CUSTOMER
INTERNATIONAL TECHPARK
PROJECT
OFFICE BUILDING
COORDINATION
TESTCOM ENGINEERS,CHENNAI,600116,MOB:9841131621
COMPILED BY
We were requested to prepare a protection co-ordination report for 33/0.415 kV Electrical substation for
the INTERNATIONAL TECH PARK, Chennai.
This report includes calculation results of the study 33/0.415 kV Switchgear.
The system data for calculation are based on the provided data by the Client .
The most important tool for documentation of over current protection co-ordination is ETAP 18.1. Typical
grading paths have been chosen in a single line and in a current/time diagram the selectivity of the
characteristic curves of the devices are shown.
The single line diagrams, and documents as listed in the report were used as data input for this network
calculation study.
3 Infeed Data
In the absense of exact short circuit data of utility ,minimum Short-circuit power 3-phase @ Battery limit is
taken as 750 MVA sec at 33 kV min and 1500MVA sec at 33kV max.
4 Protection Coordination
The short circuit currents at various busbars are calculated based on the above assumptions.Short circuit
currents calculated for each of the bus bar, and are tabulated in the report.
Based on the short circuit calculations protection coordination study was carried out for this Project
Selectivity of relays have been worked out for the 33kV Switchboard.Timing gradation of 150 milliseconds
have assumed while selecting TMS values for the relays.The Time current characteristic curves are prepared
both for phase faults and Ground faults and given in the Report.
5 Conclusion
The selectivity of the protection settings for characteristic feeders was verified with the protection grading
diagrams prepared with software ETAP18.1. Generally, attention was given to provide the largest possible
safety clearance between the individual protective devices.
Reference Documents / Drawings-
Sl.No Drawing Title File reference Drawing No
1 SINGLE LINE DIAGRAM MAIN POWER CONTROL CENTRE Pin SLD_ORIG.DWG ETA-3144-E-EL-01 REV3
TNEB S1 TNEB S2
750 MVAsc 750 MVAsc
Bus1
BD:DG1 BD:DG2 BD:DG3 BD:DG4 BD:DG5 BD:DG6
2000 A 2000 A 2000 A 2000 A 2000 A 2000 A
±
I> R:RMG_OG
RMG_OG ±
I> ±
±
I> ±
I> ± ±
I>
R:DG1 I> I>
R:DG2
C:RMG R:DG3 R:DG61
DG1_IC DG2_IC DG3_IC DG4_IC R:DG4 DG5_IC R:DG5 DG6_IC
1-3/C 300
DG SYNC PNL SEC1
SYNC PNL BC1 SYNC PNL BC2
DG SYNC PNL SEC2 DG SYNC PNL SEC 3
33kV_IC
I> R:33kV_IC
33kV HT 4 Panel Board
4000 A
BusDuct1 4000 A
BusDuc2 4000 A
BusDuct3
OG:SP1
OG:RM-6 OG:LSB-GF OG:CAP3 OG:CHILLER 6 OG:RM-4 OG:RM-2 OG:RM-8 OG:AC PUMP 1 OG:SUB SB1 OG:SP2 OG:FOOD COURT OG:PSB GF OG:CAP 2 OG:CHILLER 7 OG:CHILLER 1 OG:CHILLER 2 OG:CHILLER 5 OG:RM-7 OG:CHILLER3 OG:RM-3 OG:CAP1 OG:RM-1 OG:AC PUMP 2 OG:PSB1 GF
OG:CHILLER4 OG:SUB SB2 OG:LSB GF OG:RM-5 OG:FIRE PUMP
C:CAP1
C:CHILLER 7 C:CHILLER1 C:CHILLER 2 C:CHILLER 5 C:SUB SB2 C:RM-7 C:CHILLER 3 C:RM 3 2-3/C 300 C:RM-1 C:LSB GF C:AC PUMP 2 C:RM 5 C:FIRE PUMP C:PSB1 GF
1-3/C 300 2-3/C 300 1-3/C 300 2-3/C 300 1-3/C 240 2-3/C 300 2-3/C 185 2-3/C 300 2-3/C 300 2-3/C 185 1-3/C 240 1-3/C 300 2-3/C 185 2-3/C 185
C:RM-6 C:LSB-GF C:CAP3 C:CHILLER 6 C:RM-4 C:RM-2 C:RM-8 C:AC PUMP1 C:SUB SB1 C:FOOD COURT C:PSB GF C:CAP 2
C:CHILLER 4
2-3/C 300 2-3/C 185 2-3/C 300 1-3/C 300 2-3/C 300 2-3/C 300 2-3/C 300 1-3/C 240 2-3/C 300 2-3/C 185 2-3/C 185 2-3/C 300
1-3/C 300
SUB SB2_IC
CAP3_IC RM2_IC CHILLER 4_IC SUB SB1_IC RM7_IC RM5_IC
RM6_IC CHILLER 6_IC RM4_IC RM8_IC CAP2_IC CHILLER 7_IC CHILLER 5_IC CHILLER 3_IC RM3_IC CAP1_IC RM1_IC
CHILLER 1_IC CHILLER 2_IC
RM-6 LSB-GF CHILLER 6 RM-4 RM-2 CHILLER 4 RM-8 AC PUMP 1 SUB SB1 FOOD COURT PSB GF CHILLER 7 CHILLER 1 CHILLER 2 CHILLER 5 SUB SB2 RM-7 CHILLER 3 RM 3 RM-1 LSB GF AC PUMP 2 RM 5 FIRE PUMP PSB1 GF
CAP3 CAP 2 CAP1
792 kVA 140 kVA 420 kVA 815 kVA 775 kVA 420 kVA 716 kVA 110 kVA 276 kVA 204 kVA 90 kVA 420 kVA 420 kVA 420 kVA 420 kVA 479 kVA 716 kVA 420 kVA 811 kVA 775 kVA 145 kVA 113 kVA 795 kVA 161 kVA 90 kVA
6x100 kvar 6x100 kvar 6x100 kvar
Device Details
2 Winding transformers
Sl.No Device Name Device ID Rating Primary voltage Secondary Voltage Primary Winding Secondary Winding Vector Group Percentage of Type of Cooling Tap arrangement
Impedance
1 Transformer 1 TR1 2500 kVA 33000 V 433V Delta Star Dyn11 6.25% OIL Cooled -5% to+5%
2 Transformer 2 TR2 2500 kVA 33000 V 433V Delta Star Dyn11 6.25% OIL Cooled -5% to+5%
3 Transformer 3 TR3 2500 kVA 33000 V 433V Delta Star Dyn11 6.25% OIL Cooled -5% to+5%
33kV HT 4 Panel Board 33.000 26.248 67.414 26.196 26.208 67.311 26.208 26.208 22.732 58.383 22.732 22.732 26.232 67.372 26.232 26.232
Bus1 33.000 26.295 67.733 26.243 26.278 67.688 26.278 26.278 22.772 58.658 22.772 22.772 26.292 67.724 26.292 26.292
TR2_HV 33.000 26.201 67.099 26.149 26.138 66.937 26.138 26.138 22.691 58.109 22.691 22.691 26.182 67.050 26.182 26.182
TR3_HV 33.000 26.201 67.098 26.149 26.138 66.937 26.138 26.138 22.691 58.108 22.691 22.691 26.182 67.049 26.182 26.182
TR1_HV 33.000 26.201 67.098 26.149 26.138 66.937 26.138 26.138 22.691 58.108 22.691 22.691 26.182 67.049 26.182 26.182
MPCC_ SEC3 0.415 53.358 119.788 53.355 53.444 119.979 53.444 53.444 46.210 103.739 46.210 46.210 54.049 121.339 54.049 54.049
MPCC_SEC1 0.415 53.358 119.788 53.355 53.444 119.979 53.444 53.444 46.210 103.739 46.210 46.210 54.049 121.339 54.049 54.049
MPCC_SEC2 0.415 57.392 127.245 53.355 56.067 124.307 56.067 56.067 49.703 110.197 49.703 49.703 57.148 126.704 57.148 57.148
AC PUMP 1 0.415 21.324 32.125 21.324 14.674 22.107 14.674 14.674 18.467 27.821 18.467 18.467 20.468 30.835 20.468 20.468
AC PUMP 2 0.415 21.324 32.125 21.324 14.674 22.107 14.674 14.674 18.467 27.821 18.467 18.467 20.468 30.835 20.468 20.468
CAP1 0.415 33.623 55.985 33.623 26.547 44.202 26.547 26.547 29.119 48.484 29.119 29.119 33.566 55.889 33.566 33.566
CAP 2 0.415 34.923 57.503 33.623 27.013 44.478 27.013 27.013 30.244 49.799 30.244 30.244 34.495 56.797 34.495 34.495
CAP3 0.415 33.623 55.985 33.623 26.547 44.202 26.547 26.547 29.119 48.484 29.119 29.119 33.566 55.889 33.566 33.566
CHILLER1 0.415 14.566 21.653 14.391 9.534 14.172 9.534 9.534 12.615 18.752 12.615 12.615 13.680 20.336 13.680 13.680
CHILLER 2 0.415 24.063 37.057 23.514 16.898 26.023 16.898 16.898 20.840 32.092 20.840 20.840 23.116 35.598 23.116 23.116
CHILLER 3 0.415 29.043 44.599 29.042 21.141 32.465 21.141 21.141 25.152 38.624 25.152 25.152 28.519 43.795 28.519 28.519
CHILLER 4 0.415 23.514 36.439 23.514 16.744 25.947 16.744 16.744 20.364 31.557 20.364 20.364 22.749 35.253 22.749 22.749
CHILLER 5 0.415 14.566 21.653 14.391 9.534 14.172 9.534 9.534 12.615 18.752 12.615 12.615 13.680 20.336 13.680 13.680
CHILLER 6 0.415 23.514 36.439 23.514 16.744 25.947 16.744 16.744 20.364 31.557 20.364 20.364 22.749 35.253 22.749 22.749
CHILLER 7 0.415 26.522 41.923 23.514 17.719 28.009 17.719 17.719 22.969 36.307 22.969 22.969 25.486 40.287 25.486 25.486
Short-Circuit Summary Report
3-Phase, LG, LL, LLG Fault Currents in KA
FIRE PUMP 0.415 10.571 15.327 10.571 6.602 9.573 6.602 6.602 9.155 13.274 9.155 9.155 9.815 14.231 9.815 9.815
FOOD COURT 0.415 30.933 47.725 29.042 21.770 33.588 21.770 21.770 26.788 41.331 26.788 26.788 30.144 46.507 30.144 30.144
LSB-GF 0.415 29.043 44.599 29.042 21.141 32.465 21.141 21.141 25.152 38.624 25.152 25.152 28.519 43.795 28.519 28.519
PSB GF 0.415 29.860 45.521 29.042 21.370 32.579 21.370 21.370 25.859 39.422 25.859 25.859 29.058 44.299 29.058 29.058
PSB1 GF 0.415 29.043 44.599 29.042 21.141 32.465 21.141 21.141 25.152 38.624 25.152 25.152 28.519 43.795 28.519 28.519
RM-1 0.415 14.391 21.450 14.391 9.491 14.147 9.491 9.491 12.463 18.576 12.463 12.463 13.571 20.228 13.571 13.571
RM-2 0.415 14.391 21.450 14.391 9.491 14.147 9.491 9.491 12.463 18.576 12.463 12.463 13.571 20.228 13.571 13.571
RM 3 0.415 33.623 55.985 33.623 26.547 44.202 26.547 26.547 29.119 48.484 29.119 29.119 33.566 55.889 33.566 33.566
RM4 0.415 14.391 21.450 14.391 9.491 14.147 9.491 9.491 12.463 18.576 12.463 12.463 13.571 20.228 13.571 13.571
RM 5 0.415 23.514 36.439 23.514 16.744 25.947 16.744 16.744 20.364 31.557 20.364 20.364 22.749 35.253 22.749 22.749
RM-6 0.415 14.391 21.450 14.391 9.491 14.147 9.491 9.491 12.463 18.576 12.463 12.463 13.571 20.228 13.571 13.571
RM-8 0.415 14.391 21.450 14.391 9.491 14.147 9.491 9.491 12.463 18.576 12.463 12.463 13.571 20.228 13.571 13.571
SUB SB1 0.415 34.923 57.503 33.623 27.013 44.478 27.013 27.013 30.244 49.799 30.244 30.244 34.495 56.797 34.495 34.495
SUB SB2 0.415 21.732 32.591 21.324 14.778 22.162 14.778 14.778 18.820 28.225 18.820 18.820 20.727 31.085 20.727 20.727
TR1_LV3 0.433 56.500 129.404 56.497 57.062 130.690 57.062 57.062 48.931 112.068 48.931 48.931 56.831 130.162 56.831 56.831
TR2_LV 0.433 60.682 137.162 56.497 59.840 135.259 59.840 59.840 52.552 118.786 52.552 52.552 60.559 136.883 60.559 60.559
TR3_LV 0.433 56.500 129.404 56.497 57.062 130.690 57.062 57.062 48.931 112.068 48.931 48.931 56.831 130.162 56.831 56.831
All fault currents are in rms kA. Current ip is calculated using Method C.* LLG fault current is the larger of the two faulted line currents.
Short-Circuit Summary Report
3-Phase, LG, LL, LLG Fault Currents in KA
DG SUPPLY BUS COUPLERS OFF MODE
Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground
33 kV 0.433kV
CTHV:50/1 4000 A ACB
2.5 MVA
Transformer capacity PT 2.5 MVA
Primary Voltage Vp 33 kV
Secondary Voltage Vs 0.433 kV
CT ratio Transformer Primary side CTR1 50/1
Ratio 50
LT Breaker Rating In In 4000
Percentage Impedance of Transformer Z 6.25%
Max fault current at 33 kV Bus as per short circuit report F1max 26243.00 Amps
Max fault current at 0.433 kV Bus as per short circuit report
Transformer Full Load Primary Current Ipfl 2500 )/ (1.732 X 33) Amps
43.74 Amps
Relay reset ratio 0.95
Measuring Tolerence 10.00 %
Transformer HV side Primary current setting 43.74x 1.10/0.95 Amps
50.65
setting 1.01
IDMT setting at 33kV side 50.65/50
Setting proposed 1.00
Curve IEC Normal Inverse
Transformer Full Load Secondary Current Isfl 3333.53
Transformer Secondary current with 10 % Over load 3666.88
ACB setting at 0.433 kV side 3666.88/4000
0.92
Setting proposed 0.925
Short circuit MVA of Transformer PT X 100 / Z
2.5X100/6.25
40 MVA
Fault current at 415volts Bus as per short circuit report 53336.46 Amps
LT Breaker settings Equivalent to Max.short circuit current at 0.415 kV Bus 13.33 Amps
HT Equivalent current due to short circuit at 0.415 kV Bus 699.84 Amps
CT current CTR1 current due to short circuit at 0.415 kV Bus 14.00 Amps
Max fault current at 33 kV Bus as per short circuit report 26243 Amps
Min fault current at 33 kV Bus as per short circuit report 13121 Amps
CT current Equivalent to .short circuit current at Transformer Primary 262.42 Amps
Instantaneous setting
Setting proposed on 33 kV side I>> 16
Setting proposed on 0.433 kV side Breaker I>> 6
Protective Device Settings - Relay Synchronising Panel
K
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam) Direct. (67) Preload.
Base Multip.
PT / Device Level
Relay ID Manufacturer Model Trip Element Current Curve
Function /Stage Block
CT Setting Prim. Time Prim. Time
Pickup Pickup TOC by Direction Setting Setting
Ratio Amps Delay Amps Delay
IOC
R:DG1 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG1 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
R:DG2 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG2 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
R:DG3 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG3 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
R:DG4 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG4 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
R:DG5 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG5 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
R:DG6 GEC CDG11/21/31 2000:1 Overcurrent Phase OC1 Normal Inverse 0.750 1500.000 0.200
R:DG6 GEC CDG11/21/31 2000:1 Overcurrent GROUND OC1 Normal Inverse 0.100 200.000 0.200
Protective Device Settings - Relay 33 kV switch Boards
K
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam) Direct. (67) Preload.
PT / Base Multip.
Device Level
Relay ID Manufacturer Model Trip Element Current Curve Block
CT Function /Stage Prim. Time Prim. Time
Setting Pickup Pickup TOC by Direction Setting Setting
Ratio Amps Delay Amps Delay
IOC
R:RMG_OG ABB ICM2 100:1 Overcurrent Phase OC1 Inverse 1.000 100.000 0.800 7.000 700.00 0.03 s
R:RMG_OG ABB ICM2 100:1 Overcurrent GROUND OC1 Inverse 0.400 40.000 0.100 1.000 100.00 0.00
R:33kV_IC ABB ICM2 200:1 Overcurrent Phase OC1 Inverse 0.600 120.000 0.450 4.000 480.00 0.03 s
R:33kV_IC ABB ICM2 200:1 Overcurrent GROUND OC1 Inverse 0.150 30.000 0.150 1.000 200.00 0.00
R:33kV_OG1 ABB ICM2 50:1 Overcurrent Phase OC1 Inverse 0.800 40.000 1.000 10.000 400.00 0.03 s
R:33kV_OG1 ABB ICM2 50:1 Overcurrent GROUND OC1 Inverse 0.200 10.000 0.100 1.000 50.00 0.00
R:33kV_OG2 ABB ICM2 50:1 Overcurrent Phase OC1 Inverse 0.800 40.000 1.000 10.000 400.00 0.03 s
R:33kV_OG2 ABB ICM2 50:1 Overcurrent GROUND OC1 Inverse 0.200 10.000 0.100 1.000 50.00 0.00
R:33kV_OG3 ABB ICM2 50:1 Overcurrent Phase OC1 Inverse 0.800 40.000 1.000 10.000 400.00 0.03 s
R:33kV_OG3 ABB ICM2 50:1 Overcurrent GROUND OC1 Inverse 0.200 10.000 0.100 1.000 50.00 0.00
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device MAIN PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
MPCC_SEC3_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
1 6.0
MPCC_SEC3_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0.4 OUT
1 6.0
MPCC_SEC2_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
1 6.0
MPCC_SEC2_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0.4 OUT
1 6.0
MPCC_SEC1_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
1 6.0
MPCC_SEC1_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0.4 OUT
1 6.0
Spectronic
OG:RM-6 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-6 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-4 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-4 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-8 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-8 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-2 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-2 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device MAIN PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
Spectronic
OG:RM-7 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-7 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-3 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-3 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-5 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-5 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
Spectronic
OG:RM-1 General Electric S 2000 2000 2000 Phase 0.9 1800 5 3 5400 30 5 10000
S/L (RV)
Spectronic
OG:RM-1 General Electric S 2000 2000 2000 Ground 0.2 240 0.25
S/L (RV)
LM Series
OG:LSB-GF GEC Alsthom LM400B 400 71 Phase Fixed 284 Fixed Fixed 2272 Fixed IN Fixed 4544
(Curve D)
Spectronic
OG:CAP3 General Electric S 2000 2000 1200 Phase 0.5 600 5 3 1800 30 5 6000
S/L (RV)
Spectronic
OG:CAP3 General Electric S 2000 2000 1200 Ground 0.2 240 0.1
S/L (RV)
Spectronic
OG:CAP1 General Electric S 2000 2000 1200 Phase 0.5 600 5 3 1800 30 5 6000
S/L (RV)
Spectronic
OG:CAP1 General Electric S 2000 2000 1200 Ground 0.2 240 0.1
S/L (RV)
Spectronic
OG:CAP 2 General Electric S 2000 2000 1200 Phase 0.5 600 5 3 1800 30 5 6000
S/L (RV)
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device MAIN PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
Spectronic
OG:CAP 2 General Electric S 2000 2000 1200 Ground 0.2 240 0.1
S/L (RV)
Spectronic
OG:CHILLER 6 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Spectronic
OG:CHILLER 6 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER4 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Spectronic
OG:CHILLER4 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER 7 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Spectronic
OG:CHILLER 7 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER 1 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 4500
S/L (RV)
Spectronic
OG:CHILLER 1 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER 2 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Spectronic
OG:CHILLER 2 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER 5 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Spectronic
OG:CHILLER 5 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:CHILLER3 General Electric S 1000 1000 1000 Phase 0.9 900 5 3 2700 30 5 5000
S/L (RV)
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device MAIN PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
Spectronic
OG:CHILLER3 General Electric S 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:SUB SB1 General Electric L 1000 1000 1000 Phase 0.6 600 5 3 1800 30 5 5000
S/L (RV)
Spectronic
OG:SUB SB1 General Electric L 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
Spectronic
OG:SUB SB2 General Electric L 1000 1000 1000 Phase 0.6 600 5 3 1800 30 5 5000
S/L (RV)
Spectronic
OG:SUB SB2 General Electric L 1000 1000 1000 Ground 0.2 200 0.1
S/L (RV)
LM Series
OG:AC PUMP 1 GEC Alsthom LM400B 400 50 Phase Fixed 200 Fixed Fixed 1600 Fixed IN Fixed 3200
(Curve D)
OG:FOOD LM Series
GEC Alsthom LM630B 630 63 Phase Fixed 396.9 Fixed Fixed 3175 Fixed IN Fixed 4032
COURT (Curve D)
LM Series
OG:PSB GF GEC Alsthom LM400B 400 50 Phase Fixed 200 Fixed Fixed 1600 Fixed IN Fixed 3200
(Curve D)
LM Series
OG:LSB GF GEC Alsthom LM400B 400 71 Phase Fixed 284 Fixed Fixed 2272 Fixed IN Fixed 4544
(Curve D)
LM Series
OG:AC PUMP 2 GEC Alsthom LM200R 200 100 Phase Fixed 200 Fixed Fixed 2400
(Curve C)
LM Series
OG:FIRE PUMP GEC Alsthom LM800B 800 50 Phase Fixed 400 Fixed Fixed 3200 Fixed IN Fixed 3200
(Curve D)
LM Series
OG:PSB1 GF GEC Alsthom LM400B 400 50 Phase Fixed 200 Fixed Fixed 1600 Fixed IN Fixed 3200
(Curve D)
MICROLOGIC
BC2 Square-D NW40H1 4000 Phase 0.85 3400 0.5 3 10200 0 OUT 4 16000
6.0
MICROLOGIC
BC2 Square-D NW40H1 4000 Ground A 500 0 OUT
6.0
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device MAIN PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
MICROLOGIC
BC1 Square-D NW40H1 4000 Phase 0.85 3400 0.5 3 10200 0 OUT 4 16000
6.0
MICROLOGIC
BC1 Square-D NW40H1 4000 Ground A 500 0 OUT
6.0
MPCC_SEC3_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
2 6.0
MPCC_SEC3_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0 OUT
2 6.0
MPCC_SEC2_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
2 6.0
MPCC_SEC2_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0 OUT
2 6.0
MPCC_SEC1_IC MICROLOGIC
Square-D NW40H1 4000 Phase 0.93 3720 0.5 4 14880 0 OUT 6 24000
2 6.0
MPCC_SEC1_IC MICROLOGIC
Square-D NW40H1 4000 Ground A 500 0 OUT
2 6.0
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device SYNCHRONISING PANEL
Breaker Trip Device Sensor/ Rating Pickup Delay Pickup Delay Pickup
LVCB ID Manufacturer Function
Model Model Frame Plug
Trip Trip x Trip
Setting Curve Band Setting Curve Band It Setting
(Amps) (Amps) (Amps)
Spectronic
DG SYNC_OG1 General Electric S 4000 4000 Phase 0.98 3920 0.5 4 15680 0 OUT 6 24000
S/L (RV)
Spectronic
DG SYNC_OG1 General Electric S 4000 4000 Ground A 500 0 OUT
S/L (RV)
Spectronic
DG SYNC_OG2 General Electric S 4000 4000 Phase 0.98 3920 0.5 4 15680 0 OUT 6 24000
S/L (RV)
Spectronic
DG SYNC_OG2 General Electric S 4000 4000 Ground A 500 0 OUT
S/L (RV)
Spectronic
DG SYNC_OG3 General Electric S 4000 4000 Phase 0.98 3920 0.5 4 15680 0 OUT 6 24000
S/L (RV)
Spectronic
DG SYNC_OG3 General Electric S 4000 4000 Ground A 500 0 OUT
S/L (RV)
Spectronic
SYNC PNL BC2 General Electric S 4000 4000 Phase 1 4000 0.5 4 16000 0 OUT 6 24000
S/L (RV)
Spectronic
SYNC PNL BC2 General Electric S 4000 4000 Ground A 500 0 OUT
S/L (RV)
Spectronic
SYNC PNL BC1 General Electric S 4000 4000 Phase 1 4000 0.5 4 16000 0 OUT 6 24000
S/L (RV)
Spectronic
SYNC PNL BC1 General Electric S 4000 4000 Ground A 500 0 OUT
S/L (RV)
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device STANDALONE PANELS
LM Series
SUB SB2_IC General Electric S 1000 1000 1000 Phase 0.5 500 5 3 1500 30 4 4000
(Curve D)
Amps (Plot Ref. kV=220)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
TR3 TR2
FLA - Other 65 FLA - Other 65
300 300
MPCC_SEC2_IC1
100 100
OG:RM-6
50 50
30 30
R:RMG_OG
10 10
R:33kV_OG2
5 5
Seconds
Seconds
3
R:33kV_IC 3
TR2
1 1
.5 .5
.3 .3
.1 TR2 .1
Inrush
.05 .05
.03 .03
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K