D.A.

Steam Load Calculator

Boiler H.P. 200 BHP


13.8
City Water Make Up 45% MU
6.21
DA Operating Temp 227 deg F
City Water Make Up Temperature 55 deg F
172
534.06
55.00%
Condensate Return Temperature 180
47
7.59
178.365
Total Steam Required to Operate D.A. 712 #/HR

Tank Size Calculator


3.14
Diameter of Tank (in Inches) 32 16 803.84
Length of Tank (in Inches) 60 48230.4
27.9111111111 1728
Full Capacity of Tank 208.80 Gallons 7.481

Feed Tank Calculator

Boiler H.P. 250 BHP


Feed Tank Size Recommendation 258.75 Gallons
Conversion Factors

Deg C 2 to 35.60 Deg F


Deg F 70 to 21.1 Deg C
Gallons of Water 100 to 834.50 Lbs of Water
Boiler H.P. 100 to 3,349,300 Btu/hr
Boiler H.P. 150 to 5,175 Lbs Evaporation
Boiler H.P. 200 to 13.8 GPM Evaporation
Sq Ft. EDR 32 to 7,680 Btuh
Cubic Feet 50 to 374.05 Gallons
Kilograms 30 to 66.0 Lbs
Parts/million 32 to 1.87 Grains/US Gallon
CU Ft. Nat Gas 200 to 200,800 Btu/hr
KW 100 to 341,300.00 Btu/hr
Liters 350 to 92.47 Gallons
Kilograms 30 to 66.00 Pounds

Heating or Cooling Load on a Water Heat Exchanger

GPM 90 500
Supply Temperature 180 Max 212 deg F
40 Return Temperature 140 Min 32 deg F
1,800,000 Btu's