DO NOT SCALE FROM THIS DRAWING


KEYPLAN
A N A

MAKKAH 1
2 3

B B

GENERAL NOTES
Electronic drawings once printed, are uncontrolled and may become out-dated. Refer to Aconex for current revision.

C 1. ALL DIMENSION ARE IN MILLIMETERS. C


2. CABLE TRAY/LADDER/TRUNCKING MATERIALS REFER TO DRAWING MAR#
M-BNR-1F8DS0-CELD-MAR-000034 TO 000036.

3. EACH RUN IS TO BE COMPLETED BEFORE INSTALLATION OF CABLES.

4. FOR SUPPORT SYSTEM, REFER TO SUPPLIER CALCULATION STUDY REPORT.

5. MAKE CONNECTION TO EQUIPMENT WITH FLANGED FITTING FASTENED TO CABLE


TRAY/LADDER AND TO EQUIPMENT. SUPPORT CABLE TRAY/LADDER INDEPENDENTLY OF
FITTING. DO NOT CARRY WEIGHT OF CABLE TRAY/LADDER ON EQUIPMENT ENCLOSURE.

6. INSTALL EXPANSION CONNECTORS WHERE CABLE TRAY/LADDER CROSSES A BUILDING


D EXPANSION JOINT AND IN CABLE TRAY/LADDER RUNS THAT EXCEED 27M MAKE CHANGES IN D
DIRECTION AND ELEVATION USING STANDARD FITTINGS.

7. MAKE CABLE TRAY/LADDER CONNECTIONS USING STANDARD FITTINGS.

8. LOCATE CABLE TRAY/LADDER ABOVE PIPING, UNLESS ACCESSIBILITY TO CABLE TRAY/LADDER


IS REQUIRED OR UNLESS OTHERWISE INDICATED.

9. SEAL PENETRATIONS THROUGH FIRE AND SMOKE BNRRIERS REFERS TO DRAWING #


ENCLOSURE (FOR CRACKNELL M-BNR-1F8DS0-CELD-SDR-000065.
INTERFACE - TOTEM POLE AND
LIGHTING WALKWAY)
400W x 400H x 200D 10. WORKSPACE : INSTALL CABLE TRAYS/LADDERS WITH SUFFICIENT SPACE TO PERMIT ACCESS
FOR INSTALLING MINIMUM CLEARANCE OF 250MM IS TO BE MAINTAINED BETWEEN TOP OF
E ENCLOSURE ( DORMA SERVICES,
TRAY/LADDER AND CEILING, BEAM AND OTHER SERVICES AND BETWEEN TRAY/LADDERS IN E
FA INTERFACES & SMALL POWER)
MULTI-TIER FORMATION.
400W x 400H x 200D
11. BARRIERS : WHERE TRAY/LADDERS CARRY CONDUCTORS OF DIFFERENT SYSTEM, SUCH AS
ELECTRICAL CHAMBER POWER, COMMUNICATION AND DATA PROCESSING, OR DIFFERENT INSULATION LEVELS, SUCH
1200W x 1200H x 1000D
AS 600V, 5000V, 45000V USE SEPARATE CABLE TRAY/LADDERS.
ø100 LV ESS
ø100 LV ESS 12. CABLE TRAYS BEND RADIUS SHALL DEPEND ON THE LARGEST DIAMETER OF SUPPORTED
ø100 LV ESS CABLES WITH MINIMUM OF 10 TIMES THE OD FOR LV CABLES.
ø100 LV ESS
ø80 UPS
ø80 SPARE 13. END PLATE FITTING SHALL BE USED FOR ALL DEAD END CABLE TRAY RUNS.
ø50 FA
ø100 LTG/SP N-ESS 14. MOUNTING HEIGHT CABLE TRAY/LADDERS AS SHOWN IN LAYOUT.
ø80 EMERG LTG
F ø50 PA/VA
ø80 DATA F
ø80 BMS
CABLE TRAY COLOR DESCRIPTION CABLE TRAY COLOR DESCRIPTION
ø100 LV N-ESS (FCU)
HH LEAKY FEEDER CABLE BMS
2700
1300

2900
3100

LV ESSENTIAL TV CONTROLS

LV NON ESSENTIAL DATA

9470 ø80 DATA (& FIRE)


ø100 LV ESS LV REL FIBER OPTIC
ø100 LV ESS
21
______ ø80 DATA (& FIRE)
1000 B02-669 040060 LTG/SP ESS TRUNKING SIGNALLING LV
ELV 1 SDR ø100 LV ESS
G ø100 LV ESS G
TIMESTAMP 11/12/2018 9:26:34 AM

ø80 LV ESS EMERGENCY LIGHTING SIGNALLING ELV


ø100 STC x 4 DUCTS FOR STC ø50 FA
INCOMING SERVICES ø100 LTG/SP N-ESS
PUBLIC ADDRESS & VOICE
00-408 ø100 SPARE UPS CABLES
2060 ENTR SW
EVACUATION
B02-673
7 ø80 UPS
SMOKE EXT 00-405
ENTR SW ø80 EMERG LTG
FIRE ALARM PLATFORM SCREEN DOORS

2900
ø50 PA/VA
22 ø80 DATA
______
040060 B02-673 ø80 BMS FIRE ALARM (AFA) CMCC
SDR SMOKE EXT

1310
COM TETRA SAUDI TELECOM

470
KK TV POWER AC REL LADDER
ø50 LTG/SP N-ESS
H ø50 LTG/SP N-ESS DC TPS LADDER MV LADDER
H
E4
E4 DUCT ENTRY POSITIONED AT 219mm
FROM BOTTOM LV TRAY (FAST-TSY) 2 COMPARTMENT TRUNKING
STC CABLE CHAMBER OF THE PIT & 835mm FROM
ESCALATOR CONNECTION
BOX AS PER THYSSEN KRUPP
REQUIREMENTS
REFERENCE DRAWINGS
E1 E2 E3
E1 E2 E3 ELECTRICAL CHAMBER
DESCRIPTION DOCUMENT NUMBER
1200W x 1200H x 1000D 1. CABLE TRAY TYPICAL INSTALLATION DETAILS SHEET 1,SHEET 2,SHEET 3,SHEET 4 M-BAR-1F8TS0-CELD-SDR-000008,000009,000010,00011
ENCLOSURE ( DORMA SERVICES, 2. ARCHITECTURAL BASE MODEL M-BNR-1F8DSO-CAOO-BIM-000002
FA INTERFACES & SMALL POWER ) 3. STRUCTURAL BASE MODEL M-BNR-1F8DSO-CBOO-BIM-000003
400W x 400H x 200D
ENCLOSURE (FOR CRACKNELL DESIGN DRAWINGS:DEEP UNDERGROUND STATION LINE 1 - STATION 1F8 ELECTRICAL
4. M-BAR-1F8DS0-CE00-EDR-040000
J INTERFACE - TOTEM POLE AND CABLE CONTAINMENT 00 GROUND SHEET 1 J
LIGHTING WALKWAY)
400W x 400H x 200D
SR.NO. MAR NO. DESCRIPTION
1 M-BAR-1F4TS0-CELD-MAR-000004 SWITCH BOARDS (DISTRIBUTION & SUB-DISTRIBUATION BOARDS)

2 M-BAR-1F4TS0-CELD-MAR-000001 MAIN DISTRIBUTION PANEL (MDB'S & EMDB'S )

3 M-BAR-1F4TS0-CELD-MAR-000007 ATS PANEL

4 M-BAR-1F4TS0-CELD-MAR-000010 MOTOR CONTROL CENTER

5 M-BAR-1F4TS0-CELD-MAR-000013 POWER FACTOR CORRECTION SYSTEM

6 M-BAR-1F4TS0-CELD-MAR-000034 CABLE TRAYS, TRUNKING, LADDERS & ACCESSORIES

7 M-BAR-1F4TS0-CELD-MAR-000037 LV WIRES & CABLES


K 8 M-BAR-1F4TS0-CELD-MAR-000040 CABLE GLANDS, LUGS AND CABLE TIES K
9 M-BAR-1F4TS0-CELD-MAR-000052 CENTRAL BATTERY SYSTEM

10 M-BAR-1F4TS0-CELD-MAR-000043 BUSDUCT / BUSWAY /BUSBAR TRUNKING SYSTEM

11 M-BAR-1F4TS0-CELD-MAR-000006 CABLE TRAYS, LADDERS & ACCESSORIES

12 M-BAR-1F4TS0-CELD-MAR-000007 CABLE TRUNKING & ACCESSORIES

REVISIONS PROJECT BACS CONSORTIUM BACS APPROVAL SCALE PAPER DRAWING TITLE
11 OCTOBER SIZE
No Date Description Drawn Checked Approved
A1 DEEP UNDERGROUND STATION
L
001 06/05/2018
002 15/07/2018
ISSUED FOR REVIEW
MODIFICATION AS PER BACS COMMENTS
ES
ES
YS
YS
IS
IS 2018 L
003 11/10/2018 MODIFICATION AS PER BACS COMMENTS ES YS IS DRAWING STATUS
LINE 1 - STATION 1F8
SHOP DRAWING ELECTRICAL
SUB-CONTRACTOR/VENDOR:
CLIENT
RIYADH METRO PROJECT This drawing has been Approved and CABLE CONTAINMENT
Certified as acceptable on behalf of the
www.bacsrmp.com BACS Consortium. 00 GROUND SHEET 4
LEAD DESIGN ENTITY (LDE) APPROVED BY LDE DRAWN BY CHECKED BY APPROVED BY DRAWING NUMBER REVISION
NAME NAME NAME NAME

M
M-BNR-1F8DS0-CELD-SDR-040004 003 M
© 2015 High Commission for the Development of ArRiyadh DATE DATE 11/10/2018 DATE DATE