Академический Документы
Профессиональный Документы
Культура Документы
• Frequency
• Phase angle E VT
Ia =0
+ +
E VT V V V
Grid
- -
Grid
Generato r being
paralleled to Grid
Machine slower than system
Generator
Grid
Phase Angle
Generator
Grid
Properly Synchronized
Generator
Grid
Synchronizing Equipment
Generator being paralleled
Grid to the grid
System
w F
Slo
as
V
t
V
Sy
G
en
or
ste m er at
Armature Reaction
N
Rotor
S N
S Stator
Closing onto a dead bus
• Leading PF
– AVR will reduce excitation
• Lagging PF
– Terminal voltage will drop AVR increases excitation
• Faulted Bus
– High currents flow
• No load
– Nothing happens
Finite or Infinite
• Operation of the generator is apparently
different
• Changes in steam valve position have no
effect on speed (infinite)
• Changes in excitation only affect voltages
locally
• Generator >5% gives finite characteristics
AVR
Resistive Load
IR (Unity pf)
RG XG
VR VX= 0
E VT RLoad
Vx
Vt
Eg
I
Lagging Load
IL (Lagging pf)
RG XG
VR VX
E VT LLoad
Eg
-Vx
Vt
I
Capacitive Load
IC (Leading pf)
RG XG
VR VX
E VT CLoad
Vt
-Vx
Eg
I
V-curves
0.85 pf
Load MW Lagging
(V Curve) Load
Load MVA
(Over Excited)
(AVR Boosting)
0.95 pf
Leading
Load Unity pf
Load
(Under Excited)
(AVR Bucking)
Decrease Increase
Excitation Current
Governor Control
IL
Turbine
VT
Gov. Valve
Steam Shaft
Speed
No Load Speed Variable
Setpoint Governor Load
Droop
Setting
Speed Droop
• Electrical word for proportional control
Speed Drop NL to FL
Droop = ×100%
Rated Speed
62.4 +4%
61.8 +3%
Isochronous Governor
61.2 +2%
60.6 +1%
Constant Frequency
60Hz 0
59.4 -1%
%
Rated
58.8 -2%
Load
25% 50% 75% 100% or
58.2 -3% 200 400 600 800 MW
57.6 -4%
4% Droop
%
Speed
Freq. Change
E
62.4 +4%
Governor Speed Droop
D
61.8 +3%
C
Loading
Un-Loading
61.2 +2%
B
60.6 +1%
%
A Rated
60Hz 0
25% Load
50% 75% 100% or
59.4 -1% 200 400 800 MW
600
58.8 -2%
58.2 -3%
57.6 -4%
Effect of Adding Load
Generator Synchronized
Increasing Load
61.5
0.3 Hz { 61.2
0.3 Hz { 61
60.9
60.5
60
59.5
Frequency (Hz)
59
50 MW 50 MW
58.5
62.4
Unequal Speed Droops
61.8
61.2
A
60.6
B
60Hz
59.4
58.8
Load
MW
600 400 200 200 400 600
G1 G2
Finite Bus
61.2
61
60.5
60
} 0.6 Hz
59.4
0.6 Hz {
Frequency (Hz) 59
58.5
0.6 Hz { 61.2
61
60.5
60
} 0.6 Hz
59.4
Frequency (Hz)
59
58.5
S te a m Flo w
Ac tiv e Po we r
Re a ctive Po we r
1 .0
Po w er Fac to r (Lag g in g )
.6
Time
Adjusting Excitation
Fie ld Cu rre nt
Ac tiv e Po we r
Re active Po we r
1 .0
Po w er Fac tor (Lag gin g )
.6
Time
Stability
VT
X
Vs Large
System
Transmisson Line
P
VTVs
P= X sin ∂
Power Transfer Curve
Power Delivered to Load α V 2
Power
Before Fault
V
After Fault
Area
t0 B
P Steam
t2
Area
A
During Fault
t1
t3
MW
Output
Surges in
output power
Normal
MW
Output Time
(b)
Generator Heating
Q MVAR
Reactive Power U2 = P2 + Q2
(Circle)
Lag U MVA
Total Power
Motoring Generating
P MW
Active Power
Lead
Limits
Q MVAR U2 = P2 + Q2
Reactive Power (Circle)
A
0.85 pf Lag
Lag B
U MVA
Total Power
P MW
Active Power
C 0.95 pf Lead
Lead D
A
0.85 pf Lag
Lag B
U MVA
Total Power
Limit with
Lead No AVR
Limit with
A-B Field Heating
B-C Stator Heating Fast AVR
C-D Stator Core End Heating
H2 Pressure
Cooling
For You To Do