6
iy Radius of gyration about axis parallel to Y passing 7.1735 cm
through centroid
iz Radius of gyration about axis parallel to Z passing 4.1862 cm
through centroid
Wu+ Elastic modulus about U-axis (+ve extreme) 145.9108 cm^3
Wu- Elastic modulus about U-axis (-ve extreme) 145.9108 cm^3
Wv+ Elastic modulus about V-axis (+ve extreme) 99.3801 cm^3
Wv- Elastic modulus about V-axis (-ve extreme) 99.3801 cm^3
Wpl,u Plastic modulus about axis parallel to U-axis 181.3573 cm^3
Wpl,v Plastic modulus about axis parallel to V-axis 112.0841 cm^3
Iu Moment of inertia about U-axis 1459.1075 cm^4
Iv Moment of inertia about V-axis 496.9005 cm^4
iu Radius of gyration about U-axis 7.1735 cm
iv Radius of gyration about V-axis 4.1862 cm
au+ Centroid to edge of compression zone along +ve U- 3.5049 cm
axis
au- Centroid to edge of compression zone along -ve U- 3.5049 cm
axis
av+ Centroid to edge of compression zone along +ve V- 5.1459 cm
axis
av- Centroid to edge of compression zone along -ve V- 5.1459 cm
axis

Email us on interna.archi.systems@gmail.com
13
International Architectural Systems Fze
yM Distance to centroid along Y-axis 0 cm
zM Distance to centroid along Z-axis 0 cm
Sw Sectorial static moment 0 cm^4
Yb Distance to shear centre along Y-axis -0 cm
Zb Distance to shear centre along Z-axis -0 cm
P Perimeter 113.4232 cm
Pi Internal perimeter 55.1411 cm
Pe External perimeter 58.2822 cm
I1 Moment of inertia about Y-axis 4890.0196 cm^4
I2 Moment of inertia about Z-axis 1354.6285 cm^4
I12 Product of inertia about the centroid 1715.456 cm^4
Ip Polar moment of inertia about centroid 1956.008 cm^4
ip Polar radius of gyration about centroid 8.3056 cm
Wp Polar elastic modulus about centroid 180.2997 cm^3
yp Distance to equal area axis along Y-axis 0 cm
zp Distance to equal area axis along Z-axis 0 cm
up Distance to equal area axis along U-axis 0 cm
vp Distance to equal area axis along V-axis 0 cm

Overall dimensions 100x200x5 mm

Moment of inertia of Steel Profile 1459 cm4


Elastic Modulus of Steel Profile 145.9 cm3
Plastic Modulus of Steel Profile 181.3 cm3

Email us on interna.archi.systems@gmail.com
14
International Architectural Systems Fze
STAAD INPUT / OUTPUT
GEOMETRY

Curtain Wall Supports

Email us on interna.archi.systems@gmail.com
15
International Architectural Systems Fze
LOADINGS

1.9875 kN/m UDL

Email us on interna.archi.systems@gmail.com
16
International Architectural Systems Fze
DEFLECTION

Maximum Displacement =37.473 mm (SLS) (1.0DL+1.0WL )

Allowable deflection = L/240 + 6.35 mm

= 11800/240 + 6.35 mm
= 55.51 mm

Actual deflection = 37.473 mm (SLS) (1.0DL+1.0WL )

= 37.473 mm < 55.51 mm.

O.K !

Email us on interna.archi.systems@gmail.com
17
International Architectural Systems Fze
BENDING MOMENT

Maximum Bending Moment 35 kNm ( ULS) (1.4DL+1.4WL )

Email us on interna.archi.systems@gmail.com
18
International Architectural Systems Fze
SUPPORT REACTIONS

Maximum Factored Staad Reactions.

Email us on interna.archi.systems@gmail.com
19
International Architectural Systems Fze
Maximum Unfactored Staad Reactions.

BOTTOM CONNECTION
DESIGN OF ANCHOR BOLTS

4 NOS HIT-HY 200-A + HIT-V (8.8) M20 ,Base Plate Thickness 20 mm.

Email us on interna.archi.systems@gmail.com
20
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
21
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
22
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
23
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
24
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
25
International Architectural Systems Fze
TOP CONNECTION

Email us on interna.archi.systems@gmail.com
26
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
27
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
28
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
29
International Architectural Systems Fze
UNITY CHECK OF STEEL MULLION :

STAAD.Pro CODE CHECKING - (BSI )


***********************

PROGRAM CODE REVISION V2.13_5950-1_2000


STAAD PLANE -- PAGE NO. 3

ALL UNITS ARE - KN METE (UNLESS OTHERWISE Noted)

MEMBER TABLE RESULT/ CRITICAL COND/ RATIO/ LOADING/


FX MY MZ LOCATION
=======================================================================

1 ST TUB2001005.0 PASS ANNEX I.1 0.712 5


4.23 C 0.00 35.06 -
2 ST TUB2001005.0 PASS ANNEX I.1 0.526 5
0.59 C 0.00 26.73 -

************** END OF TABULATED RESULT OF DESIGN **************

Email us on interna.archi.systems@gmail.com
30
International Architectural Systems Fze
DESIGN OF INTERMEDIATE CONNECTION :

To be Designed by the Others .

Email us on interna.archi.systems@gmail.com
31
International Architectural Systems Fze
STAAD INPUT / OUTPUT
PAGE NO. 1

****************************************************
* *
* STAAD.Pro V8i SELECTseries6 *
* Version 20.07.11.90 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= APR 15, 2019 *
* Time= 13:16: 8 *
* *
* USER ID: *
****************************************************

1. STAAD PLANE
INPUT FILE: C:\Users\Admin\Desktop\farook\city land mall\Final
Calculations\Structure1.STD
2. START JOB INFORMATION
3. ENGINEER DATE 28-FEB-19
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KN
7. JOINT COORDINATES
8. 1 0 0 0; 2 0 13.7 0; 3 0 11.8 0
9. MEMBER INCIDENCES
10. 1 1 3; 2 3 2
11. DEFINE MATERIAL START
12. ISOTROPIC STEEL
13. E 2.05E+008
14. POISSON 0.3
15. DENSITY 76.8195
16. ALPHA 1.2E-005
17. DAMP 0.03
18. TYPE STEEL
19. STRENGTH FY 253200 FU 407800 RY 1.5 RT 1.2
20. ISOTROPIC ALUMINUM
21. E 6.89476E+007
22. POISSON 0.33
23. DENSITY 26.6018
24. ALPHA 2.3E-005
25. DAMP 0.03
26. ISOTROPIC CONCRETE
27. E 2.17185E+007
28. POISSON 0.17
29. DENSITY 23.5616
30. ALPHA 1E-005
31. DAMP 0.05
32. TYPE CONCRETE
33. STRENGTH FCU 27579
34. END DEFINE MATERIAL
35. UNIT MMS KN
36. MEMBER PROPERTY BRITISH
37. 1 2 TABLE ST TUB2001005.0
38. UNIT METER KN
STAAD PLANE -- PAGE NO. 2

39. CONSTANTS
40. MATERIAL STEEL ALL
41. SUPPORTS

Email us on interna.archi.systems@gmail.com
32
International Architectural Systems Fze
42. 2 3 FIXED BUT FY MX MY MZ
43. 1 FIXED
44. LOAD 1 LOADTYPE DEAD TITLE DEAD
45. SELFWEIGHT Y -1 LIST ALL
46. LOAD 2 LOADTYPE WIND TITLE WIND ( 1.325 KPA X 1.5 M =1.9875 KN/M)
47. MEMBER LOAD
48. 1 2 UNI GX 1.9875
49. LOAD COMB 3 DL+LL
50. 1 1.0 2 1.0
51. LOAD COMB 4 GENERATED BRITISH BS 5950 1
52. 1 1.4
53. LOAD COMB 5 GENERATED BRITISH BS 5950 2
54. 1 1.4 2 1.4
55. LOAD COMB 6 GENERATED BRITISH BS 5950 3
56. 1 1.2 2 1.2
57. PERFORM ANALYSIS

P R O B L E M S T A T I S T I C S
-----------------------------------

NUMBER OF JOINTS 3 NUMBER OF MEMBERS 2


NUMBER OF PLATES 0 NUMBER OF SOLIDS 0
NUMBER OF SURFACES 0 NUMBER OF SUPPORTS 3

SOLVER USED IS THE OUT-OF-CORE BASIC SOLVER

ORIGINAL/FINAL BAND-WIDTH= 2/ 2/ 4 DOF


TOTAL PRIMARY LOAD CASES = 2, TOTAL DEGREES OF FREEDOM = 4
TOTAL LOAD COMBINATION CASES = 4 SO FAR.
SIZE OF STIFFNESS MATRIX = 1 DOUBLE KILO-WORDS
REQRD/AVAIL. DISK SPACE = 12.0/1678587.4 MB

58. PARAMETER 1
59. CODE BS5950
60. CHECK CODE ALL

STAAD.Pro CODE CHECKING - (BSI )


***********************

PROGRAM CODE REVISION V2.13_5950-1_2000


STAAD PLANE -- PAGE NO. 3

ALL UNITS ARE - KN METE (UNLESS OTHERWISE Noted)

MEMBER TABLE RESULT/ CRITICAL COND/ RATIO/ LOADING/


FX MY MZ LOCATION
=======================================================================

1 ST TUB2001005.0 PASS ANNEX I.1 0.712 5


4.23 C 0.00 35.06 -
2 ST TUB2001005.0 PASS ANNEX I.1 0.526 5
0.59 C 0.00 26.73 -

Email us on interna.archi.systems@gmail.com
33
International Architectural Systems Fze
************** END OF TABULATED RESULT OF DESIGN **************

61. FINISH

*********** END OF THE STAAD.Pro RUN ***********

**** DATE= APR 15,2019 TIME= 13:16: 8 ****

STAAD PLANE -- PAGE NO. 4

************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2016 Bentley Systems, Inc. *
* http://www.bentley.com *
************************************************************

Email us on interna.archi.systems@gmail.com
34
International Architectural Systems Fze
Adequacy Of Glass Thickness
(AS PER ASTM E 1300 – 2002)

Introduction:

This report given structural calculation of glass


thickness for City Land Mall , as per (ASTM E 1300 –
2002) according wind load calculations done by
International Architectural Systems.
This analysis were done with the aid of software

SAFLEX programmer for determining of glass size


and thickness in conjuction with ASTM E 1300 code of
practice, Glass selection calculations ensuring the
adequacy of glass thickness so that not more than 8
glass units per thousand breaks during the building
life.

The typical Curtain Wall consists of 24 mm Double Glazed Vision Panel

(For Stick Curtain Wall)

Outer Frame -6 mm Thick Tempered,

Air Space 12mm.

Inner Pane: 6mm Thick Tempered.

The glass unit is supported on 2 nos. setting blocks as shown.

Email us on interna.archi.systems@gmail.com
35
International Architectural Systems Fze
2700 mm (MAX)

P P

a a
325
L=1500

Design wind load considered = 1.325 kpa (Hot Spot Zone)

Simplified glass panel size = 1500 x 2700 mm

Deflection:
Maximum Allowable deflection = 25 mm
(From output window below)

Email us on interna.archi.systems@gmail.com
36
International Architectural Systems Fze
Permissible deflection = (short side length) / 50, limited to 25 mm
= 1300 / 50 , limited to 25 mm
= 30 mm, limited to 25 mm

= 25 mm > 17 mm (O.K.)

The glass thicknesses are sufficient to withstand design wind load.

Email us on interna.archi.systems@gmail.com
37
International Architectural Systems Fze
CONCLUSION
The above calculation holds good for All types Curtain wall at Ground Floor
Level for 1.325 kpa.

Email us on interna.archi.systems@gmail.com
38
International Architectural Systems Fze
Reply to Consultant Comments

1) Dead Load of Glass Not Shown :

WEIGHT OF GLAZING UNIT

Weight of glass = 45 x 1.50 x 13.70


= 924.75 kg
(6 + 12 + 6 mm) DGU @ 45 kg/m2
(1500x 13700 mm)
Total (P) = 924.75 kg = 9.068 kN

Email us on interna.archi.systems@gmail.com
39
International Architectural Systems Fze
SUPPORT REACTIONS

Maximum Factored Staad Reactions.

Email us on interna.archi.systems@gmail.com
40
International Architectural Systems Fze
Maximum Unfactored Staad Reactions.

BOTTOM CONNECTION
DESIGN OF ANCHOR BOLTS

4 NOS HIT-HY 200-A + HIT-V (8.8) M20 ,Base Plate Thickness 20 mm.

Email us on interna.archi.systems@gmail.com
41
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
42
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
43
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
44
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
45
International Architectural Systems Fze
Email us on interna.archi.systems@gmail.com
46
International Architectural Systems Fze
2) Deflecton of Mullion Comparing to Glass is too much use L/360.

Maximum deflection of framing members in direction normal to wall plane is limited to


1/175 of clear span as per AAMA TIR A11 04 upto height 4110 mm

Deflection Criteria

For Span 4110 mm = 1/175

For Span > 4110 mm but < 12 m = 1/240 + 6.35 mm

We are using AAMA TIR A11 04 , Since Height of Mullion Curtain Wall is more than 4110
mm and is 13700 mm in Height .
We have used this deflection Criteria for Many Projects Including Abu dhabhi Airport
Mid Field Terminal.
Using L/360 would be a Overdesign and section would be atlest Half meter in depth ,
which is Overdesign and unnecessary.

3) Staad file and Sketch to be Provided

The Staad Files and Drawings will be sent with this report.

Email us on interna.archi.systems@gmail.com
47