Reactive current controller
DCRM series ..................................................................................................................................................................... 23 - 6
Automatic power factor controllers
DCRK series...................................................................................................................................................................... 23 - 7
DCRG series ..................................................................................................................................................................... 23 - 8
DCRJ series ...................................................................................................................................................................... 23 - 10
Thyristors modules......................................................................................................... 23 - 11
Dimensions ................................................................................................................. 23 - 12
Wiring schemes ............................................................................................................ 23 - 13
Technical characteristics ................................................................................................. 23 - 16
E NERGY M ANAGEMENT
Automatic power factor controllers and thyristor modules
23-2
Automatic power factor controllers and thryristor modules
L1
L2
L3
Current transformers
Automatic
power factor
controllers
Fuse holders
Fuse
holders
Contactors
Switch
disconnectors
23
23-3
Automatic power factor controllers and thyristor modules
DCRG series
CUSTOMISING OPTION
There is a customising slot available on the panel front
to show controller brand name, logo, trademark, part
number, brief indication or wording, etc.
44mm
9mm
MAX
4
Basic controller functionality can be easily extended using the EXP series
Trim frame profile and reduced The fixing system with metal expansion modules:
total depth simplify installation of screws guarantees excellent - Relay outputs to increase the number of steps
the controller also in very compact adhesion over time. - Capacitor protection
electric panels. - Digital and analog inputs and outputs
- Opto-isolated static outputs
- Relay outputs
44 HIGH PROTECTION DEGREE - Opto-isolated RS232 interface
The controller front and the rear - Opto-isolated RS485 interface
seal have been designed to warrant - Opto-isolated Ethernet interface with Web server function
an IP54 protection degree. - Opto-isolated Profibus-DP interface
- GPRS/GSM modem
- Data logging and calender-clock (RTC).
23
137
144
64.5
73 9,2
EXP 10...
23-4
Automatic power factor controllers and thryristor modules
DCRG series
STREAMLINE DESIGN
The DCRG controller has an ergonomic design and, at the same time,
particular care has been given to to minimum detail aesthetics.
MASTER-SLAVE FUNCTION WEB SERVER FUNCTION GSM/GPRS MODEM SUITABLE FOR MEDIUM-VOLTAGE
The DCRG controller can control the By fitting the EXP10 15 expansion SYSTEMS
outputs of other analog controllers in module, the controller is The controllers can be installed in
addition to its own steps. In this way, automatically equipped and medium-voltage systems thanks to
it offers a master-slave architecture. configures a GSM/GPRS modem. its configuration for voltage
Up to 3 slaves can be controlled to This simplifies installation and transformer ratio, thereby obtaining
obtain a system with a total of 4 wiring. measurements with regards to the
controllers, which means 64 steps. Once a data-enabled SIM card is transformer primary value both for
inserted, alarm or event SMS, the correction adjustment and the
By installing the Ethernet expansion email messages and latest logged display readouts.
module EXP10 13, the main data can be transmitted by the
measured values of the controller controller to FTP servers.
can be viewed by most common SUITABLE FOR DYNAMIC (FAST)
Web-client compatibles, on the POWER FACTOR CORRECTION
market, using Java platform and With the EXP10 01 static output
with no need to install any 5A AND 1A BOTH ON THE SAME expansion module installed, the
additional PC software. CONTROLLER controller can be used in dynamic
By configuring an apposite power factor correction systems
Master parameter, the controller can be where the reactive load quickly
enabled for use with either a 5A or varies over time.
CAPACITOR PROTECTION 1A secondary current transformer. Also taking advantage of the built-in
By adding the apposite EXP10 16 controller relay outputs, a mixed
expansion module, the DCRG system of traditional relay and
controller can be equipped with dynamic type of correction steps
additional capacitor protection GRAPHS AND TEXT IN MULTI can be obtained.
functions. The module can measure LANGUAGES
the harmonic current values and the
capacitor temperature on-site.
Slave 1
THREE CURRENT INPUTS
- Independent power factor
correction of each step can be
done.
- Identification of capacitor failure on
any of the phases being controlled. Viewing of waveforms, text, trend
- Analysis of all electrical parameters and bar graphs in 10 languages:
of the system by a multimeter. Italian, English, Spanish, French,
German, Czech, Polish, Russian,
Slave 2 Portuguese and customisable.
23
WIDE RANGE OF RATED VOLTAGE
MEASUREMENTS
The wide measurement range
between 100 to 690VAC allows to
use the controller in most types of
applications.
Slave 3
23-5
Automatic power factor controllers and thyristor modules
Reactive current controller Order code Steps Auxiliary supply Qty Wt General characteristics
DCRM series voltage per DCRM2 allows to control the reactive current of a plant,
pkg eliminating it from the total current drawn from the
n° [V] n° [kg] mains and correcting the cos-phi of the load to the best
possible value.
Single and three-phase low-voltage system. It can control the connection of two capacitor banks
Reactive current monitoring relay. maximum. Each one of the two banks can be individually
DCRM 2 2 380-415VAC 1 0.166 enabled and its power can be set through a dedicated
potentiometer.
It is also possible to adjust the time for connection and
disconnection of the capacitor banks, thereby modifying
the reaction speed of the system.
The controller can be used both in single-phase and
three-phase wiring.
ADJUSTMENTS
“C/K Step 1” C/K ratio threshold for step 1
OFF/0.15-2
“C/K Step 2” C/K ratio threshold for step 2
OFF/0.15-2
“Connection delay” Step connection delay 1-60s
“Disconnection delay” Step disconnection delay
1-60s
“System configuration” Wiring selection for single or
three-phase system 1PH-3PH.
INDICATIONS
– 1 green LED for power on and inhibition time
– 2 red LEDs for step connection.
23
23-9
Automatic power factor controllers and thyristor modules
INDICATIONS
– Auxiliary power on
– Over temperature alarm
– Trigger LED.
Reference standards
Compliant with standards: EN 50178.
23
45 (1.77")
90 (3.54")
92 (3.62”)
96 (3.78”)
PA96X96
144 (5.67”)
PACR
DCRG 8 Cutout
138.5 (5.45”)
144 (5.67”) 44
(1.73”)
138.5 (5.45”)
137 (5.39”)
144 (5.67”)
64.5 (2.54”)
73 (2.87”) 9.2
EXP 10... (0.36”)
D
DCRJ8 - DCRJ12 - DCRJ12F Cutout
138.5 (5.45”)
15 47 (1.85”) 7.7
144 (5.67”) (0.59”) (0.30”)
23
138.5 (5.45”)
144 (5.67”)
137 (5.39”)
23-12
Automatic power factor controllers and thryistor modules
Dimensions [mm (in)]
THYRISTOR MODELES
DCTM3 400 030 - DCTM3 400 050 DCTM3 400 100
157 (6.18”) 157 (6.18”)
145 (5.71”) 145 (5.71”) 205 (8.07”)
134 (5.27”) 134 (5.27”) 135 (5.31”) 64 (2.52”)
123 (4.84”) 123 (4.84”) 2.5 (0.10”)
200 (7.87”)
200 (7.87”)
170 (6.69”)
120 (4.72”)
170 (6.69”)
120 (4.72”)
253 (9.96”)
61 (2.40”)
53 (2.09”)
83 (3.27”) 78 (3.07”)
135 (5.31”) 83 (3.27”)
5 103 (4.05”)
(0.20”)
Wiring diagrams
THYRISTOR MODELES
DCTM3 400...
MAINS
L1 L2 L3
DCTM3
L1 C1
C1
L3
- +
C3
L N
23
Fan power supply 240VAC input
(DCTM3 400 100 only)
23-13
Automatic power factor controllers and thyristor modules
Wiring diagrams
1 2 3 4 5 6 7 8 9 10 11 12
VOLTAGE 380-415V
CURRENT
/5A
0V
S1 S2 15 16 C 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CT1
FU16
QS1
FU1 FU2 FU12
FU13 FU14 FU15
IMPORTANT
a. For three-phase connection, the voltage input must be connected
KM1 KM2 KM12 between two phases only; the line current transformer must be
connected on the remaining free phase.
b. The polarify of the current input is irrelevant.
LOAD CAUTION! Always remove the power supply before operating on the
terminals.
K1 K2 K12
INPUT
CURRENT VOLTAGE
100-690VAC
0V
/5A
S1-1 S1-2 S1-3 S2 S2 11 12 L1 L2 L3 C 1 2 3 4 5 6 7 8 9 10 11 14 21 24 13 14 23 24 33 34 43 44
CT1
FU17
QS1
FU1 FU2 FU12
FU13 FU16 FU14 FU15 IIMPORTANT
a. For three-phase connection, the voltage input must be connected
KM1 KM2 KM12
between two phases only; the line current transformer must be
connected on the remaining free phase.
b. The polarify of the current input is irrelevant.
LOAD
CAUTION! Always remove the power supply before operating on the
terminals.
K1 K2 K12
CURRENT INPUT
VOLTAGE
100-690VAC TEMP. 18
/5A NTC01
0V
SENSOR 19
S1 S2 15 16 17 L1 L2 L3 C 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CT1
FU17
23 QS1
FU1 FU2 FU12
FU13 FU16 FU14 FU15
IIMPORTANT
a. For three-phase connection, the voltage input must be connected
KM1 KM2 KM12 between two phases only; the line current transformer must be
connected on the remaining free phase.
b. The polarify of the current input is irrelevant.
LOAD CAUTION! Always remove the power supply before operating on the
terminals.
K1 K2 K12
23-14
Automatic power factor controllers and thyristor modules
Technical characteristics
DCRM series - Reative current controller
TYPE DCRM 2
AUXILIARY SUPPLY CIRCUIT
Rated auxiliary voltage Us 380-415VAC (standard); 220-240VAC and 440-480VAC on request
Operating range 0.85-1.1 Us
Rated frequency 50/60Hz ±5%
Power consumption/dissipation maximum 4.4VA / 2.4W
Micro-breaking immunity ≤ 17ms
No-voltage release ≥ 8ms
VOLTAGE INPUT
Maximum rated voltage Ue 480VAC
Measurement range 80-528VAC
Frequency range 50 or 60Hz ±1% self configurable
Measurement input impedance >1MΩ
Type of connection L1-L2 or L-N
CURRENT INPUT
Type of connection By current transformer (CT)
Rated current Ie 5A~
Measurement range 0.1...6A
Type of input Shunt supplied by external current transformer (low voltage). Max. 5A
Measurement method True RMS value
Overload capacity +20% Ie
Overload peak 10In for 1s
Dynamic limit 160A for 10ms
Burden ≤ 0.6W
ADJUSTMENTS
C/K step 1 and 2 OFF / 0.15-2
Connection and disconnection time delays 1 - 60s
System configuration 3 phase or 1 phase
RELAY OUTPUTS
Number of outputs 2 each with 1 changeover contact (SPDT)
Rated operational voltage 250VAC
Maximum switching voltage 400VAC
IEC conventional free air thermal current Ith 8A
UL/CSA and IEC/EN 60947-5-1 designation B300
Electrical life (with rated load) 105 cycles
Mechanical life 30x106 cycles
CONNECTIONS
Maximum tightening torque 0.8Nm (7 lbin)
Conductor section min-max 0.2-4.0mm2 (24-12AWG)
INSULATION (input-output)
Rated insulation voltage 480VAC
AMBIENT CONDITIONS
Operating temperature –20...+60°C
Storage temperature –30...+80°C
HOUSING
Material Self-extinguishing polyamide
23
23-15
Automatic power factor controllers and thyristors modules
Technical characteristics
DCRK and DCRJ series - Power factor controllers
TYPE DCRK3 - DCRK5 - DCRK7 DCRK8 - DCRK12 DCRG8 DCRJ8 - DCRJ12 DCRJ12F
AUXILIARY SUPPLY CIRCUIT
Rated auxiliary voltage Us ∂ ∂ 100-240VAC 110-127 / 110-127 /
220-240VAC 220-240VAC
dual voltage dual voltage
Operating range –– -15 to +10%
Rated frequency –– 50Hz o 60Hz ±5%
Power consumption maximum –– 7VA 9.7VA 9.2VA
Power dissipation maximum –– 5.5W
(output contacts excluded)
VOLTAGE CIRCUIT
Control voltage 380-415VAC standard∑ 100-690VAC
(self powered)
Operating range -15 to +20% 85-760VAC
Rated voltage 50 or 60Hz ±1% self configurable
Power consumption 6.2VA 5VA 0.03VA
Power dissipation maximum 2.7W 3W ––
(output contacts excluded)
dissipatadai contatti di uscita)
Power dissipation by contact of 0,5W
one output / with 5A load at 250VAC)
Immunity time for microbreakings ≤65ms ≤45ms
No-voltage release ≥8ms
CURRENT CIRCUIT
Rated current Ie 5A (1A on request) Programmable 5A/1A 5A (1A on request)
Operating range 0.125-6A
Constant overload 1.2 Ie
Short time withstand current 10 Ie for 1s
Current consumption 0.65W 0.27VA
MEASUREMENT DATA
Type of voltage-current measurement TRMS
Power factor adjustment 0.8 inductive to 0.8 capactive
Type of temperature sensor Semiconductor (internal) Internal+PT100 w/EXP... Semiconductor (internal)+NTC01 (external)
Temperature measurement range -30...+85°C –– -40...+85°C for external
RELAY OUTPUTS
Number of outputs 3, 5 or 7 8 or 12 8 (10, 12, 14, 16 w/EXP...) 8 or 12 1
Contact arrangement 3, 5 or 7 N0 (SPST) contacts 7 or 11 NO (SPST) contacts + 1 changeover (SPDT) 1 changeover (SPDT)
IEC rated capacity 5A 250V (AC1)
Maximum capacity of common 12A
terminal of contacts
Maximum switching voltage 440VAC
UL/CSA and IEC/EN 60947-5-1 B300
designation
Electrical life (at rated load) 105 cycles
Mechanical life 30x106 cycles
STATIC OUTPUTS
Number of outputs –– 4 or 8 with EXP10 01 –– 11
Type of output –– Opto-isolated bi-direc-
tional (Opto-Mosfet)
Rated operational voltage –– 40VDC - 30VAC
Rated operational current –– 55mA at 60°C
CONNECTIONS
Type of terminal Removable/plug-in
Conductor section min-max 0.2-2.5mm2 (24-12AWG)
AMBIENT CONDITIONS
Operating temperature -20...+60°C
Storage temperature -30...+80°C
HOUSING
Version Flush mount Flush mount
23 Material Self-extinguishing Noryl Self-extinguishing LEXAN
IEC degree of protection IP54 IP41 IP54 IP41 IP41
∂ Refer to data given under voltage circuit.
∑ Other voltages on request: 220-240VAC; 415-440VAC; 440-480VAC; 480-525VAC.
23-16
Automatic power factor controllers and thyristor modules
Technical characteristics
Thyristor modules
23
23-17