CONSORTIUM OF :

POWER SYSTEM STUDY FOR COMMISSIOING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

PROJECT : MUARA LABUH GEOTHERMAL POWER PROJECT


STAGE 1 DEVELOPMENT EPC CONTRACT

OWNER : PT. SUPREME ENERGY MUARA LABUH (SEML)

LOCATION : MUARA LABUH, SOLOK SELATAN, SUMATERA


BARAT, INDONESIA

0 Issued for Information 20 April 2019 MA MI/SA LUH/BR

Rev Status Date Prepared Checked Approved

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

TABLE OF CONTENTS

1. GENERAL...............................................................................................................................................4

1.1 Project Description......................................................................................................................... 4


1.2 Scope and Objection ...................................................................................................................... 4
1.3 abbreviation.................................................................................................................................... 4
1.4 Reference Document ...................................................................................................................... 5
2. ELECTRICAL SYSTEM DESCRIPTION .............................................................................................5

2.1 Normal Operation .......................................................................................................................... 5


2.2 Backfeeding Operation .................................................................................................................. 6
2.3 House Load Operation ................................................................................................................... 6
2.4 Emergency Operation .................................................................................................................... 6
2.5 Commissioning Power Supply ....................................................................................................... 6
3. ELECTRICAL SYSTEM MODELLING ...............................................................................................6

3.1 PLN Grid Modeling: ...................................................................................................................... 6


3.2 Cable Modeling:............................................................................................................................. 7
3.3 Transformer Modeling: .................................................................................................................. 7
3.4 Neutral Earthing System Modeling: .............................................................................................. 7
3.5 Big Motor Model: .......................................................................................................................... 8
4. ELECTRICAL SYSTEM STUDIES .......................................................................................................8

4.1 Case Scenario ................................................................................................................................. 8


4.2 System Study Criteria .................................................................................................................... 9
5. CALCULATION CONSIDERATION..................................................................................................11

5.1 Scheme-1...................................................................................................................................... 11
5.2 Scheme-2...................................................................................................................................... 13
5.3 Scheme-3...................................................................................................................................... 16
5.4 Scheme-4...................................................................................................................................... 19
5.5 Scheme-5...................................................................................................................................... 23
6. CONCLUSION .....................................................................................................................................25

Page 2 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

List of Attachment:

Attachments – 1 Power Plant Single Line Diagram.

Attachments – 2 Single Line Diagram for 6.3kV Switchboard.

Attachments – 3 Single Line Diagram for 400V Switchboard.

Attachments – 4 Single Line Diagram for 20kV Grid PLN.

Attachments – 5 Power System Study Result of Scheme 1 (Power Supply From 20kV GI Solok).

Attachments – 6 Power System Study Result of Scheme 2 (Power Supply From 20kV GI Solok +
Two (2) Hydro Power Plant).

Attachments – 7 Power System Study Result of Scheme 3 (Power Supply From 20kV Gi Solok + Two
(2) DEG 1MW).

Attachments – 8 Power System Study Result of Scheme 4 (Power Supply From 20kV GI Solok +
Two (2) Hydro Power Plant + Two (2) DEG 1MW).

Power System Study Result of Scheme 5 (Power Supply From 20kV GI Solok +
Attachments – 9 Two (2) Hydro Power Plant). MV System and LV System are made sperate. LV
System will be supplied by permanent EDG

Attachments – 10 TCC Curve

Attachments – 11 Reference Data.

Page 3 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

1. GENERAL

1.1 PROJECT DESCRIPTION


This report covers the electrical power system studies for the commissioning power supply of Muara
Labuh Geothermal Power Plant (GPP) Project Stage 1 Development EPC Contract, owned by PT.
Supreme Energy Muara Labuh (SEML). This project is located in Muara Labuh, Solok Selatan,
Sumatera Barat, Indonesia.

The results of the studies are to be used as consideration that PLN’s 20kV Grid which through PLN’s
is capable to supply the electricity power to Muara Labuh GPP through 150 kV GI PLTP SEML for
commissioning activity.

1.2 SCOPE AND OBJECTION


The study is for commissioning power supply of Muara Labuh GPP only and covers following key
aspects:

• Load Flow Study is to confirm continuous ratings of cable, switchboards, transformers, and to
determine steady state voltage at each switchboard in case of possible equipment operation. The
steady state voltages are assessed in terms of defined acceptable limits to ensure satisfactory power
system performance.
• Motor Starting Study is to confirm that the largest motor can be started satisfactorily.
• Short-Circuit Study is to confirm the adequacy of switchboard making and breaking short circuit
capacity for maximum prospective fault current under worst case situation.
• Protective Relay Coordination Study is to confirm that main relay coordination is already set
properly based on plant operational and coordinated well.

1.3 ABBREVIATION
FLA Full Load Ampere
kVA Kilo Volt Ampere
MVA Mega Volt Ampere
kVAR Kilo Volt Ampere reactive (Reactive Power)
MVAR Mega Volt Ampere reactive
kW Kilo Watt (Active Power)
MW Mega Watt (Active Power)
PF Power Factor
LF Load Factor
HV High Voltage

Page 4 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

LV Low Voltage
P Real Power
Q Unreal Power
S kVA power
P.S Power System

1.4 REFERENCE DOCUMENT


The latest revision following documents/drawings shall be referred:

No. Document/ Drawing No. Document/ Drawing Title

1 IEEE 141-1993 Red Book – Recommended Practice for Electric


Power Distribution for Industrial Plants

2 IEEE 242-2001 Buff Book – Recommended Practice for


Protection and Coordination of Industrial and
Commercial Power System

3 IEEE 399 - 1997 Brown Book – Recommended Practice for


Industrial and Commercial Power System
Analysis

4 ML-E-PO-P00-0001 Power Plant Single Line Diagram

5 ML-E-SG-S00-0002 SGS Single Line Diagram


Calculation Sheet for Power Plant Electrical Load
6 ML-PRD01-ENG-CCAL-0013
Data

7 ML-PRD01-ENG-CCAL-0063 Calculation Sheet for SGS Electrical Load Data


20 kV System Single Line Diagram of PLN UP3
8 Solok

9 Data Setting Protection of PLN’s Switchboard

2. ELECTRICAL SYSTEM DESCRIPTION

2.1 NORMAL OPERATION


Main power generation at Muara Labuh GPP consists of 105 MVA, 11 kV, 50 Hz, turbine generator
which will has its neutral earthed via a neutral earthing transformer of 50 kVA at the generator’s star
point. This generator’s voltage level will be stepped-down to the primary distribution of 6.3 kV via Unit
Auxiliary Transformer (UAT) with capacity of 7000 kVA, 50 Hz, which will has its neutral resistance
earthed. Primary distribution will be stepped-down to 400V via Unit Service Transformer (UST) of

Page 5 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

2500 kVA, 6.3/0.4kV, 50 Hz with neutral solidly earthed. During normal operation, the turbine
generator will supply its own auxiliary loads and the 150kV grid loads via Generator Step Up
Transformer (GSUT) with capacity of 100/110 MVA.

2.2 BACKFEEDING OPERATION


150 kV switchyard grid will supply all power plant loads when turbine generator is not ready or during
turbine generator fault. The grid is assumed as rated 9800 MVAsc, 150 kV, 50 Hz. This grid’s voltage
will be stepped-down to 11 kV via GSUT, then further stepped-down to the distribution voltage of
6.3kV and 0.4kV using UAT and UST.

2.3 HOUSE LOAD OPERATION


In case of 150 kV switchyard not ready or fault, turbine generator will supply its own auxiliary loads.

2.4 EMERGENCY OPERATION


An EDG is provided to cater the critical loads during power plant blackout for safety shutdown purpose.
The EDG is rated 800 kVA, 400 V, 50Hz, 3 phases at 0.8 power factor. Upon loss of main power
supply, the EDG will automatically supply power to essential loads.

2.5 COMMISSIONING POWER SUPPLY


Based on master planning that power supply for all load of Muara Labuh GPP during commissioning
activity will be carried out from 150kV GI Sungai Rumbai which through 150 kV Transmission Line
will supply 150kV GI Muara Labuh and then to feed all loads of Muara Labuh GPP through 150kV GI
PLTP Muara Labuh.

Regarding with 150kV GI Sungai Rumbai are not ready yet, as backup planning for power supply
during commissioning activity with some scheme (Refer to clause 4.1 Case Scenario)

3. ELECTRICAL SYSTEM MODELLING

These power system studies are carried out using ETAP Power Station software version 12.6.0 based
on the simplified single line diagram as presented in Attachment – 1 to 3. Power system components
are modeled using the respective standard model formats available within the ETAP software, which is
as per IEC standards.

3.1 PLN GRID MODELING:


PLN are modeled using ETAP model Power Grid formats. The following main parameters are
considered/assumed as the P.S simulation basis.

Page 6 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Power system analysis are modeled based on Single Line Diagram from PLN. Regarding short circuit
contribution of PLN’s 20kV Grid, we are assumption that short circuit current on 150kV system is
indefinite.

3.2 CABLE MODELING:


The cables have been modeled using ETAP model formats, with the estimated parameter same as
previous study. These models are developed in order to get the conservative values for voltage drop on
each substation.

Here below the analysis parameters.

Sr. Length R at 700 C X at 700 C


Description Cable size Remark
No. (km) Ohm/km Ohm

1 Feeder Express 1 3x1C-240 sqmm 52 0.03894 0.15341


2 Feeder Express 2 3x1C-240 sqmm 50 0.03894 0.15341
3 Feeder Express 3 3x1C-150 sqmm 18 0.06484 0.12878

3.3 TRANSFORMER MODELING:


The power transformers have been modeled using ETAP model formats, with the following parameters.

Ratio
Sr. Capacity % Impedance Z Primary / Tap Setting
Description Vector Group
No. (MVA) & X/R Ratio Secondary Range
Voltage (kV)
1 PLN TD#2 60 12.5 & 45 150/20 ±10% (1.25%) Ynyn1

2 PLN ML 30 12.5 & 45 20/150 ±10% (1.25%) Ynyn1

3 GSUT 100/110 16.419 & 59.23 150/11 ±10% (1.25%) Ynd1

4 UAT 7 6.27 & 12.96 11/6.3 ±5% (2.5%) Dyn1

5 UST 2.5 6.83 & 7.15 6.3/0.4 ±5% (2.5%) Dyn1

6 SGST 0.15 4.05 & 5.36 6.3/0.4 ±5% (2.5%) Ynd1

3.4 NEUTRAL EARTHING SYSTEM MODELING:


Neutrals of systems are earthed as below:

Page 7 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

• System of 150 kV GI Solok is solidly grounded for 150 kV system whereas the 20 kV systems
use the Low Resistance Grounded with 38.49 Ohm; 300 A.
• System of 150 kV GI Muara Labuh is solidly grounded for 150 kV system whereas the 20 kV
systems use the Low Resistance Grounded with 38.49 Ohm; 300 A.
• System of Muara Labuh GPP are solidly grounded for 150 kV System, 6.3 kV system with low
resistance grounded 36.37 Ohm; 100A and 0.4 kV system with solidly grounded.

3.5 BIG MOTOR MODEL:


Motor starting case, which is to be analyzed here, is the biggest induction motor Hot Well Pump. ETAP
model is developed based on motor name plate data:

o Motor : Hot Well Pump


o Manufacturer : Fuji Electric
o Model : MLA756ED
o Serial Number : 1803J556NS1/2
o Rated HP : 950 kW
o Voltage : 6300 V
o Nominal Current : 128 A
o RPM : 490
o Pole : 12
o Starting Method : Direct On Line
o Power factor : 71% (Refer to Data Sheet)
o Starting Power factor : 15% (Refer to Data Sheet)
o LRC : 497% (Refer to FAT Report)
o Efficiency : 94.1% (Refer to FAT Report)

4. ELECTRICAL SYSTEM STUDIES

4.1 CASE SCENARIO


The load flow study, short circuit study, large motor starting study, are conducted in the following
system operation/configuration:

Table 3 - System Studies-Case Description

Sr. No. Case No. Objective System Operation Conditions

To determine the Power System


Power supply from 20kV GI Solok only
Stud: Load Flow, Short Circuit and
1 Case-1
Starting of the largest motor
(HWP).

Page 8 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table 3 - System Studies-Case Description

Sr. No. Case No. Objective System Operation Conditions

➢ Power supply from 20kV GI Solok


To determine the Power System
➢ Power Supply from Hydro Power Plant SKE (2x4
Stud: Load Flow, Short Circuit and
2 Case-2 MW) and WSE (2x5MW)
Starting of the largest motor
➢ Two Hydro Power Plant (WSE and SKE) will be
(HWP).
synchronized with 20kV GI Solok.
To determine the Power System
➢ Power supply from 20kV GI Solok
Stud: Load Flow, Short Circuit and
3 Case-3 ➢ Power Supply from DEG (2x 1MW) synchronized
Starting of the largest motor
with 20kV GI Solok.
(HWP).
➢ Power supply from 20kV GI Solok
To determine the Power System ➢ Power supply from DEG (2x 1MW)
Stud: Load Flow, Short Circuit and ➢ Power supply form the Two Hydro Power Plant
4 Case-4
Starting of the largest motor SKE (2x4MW) and WSE (2x5MW)
(HWP). ➢ Two Hydro Power Plant (WSE and SKE), DEG (2x
1MW) will be synchronized with 20kV GI Solok.
➢ Power supply from 20kV GI Solok
➢ Power Supply from Hydro Power Plant SKE (2x4
To determine the Power System MW) and WSE (2x5MW)
Stud: Load Flow, Short Circuit and ➢ Two Hydro Power Plant (WSE and SKE) will be
5 Case-5
Starting of the largest motor synchronized with 20kV GI Solok
(HWP). ➢ LV System and MV System will be mode sperate
during HWP starting. LV System are supplied
from EDG

NOTES:

4.2 SYSTEM STUDY CRITERIA


The study carried out herein shall demonstrate the system performance on the basis / criteria given below
and ensure the effectiveness of the electrical system to perform satisfactorily under the steady state and
transient conditions.

Page 9 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

4.2.1 Steady State Conditions (Load Flow):


The study was carried out using the Newton-Raphson method of Load Flow module of the ETAP
power systems analysis software.

Under normal steady state operating conditions, the voltages at all busbars on the system should be
maintained within the range of ± 5% of the nominal voltage.

Maximum loading of Generators, Switchboards, Cables or the branch element of the system shall be
operated within its capacity without overloading.

All generators are running within acceptable power factor and within limits of their assigned rated
kW and kVAR values.

4.2.2 Large Motor Start Conditions:


The purpose of performing motor starting study is to investigate whether the largest motor can be
successfully started under the operating conditions and to ensure that the other loads in the system
is not adversely affected during starting of the large motor.

During motor start, the transient voltage dip should not exceed 10% at the switchgear/MCC busbar
and 15% at motor terminal as such voltages at terminal of all running motors should not dip below
15% during starting any large motor.

The generating sources are running near rated power factors and within their assigned capacities
after the motor start.

All parameters such as transformer rating, transformer tapping, generator rating, etc used for motor
starting study are the same as those used for load flow study. One design has been used to satisfy
both load flow and motor starting criteria

This is due to the fact that:

➢ Except motors with VFD or softstarter, motors are generally designed to be able to deliver the
full load torque at 80% terminal voltage, as long as all the motor rotor and stator limits are not
exceeded, due to the 25% excess current drawn by the running motors under the 80% reduced
voltage during the transient condition.
➢ As per IEEE std. 399-1997, electrical Contactors would drop off typically at 60% to 70% of
nominal voltage value resulting in load trips and production interruptions.

4.2.3 Short Circuit Conditions:


The system components such as circuit breakers and busbars shall be able to withstand momentary
and interrupting prospective short circuit current as per system study results.

Page 10 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

To the extent possible, the selected short circuit withstand capacity of the switchboard and the
component shall be at least 110% of the calculated prospective short circuit level at the respective
busbar.

5. CALCULATION CONSIDERATION

5.1 Scheme-1 (Power Supply From 20kV GI Solok)


The result on ATTACHMENT 5 of the Power System Study Result of Scheme 1 (Power Supply From
20kV GI Solok) indicates that:

Load Flow Study

The Load Flow Study results are attached in ATTACHMENT 5. The brief summary of load flow results
is presented in the table below:

Table - 5.1.1 Summary of Load Flow Result


Equipment Rating Simulation Result
ID Voltage Voltage
Loading Loading
(kV) (%)
SWITCHBOARD

GI PLTP SEML 150 3150 A 101.21% 10.2 A

GV BUS 11 6000 A 100.93% 138.9 A

MV UNIT 6.3 800 A 99.29% 242.5 A

MV COMMON 6.3 100 A 99.29% 6.6 A

MV COMMON SGS 6.3 100 A 99.29% 6.6 A

LV UNIT 0.4 4000 A 100.77% 846.2 A

LV ESS 0.4 1600 A 100.77% 567.7 A

LV NON-ESS 0.4 600 A 100.7% 109.1 A

TRANSFORMER

GSUT 150/11 100 MVA - 2.7 MVA

UAT 11/6.3 7 MVA - 2.7 MVA

UST 6.3/0.4 2.5 MVA - 0.6 MVA

Based on the study criteria listed in clause 4.2.1, the result of the load flow study is expected
satisfactory and meet the following criteria:

Page 11 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

• The voltage at every busbars of the system is maintained within the range of ± 5% of the nominal
voltage.
• None of the generators, switchboards, cables or the branch element of the system are overloaded.
• All transformers loading are generally within the transformer rating.
Short Circuit Study

The short circuit study results are attached in ATTACHMENT 5 and tabulated in the below Table.
Following is the summary of the short circuit studies result:

Table - 5.1.2 Summary of Short Circuit Result


3 phase
Nominal CB
ID Parameter SC (kA) Remarks
kV Rating
SC

I"k 40 0.132
GI PLTP SEML 150 Pass
Ip 100 0.275
I"k 80 1.8
GV BUS 11 Pass
Ip 154 3.8
I"k 16 3.2
MV Unit 6.3 Pass
Ip 63 6.7
I"k 16 3.2
MV COMMON 6.3 Pass
Ip 63 6.7
MV COMMON I"k 16 3.2
6.3 Pass
SGS Ip 63 6.7
I"k 63 30.7
LV UNIT 0.4 Pass
Ip 154 65.5
I"k 63 30.7
LV ESS 0.4 Pass
Ip 154 65.5
I"k 63 27.2
LV NON-ESS 0.4 Pass
Ip 154 52.5

The simulation results indicate that all short circuit current not exceed of the switchboard short circuit
rated.

Motor Starting Study

The motor starting study results are attached in ATTACHMENT 5 and tabulated in the below Table.
Following is the brief summary of motor starting study result:

Page 12 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.1.3 Summary of Motor Starting Result of HWP Motor (6.3kV, 930kW,DOL)

MS Result

Rated Voltage
Acceptance Voltage Voltage Voltage
ID Voltage Drop Remarks
Criteria Before During After
kV During
Starting Starting Starting
Starting
(%) (%) (%)
(%)

GI PLTP SEML 150 10% 108.46 77.3 100.23 22.7 Fail


GV BUS 11 10% 108.38 76.36 99.96 23.64 Fail
MV UNIT 6.3 10% 107.86 71.17 98.43 28.83 Fail
MV COMMON 6.3 10% 107.86 71.17 98.43 28.83 Fail
MV COMMON Fail
6.3 10% 107.86 71.17 98.43 28.83
SGS
LV UNIT 0.4 10% 109.64 71.5 99.88 28.5 Fail
LV ESS 0.4 10% 109.64 71.5 99.88 28.5 Fail
LV NON-ESS 0.4 10% 109.58 71.41 99.81 28.59 Fail
TERMINAL Fail
6.3 15% - 70.94 98.3 29.06
MOTOR

From the above table, following are observed:

• The voltage drop at various buses during motor start exceed the acceptance limit of 10%.
• The voltage drop at the motor terminal during motor start exceed the acceptance limit of 15%.

5.2 Scheme-2 (Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant)
The result on ATTACHMENT 6 of the Power System Study Result of Scheme 2 (Power Supply From
20kV GI Solok + Two (2) Hydro Power Plant indicates that:

Load Flow Study

The Load Flow Study results are attached in Attachment-6. The brief summary of load flow results is
presented in the table below:

Page 13 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.2.1 Summary of Load Flow Result


Equipment Rating Simulation Result
ID Voltage Voltage
Loading Loading
(kV) (%)
SWITCHBOARD

GI PLTP SEML 150 3150 A 98.58 10.5 A

GV BUS 11 6000 A 100.83 139 A

MV UNIT 6.3 800 A 99.19 242.7 A

MV COMMON 6.3 100 A 99.19 6.6 A

MV COMMON SGS 6.3 100 A 99.19 6.6 A

LV UNIT 0.4 4000 A 100.66 847 A

LV ESS 0.4 1600 A 100.66 568.2 A

LV NON-ESS 0.4 600 A 100.6 109.2 A

TRANSFORMER

GSUT 150/11 100 MVA - 2.7 MVA

UAT 11/6.3 7 MVA - 2.7 MVA

UST 6.3/0.4 2.5 MVA - 0.6 MVA

Based on the study criteria listed in clause 4.2.1, the result of the load flow study is expected
satisfactory and meet the following criteria:

• The voltage at every busbars of the system is maintained within the range of ± 5% of the nominal
voltage.
• None of the generators, switchboards, cables or the branch element of the system are overloaded.
• All transformers loading are generally within the transformer rating.

Short Circuit Study

The short circuit study results are attached in ATTACHMENT 6 and tabulated in the below Table.
Following is the summary of the short circuit studies result:

Page 14 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.2.2 Summary of Short Circuit Result


3 phase
Nominal CB
ID Parameter SC (kA) Remarks
kV Rating
SC

I"k 40 0.278
GI PLTP SEML 150 Pass
Ip 100 0.595
I"k 80 3.4
GV BUS 11 Pass
Ip 154 7.4
I"k 16 5.0
MV Unit 6.3 Pass
Ip 63 11.1
I"k 16 5.0
MV COMMON 6.3 Pass
Ip 63 11.1
MV COMMON I"k 16 5.0
6.3 Pass
SGS Ip 63 11.1
I"k 63 37.6
LV UNIT 0.4 Pass
Ip 154 83.4
I"k 63 37.6
LV ESS 0.4 Pass
Ip 154 83.4
I"k 63 32.6
LV NON-ESS 0.4 Pass
Ip 154 63.3

The simulation results indicate that all short circuit current not exceed of the switchboard short circuit
rated.

Motor Starting Study

The motor starting study results are attached in ATTACHMENT 6 and tabulated in the below Table.
Following is the brief summary of motor starting study result:

Page 15 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.2.3 Summary of Motor Starting Result of HWP Motor (6.3kV, 930kW,DOL)
MS Result

Rated Voltage
Acceptance Voltage Voltage Voltage
ID Voltage Drop Remarks
Criteria Before During After
kV During
Starting Starting Starting
Starting
(%) (%) (%)
(%)

GI PLTP SEML 150 10% 108.46 90.94 104.76 9.06 Pass


GV BUS 11 10% 108.37 89.87 104.51 10.13 Tolerable*
MV UNIT 6.3 10% 107.86 84.01 103.04 15.99 Tolerable*
MV COMMON 6.3 10% 107.86 84.01 103.04 15.99 Tolerable*
MV COMMON Tolerable*
6.3 10% 107.86 84.01 103.04 15.99
SGS
LV UNIT 0.4 10% 109.64 84.91 104.66 15.09 Tolerable*
LV ESS 0.4 10% 109.64 84.91 104.66 15.09 Tolerable *
LV NON-ESS 0.4 10% 109.58 84.83 104.6 15.17 Tolerable *
TERMINAL Tolerable*
6.3 15% - 83.74 102.92 16.26
MOTOR
Note:
* Based on IEEE 399 1997 Brow Book, during motor-starting, the voltage level at the motor terminals should
be maintained, as a minimum, at approximately 80% of rated voltage or depending on actual motor and load
characteristics. Contactors are required to hold-in with line voltage as low as 80% of their rating

From the above table, following are observed:

• The voltage drop at various buses during motor start exceed the acceptance limit of 10%.
However, these voltages drop are not more than 20% which this drop voltage will be resulting
contractor trips and load interruptions.
• The voltage drop at the motor terminal during motor start exceed the acceptance limit of 15%.
However, drop voltage on motor terminal is not more than 20% which minimum requirement
of drop voltage on motor terminal based on IEEE 399.

5.3 Scheme-3 (Power supply from 20kV GI Solok + Two (2) DEG 1MW)
The result on ATTACHMENT 7 of the Power System Study Result of Scheme 3 (Power Supply From
20kV Gi Solok + Two (2) DEG 1MW indicates that:

Page 16 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Load Flow Study

The Load Flow Study results are attached in ATTACHMENT 7. The brief summary of load flow results
is presented in the table below:

Table - 5.3.1 Summary of Load Flow Result


Equipment Rating Simulation Result
ID Voltage Voltage
Loading Loading
(kV) (%)
SWITCHBOARD

GI PLTP SEML 150 3150 A 100.77 6.4 A

GV BUS 11 6000 A 100.52 87.6 A

MV UNIT 6.3 800 A 99.15 152.9 A

MV COMMON 6.3 100 A 99.15 6.6 A

MV COMMON SGS 6.3 100 A 99.15 6.6 A

LV UNIT 0.4 4000 A 100.62 847.3 A

LV ESS 0.4 1600 A 100.62 568.5 A

LV NON-ESS 0.4 600 A 100.56 109.3A

TRANSFORMER

GSUT 150/11 100 MVA - 1.7 MVA

UAT 11/6.3 7 MVA - 1.7 MVA

UST 6.3/0.4 2.5 MVA - 0.6 MVA

Based on the study criteria listed in clause 4.2.1, the result of the load flow study is expected
satisfactory and meet the following criteria:

• The voltage at every busbars of the system is maintained within the range of ± 5% of the nominal
voltage.
• None of the generators, switchboards, cables or the branch element of the system are overloaded.
• All transformers loading are generally within the transformer rating

Short Circuit Study

The short circuit study results are attached in ATTACHMENT 7 and tabulated in the below Table.
Following is the summary of the short circuit studies result:

Page 17 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.3.2 Summary of Short Circuit Result


3 phase
Nominal CB
ID Parameter SC (kA) Remarks
kV Rating
SC

I"k 40 0.278
GI PLTP SEML 150 Pass
Ip 100 0.348
I"k 80 3.4
GV BUS 11 Pass
Ip 154 4.8
I"k 16 5.0
MV Unit 6.3 Pass
Ip 63 9.1
I"k 16 5.0
MV COMMON 6.3 Pass
Ip 63 9.1
MV COMMON I"k 16 5.0
6.3 Pass
SGS Ip 63 9.1
I"k 63 37.6
LV UNIT 0.4 Pass
Ip 154 76.2
I"k 63 37.6
LV ESS 0.4 Pass
Ip 154 76.2
I"k 63 32.6
LV NON-ESS 0.4 Pass
Ip 154 59.1

The simulation results indicate that all short circuit current not exceed of the switchboard short circuit
rated.

Motor Starting Study

The motor starting study results are attached in ATTACHMENT 7 and tabulated in the below Table.
Following is the brief summary of motor starting study result:

Page 18 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.3.3 Summary of Motor Starting Result of HWP Motor (6.3kV, 930kW,DOL)

MS Result

Rated Voltage
Acceptance Voltage Voltage
ID Voltage Voltage Drop Remarks
Criteria During After
kV During During
Starting Starting
Starting Starting
(%) (%)
(%)

GI PLTP SEML 150 10% 105.26 82.44 99.91 17.56 Fail


GV BUS 11 10% 105.12 81.66 99.66 18.34 Tolerable*
MV UNIT 6.3 10% 104.39 77.38 98.24 22.62 Fail
MV COMMON 6.3 10% 104.39 77.38 98.24 22.62 Fail
MV COMMON Fail
6.3 10% 104.39 77.38 98.24 22.62
SGS
LV UNIT 0.4 10% 106.05 78 99.68 22 Fail
LV ESS 0.4 10% 106.05 78 99.68 22 Fail
LV NON-ESS 0.4 10% 105.99 77.91 99.61 22.09 Fail
TERMINAL Fail
6.3 15% - 77.13 98.1 22.87
MOTOR
Note:

From the above table, following are observed:

• The voltage drop at various buses during motor start exceed the acceptance limit of 10%.
• The voltage drop at the motor terminal during motor start exceed the acceptance limit of 15%.

5.4 Scheme-4 (Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2)
DEG 1MW)
The result on ATTACHMENT 8 of the Power System Study Result of Scheme 4 (Power Supply From
20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW) indicates that:

Page 19 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Load Flow Study

The Load Flow Study results are attached in ATTACHMENT 8. The brief summary of load flow results
is presented in the table below:

Table - 5.4.1 Summary of Load Flow Result


Equipment Rating Simulation Result
ID Voltage Voltage
Loading Loading
(kV) (%)
SWITCHBOARD

GI PLTP SEML 150 3150 A 99.01 4.9 A

GV BUS 11 6000 A 100.08 65.6 A

MV UNIT 6.3 800 A 99 114.5 A

MV COMMON 6.3 100 A 99 6.6 A

MV COMMON SGS 6.3 100 A 99 6.6 A

LV UNIT 0.4 4000 A 100.47 848.6 A

LV ESS 0.4 1600 A 100.47 569.2 A

LV NON-ESS 0.4 600 A 100.4 109.4

TRANSFORMER

GSUT 150/11 100 MVA - 1.3 MVA

UAT 11/6.3 7 MVA - 1.3 MVA

UST 6.3/0.4 2.5 MVA - 0.6 MVA

Based on the study criteria listed in clause 4.2.1, the result of the load flow study is expected
satisfactory and meet the following criteria:

• The voltage at every busbars of the system is maintained within the range of ± 5% of the nominal
voltage.
• None of the generators, switchboards, cables or the branch element of the system are overloaded.
• All transformers loading are generally within the transformer rating

Short Circuit Study

The short circuit study results are attached in ATTACHMENT 8 and tabulated in the below Table.
Following is the summary of the short circuit studies result:

Page 20 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.4.2 Summary of Short Circuit Result


3 phase
Nominal CB
ID Parameter SC (kA) Remarks
kV Rating
SC

I"k 40 0.318
GI PLTP SEML 150 Pass
Ip 100 0.696
I"k 80 0.4
GV BUS 11 Pass
Ip 154 9
I"k 16 6.1
MV Unit 6.3 Pass
Ip 63 13.9
I"k 16 6.1
MV COMMON 6.3 Pass
Ip 63 13.9
MV COMMON I"k 16 6.1
6.3 Pass
SGS Ip 63 13.9
I"k 63 40.5
LV UNIT 0.4 Pass
Ip 154 91.1
I"k 63 40.5
LV ESS 0.4 Pass
Ip 154 91.1
I"k 63 34.7
LV NON-ESS 0.4 Pass
Ip 154 67.6

The simulation results indicate that all short circuit current not exceed of the switchboard short circuit
rated.

Motor Starting Study

The motor starting study results are attached in ATTACHMENT 8 and tabulated in the below Table.
Following is the brief summary of motor starting study result:

Page 21 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.4.3 Summary of Motor Starting Result of HWP Motor (6.3kV, 930kW,DOL)

MS Result

Rated Voltage
Acceptance Voltage Voltage Voltage
ID Voltage Drop Remarks
Criteria Before During After
kV During
Starting Starting Starting
Starting
(%) (%) (%)
(%)

GI PLTP SEML 150 10% 100.41 87.41 97.46 12.59 Tolerable*


GV BUS 11 10% 100.32 86.55 97.22 13.45 Tolerable*
MV UNIT 6.3 10% 99.82 81.85 95.91 18.15 Tolerable*
MV COMMON 6.3 10% 99.82 81.85 95.91 18.15 Tolerable*
MV COMMON Tolerable*
6.3 10% 99.82 81.85 95.91 18.15
SGS
LV UNIT 0.4 10% 101.32 82.66 97.27 17.34 Tolerable*
LV ESS 0.4 10% 101.32 82.66 97.27 17.34 Tolerable*
LV NON-ESS 0.4 10% 101.26 82.58 97.2 17.42 Tolerable*
TERMINAL Tolerable*
6.3 15% - 81.58 95.77 18.42
MOTOR
Note:
* Based on IEEE 399 1997 Brow Book, during motor-starting, the voltage level at the motor terminals should
be maintained, as a minimum, at approximately 80% of rated voltage or depending on actual motor and load
characteristics. Contactors are required to hold-in with line voltage as low as 80% of their rating

From the above table, following are observed:

• The voltage drop at various buses during motor start exceed the acceptance limit of 10%.
However, these voltages drop are not more than 20% which this drop voltage will be resulting
contractor trips and load interruptions.
• The voltage drop at the motor terminal during motor start exceed the acceptance limit of 15%.
However, drop voltage on motor terminal is not more than 20% which minimum requirement
of drop voltage on motor terminal based on IEEE 399.

Page 22 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

5.5 Scheme-5 (Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant) and MV
System and LV System are made Separate.
The result on ATTACHMENT 9 of the Power System Study Result of Scheme 5 (Power Supply From
20kV GI Solok + Two (2) Hydro Power Plant and MV System and LV System will be made sperate
during starting of HWP motor. LV System will be supplied from EDG permanent. This scheme indicates
that:

Load Flow Study

The Load Flow Study results are attached in Attachment-9. The brief summary of load flow results is
presented in the table below:

Table - 5.5.1 Summary of Load Flow Result


Equipment Rating Simulation Result
ID Voltage Voltage
Loading Loading
(kV) (%)
SWITCHBOARD

GI PLTP SEML 150 3150 A 101.89 6.1 A

GV BUS 11 6000 A 101.7 83.3 A

MV UNIT 6.3 800 A 100.66 145.4 A

MV COMMON 6.3 100 A 100.66 6.5 A

MV COMMON SGS 6.3 100 A 100.66 6.5 A

LV UNIT 0.4 4000 A 100 281.5

LV ESS 0.4 1600 A 100 852.3 A

LV NON-ESS 0.4 600 A 99.93 110 A

TRANSFORMER

GSUT 150/11 100 MVA - 1.6 MVA

UAT 11/6.3 7 MVA - 1.6 MVA

UST 6.3/0.4 2.5 MVA - -

Based on the study criteria listed in clause 4.2.1, the result of the load flow study is expected
satisfactory and meet the following criteria:

• The voltage at every busbars of the system is maintained within the range of ± 5% of the nominal
voltage.
• None of the generators, switchboards, cables or the branch element of the system are overloaded.

Page 23 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

• All transformers loading are generally within the transformer rating

Short Circuit Study

The short circuit study results are attached in ATTACHMENT 9 and tabulated in the below Table.
Following is the summary of the short circuit studies result:

Table - 5.5.2 Summary of Short Circuit Result


3 phase
Nominal CB
ID Parameter SC (kA) Remarks
kV Rating
SC

I"k 40 0.254
GI PLTP SEML 150 Pass
Ip 100 0.543
I"k 80 3.3
GV BUS 11 Pass
Ip 154 7.1
I"k 16 4.3
MV Unit 6.3 Pass
Ip 63 9.8
I"k 16 4.3
MV COMMON 6.3 Pass
Ip 63 9.8
MV COMMON I"k 16 4.3
6.3 Pass
SGS Ip 63 9.8
I"k 63 21.0
LV UNIT 0.4 Pass
Ip 154 50.1
I"k 63 21.0
LV ESS 0.4 Pass
Ip 154 50.1
I"k 63 19.5
LV NON-ESS 0.4 Pass
Ip 154 42.4

The simulation results indicate that all short circuit current not exceed of the switchboard short circuit
rated.

Motor Starting Study

The motor starting study results are attached in ATTACHMENT 9 and tabulated in the below Table.
Following is the brief summary of motor starting study result:

Page 24 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Table - 5.5.3 Summary of Motor Starting Result of HWP Motor (6.3kV, 930kW,DOL)
MS Result

Rated Voltage
Acceptance Voltage Voltage Voltage
ID Voltage Drop Remarks
Criteria Before During After
kV During
Starting Starting Starting
Starting
(%) (%) (%)
(%)

GI PLTP SEML 150 10% 110.04 92.88 106.61 7.12 Pass


GV BUS 11 10% 110 91.86 106.42 8.14 Pass
MV UNIT 6.3 10% 109.8 86.26 105.3 13.74 Tolerable*
MV COMMON 6.3 10% 109.8 86.26 105.3 13.74 Tolerable*
MV COMMON Tolerable*
6.3 10% 109.8 86.26 105.3 13.74
SGS
LV UNIT 0.4 10% 100 100 100 0 Pass
LV ESS 0.4 10% 100 100 100 0 Pass
LV NON-ESS 0.4 10% 99.93 99.93 99.93 0.07 Pass
TERMINAL Pass
6.3 15% - 85.98 105.18 14.02
MOTOR
Note:
* Based on IEEE 399 1997 Brow Book, during motor-starting, the voltage level at the motor terminals should
be maintained, as a minimum, at approximately 80% of rated voltage or depending on actual motor and load
characteristics. Contactors are required to hold-in with line voltage as low as 80% of their rating

From the above table, following are observed:

• The voltage drop at various buses during motor start exceed the acceptance limit of 10%.
However, these voltages drop are not more than 20% which this drop voltage will be resulting
contractor trips and load interruptions.
• The voltage drop at the motor terminal during motor start exceed the acceptance limit of 15%

6. CONCLUSION

Based on the load flow study result, loading of Transformer, switchboards and cables rating are not
exceed the acceptable value at all of cases. Voltage drop value at all bus are not exceed the design value
of ± 5% of the nominal voltage at all of cases.

Page 25 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-CAS-CCAL-0001 MA 0 14000011-OS-10101

Based on the short circuit study result, short circuit current at the switchboard are not exceed the short
circuit current of switchboard rating at all of cases.

Based on the motor starting study, following are observed:

➢ Scheme 1
During starting, the largest voltage drop at bases is 28.83% on MV Switchboard, more than
project requirement 10%. The Voltage drop at terminal motor of HWP is 29.06%, more than
project requirement 15%. Based on this result, scheme-1 are not recommended to supply power
for commissioning.

➢ Scheme 2
During starting, the largest voltage drop at bases is 15.99% on MV Switchboard more than
project requirement 10%. The Voltage drop at terminal motor of HWP is 16.26%, more than
project requirement 15%. However, refer to IEEE 399 Brown Book, voltage drop at terminal
voltage is not exceed acceptance limit 20%. Based on this result, scheme-2 are recommended
to supply power for commissioning.

➢ Scheme 3
During starting, the largest voltage drop at bases is 22.62% on MV Switchboard. The Voltage
drop at terminal motor of HWP is 22.87%. Based on this result, scheme-3 are not recommended
to supply power for commissioning.

➢ Scheme 4
During starting, the largest voltage drop at bases is 18.15% on MV Switchboard. The Voltage
drop at terminal motor of HWP is 18.42%. However, refer to IEEE 399 Brown Book, voltage
drop at terminal voltage is not exceed acceptance limit 20%. Based on this result, scheme-4 are
capable to supply power for commissioning but not recommended.

➢ Scheme 5
During starting, the largest voltage drop at bases is 13.74% on MV Switchboard. The Voltage
drop at terminal motor of HWP is 14.02%, not exceed of project requirement 15%. Based on
this result, scheme-5 are more recommended to supply power for commissioning than another
scheme.

Page 26 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 1

POWER PLANT SINGL LINE DIAGRAM

Page 27 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


1 2 3 4 5 6 7 8 9 10 11 12

A A

B B

C C

D D

E E

F F

G G

ATTACHED XREF FILES PROJECT TITLE

H H

DRAWN DRAFT. CHECK REVIEWED APPROVED


SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No
DESIGNED DESGN. REVIEW
DATE DATE

1 2 3 4 5 6 7 8 9 10 11 12 A3
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 2

SIGLE LINE DIAGRAM FOR 6.3 KV SWITCHBOARD

Page 28 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


1 2 3 4 5 6 7 8 9 10 11 12

A A

B B

C C

D D

E E

F F

G G

ATTACHED XREF FILES PROJECT TITLE


Plot Date: 29 Oct 2018, - 11:25:56

H H

DRAWN DRAFT. CHECK REVIEWED APPROVED


SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE

1 2 3 4 5 6 7 8 9 10 11 12 A3
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 3

SINGLE LINE DIAGRAM POWER PLANT 400V SWITCHBOARD

Page 29 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


1 2 3 4 5 6 7 8 9 10 11 12

A A

B B

C C

D D

E E

F F

G G

ATTACHED XREF FILES PROJECT TITLE

H H

DRAWN DRAFT. CHECK REVIEWED APPROVED


SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE

1 2 3 4 5 6 7 8 9 10 11 12 A3
1 2 3 4 5 6 7 8 9 10 11 12

A A

B B

C C

D D

E E

F F

G G

ATTACHED XREF FILES PROJECT TITLE

H H

DRAWN DRAFT. CHECK REVIEWED APPROVED


SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE

1 2 3 4 5 6 7 8 9 10 11 12 A3
1 2 3 4 5 6 7 8 9 10 11 12

A A

B B

C C

D D

E E

F F

G G

ATTACHED XREF FILES PROJECT TITLE

H H

DRAWN DRAFT. CHECK REVIEWED APPROVED


SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE

1 2 3 4 5 6 7 8 9 10 11 12 A3
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 4

SINGLE LINE DIAGRAM FOR 20KV GRID PLN

Page 30 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


SINGLE LINE DIAGRAM OPERASI PT. PLN (PERSERO) UNIT PELAKSANA PELAYANAN PELANGGAN (UP3) SOLOK
TD#2 TD#1 TD#2 TD#1 TD#2 2.000/5 GI KILIRAN TD#1 TD#
GI SOLOK GI SALAK 2.000/5 GI Muaro MVA /5
60 MVA 20 MVA 1.000/5 20 MVA 2.000/5 20 MVA 60 MVA (377 A) 20 MVA 1.000/5
2.000/5 (194 A) JAO Bungo ( A) ( A)
(1732 A) (440 A) (577 A) (370 A) (577 A) (275 A) (577 A) (1732 A) (577 A) (243 A)
25,41 % 64,12 % 47,66 % 33,62 % 21,77 % 42,11 % %
F. 7/3
F. T. F. 7 F. 6 F. 1 Batu F. 2 Saok F. 3 F. 4 Muaro F. 1 PT. F. 6 F. 2 F. 3 F. Exp.P. Sei. F. 6 Sei. F. 5
F. Exp. 8 Garam KYA Selayo F. 5 Kota Palano Laweh Paneh F. 4 BA UPO Sijantang F. 5 AIC Santur Lintau F. 2 Sei. Punjuang Tmbg Lansek Balitan F. 7 Pinang
Sumani
(159 A) (93 A) (20 A) (95 A) (73 A) (110 A) (60 A) (95 A) Sijunjung (9 A) (37 A) (6 A) (130 A) (58 A) Dareh (193 A) (66 A) (70 A) (243 A) (205 A)
(105 A) Recloser
Payo (229 A) (48 A)
Jambi WRKR

400/5

400/5

400/5
400/5

400/5
600/5

600/5

600/5
600/5

600/5

400/5

400/5

600/5

600/5

400/5

600/5
ULP Sitiung

600/5

600/5

300/5

300/5

300/5
LBS Manual
Batas (NO)
LBS Manual
T.Garam (NC) LBS Manual
LBS Manual LBS Motorize
LBS Manual LBS Manual Manuver
Jl.Lingkar (NO)

Recloser
GH Santur Manuver
(NC)
Manuver
(NC)
(NC) Pulau Punjung
(NC)
Ampang
LBS Motorize Kualo Inc. LBS
T. Garam LBS Manual Recloser LBS Manual
600/5 Motorize
(NC)
ULP Solok LBS Motorize F. 3
Sikalang
(NC)
LBS
Motorize
Sikalang
(NC)
Inc.
GH Tanjuang ULP
Sei.
Tambang
LBS Manual
Sei. Tenang
Beringin
Sakti (NC) LBS Motorize
LBS Manual LBS Motorize Jl.Lingkar (NO) Talago F. 2 F. 1 Kuncai (NC) (NC) (NC) Sopan jaya
LBS Manual Rayon (NC) UncuAmin (NC)
Gunuang Kota Kolok 600/5 Ampalu Recloser LBS Motorize (NC)
Depan Area
(NC)
LBS Motorize
LBS Motorize
Desta mart (NC)
LBS
Manual
KM 4 (NC) (23 A) (86 A) (10 A) Sijunjung LBS Manual
Pink
(NC)
Sei. Tambang
(NO) LBS Motorize
LBS Manual
BMT (NC)

F. Bukit F. 1 F. 2 F. Pdg. LBS Motorize


F. KTK Tembok (NC) LBS Manual LBS Motorize F. 3 Kamang Sei. Tenang
GH Solok (NC) (NO)
Siaur (NC) LBS Motorize LBS Manual

600/5
Swh.Sianik (NC) Spg.Dama (NO) Bual Palangki Muaro Laweh Kumanis
(62 A)

600/5

600/5
Polres (NC) Timpeh
(NO)
(11 A) (67 A) (96 A) (16 A) (43 A) LBS Parit
Kampuang
(NC)
GH Balitan
LBS Motorize BD LBS M.O.F Recloser
LBS Motorize F. VI Suku F. Sembiko Panduang (NC) Motorize
ULP Sawah FCO Kamang
Rantang Siaur
F. Sei.

300/5

300/5
Spg. Sigege LBS Motorize (NC)

300/5

300/5
Kamang
GH Sungai (NC)

300/5
(NC) (25 A) (5 A) Ktr.Rayon
Baing (NO) LBS Manual
F. Aur F. Exp.
LBS (NC) Panyubarang Duo F. Timpeh
Manual
Yasmin
(NC) Recloser
KM. 4 (NC)
LBS Manual
Kayu
Gadang (NC)
Lunto LBS Manual LBS Motorize
Kiliran Jao
Inc. Dareh LBS Manual (NC) Jaya
(55 A) (60 A)
Koto Baru
(195 A)
(10 A)
200/5

LBS Sei. Rambutan


M.O.F /5
200/5

(NC) LBS LBS LBS Manual


200/5

(NO) Bukit
LBS Motorize LBS Manual Motorize Motorize
Motorize LBS Bunduang
(NC) F. Kp. F. G. Talawuang Trimulya
Parambahan LBS LBS LBS Manual LBS Manual
Ktr.Rayon Nan Balimo Kpg Surian Kandih (NO) LBS Manual Surau (NC)
LBS Manual LBS Manual (NC) Manual Motorize RM Palapa F. Silago Medan (NC) SP 6 (NC)
(NC) (NC) (NC) Manual Bukit LBS LBS Motorize

400/5
LBS Pattimura Sapan (NC) Kandang Buluah FCO (NO)
Gambok
Motorize LBS Motorize
(NC) LBS Manual
SCTV (NC)
Itiak Batu
Gandang (NC)
Rotan Motorize
Bundung
Maloro(NC) (0 A) (9 A) (150 A) Trimulya
(NC) LBS Motorize
VI Suku LBS Motorize (NC) (NC) Spg Rimbo
Spg.Rumbio (NO) (NC) (NC) FCO
(NO) Talago Gunung LBS LBS LBS Manual Taratak(NC) Bujang (NC)

300/5

300/5

300/5
(NC) Manual LBS Manual LBS Manual
LBS Manual Aia Amo LBS Motorize
LBS SMP (NC) (NC) Parit Rantang
Spg. Manual Depan Bunduang
Manual (NO) LBS Manual
Koramil AlamAsri Kanja LBS LBS (NO) LBS Motorize
Pdg. Pulai (NC)
LBS Manual LBS LBS Manual (NC) (NC) (NC) Manual Motorize Recloser LBS Motorize LBS Manual LBS Motorize
Recloser Recloser Spg. LBS Manual Laweh Exp Koto baru
Piliang (NC) Motorize Kandang LBS Kucai Batu Batu KM 5 (NC) Tanjung Sikabau (NC)
Parak Tembok (NC) LBS Manual Paninjauan (NC) (NC)
Paninjauan Kudo (NC) Motorize (NC) Gandang Balang Lolo (NC) LBS
Gadang (NC) Katialo (NC) (NC) LBS LBS Manual
(NO) Kolok (NC) (NC) LBS Motorize Motorize
Motorize Tapian LBS Manual
LBS Manual LBS Manual Mudik (NC) FCO Pisang Jalan P
LBS Kanja Kumanis Paru (NC)
Rayon (NC) Lubang (NO) LBS Manual bererbus Punjung
LBS Manual Talawi (NC) Recloser LBS (NC) LBS Motorize
LBS Motorize Motorize Panjang (NC) LBS Pandam (NO) (NC)
VI.Suku (NC) Batu Motorize KP Sei Duo LBS Motorize
Gubalo (NO) Koto Manual Pd Laweh (NC)
LBS Motorize Gandang LBS Manual LBS Manual Recloser (NC) Ambacang
sumani Pasar LBS Manual Recloser
Tanjuang LBS Manual (NC) (NC) Kuok (NC) Pulau Anjolai Spg. (NC)
(NO) LBS Gambok Tj. Keling Pandam
Balik (NC) Bukit (NC) Silago (NC) Recloser LBS Motorize
Motorize (NC) (NC)
LBS Motorize Gadang M.O.F (NC) M.O.F Lawai Koto Padang
LBS Manual Kolok (NO)
KTK (NC)
Swh.Sudut
(NC)
LBS Manual Spg.
Tembok (NC) LBS Manual Koto
Sumani (NC)
ULP LBS Manual
Recloser
MudikAir
(NC)
LBS Manual
AIC (NC)
Pamuatan

LBS Motorize
LBS Motorize
Pandam
LBS Manual
(NC) (NC)

LBS Motorize LBS Bendungan Koto Ranah LBS Motorize


(NC)
Selayo (NO)
Perc.PadangKunik
Singkarak Gando (NC) Motorize
Guguk
Psr. Gambok
(NC) Recloser
Kuok
LBS
Manual
LBS Manual
(NC) (NC) Sp3 S Duo
(NC)
LBS Manual
Koto Padang
LBS Motorize
SMA Koto
LBS Motorize Cubadak LBS Durian Simpai
(NC) Simaru (NC) Padang (NC)
(NC) Manual (NC)
Guci (NC) LBS Manual LBS Manual LBS LBS Manual (NC) LBS Manual
Recloser Panorama LBS Manual Motorize Batu Kuali Pamuatan Pulasan
Balai-Balai LBS Manual
Recloser Saok Laweh (NC) SMA (NO) (NC) (NC) LBS (NC)
Cupak (NC)
LBS Manual
LBS Manual Kubu
Harimau (NC)
LBS Motorize
(NC)
(NC) SMA (NO) LBS Motorize
Pondok Motorize
Balai.
LBS
Motorize
Koto Agung
(NC)
GH Koto Baru
Kapur (NC) Simaru (NC)
Lap.Bola Muara Panas Wartawan LBS Manual
(NC) (NC) (NC) Pasar Silago
LBS Manual LBS Motorize
Polsek (NC) LBS Manual LBS (NC)
Kumbayak
F. Abai F. Pulau F. Incasi F. Sei.
Perc.AiaTabik LBS Manual Manual
LBS Manual Guguak Rayo LBS (NC) Siat Mainan Raya Kalang
Ujung (NC) Manual Calau (NC)
LBS Manual Spg.KotoBaru Perc.Kt.Hilalang Balerong
By Pass (NC)
Guguak (NC) Depan
Kantor
(35 A) (55 A) (0 A) (25 A) LBS Manual

240 mm2
Cupak (NC) LBS Manual
(NC) LBS Tarantang
FAI Gantuang Kampung

200/5
LBS Manual (NO)

200/5

100/5
LBS Motorize Manual

400/5
Ciri (NC) Baru (NC)
Spg 4 M. Panas Saok Laweh LBS LBS Manual Palo
(NO) (NC) LBS Manual Motorize Taratak Padang PT DJAMBI
LBS Manual
LBS Manual ULP Simancuang Depan
Padang Alai Baru (NC) (NC) WARAS

62 kMs
LBS Manual I (NC) Kantor (NC) LBS
Spg.III (NC)
Kinari (NC) Perc. BBI Motorize

Perum.KotoBaru
LBS Manual
Panyalai
(NC)
LBS
Manual
Gtg. Ciri LBS LBS
LBS
Motorize
M.Kalaban
(NC) Silungkang Kandang
Harimau
(NC)

150 mm2
LBS LBS Motorize

150 mm2
(NC) Manual LBS Manual Kantor
Motorize LBS Motorize LBS Motorize Sungai lasi LBS Manual LBS Manual LBS Motorize LBS Manual LBS Manual LBS Manual LBS Manual M.O.F LBS Manual
Spg. 4 Kayu Gadang Kebun Gapersil Rayon (NO) Kantor Camat Simancuang II Lubuak Batu Pasar Ternak Kandang Baru Kandang LBS Manual MegaHex
SMK 2 Gn LBS Motorize Luang (NC) Guguak Sarai (NC)
(NC) (NC) Jeruk (NC) (NC) (NO) (NC) (NC) (NC) (NC) (NC) LBS Tjg. LBS
Talang Motorize Gantung (NC) Baru Lubuak Tarok
Pucuk (NC) Motorize
(NC) Recloser Sei Rotan Ciri (NC) LBS (NC) Recloser Recloser
Psr.Usang Motorize Sp Kt Baru Subarang LBS
(NO) Abai (NC) LBS Motorize

18 kMs
Cupak (NC) Batu LBS Manual (NC) Piruko Motorize
LBS Manual LBS Manual LBS Motorize LBS Motorize LBS Motorize Sp 3 Koto
LBS Manual LBS Manual Banyak Kbg. Duo (NC) (NC) Incasi raya
Guguak (NC) Talang Permai Kupitan (NC) Pale (NO) Tanah baru (NC)
Sei. Rotan Titian Batu LBS Manual (NC) (NC)

(18 kMs)
(NO) (NO) Jawi-Jawi (NC) Badantuang
(NC) (NO)
LBS Manual
Batu Banyak
LBS
(NC)
Motorize LBS
Supayang Manual Tjg.
LBS Manual
(NC) Harapan
LBS Motorize Koramil (NC)
(NC)
Suka Rami
(NC) LBS Manual
Bkt. Sileh LBS Motorize
(NC) Pulau mainan
LBS Manual Balai (NC)
Akad (NO)
LBS Manual Inc. FCO Pulau
Blkg. LBS Motorize DS
Psr.Ternak 119 A Karam (NC)
Spg. Tnjg. Manuver LBS Manual
(NC) Nan 4 (NO) (NO)
Inc.
LBS Manual GH Lbk. Gadang 300/5
LBS Motorize
Ampalu (NC)

PT. TIRTA 300/5 GH Balun Ktr. Rayon F. Exp. Sei kalang


(NC)
INVESTAMA (NC) Selo
(AQUA)
F. Mitra F. Kota Lbk. F. Lbk.
LBS Manual
Kayu Aro LBS
LBS Manual F. Exp. Lbk.
Kerinci Gadang F. Tandai Kencana Malako FCO Ombak
Kubu (NC)
GH Sei. Rumbai F. Kota F.
F. (23 A) (21 A) (207 A) (60 A)
(NC) Motorize
Air Tawar
... Gadang (25 A) Sei. Mayang
LBS (NC) Muaralabuh F. Sei. Baye
Motorize (NC)
(83 A) Rumbai Taurai
LBS Manual (82 A) LBS Motorize
(10 A)

300/5
Kubang

300/5

600/5

600/5

300/5
duo (NC) Kayu Jao LBS Manual Kelampaian (65 A) (50 A)
(NC) Air Tawar
ULP (NC)
300/5
300/5

(NC) FCO Trans

200/5

200/5
400/5
Sinuek (NC) LBS Motorize
LBS Motorize
Depan Rayon
(NC)
LBS Motorize
Panorama
(NO)
Muaralabuh LBS Motorize
LBS Manual
Depan GH LBS Manual
Sei Betung
(NC)
Lbk. Gadang LBS Motorize
Kepala Bukit (NC)
(NC)
FCO Sitapuih TKA (NC)
(NC)

LBS
(NC)
LBS Motorize
ULP Sungai
Sitapus (NC)
Motorize
Tower
Rimbo
LBS Manual
Btg. LBS Manual
Rumbai
LBS Manual Basampan
LBS Manual Batu Nago
Data (NC) Tlk. Dalam (NC)
Blkg. Pasar LBS Manual LBS Motorize (NC)
(NC) (NC) Ampalu Jembatan P

240 mm2
(NC) Awan (NC)
Recloser
GH Alahan
240 mm2
LBS Motorize
Sampu Sei Limau
(NC) (NC)
Panjang
F. Aia F. Exp. F. Tlg.
(NO)
F. Sei.
ULP Kayu 50 kMs
FCO Pinang
Awan
Manuver (NO)
LBS Manual
Spg. Mitra
(NC)
40 kMs
LBS Manual
RPC LBS
Manual LBS
Dingin Balun Babungo Nanam LBS Manual FCO Jujutan (NC) Sinamar
Recloser
Manual Sitiung IV
(63 A) (30 A) Spg. Pinang
(41 A) (66 A) Aro (NC) (NC) Bukit

PLTP ML
(NC)
Awan Berbunga
(NO) LBS Manual (NC)
Liki LBS Manual FCO
600/5

600/5

600/5

(NC) Sampu Manuver


600/5

FCO Spg. (NO)


(NC) Recloser
Pasar (NC) LBS
Motorize Spg. Kelapa
GH Pinang F. Liki Durian
Taruang
(NC)
LBS
Motorize
(Mitra LBS Motorize
LBS Awan Kerinci)
FCO Spg.
(NO)
LBS Manual
Blok B Recloser
Sitiung III Tukun (NC)

240 mm2
Motorize LBS Manual KP (NC)
Tigo
Limau (NC) Batikan (NC)
Surian (NC)
Lurah ( A) LBS Motorize
(NC)
(NC) LBS Motorize LBS Manual
Sungai Padai
Simp Sei LBS Manual
Limau (NC)
(NO) Kapalo
Blok A (NC)

42 kMs
LBS Manual
Malako
(OFF) FCO Pinang (NC)
Spg. Kelapa
LBS Manual
Prolibas (NC)
(NC)
Awan (NC)

LBS Manual LBS


Tnjg. Balik Motorize LBS Motorize
LBS Manual Psr. LBS Motorize Kp Lubuk
(NC) Puskesmas LBS Manual
Taratak Pauah Kapalo Malako (NC) LBS
(NC) Blok B (NC) LBS Manual
LBS Manual
(NC)
PLTMH LBS Manual
Selo Kencana
malako (NC) LBS Manual
Lbk. Betung
Motorize
Blok B Blok C (NC)
Puskesmas LBS Motorize (NC)
LBS Manual
(NC) Lekok Batu
Gadang (NC)
LBS Motorize
Nanggalo (NC) Pinang Awan Kubang (NO) GH WSE (NC) (NC)

(400 KW) Gajah


F. Exp.
GH SKE
Recloser
Tnjg. Balik
LBS Manual
Taratak
(NC)
Kresik Tuo 400/5
F. Kresik
Tuo
400/5
(NC) Pauah (NC) LBS Manual

LBS
Lolo Surian
(NC) LBS Manual (163 A) (183 A) ( A) (208 A)
Motorize
Batang
Telung Berasap SINGLE LINE DIAGRAM OPERASI
hari (NC) (NO)
LBS Manual
(NO) Spg. Karet
(NC) PT.PLN (PERSERO) UIW SUMBAR
LBS Manual
UP3 SOLOK
Tlg. Babungo F. Palompek FCO Sei.
(NC)
LBS Motorize
Aia Dingin
LBS Manual
Titian Panjang LWBP PLTMH LWBP PLTMH
Takuak (NC)
DISURVEY & DIGAMBAR
(NC) (NO) GH Kresik Tuo FCO DIPERIKSA
(2,4 MW) WSE Tandai (4,6 MW) SKE FCO Talao JT. Operasi & Proteksi Spv.Operasi
DISETUJUI Manajer
S2JB (NC)
(NC)
FCO PTPN
Bag. JAR
F. Exp. Kresik WBP (2 X 5 MW) WBP (2 X 4 MW) FCO Mercu
(NC)
Update November 2018
Tuo AGUNG ARY WIBOWO
(6,1 MW) (7,3 MW) (NC)
RIDWAN YUSEPRIZAL
FCO Sei.
Kunyit (NC)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 5

POWER SYSTEM STUDY RESULT OF SCHEME 1

(POWER SUPPLY FROM 20KV GI SOLOK)

Page 31 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


One-Line Diagram - SLD (Load Flow Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Load Flow Study Result
150 kV CB3
3150 A
40 kA
150 kV
Case Study Scheme - 1
Power Supply from GI Solok
2.6 MVA
10.1 A
150 kV 82.7% PF
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP
2.6 MVA
69.9 A %
GH Solok 20 kV 82.9% PF 107.82

2.6 MVA
69.9 A
82.9%
CB121 PF
630 A
0 kA
24 kV
Bus8
20 kV SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
AL 1 km CU 100 m AL 62 km
SATURN
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77 2000 A
630 A 2000 A 2000 A 2000 A 16 kA
0 kA 16 kA 16 kA 16 kA 6.6 kV
24 kV 6.6 kV 6.6 kV 6.6 kV

2.6 MVA %
GH Alahan 73.3 A 103.11 6.3 kV
20 kV 800 A 16 kA 81.2% PF Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV
2.6 MVA
73.3 A
81.2% PF T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
630 A Open 0 A 630 A 630 A 6 MVA YNd1
0 kA 0 kA 0 kA 0 kA 6 MVA YNd1 YNd1 YNd1
24 kV 24 kV 24 kV 24 kV

AL CB117 CB120 CB123


50 km 630 A 630 A CB122 630 A
NITROGEN 0 kA 0 kA 630 A 0 kA
Sungai Cehana 20kV IPP 24 kV 24 kV 0 kA 24 kV
Open Taman Babungo 1.5 MVA 20 kV 24 kV
20 kV 0.5 MVA
GH Balun4 900 kvar
CB118 0 A 2.6 MVA CAP1
CAP5 0 kA 24 kV 76.8 A
900 kvar 78.8% PF CB115 CB107
630 A 630 A
0 kA 0 kA
CB91 24 kV 24 kV
630 A 42 km
0 kA AL AL
GH Balun 24 kV DARTS 1120 42 km
20 kV 800 A16 kA 99.46% DARTS 1120

2.6 MVA CB7 CB5


76.8 A 630 A 630 A
0 kA 0 kA
78.8% PF 24 kV 24 kV
CB89
630 A
0 kA
24 kV GH Lbk Gadang
20 kV
Open

20 kV
CB114 0 A GH Balun2 CB2
Open 630 A
CAP3 0 kA 24 kV 0 kA
900 kvar AL 24 kV CB90 CB92
24 km 630 A 630 A
KRYPTON 0 kA 0 kA
24 kV 24 kV

CB88
630 A AL 25 km
0 kA
24 kV
CRICKET 1120 Feeder Lbk Kota Feeder Malako
2.6 MVA 0.09 MVA 1 MVA 1 MVA
78.5 A 2.7 A
20kV GI ML 77.7% PF -0.0% PF
20 kV
%
2.7 MVA 97.16
80.2 A
76.0% PF
CB86 CB99 CB101
0 A Open 630 A Open 630 A Fuse1
0 kA 0 kA 0 kA
24 kV 24 kV 24 kV Open
20/150 kV
T1 30 MVA YNyn0
5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA
3150 A
40 kA
150 kV

GI Sungai Rumbai GI Muara Laboh %


150 kV 3200 A 40 kA 101.21
9800 MVAsc
2.7 MVA
10.2 A
76.6% PF

150 kV CB2
3150 A
40 kA
150 kV
Open 150 kV CB1 Z1
3150 A
40 kA
150 kV
EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2
1 MW 1 MW

GI PLTP SEML 150 kV CB


3150 A 1%
150 kV 3150 A 40 kA 40 kA 101.2
150 kV
2.7 MVA
10.2 A CB129
76.6% PF GENERATOR STAGE-1 CB171
89.25 MW 0 A 0 A
0 kV 0 kV
GENERATOR TRANSFORMER CB 0 kA
3150 A 150 kV 0 kA
50 kA
GSUT Bus25
0.4 kV 3200 A
150/11 kV
100 MVAYNd1 GENERATOR CB 0 kA
Open 6300 A
80 kA
GV BUS 12 kV %
100.93
11 kV 6500 A 200 kA
±
T11
R 2.7 MVA 0.4/6.3 kV
138.9 A 3 MVA Dyn1
76.8% PF T10
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
1250 A
MV-SGS CB2 Open 16 kA
7.2 kV
UAT CB2
630 A 1250 A
16 kA Open 16 kA
7.2 kV % UAT CB 7.2 kV
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 99.29 MV UNIT SWITCHBOARD 1250 A
6.3 kV 225 A 0 kA 99.29% 6.3 kV 100 A0 kA 6.3 kV 800 A 0 kA 16 kA 99.29%
7.2 kV
0.01 MVA 0.02 MVA 0.02 MVA 0.02 MVA 0.07 MVA 0.07 MVA 0.6 MVA 1.2 MVA 0.4 MVA 0.3 MVA
1 A 1.8 A 1.7 A 2.1 A 6.6 A 6.3 kV 6.6 A 55.1 A 112 A 40.7 A 29.2 A
87.4% PF 87.4% PF 86.1% PF 87.3% PF 87.1% PF 200 A 87.1% PF 83.3% PF 71.0% PF 84.0% PF 80.0% PF
UST HVCB CB30 CB32
SGS TRANSFORMER HVCB BUS COUPLER 630 A 630 A 630 A CB96 CB97 CB194 Open CB196
Open 100 A CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB 16 kA 16 kA 16 kA 16 kA 630 A 630 A 630 A 630 A
16 kA 0 A 0 A 0 A 0 A 630 A 630 A 12 kV 7.2 kV Open 6.3 kV 16 kA 16 kA
Open 6.3 16 kA 16 kA
6.3 kV 0 kA 0 kA 0 kA 0 kA 16 kA Open 16 kA 6.3 kV kV 6.3 kV 6.3 kV
7.2 kV 7.2 kV 7.2 kV 7.2 kV 12 kV 12 kV ±

R
CU 40 m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R 6.3 kV Bus1
±
±
R UTILITY TRANSFORMER R 124 m
CU 1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
CU 1500 m 6.3/0.4 kV 99.17%
Terminal HWP
CU 500 m -2.5% TapP -2.5% TapP 2.5 MVA 6.3 kV
CU 2000 m 1-3/C 35 1.2 MVA
1-3/C 35 1-3/C 25 CU 1000 m OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
112 A 400 kW
1-3/C 35 400 A0.4 kV0 kA ±
71.0% PF 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
4000 A HOT WELL PUMP-A VACUUM PUMP-B 265 kW
0.4 kV 930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX 63 kA
250 kVA 0.6 MVA 7%
LV UNIT SWITCHBOARD 846.2 A 100.7
0.4 kV 4000 A 0 kA 83.9% PF
0.4 MVA 0.1 MVA 0.01 MVA 0 MVA 0.08 MVA
567.7
CB72 A 160.4 A 9.5 A 0.6 A 109.1 A
82.2% PF 89.0% PF 80.0% PF 0.0% PF 85.0% PF
1600 A CB60
0.415 kV CB61 Open CB10
300 A 300 A 0 A Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
70 kA 0 kV Open 0.415 kV 0 A 0 A CB21 Open 0 A 0 A Open 0 A CB202 Open CB53 0 A CB50 CB40 Open 0 A CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
0 kV Open 0 kV 0 A 0 A 0 A 0 A 0 A Open 20 A 0 A Open 0 A 0 A 0 A Open 0 A 0 A 0 A Open 0 kV 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 630 A
0 kA 70 kA 0 kA 0 kV 0 kV Open 0 kV 0 kV 0 kV 0 kV Open 0 kV 0 kV 0.415 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 A Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV 0 kV Open Open 0 kV
±
± 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kV 0 kA 0 kV Open 0 kV 0 kA 0 kV Open 0 kV Open 0 kV Open 0 kV Open 0 kV 0 kV 0.415 kV
0 kA 0 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 70 kA
0 kA
Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

CU 20 m
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

EDG CB R
630 A
Open 0.415 kV
1250 A 70 kA
0.4 kV
63 kA AUX-ESS CB
1600 A
LV COMMON ESS SWITCHBORD 0.4 kV .77%
LV COMMON NON ESS SWCHBRD
0.4 kV 1600 0A kA 63 kA 100 0.4 kV 600 A0 kA 100.7%

0.0% PF 0.03 MVA 0.04 MVA 0.01 MVA 0 MVA 0 MVA 0.09 MVA 0 MVA 0 MVA 0.01 MVA 0.04 MVA 0 MVA 0 MVA 0.04 MVA 0 MVA 0.09 MVA 0.03 MVA 0.04 MVA 0 MVA 0.02 MVA 0 MVA 0.01 MVA
38.1 A 51.4 A 19.2 A 0.9 A 1.6 A 134.3 A 4.3 A 4.3 A 21.5 A 57.7 A 0.9 A 2.1 A 58.6 A 0 A 129.2 A 45.8 A 59.1 A 1.5 A 27.3 A 0.1 A 21.5 A
80.0% PF 80.0% PF 80.0% PF 75.0% PF 75.0% PF 80.0% PF 66.7% PF 66.7% PF 80.0% PF 90.0% PF 90.0% PF 82.0% PF 90.0% PF 0.0% PF 80.0% PF 80.5% PF 0.415 kV 83.0% PF 87.0% PF 92.0% PF 0.0% PF 0 kV 80.0% PF
SGS TRANSFORMER LVCB 100 A 0 A
250 A CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open 0 A CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
0.415 kV 0 A 0 A 0 A Open 0 A 0 A 0 A 0 A Open 0 A Open 0 A 0 A 0 A 0 A CB108 0 A 0 A 160 A 0 A 0 A 0 A 200 A 0 A 125 A Open 0 A 70 kA 0 A 0 A 0 A 0 A 0 A Open 0 A 0 A Open
70 kA 0 A Open 0 A 0 A 0 A Open 0 A 0 A Open 0 kV 0 A 0 kV Open 0 A 0 A 0 A 0 A 0 A 0 kV 0 kV 0 kV 0 kV 0 A 0 A 0 kA
Open 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0.415 kV 0 kV 0.415 kV 0 kV 0.4 kV 0 kV 0 kA 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV Battery2
SGS TRANSFORMER 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA
Cont9 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA Cont2 0 kA Open 0 kA 0 kA 0 kA
0.4/6.3 kV Cont10 Cont42 Cont6 Cont1 Cont4 CU 150 m
150 kVA Cont8 Cont39 Cont7 UPS1 Cont5 ± CU 30 m 1-4/C 240 Cont11 Cont12 Cont13 Cont14 Cont15
6.3 kV UPS19 CU 30 m Cont16
YNd1 UPS18 R 1-4/C 240 Open UPS2
Bus2 CU 30 m 1-4/C 240 Open Open
225 A 0.4 kV CU 150 m
CU 0 ft Bus3 CU 30 m 1-4/C 240 1-4/C 240 ±

0.23 kV 225 A
1-3/C 35 1-4/C 240
Bus20 Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB 225
0.23A kV AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA 0.4 kV
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 225 A
230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 13:57:16 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Short Circuit Study Result
150 kV CB3 (Initial Short Circuit/I"k) Case Study Scheme - 1
Bus14

T3
37.72 kA
Power Supply from GI Solok
Page 1 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91

GH Balun
20 kV
CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3
900 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101


Open Open Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.132


150 kV .068 kA kA

.064 kA
GENERATOR STAGE-1 CB129 CB171
89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV .911 kA
±
T11
R .889 kA 1.8
kA
T10 3 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 3.15 kA 6.3 kV 6.3 kV 1.4 kA
.006 kA .011 kA .012 kA .015 kA 3.2 .044 kA 3.15 kA .044 kA .495 kA .698 kA .318 kA .252 kA 3.2
kA kA

3.2 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
2.15 kA LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV 22.72 kA
5.81 kA 1.56 kA .07 kA .009 kA .666 kA 30.7
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 25 kA 0.4 kV 26.56 kA
.278 kA .375 kA .467 kA .021 kA .011 kA 1.14 kA .421 kA .018 kA .051 kA 1.56 kA 1.08 kA .412 kA .431 kA .037 kA .199 kA .004 kA 27.
2 kA
30.7
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable 22.28 kA 22.28 kA
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW 21.5 kA TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 9.87 kA
21.74 kA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 13:59:45 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Short Circuit Study Result
150 kV CB3 (Peak Short Circuit/Ip) Case Study Scheme - 1
Bus14

T3
Power Supply from GI Solok
Page 2 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91

GH Balun
20 kV
CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3
900 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101


Open Open Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.275


150 kV kA

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV
±
T11
R
3.8
kA
T10 3 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.3 kV 6.3 kV
6.7 6.7
kA kA

6.7 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
65.5
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 0.4 kV
52.
5 kA
65.5
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:00:13 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Motor Starting Study Result
150 kV CB3
(Before) Case Study Scheme - 1
Bus14

T3
0.8 MW
-0.07 Mvar

150/20 kV
60 MVAYNyn1
Power Supply from GI Solok
GH Solok 20 kV
-7.5% TapP

108.12
% Page 1 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
GH Alahan 107.54 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 106.71 DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
5%
106.0

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 108.46
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


6%
150 kV 108.4

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
108.38
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
6% UAT CB
MV COMMON SGS SWBD % MV COMMON SWITCHBOARD 107.8 MV UNIT SWITCHBOARD
6.3 kV 107.86 6.3 kV 6.3 kV 107.86
%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
1500
ML-Em Cable 6.3/0.4 kV 107.86
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1-3/C 35 0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 4%
LV UNIT SWITCHBOARD 109.6
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD .64%


LV COMMON NON ESS SWCHBRD %
0.4 kV 109 0.4 kV 109.58

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:59:45 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Motor Starting Study Result
150 kV CB3
(During) Case Study Scheme - 1
Bus14

T3
2 MW
5.7 Mvar

150/20 kV
60 MVAYNyn1
Power Supply from GI Solok
GH Solok 20 kV
-7.5% TapP

106.93
% Page 2 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

GH Alahan 92.86% 6.3 kV


20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 83.16% DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
%
77.86

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 77.3%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


150 kV 77.3%

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 76.36%
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
% UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 71.17 MV UNIT SWITCHBOARD
6.3 kV 71.17% 6.3 kV 6.3 kV 71.17%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 70.94%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
0.5 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
3.5 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD 71.5%
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 71.5% 0.4 kV 71.41%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 15:00:07 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 5 : Motor Starting Study Result
150 kV CB3
(After) Case Study Scheme - 1
Bus14

T3
1.9 MW
1.3 Mvar

150/20 kV
60 MVAYNyn1
Power Supply from GI Solok
GH Solok 20 kV
-7.5% TapP

107.84
% Page 3 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
GH Alahan 103.76 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 100.53 DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
%
98.49

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 100.23
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


3%
150 kV 100.2

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 99.96%
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
% UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 98.43 MV UNIT SWITCHBOARD
6.3 kV 98.43% 6.3 kV 6.3 kV 98.43%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 98.3%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA %
LV UNIT SWITCHBOARD 99.88
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 99.88% 0.4 kV 99.81%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 15:01:04 Apr 25, 2019 Project File: MuaraLaboh


ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI
Engineer: Study Case: MS HWP Config.: MS-GI

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI

MOTOR STARTING ANALYSIS


Motor Terminal Voltage (Motor Base)
Attachment 5 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 1
Power Supply from GI Solok
120 Page 4 of 6

100

80
Vt (% of Motor Rated kV)

60

40

20

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI
Engineer: Study Case: MS HWP Config.: MS-GI

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI

MOTOR STARTING ANALYSIS


Bus Voltage
Attachment 5 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 1
Power Supply from GI Solok
120 Page 5 of 6

110
Vbus (% of Bus Nominal kV)

100

90

80

70

60
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI
Engineer: Study Case: MS HWP Config.: MS-GI

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI

MOTOR STARTING ANALYSIS


Motor Line Current

Attachment 5 : Motor Starting Study Result


HOT WELL PUMP-A Case Study Scheme - 1
Power Supply from GI Solok
400 Page 6 of 6

300
I (% of FLA)

200

100

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 6

POWER SYSTEM STUDY RESULT OF SCHEME 2

(POWER SUPPLY FROM 20KV GI SOLOK + TWO (2) HYDRO POWER PLANT)

Page 32 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


One-Line Diagram - SLD (Load Flow Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Load Flow Study Result
150 kV CB3
3150 A
40 kA
150 kV
Case Study Scheme - 2
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
2.2 MVA
8.6 A
150 kV 62.4% PF
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP
2.2 MVA
59.7 A %
GH Solok 20 kV 62.6% PF 107.77

2.2 MVA
59.7 A
62.6%
CB121 PF
630 A
0 kA
24 kV
Bus8
20 kV SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
AL 1 km CU 100 m AL 62 km
SATURN
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77 2000 A
630 A 2000 A 2000 A 2000 A 16 kA
0 kA 16 kA 16 kA 16 kA 6.6 kV
24 kV 6.6 kV 6.6 kV 6.6 kV
1.1 MVA 1.1 MVA 1.1 MVA
2.3 MVA %
94 A 94 A 94 A
GH Alahan 64.4 A 102.86
1.1 MVA 95.0% PF % 95.0% PF 6.3 kV 95.0% PF 102.63%
Bus23 94 A Bus24 102.64
20 kV 800 A 16 kA 59.6% PF Bus10 Bus15
6.3 kV 95.0% PF 6.3 kV 1.1 MVA 6.3 kV 3% 1.1 MVA 1.1 MVA
102.6
2.3 MVA %
94 A 94 A 94 A
64.4 A 102.64
1.1 MVA 95.0% PF 95.0% PF 95.0% PF
59.6% PF 94 A T5 T7
95.0%
T4 PF T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
630 A Open 0 A 630 A 630 A 6 MVA YNd1
0 kA 0 kA 0 kA 0 kA 6 MVA YNd1 YNd1 YNd1
24 kV 24 kV 24 kV 24 kV

AL CB117 CB120 CB123


50 km 630 A 630 A CB122 630 A
NITROGEN 0 kA 0 kA 630 A 0 kA
Sungai Cehana 20kV IPP 24 kV 24 kV 0 kA 24 kV
Open Taman Babungo 1.5 MVA 20 kV 24 kV
20 kV 0.5 MVA %
GH Balun4 900 kvar 4.2 MVA 102.13
CB118 0 A 2.4 MVA CAP1 118.4 A
CAP5 0 kA 24 kV 69.2 A 95.3% PF
900 kvar 56.1% PF Open CB115 CB107
630 A 630 A
0 kA 0 kA
CB91 24 kV 24 kV
630 A 42 km
0 kA AL AL
GH Balun 24 kV DARTS 1120 42 km
20 kV 800 A16 kA 99.15% DARTS 1120

2.4 MVA Open CB7 CB5


69.2 A 630 A 630 A
0 kA 0 kA
56.1% PF 24 kV 24 kV
CB89
630 A
0 kA
24 kV GH Lbk Gadang
20 kV
Open 2.4 MVA 0.9 MVA 0.9 MVA 98.51%
69.9 A 25.5 A 25.5 A
20 kV 98.1% PF 90.0% PF 90.0% PF
CB114 0 A GH Balun2 CB2
CAP3 0 kA 24 kV 630 A
7200 kvar 0 kA CB92
AL 24 km 24 kV CB90 630 A
630 A 0 kA
KRYPTON 0 kA 24 kV
24 kV

CB88
630 A AL 25 km
0 kA
24 kV
CRICKET 1120 Feeder Lbk Kota Feeder Malako
2.4 MVA 1 MVA 1 MVA
71.3 A
20kV GI ML 54.5% PF
20 kV
%
2.7 MVA 0.9 MVA 0.9 MVA 96.94
80.4 A 25.9 A 25.9 A
76.0% PF 90.0% PF 90.0% PF
CB86 CB99 CB101
0 A 630 A 630 A Fuse1
0 kA 0 kA 0 kA
24 kV 24 kV 24 kV Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA
3150 A
40 kA
150 kV

GI Sungai Rumbai GI Muara Laboh


150 kV 3200 A 40 kA 98.58%
9800 MVAsc
2.7 MVA
10.5 A
76.6% PF

150 kV CB2
3150 A
40 kA
150 kV
Open 150 kV CB1 Z1
3150 A
40 kA
150 kV
EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2
1 MW 1 MW

GI PLTP SEML 150 kV CB


3150 A %
150 kV 3150 A 40 kA 40 kA 98.58
150 kV
2.7 MVA
10.5 A CB129
76.6% PF GENERATOR STAGE-1 CB171
89.25 MW 0 A 0 A
0 kV 0 kV
GENERATOR TRANSFORMER CB 0 kA
3150 A 150 kV 0 kA
50 kA
GSUT Bus25
0.4 kV 3200 A
150/11 kV
100 MVAYNd1 GENERATOR CB 0 kA
-2.5% TapP Open 6300 A
80 kA
GV BUS 12 kV %
100.83
11 kV 6500 A 200 kA
±
T11
R 2.7 MVA 0.4/6.3 kV
139 A 5 MVA Dyn1
76.8% PF T10
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
1250 A
MV-SGS CB2 Open 16 kA
7.2 kV
UAT CB2
630 A 1250 A
16 kA Open 16 kA
7.2 kV % UAT CB 7.2 kV
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 99.19 MV UNIT SWITCHBOARD 1250 A
6.3 kV 225 A 0 kA 99.19% 6.3 kV 100 A0 kA 6.3 kV 800 A 0 kA 16 kA 99.19%
7.2 kV
0.01 MVA 0.02 MVA 0.02 MVA 0.02 MVA 0.07 MVA 0.07 MVA 0.6 MVA 1.2 MVA 0.4 MVA 0.3 MVA
1 A 1.8 A 1.7 A 2.1 A 6.6 A 6.3 kV 6.6 A 55.2 A 112.1 A 40.7 A 29.3 A
87.4% PF 87.4% PF 86.1% PF 87.3% PF 87.1% PF 200 A 87.1% PF 83.3% PF 71.0% PF 84.0% PF 80.0% PF
UST HVCB CB30 CB32
SGS TRANSFORMER HVCB BUS COUPLER 630 A 630 A 630 A CB96 CB97 CB194 Open CB196
Open 100 A CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB 16 kA 16 kA 16 kA 16 kA 630 A 630 A 630 A 630 A
16 kA 0 A 0 A 0 A 0 A 630 A 630 A 12 kV 7.2 kV Open 6.3 kV 16 kA 16 kA
Open 6.3 16 kA 16 kA
6.3 kV 0 kA 0 kA 0 kA 0 kA 16 kA Open 16 kA 6.3 kV kV 6.3 kV 6.3 kV
7.2 kV 7.2 kV 7.2 kV 7.2 kV 12 kV 12 kV ±

R
CU 40 m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R 6.3 kV Bus1
±
±
R UTILITY TRANSFORMER R 124 m
CU 1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
CU 1500 m 6.3/0.4 kV 99.07%
Terminal HWP
CU 500 m -2.5% TapP -2.5% TapP 2.5 MVA 6.3 kV
CU 2000 m 1-3/C 35 1.2 MVA
1-3/C 35 1-3/C 25 CU 1000 m OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
112.1 A 400 kW
1-3/C 35 400 A0.4 kV0 kA ±
71.0% PF 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
4000 A HOT WELL PUMP-A VACUUM PUMP-B 265 kW
0.4 kV 930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX 63 kA
250 kVA 0.6 MVA 6%
LV UNIT SWITCHBOARD 847 A 100.6
0.4 kV 4000 A 0 kA 83.9% PF
0.4 MVA 0.1 MVA 0.01 MVA 0 MVA 0.08 MVA
568.2
CB72 A 160.6 A 9.5 A 0.6 A 109.2 A
82.2% PF 89.0% PF 80.0% PF 0.0% PF 85.0% PF
1600 A CB60
0.415 kV CB61 Open CB10
300 A 300 A 0 A Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
70 kA 0 kV Open 0.415 kV 0 A 0 A CB21 Open 0 A 0 A Open 0 A CB202 Open CB53 0 A CB50 CB40 Open 0 A CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
0 kV Open 0 kV 0 A 0 A 0 A 0 A 0 A Open 20 A 0 A Open 0 A 0 A 0 A Open 0 A 0 A 0 A Open 0 kV 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 630 A
0 kA 70 kA 0 kA 0 kV 0 kV Open 0 kV 0 kV 0 kV 0 kV Open 0 kV 0 kV 0.415 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 A Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV 0 kV Open Open 0 kV
±
± 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kV 0 kA 0 kV Open 0 kV 0 kA 0 kV Open 0 kV Open 0 kV Open 0 kV Open 0 kV 0 kV 0.415 kV
0 kA 0 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 70 kA
0 kA
Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

CU 20 m
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

EDG CB R
630 A
Open 0.415 kV
1250 A 70 kA
0.4 kV
63 kA AUX-ESS CB
1600 A
LV COMMON ESS SWITCHBORD 0.4 kV .66%
LV COMMON NON ESS SWCHBRD
0.4 kV 1600 0A kA 63 kA 100 0.4 kV 600 A0 kA 100.6%

0.0% PF 0.03 MVA 0.04 MVA 0.01 MVA 0 MVA 0 MVA 0.09 MVA 0 MVA 0 MVA 0.01 MVA 0.04 MVA 0 MVA 0 MVA 0.04 MVA 0 MVA 0.09 MVA 0.03 MVA 0.04 MVA 0 MVA 0.02 MVA 0 MVA 0.01 MVA
38.1 A 51.4 A 19.2 A 0.9 A 1.6 A 134.4 A 4.3 A 4.3 A 21.5 A 57.8 A 0.9 A 2.1 A 58.6 A 0 A 129.3 A 45.8 A 59.2 A 1.5 A 27.3 A 0.1 A 21.5 A
80.0% PF 80.0% PF 80.0% PF 75.0% PF 75.0% PF 80.0% PF 66.7% PF 66.7% PF 80.0% PF 90.0% PF 90.0% PF 82.0% PF 90.0% PF 0.0% PF 80.0% PF 80.5% PF 0.415 kV 83.0% PF 87.0% PF 92.0% PF 0.0% PF 0 kV 80.0% PF
SGS TRANSFORMER LVCB 100 A 0 A
250 A CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open 0 A CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
0.415 kV 0 A 0 A 0 A Open 0 A 0 A 0 A 0 A Open 0 A Open 0 A 0 A 0 A 0 A CB108 0 A 0 A 160 A 0 A 0 A 0 A 200 A 0 A 125 A Open 0 A 70 kA 0 A 0 A 0 A 0 A 0 A Open 0 A 0 A Open
70 kA 0 A Open 0 A 0 A 0 A Open 0 A 0 A Open 0 kV 0 A 0 kV Open 0 A 0 A 0 A 0 A 0 A 0 kV 0 kV 0 kV 0 kV 0 A 0 A 0 kA
Open 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0.415 kV 0 kV 0.415 kV 0 kV 0.4 kV 0 kV 0 kA 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV Battery2
SGS TRANSFORMER 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA
Cont9 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA Cont2 0 kA Open 0 kA 0 kA 0 kA
0.4/6.3 kV Cont10 Cont42 Cont6 Cont1 Cont4 CU 150 m
150 kVA Cont8 Cont39 Cont7 UPS1 Cont5 ± CU 30 m 1-4/C 240 Cont11 Cont12 Cont13 Cont14 Cont15
6.3 kV UPS19 CU 30 m Cont16
YNd1 UPS18 R 1-4/C 240 Open UPS2
Bus2 CU 30 m 1-4/C 240 Open Open
225 A 0.4 kV CU 150 m
CU 0 ft Bus3 CU 30 m 1-4/C 240 1-4/C 240 ±

0.23 kV 225 A
1-3/C 35 1-4/C 240
Bus20 Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB 225
0.23A kV AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA 0.4 kV
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 225 A
230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 13:58:27 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Short Circuit Study Result
150 kV CB3 (Initial Short Circuit/I"k) Case Study Scheme - 2
Bus14

T3
37.72 kA
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
Page 1 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.278


150 kV .211 kA kA

.067 kA
GENERATOR STAGE-1 CB129 CB171
89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV 2.56 kA
±
T11
R .889 kA 3.4
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 4.95 kA 6.3 kV 6.3 kV 3.2 kA
.006 kA .011 kA .012 kA .015 kA 5.0 .044 kA 4.95 kA .044 kA .495 kA .698 kA .318 kA .252 kA 5.0
kA kA

5.0 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
2.75 kA LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV 29.69 kA
5.81 kA 1.56 kA .07 kA .009 kA .666 kA 37.6
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 31.95 kA 0.4 kV 31.91 kA
.278 kA .375 kA .467 kA .021 kA .011 kA 1.14 kA .421 kA .018 kA .051 kA 1.56 kA 1.08 kA .412 kA .431 kA .037 kA .199 kA .004 kA 32.
6 kA
37.6
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable 25.76 kA 25.76 kA
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW 25.09 kA TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 10.48 kA
25.3 kA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:06:42 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Short Circuit Study Result
150 kV CB3 (Peak Short Circuit/Ip) Case Study Scheme - 2
Bus14

T3
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
Page 2 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.595


150 kV kA

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV
±
T11
R
7.4
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.3 kV 6.3 kV
11.1 11.1
kA kA

11.1 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
83.4
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 0.4 kV
63.
3 kA
83.4
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:05:28 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Motor Starting Study Result
150 kV CB3
(Before) Case Study Scheme - 2
Bus14

T3
1.2 MW
0.09 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
GH Solok 20 kV
-7.5% TapP

108.09
% Page 1 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
0.7 MW 0.7 MW 0.7 MW
GH Alahan 106.94 0.3 Mvar 109.29
% 0.3 Mvar 6.3 kV 0.3 Mvar 109.29%
20 kV Bus23 0.7 MW Bus24 Bus10 Bus15
6.3 kV 0.3 Mvar 6.3 kV 6.3 kV 9%
109.2
%
109.29
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 108.83
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 105.7% DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV %
Open 105.86

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
7%
104.7

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
3.75% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 108.46
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


6%
150 kV 108.4

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
108.37
11 kV
±
T11
R
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
6% UAT CB
MV COMMON SGS SWBD % MV COMMON SWITCHBOARD 107.8 MV UNIT SWITCHBOARD
6.3 kV 107.86 6.3 kV 6.3 kV 107.86
%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
1500
ML-Em Cable 6.3/0.4 kV 107.86
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1-3/C 35 0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 4%
LV UNIT SWITCHBOARD 109.6
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD .64%


LV COMMON NON ESS SWCHBRD %
0.4 kV 109 0.4 kV 109.58

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 15:58:04 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Motor Starting Study Result
150 kV CB3
(During) Case Study Scheme - 2
Bus14

T3
1.9 MW
3 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
GH Solok 20 kV
-7.5% TapP

107.49
% Page 2 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

0.8 MW 0.9 MW 0.9 MW


GH Alahan 99.52% 1.2 Mvar 104.19
% 1.4 Mvar 6.3 kV 1.4 Mvar 104.47%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 1.2 Mvar 6.3 kV 6.3 kV 7%
104.4
%
104.19
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 102.71
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 93.77% DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open 94.66%

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
%
90.45

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
3.75% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 90.94%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 90.94

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 89.87%
11 kV
±
T11
R
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
% UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 84.01 MV UNIT SWITCHBOARD
6.3 kV 84.01% 6.3 kV 6.3 kV 84.01%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 83.74%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
0.7 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
4.8 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA %
LV UNIT SWITCHBOARD 84.91
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 84.91% 0.4 kV 84.83%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 15:58:37 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 6 : Motor Starting Study Result
150 kV CB3
(After) Case Study Scheme - 2
Bus14

T3
1.7 MW
0.6 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
GH Solok 20 kV
-7.5% TapP

107.97
% Page 3 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
0.8 MW 0.9 MW 0.9 MW
GH Alahan 105.39 0.5 Mvar 108.3%
0.5 Mvar 6.3 kV 0.5 Mvar 108.35%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 0.5 Mvar 6.3 kV 6.3 kV 5%
108.3

108.3%
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 107.64
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 103.15 DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV %
Open 103.51

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
5%
101.6

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
3.75% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 104.76
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


6%
150 kV 104.7

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
104.51
11 kV
±
T11
R
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
4% UAT CB
MV COMMON SGS SWBD % MV COMMON SWITCHBOARD 103.0 MV UNIT SWITCHBOARD
6.3 kV 103.04 6.3 kV 6.3 kV 103.04
%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
1500
ML-Em Cable 6.3/0.4 kV 102.92
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 6%
LV UNIT SWITCHBOARD 104.6
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD .66%


LV COMMON NON ESS SWCHBRD
0.4 kV 104 0.4 kV 104.6%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 15:59:24 Apr 25, 2019 Project File: MuaraLaboh


ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP
Engineer: Study Case: MS HWP Config.: MS-GI+IPP

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP

MOTOR STARTING ANALYSIS


Motor Terminal Voltage (Motor Base)
Attachment 6 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 2
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
120 Page 4 of 6

100

80
Vt (% of Motor Rated kV)

60

40

20

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP
Engineer: Study Case: MS HWP Config.: MS-GI+IPP

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP

MOTOR STARTING ANALYSIS


Bus Voltage
Attachment 6 : Motor Starting Study Result
Case Study Scheme - 2
HOT WELL PUMP-A Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
Page 5 of 6
120

110
Vbus (% of Bus Nominal kV)

100

90

80

70
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP
Engineer: Study Case: MS HWP Config.: MS-GI+IPP

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP

MOTOR STARTING ANALYSIS


Motor Line Current
Attachment 6 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 2
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant
500 Page 6 of 6

400

300
I (% of FLA)

200

100

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 7

POWER SYSTEM STUDY RESULT OF SCHEME 3

(POWER SUPPLY FROM 20KV GI SOLOK + TWO (2) DEG 1MW)

Page 33 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


One-Line Diagram - SLD (Load Flow Analysis)
GI Solok
9800 MVAsc Attachment 7 : Load Flow Study Result
150 kV CB3
3150 A
40 kA
150 kV
1.3 MVA
4.8 A
Case Study Scheme - 3
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
150 kV 64.0% PF
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP
1.3 MVA
33.5 A %
GH Solok 20 kV 64.1% PF 107.92

1.3 MVA
33.5 A
64.1%
CB121 PF
630 A
0 kA
24 kV
Bus8
20 kV SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
AL 1 km CU 100 m AL 62 km
SATURN
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77 2000 A
630 A 2000 A 2000 A 2000 A 16 kA
0 kA 16 kA 16 kA 16 kA 6.6 kV
24 kV 6.6 kV 6.6 kV 6.6 kV

1.4 MVA %
GH Alahan 38.2 A 105.08 6.3 kV
20 kV 800 A 16 kA 57.0% PF Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV
1.4 MVA
38.2 A
57.0% PF T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
630 A Open 0 A 630 A 630 A 6 MVA YNd1
0 kA 0 kA 0 kA 0 kA 6 MVA YNd1 YNd1 YNd1
24 kV 24 kV 24 kV 24 kV

AL CB117 CB120 CB123


50 km 630 A 630 A CB122 630 A
NITROGEN 0 kA 0 kA 630 A 0 kA
Sungai Cehana 20kV IPP 24 kV 24 kV 0 kA 24 kV
Open Taman Babungo 1.5 MVA 20 kV 24 kV
20 kV 0.5 MVA
GH Balun4 900 kvar
CB118 0 A 1.5 MVA CAP1
CAP5 0 kA 24 kV 43.3 A
900 kvar 50.6% PF CB115 CB107
630 A 630 A
0 kA 0 kA
CB91 24 kV 24 kV
630 A 42 km
0 kA AL AL
GH Balun 24 kV % DARTS 1120 42 km
20 kV 800 A16 kA 102.79 DARTS 1120

1.5 MVA CB7 CB5


43.3 A 630 A 630 A
0 kA 0 kA
50.6% PF 24 kV 24 kV
CB89
630 A
0 kA
24 kV GH Lbk Gadang
20 kV
Open

20 kV
CB114 0 A GH Balun2 CB2
Open 630 A
CAP3 0 kA 24 kV 0 kA
900 kvar AL 24 kV CB90 CB92
24 km 630 A 630 A
KRYPTON 0 kA 0 kA
24 kV 24 kV

CB88
630 A AL 25 km
0 kA
24 kV
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1.6 MVA 0.1 MVA 1 MVA 1 MVA
45.7 A 2.8 A
20kV GI ML 48.0% PF -0.0% PF
20 kV
9%
1.7 MVA 101.3
48.2 A
45.4% PF
CB86 CB99 CB101
0 A Open 630 A Open 630 A Fuse1
0 kA 0 kA 0 kA
24 kV 24 kV 24 kV Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA
3150 A
40 kA
150 kV

GI Sungai Rumbai GI Muara Laboh %


150 kV 3200 A 40 kA 100.77
9800 MVAsc
1.7 MVA
6.4 A
45.7% PF

150 kV CB2
3150 A
40 kA
150 kV
Open 150 kV CB1 Z1
3150 A
40 kA
150 kV
EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2
1 MW 1 MW

GI PLTP SEML 150 kV CB


3150 A 7%
150 kV 3150 A 40 kA 40 kA 100.7
150 kV
1.7 MVA
6.4 A CB129
45.7% PF GENERATOR STAGE-1 CB171
89.25 MW 0 A 0 A
0 kV 0 kV
GENERATOR TRANSFORMER CB 0 kA
3150 A 150 kV 0 kA 0.7 MVA 0.7 MVA 100%
50 kA
GSUT Bus25 939.9 A 939.9 A
0.4 kV 98.6% PF 98.6% PF 3200 A
150/11 kV
100 MVAYNd1 GENERATOR CB 1.3 MVA 0 kA
Open 6300 A 1879.8 A
80 kA 98.6% PF
GV BUS 12 kV %
100.52
11 kV 6500 A 200 kA
±
T11
R 1.7 MVA 0.4/6.3 kV
87.6 A 3 MVA Dyn1
45.8% PF T10
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
1250 A
MV-SGS CB2 16 kA
7.2 kV
UAT CB2
630 A 1250 A
16 kA Open 16 kA
7.2 kV % UAT CB 7.2 kV
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 99.15 MV UNIT SWITCHBOARD 1250 A
6.3 kV 225 A 0 kA 99.15% 6.3 kV 100 A0 kA 6.3 kV 800 A 0 kA 16 kA 99.15%
7.2 kV
0.01 MVA 0.02 MVA 0.02 MVA 0.02 MVA 0.07 MVA 0.07 MVA 0.6 MVA 1.2 MVA 0.4 MVA 0.3 MVA
1 A 1.8 A 1.7 A 2.1 A 6.6 A 6.3 kV 6.6 A 55.2 A 112.2 A 40.7 A 29.3 A
87.4% PF 87.4% PF 86.1% PF 87.3% PF 87.1% PF 200 A 87.1% PF 83.3% PF 71.0% PF 84.0% PF 80.0% PF
UST HVCB CB30 CB32
SGS TRANSFORMER HVCB BUS COUPLER 630 A 630 A 630 A CB96 CB97 CB194 Open CB196
Open 100 A CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB 16 kA 16 kA 16 kA 16 kA 630 A 630 A 630 A 630 A
16 kA 0 A 0 A 0 A 0 A 630 A 630 A 12 kV 7.2 kV Open 6.3 kV 16 kA 16 kA
Open 6.3 16 kA 16 kA
6.3 kV 0 kA 0 kA 0 kA 0 kA 16 kA Open 16 kA 6.3 kV kV 6.3 kV 6.3 kV
7.2 kV 7.2 kV 7.2 kV 7.2 kV 12 kV 12 kV ±

R
CU 40 m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R 6.3 kV Bus1
±
±
R UTILITY TRANSFORMER R 124 m
CU 1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
CU 1500 m 6.3/0.4 kV 99.03%
Terminal HWP
CU 500 m -2.5% TapP -2.5% TapP 2.5 MVA 6.3 kV
CU 2000 m 1-3/C 35 1.2 MVA
1-3/C 35 1-3/C 25 CU 1000 m OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
112.2 A 400 kW
1-3/C 35 400 A0.4 kV0 kA ±
71.0% PF 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
4000 A HOT WELL PUMP-A VACUUM PUMP-B 265 kW
0.4 kV 930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX 63 kA
250 kVA 0.6 MVA 2%
LV UNIT SWITCHBOARD 847.3 A 100.6
0.4 kV 4000 A 0 kA 83.9% PF
0.4 MVA 0.1 MVA 0.01 MVA 0 MVA 0.08 MVA
568.5
CB72 A 160.7 A 9.5 A 0.6 A 109.3 A
82.2% PF 89.0% PF 80.0% PF 0.0% PF 85.0% PF
1600 A CB60
0.415 kV CB61 Open CB10
300 A 300 A 0 A Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
70 kA 0 kV Open 0.415 kV 0 A 0 A CB21 Open 0 A 0 A Open 0 A CB202 Open CB53 0 A CB50 CB40 Open 0 A CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
0 kV Open 0 kV 0 A 0 A 0 A 0 A 0 A Open 20 A 0 A Open 0 A 0 A 0 A Open 0 A 0 A 0 A Open 0 kV 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 630 A
0 kA 70 kA 0 kA 0 kV 0 kV Open 0 kV 0 kV 0 kV 0 kV Open 0 kV 0 kV 0.415 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 A Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV 0 kV Open Open 0 kV
±
± 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kV 0 kA 0 kV Open 0 kV 0 kA 0 kV Open 0 kV Open 0 kV Open 0 kV Open 0 kV 0 kV 0.415 kV
0 kA 0 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 70 kA
0 kA
Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

CU 20 m
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

EDG CB R
630 A
Open 0.415 kV
1250 A 70 kA
0.4 kV
63 kA AUX-ESS CB
1600 A
LV COMMON ESS SWITCHBORD 0.4 kV .62%
LV COMMON NON ESS SWCHBRD %
0.4 kV 1600 0A kA 63 kA 100 0.4 kV 600 A0 kA 100.56

0.0% PF 0.03 MVA 0.04 MVA 0.01 MVA 0 MVA 0 MVA 0.09 MVA 0 MVA 0 MVA 0.01 MVA 0.04 MVA 0 MVA 0 MVA 0.04 MVA 0 MVA 0.09 MVA 0 MVA 0.03 MVA 0.04 MVA 0 MVA 0.02 MVA 0 MVA 0.01 MVA
38.1 A 51.4 A 19.2 A 0.9 A 1.6 A 134.5 A 4.3 A 4.3 A 21.5 A 57.8 A 0.9 A 2.1 A 58.6 A 0 A 129.4 A 0 A 45.8 A 59.2 A 1.5 A 27.3 A 0.1 A 21.5 A
80.0% PF 80.0% PF 80.0% PF 75.0% PF 75.0% PF 80.0% PF 66.7% PF 66.7% PF 80.0% PF 90.0% PF 90.0% PF 82.0% PF 90.0% PF 80.0% PF 80.5% PF 0.415 kV 83.0% PF 87.0% PF 92.0% PF 0.0% PF 0 kV 80.0% PF
SGS TRANSFORMER LVCB 100 A 0 A
250 A CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open 0 A CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
0.415 kV 0 A 0 A 0 A Open 0 A 0 A 0 A 0 A Open 0 A Open 0 A 0 A 0 A 0 A CB108 0 A 0 A 160 A 0 A 0 A 0 A 200 A 0 A 125 A Open 0 A 70 kA 0 A 0 A 0 A 0 A 0 A Open 0 A 0 A Open
70 kA 0 A Open 0 A 0 A 0 A Open 0 A 0 A Open 0 kV 0 A 0 kV Open 0 A 0 A 0 A 0 A 0 A 0 kV 0 kV 0 kV 0 kV 0 A 0 A 0 kA
Open 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0.415 kV 0 kV 0.415 kV 0 kV 0.4 kV 0 kV 0 kA 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV Battery2
SGS TRANSFORMER 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA
Cont9 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA Cont2 0 kA Open 0 kA 0 kA 0 kA
0.4/6.3 kV Cont10 Cont42 Cont6 Cont1 Cont4 CU 150 m
150 kVA Cont8 Cont39 Cont7 UPS1 Cont5 ± CU 30 m 1-4/C 240 Cont11 Cont12 Cont13 Cont14 Cont15
6.3 kV UPS19 CU 30 m Cont16
YNd1 UPS18 R 1-4/C 240 Open UPS2
Bus2 CU 30 m 1-4/C 240 Open Open
225 A 0.4 kV CU 150 m
CU 0 ft Bus3 CU 30 m 1-4/C 240 1-4/C 240 ±

0.23 kV 225 A
1-3/C 35 1-4/C 240
Bus20 Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB 225
0.23A kV AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA 0.4 kV
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 225 A
230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 13:57:48 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 7 : Short Circuit Study Result
150 kV CB3 (Initial Short Circuit/I"k) Case Study Scheme - 3
Bus14

T3
37.72 kA
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
Page 1 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.278


150 kV .211 kA kA

.067 kA
GENERATOR STAGE-1 CB129 CB171
89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV 2.56 kA
±
T11
R .889 kA 3.4
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 4.95 kA 6.3 kV 6.3 kV 3.2 kA
.006 kA .011 kA .012 kA .015 kA 5.0 .044 kA 4.95 kA .044 kA .495 kA .698 kA .318 kA .252 kA 5.0
kA kA

5.0 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
2.75 kA LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV 29.69 kA
5.81 kA 1.56 kA .07 kA .009 kA .666 kA 37.6
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 31.95 kA 0.4 kV 31.91 kA
.278 kA .375 kA .467 kA .021 kA .011 kA 1.14 kA .421 kA .018 kA .051 kA 1.56 kA 1.08 kA .412 kA .431 kA .037 kA .199 kA .004 kA 32.
6 kA
37.6
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable 25.76 kA 25.76 kA
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW 25.09 kA TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 10.48 kA
25.3 kA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:04:55 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 7 : Short Circuit Study Result
150 kV CB3 (Peak Short Circuit/Ip) Case Study Scheme - 3
Bus14

T3
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
Page 2 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91

GH Balun
20 kV
CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3
900 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101


Open Open Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.348


150 kV kA

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA 102.8
Open GENERATOR CB kA

GV BUS
11 kV
±
T11
R
4.8
kA
T10 3 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.3 kV 6.3 kV
9.1 9.1
kA kA

9.1 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
76.2
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 0.4 kV
59.
1 kA
76.2
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:03:52 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 7 : Motor Starting Study Result
150 kV CB3
(Before) Case Study Scheme - 3
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
0.3 MW
0.2 Mvar
Bus14

150/20 kV
T3 60 MVAYNyn1

Page 1 of 6
-7.5% TapP

%
GH Solok 20 kV 108.07

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
GH Alahan 107.19 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 106.24 DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
9%
105.5

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 105.26
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


6%
150 kV 105.2

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
104%
GSUT Bus25 0.2 MW 0.2 MW
0.4 kV -0.1 Mvar -0.1 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
105.12
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
9% UAT CB
MV COMMON SGS SWBD % MV COMMON SWITCHBOARD 104.3 MV UNIT SWITCHBOARD
6.3 kV 104.39 6.3 kV 6.3 kV 104.39
%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
1500
ML-Em Cable 6.3/0.4 kV 104.39
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1-3/C 35 0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 5%
LV UNIT SWITCHBOARD 106.0
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD .05%


LV COMMON NON ESS SWCHBRD %
0.4 kV 106 0.4 kV 105.99

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 17:34:28 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 7 : Motor Starting Study Result
150 kV CB3
(During) Case Study Scheme - 3
Bus14

T3
1.4 MW
4.5 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
GH Solok 20 kV
-7.5% TapP

107.19
% Page 2 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

GH Alahan 96.2% 6.3 kV


20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 88.58% DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
%
84.41

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 82.44%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 82.44

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
80.28%
GSUT Bus25 0.2 MW 0.2 MW
0.4 kV 0.5 Mvar 0.5 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 81.66%
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
% UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 77.38 MV UNIT SWITCHBOARD
6.3 kV 77.38% 6.3 kV 6.3 kV 77.38%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 77.13%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
0.6 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
4.1 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD 78%
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 78% 0.4 kV 77.91%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:11:49 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 7 : Motor Starting Study Result
150 kV CB3
(After) Case Study Scheme - 3
Bus14

T3
1.2 MW
1 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
GH Solok 20 kV
-7.5% TapP

107.9%
Page 3 of 6
CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

%
GH Alahan 104.71 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 102.15 DARTS 1120

CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


Open
CAP3 Line2
900 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
6%
100.5

CB86 CB99 CB101


Open Open Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 99.91%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 99.91

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
98.62%
GSUT Bus25 0.3 MW 0.3 MW
0.4 kV 0.04 Mvar 0.04 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 99.66%
11 kV
±
T11
R
0.4/6.3 kV
T10 3 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
% UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 98.24 MV UNIT SWITCHBOARD
6.3 kV 98.24% 6.3 kV 6.3 kV 98.24%

UST HVCB CB30 CB32


SGS TRANSFORMER HVCB BUS COUPLER Open CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 98.1%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-AmCable 1-3/C 35 2.5 MVA
1 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1 Mvar 400 kW
1-3/C 35 0.4 kV ± 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA %
LV UNIT SWITCHBOARD 99.68
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 99.68% 0.4 kV 99.61%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± 30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R 1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240 ±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 17:35:20 Apr 25, 2019 Project File: MuaraLaboh


ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&EDG

MOTOR STARTING ANALYSIS


Motor Terminal Voltage (Motor Base)
Attachment 7 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 3
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
120 Page 4 of 6

100

80
Vt (% of Motor Rated kV)

60

40

20

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&EDG

MOTOR STARTING ANALYSIS


Bus Voltage
Attachment 7 : Motor Starting Study Result
Case Study Scheme - 3
HOT WELL PUMP-A Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
Page 5 of 6
110

100
Vbus (% of Bus Nominal kV)

90

80

70
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&EDG

MOTOR STARTING ANALYSIS


Motor Line Current
Attachment 7 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 3
Power Supply From 20kV Gi Solok + Two (2) DEG 1MW
500 Page 6 of 6

400

300
I (% of FLA)

200

100

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 8

POWER SYSTEM STUDY RESULT OF SCHEME 4

(POWER SUPPLY FROM 20KV GI SOLOK + TWO (2) HYDRO POWER PLANT + TWO (2)
DEG 1MW)

Page 34 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


One-Line Diagram - SLD (Load Flow Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Load Flow Study Result
150 kV CB3
3150 A
40 kA
150 kV
Case Study Scheme - 4
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
1.9 MVA
7.4 A
150 kV 76.6% PF
Bus14

150/20 kV
T3 60 MVAYNyn1
-5% TapP
1.9 MVA
52.9 A %
GH Solok 20 kV 76.7% PF 105.01

1.9 MVA
52.9 A
76.7%
CB121 PF
630 A
0 kA
24 kV
Bus8
20 kV SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
AL 1 km CU 100 m AL 62 km
SATURN
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77 2000 A
630 A 2000 A 2000 A 2000 A 16 kA
0 kA 16 kA 16 kA 16 kA 6.6 kV
24 kV 6.6 kV 6.6 kV 6.6 kV
1 MVA 1.1 MVA 1.1 MVA
2 MVA %
86.4 A 96 A 96 A
GH Alahan 56.7 A 101.09
1 MVA 90.0% PF % 90.0% PF 6.3 kV 90.0% PF 106.12%
Bus23 86.4 A Bus24 106.05
20 kV 800 A 16 kA 73.2% PF Bus10 Bus15
6.3 kV 90.0% PF 6.3 kV 1 MVA 6.3 kV 2% 1.1 MVA 1.1 MVA
106.1
0.6 MVA 0.4 MVA 1.3 MVA %
86.4 A 96 A 96 A
17.3 A 12.4 A 37.3 A 106.05
1 MVA 90.0% PF 90.0% PF 90.0% PF
-18.6% PF 90.0% PF 90.0% PF 86.4 A T5 T7
90.0%
T4 PF T8 6.3/20 kV 6.3/20 kV
CB98 CB103 CB87 CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
630 A Open 0 A 630 A 630 A 6 MVA YNd1
0 kA 0 kA 0 kA 0 kA 6 MVA YNd1 YNd1 YNd1
24 kV 24 kV 24 kV 24 kV

AL CB117 CB120 CB123


50 km 630 A 630 A CB122 630 A
NITROGEN 0 kA 0 kA 630 A 0 kA
Sungai Cehana 20kV IPP 24 kV 24 kV 0 kA 24 kV
Open Taman Babungo 1.5 MVA 20 kV 24 kV
20 kV 0.5 MVA %
GH Balun4 900 kvar 4.2 MVA 105.45
CB118 0 A CAP1 114.9 A
CAP5 0 kA 24 kV 90.4% PF
900 kvar Open CB115 CB107
630 A 630 A
0 kA 0 kA
CB91 24 kV 24 kV
630 MVA
0.8 A 42 km
0 kA AL AL
GH Balun 24 kVA
23.1 DARTS 1120 42 km
20 kV 800 A16 kA -14.5% PF 100.1% DARTS 1120

Open CB7 CB5


630 A 630 A
0 kA 0 kA
24 kV 24 kV
CB89
630 A
0 kA
24 kV GH Lbk Gadang
20 kV %
0.8 MVA 101.37
Open 23.1 A 2.4 MVA 0.9 MVA 0.9 MVA
-14.5% PF 67.5 A 24.8 A 24.8 A
20 kV 90.5% PF 90.0% PF 90.0% PF
CB114 0 A GH Balun2 CB2
CAP3 0 kA 24 kV 630 A
7200 kvar 0 kA CB92
AL 24 km 24 kV CB90 630 A
630 A 0 kA
KRYPTON 0 kA 24 kV
24 kV

CB88
630 A AL 25 km
0 kA
24 kV
CRICKET 1120 Feeder Lbk Kota Feeder Malako
0.9 MVA 1 MVA 1 MVA
25.7 A
20kV GI ML -13.4% PF
20 kV
%
1.3 MVA 0.9 MVA 0.9 MVA 99.51
36.5 A 25.2 A 25.2 A
34.4% PF 90.0% PF 90.0% PF
CB86 CB99 CB101
0 A 630 A 630 A Fuse1
0 kA 0 kA 0 kA
24 kV 24 kV 24 kV Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA
3150 A
40 kA
150 kV

GI Sungai Rumbai GI Muara Laboh


150 kV 3200 A 40 kA 99.01%
9800 MVAsc
1.3 MVA
4.9 A
34.6% PF

150 kV CB2
3150 A
40 kA
150 kV
Open 150 kV CB1 Z1
3150 A
40 kA
150 kV
EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2
1 MW 1 MW

GI PLTP SEML 150 kV CB


3150 A %
150 kV 3150 A 40 kA 40 kA 99.01
150 kV
1.3 MVA
4.9 A CB129
34.6% PF GENERATOR STAGE-1 CB171
89.25 MW 0 A 0 A
0 kV 0 kV
GENERATOR TRANSFORMER CB 0 kA
3150 A 150 kV 0 kA 0.9 MVA 0.9 MVA 100%
50 kA
GSUT Bus25 1229.1 A 1229.1 A
0.4 kV 95.0% PF 95.0% PF 4200 A
150/11 kV
100 MVAYNd1 GENERATOR CB 1.7 MVA 0 kA
-1.25% TapP Open 6300 A 2458.2 A
80 kA 95.0% PF
GV BUS 12 kV %
100.08
11 kV 6500 A 200 kA
±
T11
R 1.3 MVA 0.4/6.3 kV
65.6 A 5 MVA Dyn1
34.6% PF T10
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP

R
UAT CB3
±
1250 A
MV-SGS CB2 16 kA
7.2 kV
UAT CB2
630 A 1250 A
16 kA Open 16 kA
7.2 kV UAT CB 7.2 kV
MV COMMON SGS SWBD MV COMMON SWITCHBOARD 99% MV UNIT SWITCHBOARD 1250 A
6.3 kV 225 A 0 kA 99% 6.3 kV 100 A0 kA 6.3 kV 800 A 0 kA 16 kA 99%
7.2 kV
0.01 MVA 0.02 MVA 0.02 MVA 0.02 MVA 0.07 MVA 0.07 MVA 0.6 MVA 1.2 MVA 0.4 MVA 0.3 MVA
1 A 1.8 A 1.7 A 2.1 A 6.6 A 6.3 kV 6.6 A 55.3 A 112.4 A 40.8 A 29.3 A
87.4% PF 87.4% PF 86.1% PF 87.3% PF 87.1% PF 200 A 87.1% PF 83.3% PF 71.0% PF 84.0% PF 80.0% PF
UST HVCB CB30 CB32
SGS TRANSFORMER HVCB BUS COUPLER 630 A 630 A 630 A CB96 CB97 CB194 Open CB196
Open 100 A CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB 16 kA 16 kA 16 kA 16 kA 630 A 630 A 630 A 630 A
16 kA 0 A 0 A 0 A 0 A 630 A 630 A 12 kV 7.2 kV Open 6.3 kV 16 kA 16 kA
Open 6.3 16 kA 16 kA
6.3 kV 0 kA 0 kA 0 kA 0 kA 16 kA Open 16 kA 6.3 kV kV 6.3 kV 6.3 kV
7.2 kV 7.2 kV 7.2 kV 7.2 kV 12 kV 12 kV ±

R
CU 40 m
±
± ± 1-3/C 240 R
± ± ± ±
R R
R R R R 6.3 kV Bus1
±
±
R UTILITY TRANSFORMER R 124 m
CU 1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
CU 1500 m 6.3/0.4 kV 98.88%
Terminal HWP
CU 500 m -2.5% TapP -2.5% TapP 2.5 MVA 6.3 kV
CU 2000 m 1-3/C 35 1.2 MVA
1-3/C 35 1-3/C 25 CU 1000 m OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
112.4 A 400 kW
1-3/C 35 400 A0.4 kV0 kA ±
71.0% PF 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
4000 A HOT WELL PUMP-A VACUUM PUMP-B 265 kW
0.4 kV 930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX 63 kA
250 kVA 0.6 MVA 7%
LV UNIT SWITCHBOARD 848.6 A 100.4
0.4 kV 4000 A 0 kA 83.9% PF
0.4 MVA 0.1 MVA 0.01 MVA 0 MVA 0.08 MVA
569.2
CB72 A 160.9 A 9.6 A 0.6 A 109.4 A
82.2% PF 89.0% PF 80.0% PF 0.0% PF 85.0% PF
1600 A CB60
0.415 kV CB61 Open CB10
300 A 300 A 0 A Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
70 kA 0 kV Open 0.415 kV 0 A 0 A CB21 Open 0 A 0 A Open 0 A CB202 Open CB53 0 A CB50 CB40 Open 0 A CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
0 kV Open 0 kV 0 A 0 A 0 A 0 A 0 A Open 20 A 0 A Open 0 A 0 A 0 A Open 0 A 0 A 0 A Open 0 kV 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 630 A
0 kA 70 kA 0 kA 0 kV 0 kV Open 0 kV 0 kV 0 kV 0 kV Open 0 kV 0 kV 0.415 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 A Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV 0 kV Open Open 0 kV
±
± 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kV 0 kA 0 kV Open 0 kV 0 kA 0 kV Open 0 kV Open 0 kV Open 0 kV Open 0 kV 0 kV 0.415 kV
0 kA 0 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 70 kA
0 kA
Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

CU 20 m
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

EDG CB R
630 A
Open 0.415 kV
1250 A 70 kA
0.4 kV
63 kA AUX-ESS CB
1600 A
LV COMMON ESS SWITCHBORD 0.4 kV .47%
LV COMMON NON ESS SWCHBRD
0.4 kV 1600 0A kA 63 kA 100 0.4 kV 600 A0 kA 100.4%

0.0% PF 0.03 MVA 0.04 MVA 0.01 MVA 0 MVA 0 MVA 0.09 MVA 0 MVA 0 MVA 0.01 MVA 0.04 MVA 0 MVA 0 MVA 0.04 MVA 0 MVA 0.09 MVA 0 MVA 0.03 MVA 0.04 MVA 0 MVA 0.02 MVA 0 MVA 0.01 MVA
38.2 A 51.5 A 19.3 A 0.9 A 1.6 A 134.7 A 4.3 A 4.3 A 21.5 A 57.9 A 0.9 A 2.1 A 58.6 A 0 A 129.5 A 0 A 45.9 A 59.3 A 1.5 A 27.3 A 0.1 A 21.6 A
80.0% PF 80.0% PF 80.0% PF 75.0% PF 75.0% PF 80.0% PF 66.7% PF 66.7% PF 80.0% PF 90.0% PF 90.0% PF 82.0% PF 90.0% PF 80.0% PF 80.5% PF 0.415 kV 83.0% PF 87.0% PF 92.0% PF 0.0% PF 0 kV 80.0% PF
SGS TRANSFORMER LVCB 100 A 0 A
250 A CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open 0 A CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
0.415 kV 0 A 0 A 0 A Open 0 A 0 A 0 A 0 A Open 0 A Open 0 A 0 A 0 A 0 A CB108 0 A 0 A 160 A 0 A 0 A 0 A 200 A 0 A 125 A Open 0 A 70 kA 0 A 0 A 0 A 0 A 0 A Open 0 A 0 A Open
70 kA 0 A Open 0 A 0 A 0 A Open 0 A 0 A Open 0 kV 0 A 0 kV Open 0 A 0 A 0 A 0 A 0 A 0 kV 0 kV 0 kV 0 kV 0 A 0 A 0 kA
Open 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0.415 kV 0 kV 0.415 kV 0 kV 0.4 kV 0 kV 0 kA 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV Battery2
SGS TRANSFORMER 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA
Cont9 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA Cont2 0 kA Open 0 kA 0 kA 0 kA
0.4/6.3 kV Cont10 Cont42 Cont6 Cont1 Cont4 CU 150 m
150 kVA Cont8 Cont39 Cont7 UPS1 Cont5 ± CU 30 m 1-4/C 240 Cont11 Cont12 Cont13 Cont14 Cont15
6.3 kV UPS19 CU 30 m Cont16
YNd1 UPS18 R 1-4/C 240 Open UPS2
Bus2 CU 30 m 1-4/C 240 Open Open
225 A 0.4 kV CU 150 m
CU 0 ft Bus3 CU 30 m 1-4/C 240 1-4/C 240 ±

0.23 kV 225 A
1-3/C 35 1-4/C 240
Bus20 Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB 225
0.23A kV AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA 0.4 kV
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 225 A
230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 13:59:01 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Short Circuit Study Result
150 kV CB3 (Initial Short Circuit/I"k) Case Study Scheme - 4
Bus14

T3
37.72 kA
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Page 1 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 CB87 CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.318


150 kV .229 kA kA

.089 kA
GENERATOR STAGE-1 CB129 CB171
89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV 7.33 kA 7.33 kA
100 MVA 45.12 kA 59.7
Open GENERATOR CB kA

GV BUS
11 kV 2.82 kA
±
T11
R 1.23 kA 4.0
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.03 kA 6.3 kV 6.3 kV 3.43 kA .857 kA
.006 kA .011 kA .012 kA .015 kA 6.1 .044 kA 6.03 kA .044 kA .495 kA .698 kA .318 kA .252 kA 6.1
kA kA

6.1 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
3 kA LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV 32.58 kA
5.81 kA 1.56 kA .07 kA .009 kA .666 kA 40.5
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 34.85 kA 0.4 kV 34.07 kA
.278 kA .375 kA .467 kA .021 kA .011 kA 1.14 kA .421 kA .018 kA .051 kA 1.56 kA 1.08 kA .412 kA .431 kA .037 kA .199 kA .004 kA 34.
7 kA
40.5
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable 27.1 kA 27.1 kA
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW 26.47 kA TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 10.69 kA
26.67 kA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:07:40 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Short Circuit Study Result
150 kV CB3 (Peak Short Circuit/Ip) Case Study Scheme - 4
Bus14

T3
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Page 2 of 2
60 MVA

GH Solok 20 kV

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
GT Cable

CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 CB87 CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.696


150 kV kA

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA 142.7
Open GENERATOR CB kA

GV BUS
11 kV
±
T11
R
9.0
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.3 kV 6.3 kV
13.9 13.9
kA kA

13.9 UST HVCB CB30 CB32


SGS TRANSFORMER HVCB kA BUS COUPLER CB96 CB97 CB194 Open CB196
Open CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ± R
R R
R R R R Bus1
±
± Cable3
R UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ±
400 kW 265 kW
R
LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
91.1
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
±
Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
± Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
640 kW 110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA ±

CB66
±

Open EDG CB R

AUX-ESS CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 0.4 kV
67.
6 kA
91.1
kA
SGS TRANSFORMER LVCB
CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ± Cont13 Cont14 Cont15
UPS18 R Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 14:07:57 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Motor Starting Study Result
150 kV CB3
(Before) Case Study Scheme - 4
Bus14

T3
1.5 MW
1 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Page 1 of 6
-5% TapP

%
GH Solok 20 kV 105.06

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100 Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

% 0.7 MW 0.7 MW 0.7 MW


GH Alahan 101.72 0.3 Mvar 105 .31
% 0.3 Mvar 6.3 kV 0.3 Mvar 105.31%
20 kV Bus23 0.7 MW Bus24 Bus10 Bus15
6.3 kV 0.3 Mvar 6.3 kV 6.3 kV %
105 .31
%
105.31
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 CB87 CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 104.84
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 101.09 DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV %
Open 101 .76

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV %
100.66

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 100.41
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 100.41

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
100 %
GSUT Bus25 0.6 MW 0.6 MW
0.4 kV 0 Mvar 0 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
100.32
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
99.82% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 99.82% 6.3 kV 6.3 kV 99.82%

Open SGS TRANSFORMER HVCB UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 99.82%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1-3/C 35 0.4 kV ± 400 kW 265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA %
LV UNIT SWITCHBOARD 101.32
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
Open EDG CB

LV COMMON ESS SWITCHBORD % LV COMMON NON ESS SWCHBRD %


0.4 kV 101 .32 0.4 kV 101.26

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:58:32 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Motor Starting Study Result
150 kV CB3
(During) Case Study Scheme - 4
Bus14

T3
2.2 MW
3.2 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Page 2 of 6
-5% TapP

GH Solok 20 kV 104.6%

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100 Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

0.8 MW 0.9 MW 0.9 MW


GH Alahan 95.91% 1 Mvar 101 .4%
1.1 Mvar 6.3 kV 1.1 Mvar 101.61%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 1 Mvar 6.3 kV 6.3 kV %
101 .61

101.4%
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 CB87 CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 100.14
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 91.84% DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open 93. 13%

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
89.59%

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 87.41%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


150 kV 87.41%

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
83. 6%
GSUT Bus25 0.5 MW 0.5 MW
0.4 kV 0.5 Mvar 0.5 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 86.55%
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
81.85% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 81.85% 6.3 kV 6.3 kV 81.85%

Open SGS TRANSFORMER HVCB UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 81.58%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
0.7 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
4.6 Mvar 400 kW
1-3/C 35 0.4 kV ±
265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 82.66%
LV UNIT SWITCHBOARD
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
Open EDG CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 82. 66% 0.4 kV 82.58%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:58:57 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc
Attachment 8 : Motor Starting Study Result
150 kV CB3
(After) Case Study Scheme - 4
Bus14

T3
2 MW
1.4 Mvar

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Page 3 of 6
-5% TapP

%
GH Solok 20 kV 104.97

CB121

Bus8
SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
1 km 100 Cable
GT m 62 km
SATURN
Line1 Line5
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

% 0.8 MW 0.8 MW 0.8 MW


GH Alahan 100.42 0.5 Mvar 104 .49
% 0.5 Mvar 6.3 kV 0.5 Mvar 104.54%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 0.5 Mvar 6.3 kV 6.3 kV %
104 .54
%
104.49
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 CB87 CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 103.85
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 98.97% DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open 99. 82%

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
98.06%

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 97.46%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


150 kV 97.46%

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB
96. 4%
GSUT Bus25 0.7 MW 0.7 MW
0.4 kV 0.09 Mvar 0.09 Mvar
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 97.22%
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2
UAT CB2
Open
95.91% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 95.91% 6.3 kV 6.3 kV 95.91%

Open SGS TRANSFORMER HVCB UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 95.77%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
1 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1 Mvar 400 kW
1-3/C 35 0.4 kV ±
265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 97.27%
LV UNIT SWITCHBOARD
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
Open EDG CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 97. 27% 0.4 kV 97.2%

SGS TRANSFORMER LVCB


CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:59:41 Apr 25, 2019 Project File: MuaraLaboh


ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IP+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP&EDG

MOTOR STARTING ANALYSIS


Motor Terminal Voltage (Motor Base)

Attachment 8 : Motor Starting Study Result


HOT WELL PUMP-A Case Study Scheme - 4
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
120 Page 4 of 6

100

80
Vt (% of Motor Rated kV)

60

40

20

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IP+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP&EDG

MOTOR STARTING ANALYSIS


Bus Voltage

Attachment 8 : Motor Starting Study Result


HOT WELL PUMP-A Case Study Scheme - 4
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
105 Page 5 of 6

100
Vbus (% of Bus Nominal kV)

95

90

85

80

75
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP+EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IP+EDG

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-HWP GI&IPP&EDG

MOTOR STARTING ANALYSIS


Motor Line Current

Attachment 8 : Motor Starting Study Result


HOT WELL PUMP-A Case Study Scheme - 4
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
500 Page 6 of 6

400

300
I (% of FLA)

200

100

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 9

POWER SYSTEM STUDY RESULT OF SCHEME 5

(POWER SUPPLY FROM 20KV GI SOLOK + TWO (2) HYDRO POWER PLANT)

MV SYSTEM AND LV SYSTEM ARE MADE SEPARATE

Page 35 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


One-Line Diagram - SLD (Load Flow Analysis)
GI Solok
9800 MVAsc
Attachment 9 : Load Flow Study Result
150 kV CB3
3150 A
40 kA
150 kV
1.8 MVA
Case Study Scheme - 5
150 kV
Bus14

T3
6.9 A
90.4% PF

150/20 kV
60 MVAYNyn1
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
MV System and LV System are made Separate
-7.5% TapP
1.8 MVA
48 A %
GH Solok 20 kV 90.5% PF 107.95

1.8 MVA
48 A
90.5%
CB121 PF
630 A
0 kA
24 kV
Bus8
20 kV SKE Unit 1 SKE Unit 2 WSE Unit 1 WSE Unit 2
4 MW 5 MW
4 MW 5 MW
AL 1 km CU 100 m AL 62 km
SATURN
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77 2000 A
630 A 2000 A 2000 A 2000 A 16 kA
0 kA 16 kA 16 kA 16 kA 6.6 kV
24 kV 6.6 kV 6.6 kV 6.6 kV
0.8 MVA 0.8 MVA 0.8 MVA
1.8 MVA % 67.4 A 67.4 A 67.4 A
GH Alahan 50.8 A 105.09
0.8 MVA 90.0% PF % 90.0% PF 6.3 kV 90.0% PF 105.74%
Bus23 67.4 A Bus24 105 .73
20 kV 800 A 16 kA 86.9% PF Bus10 % Bus15
6.3 kV 90.0% PF 6.3 kV 0.8 MVA 6.3 kV 105 .74
0.8 MVA 0.8 MVA
1.8 MVA %
67.4 A 67.4 A 67.4 A
50.8 A 105.73
0.8 MVA 90.0% PF 90.0% PF 90.0% PF
86.9% PF 67.4 A T5 T7
90.0%
T4 PF T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
630 A Open 0 A 630 A 630 A 6 MVA YNd1
0 kA 0 kA 0 kA 0 kA 6 MVA YNd1 YNd1 YNd1
24 kV 24 kV 24 kV 24 kV

AL CB117 CB120 CB123


50 km 630 A 630 A CB122 630 A
NITROGEN 0 kA 0 kA 630 A 0 kA
Sungai Cehana 20kV IPP 24 kV 24 kV 0 kA 24 kV
Open Taman Babungo 1.5 MVA 20 kV 24 kV
20 kV 0.5 MVA %
GH Balun4 900 kvar 3.1 MVA 105.26
CB118 0 A 1.9 MVA CAP1 84.9 A
CAP5 0 kA 24 kV 54 A 90.3% PF
900 kvar 82.7% PF Open CB115 CB107
630 A 630 A
0 kA 0 kA
CB91 24 kV 24 kV
630 A 42 km
0 kA AL AL
GH Balun 24 kV % DARTS 1120 42 km
20 kV 800 A16 kA 102.68 DARTS 1120

1.9 MVA Open CB7 CB5


54 A 630 A 630 A
0 kA 0 kA
82.7% PF 24 kV 24 kV
CB89
630 A
0 kA
24 kV GH Lbk Gadang
20 kV
Open 1.3 MVA 0.9 MVA 0.9 MVA 102 .2%
38.1 A 24.6 A 24.6 A
20 kV 88.0% PF 90.0% PF 90.0% PF
CB114 0 A GH Balun2 CB2
CAP3 0 kA 24 kV 630 A
7200 kvar 0 kA CB92
AL 24 km 24 kV CB90 630 A
630 A 0 kA
KRYPTON 0 kA 24 kV
24 kV

CB88
630 A AL 25 km
0 kA
24 kV
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1.9 MVA 1 MVA 1 MVA
55.5 A
20kV GI ML 80.7% PF
20 kV
1.6 MVA 0.9 MVA 0.9 MVA 101.1%
46.4 A 24.8 A 24.8 A
72.6% PF 90.0% PF 90.0% PF
CB86 CB99 CB101
0 A 630 A 630 A Fuse1
0 kA 0 kA 0 kA
24 kV 24 kV 24 kV Open
20/150 kV
T1 30 MVA YNyn0
1.25% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA
3150 A
40 kA
150 kV

GI Sungai Rumbai GI Muara Laboh %


150 kV 3200 A 40 kA 101.89
9800 MVAsc
1.6 MVA
6.1 A
73.0% PF

150 kV CB2
3150 A
40 kA
150 kV
Open 150 kV CB1 Z1
3150 A
40 kA
150 kV
EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2
1 MW 1 MW

GI PLTP SEML 150 kV CB


3150 A %
150 kV 3150 A 40 kA 40 kA 101.89
150 kV
1.6 MVA
6.1 A CB129
73.0% PF GENERATOR STAGE-1 CB171
89.25 MW 0 A 0 A
0 kV 0 kV
GENERATOR TRANSFORMER CB 0 kA
3150 A 150 kV 0 kA
50 kA
GSUT Bus25
0.4 kV 3200 A
150/11 kV
100 MVAYNd1 GENERATOR CB 0 kA
Open 6300 A
80 kA
GV BUS 12 kV
101.7%
11 kV 6500 A 200 kA
±

R T11
1.6 MVA 0.4/6.3 kV
83.3 A 5 MVA Dyn1
73.1% PF T10
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
1250 A
MV-SGS CB2 Open 16 kA
7.2 kV
UAT CB2
630 A 1250 A
16 kA %
Open 16 kA
7.2 kV 100.66 MV UNIT SWITCHBOARD UAT CB 7.2 kV
MV COMMON SGS SWBD % MV COMMON SWITCHBOARD 1250 A %
6.3 kV 225 A 0 kA 100.66 6.3 kV 100 A0 kA 6.3 kV 800 A 0 kA 16 kA 100.66
7.2 kV
0.01 MVA 0.02 MVA 0.02 MVA 0.02 MVA 0.07 MVA 0.07 MVA 1.2 MVA 0.3 MVA
1 A 1.8 A 1.7 A 2.1 A 6.5 A 6.3 kV 6.5 A 110.5 A 28.8 A
87.4% PF 87.5% PF 86.1% PF 87.4% PF 87.1% PF 200 A 87.1% PF 71.0% PF 80.0% PF
Open SGS TRANSFORMER HVCB Open UST HVCB CB30 CB32
100 A BUS COUPLER 630 A 630 A 630 A Open CB96 CB97 CB194 Open CB196
16 kA CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB 16 kA 16 kA 16 kA 16 kA 630 A 630 A 630 A 630 A
6.3 kV 0 A 0 A 0 A 0 A 630 A 630 A 12 kV 7.2 kV Open 6.3 kV 16 kA 16 kA
Open 6.3 16 kA 16 kA
0 kA 0 kA 0 kA 0 kA 16 kA Open 16 kA 6.3 kV kV 6.3 kV 6.3 kV
7.2 kV 7.2 kV 7.2 kV 7.2 kV 12 kV 12 kV ±

R
CU 40 m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R 6.3 kV Bus1
±

UTILITY TRANSFORMER R
CU 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
CU 1500 m 6.3/0.4 kV 100.55
Terminal HWP
CU 500 m -2.5% TapP -2.5% TapP 2.5 MVA 6.3 kV
CU 2000 m 1-3/C 35 1.2 MVA
1-3/C 35 1-3/C 25 CU 1000 m OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
110.5 A 400 kW
1-3/C 35 400 A0.4 kV0 kA ±
71.0% PF 265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
Open 4000 A HOT WELL PUMP-A VACUUM PUMP-B 265 kW
0.4 kV 930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX 63 kA
250 kVA 100%
LV UNIT SWITCHBOARD
0.4 kV 4000 A 0 kA
0.1 MVA 0.01 MVA 0 MVA 0.08 MVA
CB72 161.7 A 9.6 A 0.6 A 110 A
89.0% PF 80.0% PF 0.0% PF 85.0% PF
1600 A CB60
0.415 kV CB61 Open CB10
300 A 300 A 0 A Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
70 kA 0 kV Open 0.415 kV 0 A 0 A CB21 Open 0 A 0 A Open 0 A CB202 Open CB53 0 A CB50 CB40 Open 0 A CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
0 kV Open 0 kV 0 A 0 A 0 A 0 A 0 A Open 20 A 0 A Open 0 A 0 A 0 A Open 0 A 0 A 0 A Open 0 kV 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 630 A
0 kA 70 kA 0 kA 0 kV 0 kV Open 0 kV 0 kV 0 kV 0 kV Open 0 kV 0 kV 0.415 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 A Open 0 kV Open 0 kV 0 kV Open 0 kV Open 0 kV 0 kV 0 kV Open Open 0 kV
±
±
0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kV 0 kA 0 kV Open 0 kV 0 kA 0 kV Open 0 kV Open 0 kV Open 0 kV Open 0 kV 0 kV 0.415 kV
0 kA 0 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 70 kA
0 kA
Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

CU 20 m
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB 1600 A 630 A
1250 A 0.4 kV 0.415 kV
0.4 kV 63 kA 70 kA
63 kA
0.6 MVA 0.2 MVA
LV COMMON ESS SWITCHBORD 852.3 A 281.5 A LV COMMON NON ESS SWCHBRD
0.4 kV 1600 0A kA 83.9% PF 87.2% PF 100 % 0.4 kV 600 A0 kA 99.93%

0.03 MVA 0.04 MVA 0.01 MVA 0 MVA 0 MVA 0.09 MVA 0 MVA 0 MVA 0.01 MVA 0.04 MVA 0 MVA 0 MVA 0.04 MVA 0 MVA 0.09 MVA 0 MVA 0.03 MVA 0.04 MVA 0 MVA 0.02 MVA 0 MVA 0.01 MVA
38.4 A 51.7 A 19.4 A 0.9 A 1.6 A 135.3 A 4.3 A 4.3 A 21.7 A 58.1 A 0.9 A 2.1 A 58.7 A 0 A 130.2 A 0 A 46 A 59.6 A 1.5 A 27.5 A 0.1 A 21.7 A
80.0% PF 80.0% PF 80.0% PF 75.0% PF 75.0% PF 80.0% PF 66.7% PF 66.7% PF 80.0% PF 90.0% PF 90.0% PF 82.0% PF 90.0% PF 80.0% PF 80.5% PF 0.415 kV 83.0% PF 87.0% PF 92.0% PF 0.0% PF 0 kV 80.0% PF
SGS TRANSFORMER LVCB 100 A 0 A
Open 250 A CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open 0 A CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
0.415 kV 0 A 0 A 0 A Open 0 A 0 A 0 A 0 A Open 0 A Open 0 A 0 A 0 A 0 A CB108 0 A 0 A 160 A 0 A 0 A 0 A 200 A 0 A 125 A Open 0 A 70 kA 0 A 0 A 0 A 0 A 0 A Open 0 A 0 A Open
70 kA 0 A Open 0 A 0 A 0 A Open 0 A 0 A Open 0 kV 0 A 0 kV Open 0 A 0 A 0 A 0 A 0 A 0 kV 0 kV 0 kV 0 kV 0 A 0 A 0 kA
Open 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0.415 kV 0 kV 0.415 kV 0 kV 0.4 kV 0 kV 0 kA 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV 0 kV Battery2
SGS TRANSFORMER 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kV 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 70 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA 0 kA
Cont9 0 kA 0 kA 0 kA 0 kA 0 kA Open 0 kA 0 kA 0 kA 0 kA 0 kA Cont2 0 kA Open 0 kA 0 kA 0 kA
0.4/6.3 kV Cont10 Cont42 Cont6 Cont1 Cont4 CU 150 m
150 kVA Cont8 Cont39 Cont7 UPS1 Cont5 ±
CU 30 m 1-4/C 240 Cont11 Cont12 Cont13 Cont14 Cont15
6.3 kV UPS19 R CU 30 m Cont16
Bus2 YNd1 UPS18 1-4/C 240 1-4/C 240 Open UPS2
225 A 0.4 kV CU 30 m CU 150 m Open Open
CU 0 ft Bus3 CU 30 m 1-4/C 240 1-4/C 240
±

0.23 kV 225 A
1-3/C 35 1-4/C 240
Bus20 Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB 225
0.23A kV AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA 0.4 kV
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 225 A
230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:12:23 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc Attachment 9 : Short Circuit Study Result
150 kV CB3

37.72 kA
(Initial Short Circuit/I"k) Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Bus14

T3 60 MVA

GH Solok 20 kV

CB121
MV System and LV System are made Separate
GT Cable
Bus8
SKE Unit 1
4 MW
SKE Unit 2
4 MW
WSE Unit 1
5 MW
WSE Unit 2
5 MW Page 1 of 2
CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.254


150 kV .216 kA kA

.038 kA
GENERATOR STAGE-1 CB129 CB171
89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV 2.74 kA
±

R T11
.522 kA 3.3
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 4.31 kA 6.3 kV 6.3 kV 3.36 kA
.006 kA .011 kA .012 kA .015 kA 4.3 .044 kA 4.31 kA .044 kA .698 kA .252 kA 4.3
kA kA

Open SGS TRANSFORMER HVCB 4.3 Open UST HVCB CB30 CB32
kA BUS COUPLER CB96 CB97 CB196
CB46 Open CB194 Open
CB45 CB228 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ±
R R R
±

R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ± 400 kW 265 kW
R
2.6 kA LV UNIT CB HOT WELL PUMP-B
930 kW AUX COOLING WATER PUMP B
Open HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
18.71 kA 1.56 kA .07 kA .009 kA .666 kA 21.0
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 13.18 kA 2.29 kA 0.4 kV 18.8 kA
.278 kA .375 kA .467 kA .021 kA .011 kA 1.14 kA .421 kA .018 kA .051 kA 1.56 kA 1.08 kA .412 kA .431 kA .037 kA .199 kA .004 kA 19. 5
kA
21.0
kA
SGS TRANSFORMER LVCB
Open CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
Cont13 Cont14 Cont15
UPS18 R
Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable 16.89 kA 16.89 kA
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW 15.94 kA TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 8.78 kA
16.24 kA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:18:06 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Short-Circuit Analysis)
GI Solok
9800 MVAsc Attachment 9 : Short Circuit Study Result
150 kV CB3

(Peak Short Circuit/Ip) Case Study Scheme - 5


Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant + Two (2) DEG 1MW
Bus14

T3 60 MVA

GH Solok 20 kV

CB121
MV System and LV System are made Separate
GT Cable
Bus8
SKE Unit 1
4 MW
SKE Unit 2
4 MW
WSE Unit 1
5 MW
WSE Unit 2
5 MW Page 2 of 2
CB78
CB100 CB9 CB55 CB77

GH Alahan 6.3 kV
20 kV Bus23 Bus24 Bus10 Bus15
6.3 kV 6.3 kV 6.3 kV

T5 T7
T4 T8
CB98 CB103 Open CB87 Open CB83 6.5 MVA 6.5 MVA
Open 6 MVA 6 MVA

CB117 CB120 CB123


CB122
Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA
GH Balun4 900 kvar
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91

GH Balun
20 kV

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open

CB114 GH Balun2 CB2


CAP3
7200 kvar CB90 CB92

CB88

Feeder Lbk Kota Feeder Malako


1 MVA 1 MVA
20kV GI ML
20 kV

CB86 CB99 CB101 Fuse1

Open
T1 30 MVA

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


9800 MVAsc 150 kV

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB 0.543


150 kV kA

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
100 MVA GENERATOR CB
Open

GV BUS
11 kV
±

R T11
7.1
kA
T10 5 MVA
UAT
3 MVA
7 MVA
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 6.3 kV 6.3 kV
9.8 9.8
kA kA

Open SGS TRANSFORMER HVCB 9.8 Open UST HVCB CB30 CB32
kA BUS COUPLER CB96 CB97 CB196
CB46 Open CB194 Open
CB45 CB228 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R Cable8 ±
± ±

± ± ± ±
R R R
±

R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R

UNIT SERVICE TRANSFORMER


250 kVA Terminal HWP
ML-E Cable 6.3 kV
ML-B Cable ML-A Cable 2.5 MVA
ML-F Cable OWNER'S ADMIN COMPLEX VACUUM PUMP-A AUX COOLING WATER PUMP A
0.4 kV ± 400 kW 265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
Open HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA
LV UNIT SWITCHBOARD
0.4 kV
50.1
kA
CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

COMMNON Cable

COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB

LV COMMON ESS SWITCHBORD LV COMMON NON ESS SWCHBRD


0.4 kV 0.4 kV
42. 4
kA
50.1
kA
SGS TRANSFORMER LVCB
Open CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
Cont10 Cont2 SWTCH NORM PDB Cable
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
Cont13 Cont14 Cont15
UPS18 R
Open Cont16 UPS2
Bus2 ESS PDB2 Cable Open Open
Cable9 Bus3 Workshop PDB Cable2 ±

ESS PDB3 Cable SWTCH ESS PDB Cable


Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:18:25 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc Attachment 9 : Motor Starting Study Result
150 kV CB3

0.7 MW
-0.3 Mvar
(Before) Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP

GH Solok 20 kV

CB121
108.17
%

LV System are made Separate


1 km
SATURN
Line1 100 Cable
GT m
Bus8

62 km
Line5
SKE Unit 1
4 MW
SKE Unit 2
4 MW
WSE Unit 1
5 MW
WSE Unit 2
5 MW Page 1 of 6
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

% 0.7 MW 0.7 MW 0.7 MW


GH Alahan 108.25 0.3 Mvar 111 .88
% 0.3 Mvar 6.3 kV 0.3 Mvar 111.88%
20 kV Bus23 0.7 MW Bus24 Bus10 Bus15
6.3 kV 0.3 Mvar 6.3 kV 6.3 kV %
111 .88
%
111.88
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 111.43
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 107.87 DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV %
Open 108 .52

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV %
107.44

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 110.04
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 110.04

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 110%
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
109.8% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 109.8% 6.3 kV 6.3 kV 109.8%

Open SGS TRANSFORMER HVCB Open UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 109.8%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1-3/C 35 0.4 kV ± 400 kW 265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
Open HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 100%
LV UNIT SWITCHBOARD
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB

LV COMMON ESS SWITCHBORD 0.5 MW LV COMMON NON ESS SWCHBRD


0.4 kV 0.3 Mvar 100 % 0.4 kV 99.93%

SGS TRANSFORMER LVCB


Open CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:42:39 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc Attachment 9 : Motor Starting Study Result
150 kV CB3

1.4 MW
2.6 Mvar
(During) Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP

GH Solok 20 kV

CB121
107.58
%

LV System are made Separate


1 km
SATURN
Line1 100 Cable
GT m
Bus8

62 km
Line5
SKE Unit 1
4 MW
SKE Unit 2
4 MW
WSE Unit 1
5 MW
WSE Unit 2
5 MW Page 2 of 6
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

% 0.8 MW 0.9 MW 0.9 MW


GH Alahan 100.88 1.2 Mvar 106 .81
% 1.4 Mvar 6.3 kV 1.4 Mvar 107.09%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 1.2 Mvar 6.3 kV 6.3 kV %
107 .09
%
106.81
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 105.36
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun DARTS 1120 42 km
20 kV 96.04% DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV
Open 97. 42%

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV
93.26%

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh


150 kV 92.88%
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


150 kV 92.88%

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS 91.86%
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
86.26% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 86.26% 6.3 kV 6.3 kV 86.26%

Open SGS TRANSFORMER HVCB Open UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA
1500
ML-Em Cable 6.3/0.4 kV 85.98%
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
0.8 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
5.1 Mvar 400 kW
1-3/C 35 0.4 kV ±
265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
Open HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 100%
LV UNIT SWITCHBOARD
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB

LV COMMON ESS SWITCHBORD 0.5 MW LV COMMON NON ESS SWCHBRD


0.4 kV 0.3 Mvar 100 % 0.4 kV 99.93%

SGS TRANSFORMER LVCB


Open CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:43:14 Apr 25, 2019 Project File: MuaraLaboh


One-Line Diagram - SLD (Motor Acceleration Analysis)
GI Solok
9800 MVAsc Attachment 9 : Motor Starting Study Result
150 kV CB3

1.2 MW
0.2 Mvar
(After) Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
Bus14

150/20 kV
T3 60 MVAYNyn1
-7.5% TapP

GH Solok 20 kV

CB121
108.07
%

LV System are made Separate


1 km
SATURN
Line1 100 Cable
GT m
Bus8

62 km
Line5
SKE Unit 1
4 MW
SKE Unit 2
4 MW
WSE Unit 1
5 MW
WSE Unit 2
5 MW Page 3 of 6
3-1/C 750 NITROGEN
CB78
CB100 CB9 CB55 CB77

0.8 MW 0.9 MW 0.9 MW


GH Alahan 106.8% 0.5 Mvar 110 .96
% 0.5 Mvar 6.3 kV 0.5 Mvar 111.01%
20 kV Bus23 0.8 MW Bus24 Bus10 Bus15
6.3 kV 0.5 Mvar 6.3 kV 6.3 kV %
111 .01
%
110.96
T5 T7
T4 T8 6.3/20 kV 6.3/20 kV
CB98 CB103 Open CB87 Open CB83 6.3/20 kV 6.3/20 kV 6.5 MVA 6.5 MVA
Open 6 MVA YNd1 6 MVA YNd1 YNd1 YNd1

Line3 CB117 CB120 CB123


50 km CB122
NITROGEN Sungai Cehana 20kV IPP
Open Taman Babungo 1.5 MVA 20 kV
0.5 MVA %
GH Balun4 900 kvar 110.32
CB118 CAP1
CAP5
900 kvar Open CB115 CB107
CB91
42 km
Line9 Line10
GH Balun % DARTS 1120 42 km
20 kV 105.48 DARTS 1120

Open CB7 CB5

CB89

GH Lbk Gadang
20 kV %
Open 106 .33

CB114 GH Balun2 CB2


CAP3 Line2
7200 kvar CB90 CB92
24 km
KRYPTON

CB88
25 km
Line7
CRICKET 1120 Feeder Lbk Kota Feeder Malako
1 MVA 1 MVA
20kV GI ML
20 kV %
104.52

CB86 CB99 CB101 Fuse1

Open
20/150 kV
T1 30 MVA YNyn0
2.5% TapS

Feeder ML Kota Feeder Mitra


150 kV CB4 1 MVA 1 MVA

GI Sungai Rumbai GI Muara Laboh %


150 kV 106.61
9800 MVAsc

150 kV CB2

Open 150 kV CB1 Z1

EMERGENCY DIESEL GEN5 EMERGENCY DIESEL GEN2


1 MW 1 MW

GI PLTP SEML 150 kV CB


%
150 kV 106.61

GENERATOR STAGE-1 CB129 CB171


89.25 MW

GENERATOR TRANSFORMER CB

GSUT Bus25
0.4 kV
150/11 kV
100 MVAYNd1 GENERATOR CB
Open

GV BUS %
106.42
11 kV
±

R T11
0.4/6.3 kV
T10 5 MVA Dyn1
UAT 20/6.3 kV
11/6.3 kV 3 MVA Dyn1
7 MVA Dyn1 -2.5% TapP
±

R
UAT CB3
±
MV-SGS CB2 Open
UAT CB2
Open
105.3% MV UNIT SWITCHBOARD UAT CB
MV COMMON SGS SWBD MV COMMON SWITCHBOARD
6.3 kV 105.3% 6.3 kV 6.3 kV 105.3%

Open SGS TRANSFORMER HVCB Open UST HVCB CB30 CB32


BUS COUPLER Open CB96 CB97 CB194 Open CB196
CB45 CB228 CB46 CB15 MV-SGS CB1 UT HVCB Open Open
Open
±

R
40Cable8
m
±
± ±
1-3/C 240 R
±
± ± ± ±
R R
R R R R R Bus1
±
Cable3
UTILITY TRANSFORMER R 124 m
1-3/C 70
6.3/0.4 kV UNIT SERVICE TRANSFORMER
Dyn1 250 kVA %
1500
ML-Em Cable 6.3/0.4 kV 105.18
Terminal HWP
500 -2.5% TapP -2.5% TapP 6.3 kV
2000
ML-B mCable ML-A m Cable 1-3/C 35 2.5 MVA
1 MW
1-3/C 35 1-3/C 25 1000
ML-Fm Cable OWNER'S ADMIN COMPLEX Dyn1 VACUUM PUMP-A AUX COOLING WATER PUMP A
1 Mvar 400 kW
1-3/C 35 0.4 kV ±
265 kW
R

LV UNIT CB HOT WELL PUMP-B


930 kW AUX COOLING WATER PUMP B
Open HOT WELL PUMP-A VACUUM PUMP-B 265 kW
930 kW 400 kW
ML-B ML-A ML-H1 ML-F ML-E ML-D OWNER ADMIN COMPLEX
250 kVA 100%
LV UNIT SWITCHBOARD
0.4 kV

CB72
CB60 CB61 Open CB10
Open CB14 CB19 Open CB20 Open CB22 CB49 Open CB56 CB57 CB3 CB4 CB64 CB35 CB51 CB203 CB52 CB54 CB42 CB31 CB204 CB67 CB68 CB69 CB74 CB58 CB59 CB94
Open CB21 Open Open CB202 Open CB53 CB50 CB40 Open CB197 CB71 CB73 Open CB79 CB80 CB95 CB65
Open Open Open Open Open
Open Open Open Open Open Open Open Open Open Open Open Open Open
±
± Open Open Open Open Open
Open

Cont34 Cont62 Cont63 ±

Cont38 R
Cont18 Cont33 Cont37 Cont44 Cont45 Cont40 Cont3
Cont22 Cont23 Cont24
Cont21 Cont25 Cont26 Cont27 Cont28 Cont41 Cont43 Cont17
±
Cont64

20
COMMNON
m Cable
2-4/C 185
COOLING TOWER FAN-A COOLING TOWER FAN-C NaOH INJECTION PUMP (B) MAIN OIL PUMP (B) 1st STG EJECT (A) NCG IIV GRS (A) COOL WTR ISO VLV GRS (C) COOL WTR ISO VLV HWP (B) DISCHRG ISLTG VLV
110 kW COOLING TOWER FAN-E COOLING TOWER FAN-G SCREW CONVEYOR VIBRATOR BIOCIDE(A) DOSING PUMP(A) BIOCIDE(B) DOSING PUMP(A) 22 kW CONTROL OIL PUMP(B) FAN OF ACWP (B) VSD 1.3 kVA 1st STG EJECT (C) NCG IIV 0.05 kVA 0.33 kVA HWP (B) MIN. FLOW VALVE
110 kW 2.2 kW 0.31 kW 0.37 kW 0.37 kW 15 kW WASH WATER PUMP-B 1.3 kVA GSUT CUBICLE (OLTC,FAN)
110 kW 110 kW 0.37 kW 18.5 kW 5.2 kW 1.3 kVA 0.33 kVA 10 kVA

COOLING TOWER FAN-B COOLING TOWER FAN-F


EMERGENCY DIESEL GEN 110 kW COOLING TOWER FAN-D COOLING TOWER FAN-H BIOCIDE(A) DOSING PUMP(B) BIOCIDE(B) DOSING PUMP(B) CONTROL OIL RADIATOR FAN OF ACWP (A) VSD 1st STG EJECT (B) NCG IIV MAIN OIL TANK HEATER HWP (A) DISCHRG ISLTG VLV HWP (A) MIN. FLOW VALVE
640 kW 110 kW LUMP BREAKER NaOH INJECTION PUMP (A) AGITATOR OIL PURIFIER NaOH POWDER FEEDING SYS 1.3 kVA 1.3 kVA 0.33 kVA ACWP MINI FLOW VALVE
110 kW 110 kW 2.2 kW 1.1 kW 0.75 kW 0.37 kW 0.37 kW 0.75 kW 0.4 kW 5.2 kW GRS (B) COOL WTR ISO VLV 1.3 kVA 0.05 kVA
2.18 kW 0.05 kVA
±

AUX-ESS CB CB66
EDG CB

LV COMMON ESS SWITCHBORD 0.5 MW LV COMMON NON ESS SWCHBRD


0.4 kV 0.3 Mvar 100 % 0.4 kV 99.93%

SGS TRANSFORMER LVCB


Open CB17 CB113 CB270 CB144 CB160 CB41 CB110
CB62 CB102 CB63 CB36 CB75 CB76 CB48 CB266 CB82 CB29 CB33 CB37 CB18 CB106 CB367 CB84 CB168 CB109 CB111 CB112 CB265 CB269 Open CB167 CB209 CB6 CB105 CB16 CB369 Open CB119 CB43 CB24 CB44 CB23 CB34 CB38 CB70 CB39 CB169
Open Open Open CB108 Open Open Open
Open Open Open Open
Open Battery2
SGS TRANSFORMER
Cont9 Open Open Open Open
0.4/6.3 kV Cont10 Cont2 SWTCH NORM PDB Cable 150 m
Cont42 Cont6 UPS1 Cont1 Cont4 Cont11 Cont12
150 kVA Cont8 Cont39 Cont7 UPS19 Cont5 ±
30 m 30 m 1-4/C 240 Cont13 Cont14 Cont15
YNd1 UPS18 R
1-4/C 240 Open Cont16 UPS2
Bus2 ESS PDB2 Cable 30 m 1-4/C 240 Open Open
150 m
0 ft
Cable9 Bus3 30 m 1-4/C 240 Workshop PDB Cable2 1-4/C 240
±

1-3/C 35 1-4/C 240 ESS PDB3 Cable SWTCH ESS PDB Cable
Bus20 ESS PDB1 Cable
Bus7
GRS U-SEAL PIT SUM PUMP-A EXCITER SPACE HEATER 1 PHASE PDB AIR COMPRESSOR (A) FIRE WATER JOCKEY PUMP
MAIN OIL PUMP-A JACKING OIL PUMP WASH WATER PUMP-A 2.5 kVA HOT WELL PUMP HOIST FIRE FIGHT MAIN PUMP
5.5 kW OIL TANK VAPOR EXTRACTOR 0.46 kVA 39.9 kVA HVAC-01 FOR PWR HOUSE 230 VAC UPS (A) 46.3 kVA 18.9 kVA
22 kW 37 kW 22 kW 0.75 kW 110V DC SWG BAT CHRG-A 15 kVA 75 kW TO ESS PDB2 TO WORKSHOP PDB Bus4
125 kVA 10 kVA 230 VAC UPS BYPASS (B)
FIRE FIGHTING MAIN PUMP 15 kVA
93.8 kVA AIR COMPRESSOR (B)
GRS U-SEAL PIT SUM PUMP-B CONTROL OIL PUMP(A) TURBINE O/H CRANE GENERATOR SPACE HEATER DOMESTIC WATER PUMP-A DOMESTIC WATER PUMP-B 230 VAC UPS BYPASS(A) DIESEL FUEL PUMP JIB CRANE 46.3 kVA
5.5 kW TURNING GEAR 3.7 kW 3.7 kW HVAC-02 FOR PWR HOUSE 110V DC BATTERY CHARGER-A 15 kVA 4 kW TO ESS PDB1 WTP BOOSTER PUMP-B WTP Dosing Pump-A 110V DC SWG BAT CHRG-B 230 VAC UPS (B)
30 kW 1.5 kW 49.8 kVA 6.5 kVA 15 kVA 12 kVA TO ESS PDB3 TO 150kV SWTYRD ESS PDB TO 150kV SWTYRD NON-E PDB WTP BOOSTER PUMP-A 3 kW 0.25 kW 10 kVA 15 kVA
125 kVA 3 kW

COND REINJECT PUMP-A 110VDC UNIT BAT CHARGER-B


COND REINJECT PUMP-B THERMAL POND PUMP-B THERMAL POND PUMP-A WTP Dosing Pump-B
37 kW 37 kW 18.5 kW 18.5 kW 0.25 kW 15 kVA

page 1 19:43:35 Apr 25, 2019 Project File: MuaraLaboh


ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP /s EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IPP/s

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-GI&IPP s EDG

MOTOR STARTING ANALYSIS


Motor Terminal Voltage (Motor Base)
Attachment 9 : Motor Starting Study Result
Case Study Scheme - 5
HOT WELL PUMP-A Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
LV System are made Separate
120
Page 4 of 6

100

80
Vt (% of Motor Rated kV)

60

40

20

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP /s EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IPP/s

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-GI&IPP s EDG

MOTOR STARTING ANALYSIS


Bus Voltage
Attachment 9 : Motor Starting Study Result
HOT WELL PUMP-A
Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
120 LV System are madeSeparate
Page 5 of 6

110
Vbus (% of Bus Nominal kV)

100

90

80
0 2 4 6 8 10 12 14 16
Time (Sec.)
ETAP
Project: Muara Laboh GPP 12.6.0H Date: 04-25-2019
Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Revision: MS GI+IPP /s EDG
Engineer: Study Case: MS HWP Config.: MS-GI+IPP/s

Project File: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0)\ETAP\MuaraLaboh


Output Report: MS-GI&IPP s EDG

MOTOR STARTING ANALYSIS


Motor Line Current

Attachment 9 : Motor Starting Study Result


HOT WELL PUMP-A Case Study Scheme - 5
Power Supply From 20kV GI Solok + Two (2) Hydro Power Plant and MV System and
500 LV System are made Separate
Page 6 of 6

400

300
I (% of FLA)

200

100

0
0 2 4 6 8 10 12 14 16
Time (Sec.)
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 10

TCC CURVE

Page 36 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


Refer to Curve, Setting relay of Hot Well
Pump Motor capable to protect and save
motor during starting impact from drop
voltage motor, even drop voltage more
than 20%. Relay protection curve still
under the themal demage curve motor
(Hot).

Based on Data Motor. starting motor are


following
100% Voltage: 2 Sec
80% Voltage: 4 Sec
70% Voltage: 8 Sec (Assumption)

Amps X 100 MV UNIT SWITCHBOARD (Nom. kV=6.3, Plot Ref. kV=6.3)


.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
Cable1
500 Ampacity Relay4 - OL 500

ABB
300 Based on Thermal Curve REM 615B 300

of motor data CT Ratio 150:1


Thermal Overload Curve
Pickup = 0.85 (0.3 - 1.5 xCT Sec) MV UNIT SWITCHBOARD
100
Time Constant = 2 100

50
HOT WELL PUMP-A 50

30 30

Relay4 - P CB30
10 10
OC1
ABB
5 REM 615B 5
Seconds

Seconds
±
CT Ratio 150:1
IEC - Long Time Inverse R Relay4
3 3
Pickup = 1.1 (0.3 - 5 xCT Sec)
Time Dial = 0.25
3x = 15 s, 5x = 7.5 s, 8x = 4.29 s
Inst = 7.7 (0.5 - 35 xCT Sec)
1 Time Delay = 0.04 s 1

.5 .5
HOT WELL PUMP-A
930 kW
.3 .3
Cable1 - P

HOT WELL PUMP-A-100%


930 KW
.1 .1

HOT WELL PUMP-A-80%


.05 .05

.03 HOT WELL PUMP-A-70% .03

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 MV UNIT SWITCHBOARD (Nom. kV=6.3, Plot Ref. kV=6.3)


ETAP Star 12.6.0H

Hotwell Pump

Project: Muara Laboh GPP Date: 24-04-2018


Location: Muara Labuh SN:
Contract: 14000011-OS-10101 Rev: PRE-COMM
Engineer: Fault: Phase
Filename: D:\02\02 MLB\03 Basic\Etap 20190318 (16.0.0
POWER SYSTEM STUDY FOR COMMISSIONING POWER SUPPLY

Document No : Origin Rev No. Contract No :

ML-PRD01-ENG-CCAL-00XX MA 0 14000011-OS-10101

ATTACHMENT 11

REFERENCE DATA

Page 37 of 37

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


Attachment 10 : Hot Well Pump Motor
(1) Engineering Design
Page 1 of 3
Attachment 9 : Hot Well Pump Motor
(1) Engineering Design
Page 2 of 3
Attachment 9 : Hot Well Pump Motor
(1) Engineering Design
Page 3 of 3
Attachment 10 : Hot Well Pump Motor
(2) FAT Report
Witness Test Record for Motor of Hotwell Pump
Document No : Origin Rev No. Contract No :

ML-PRD01-QAC-CRPT-7004 FH 0 14000011-OS-10101

Table of Contents
Table of Contents ............................................................................................................................................2

Witness Test Record for Motor of Hotwell Pump ................................................................................... 3~11

Page 2 of 11

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


KE0110P1-DEQ/7004 Rev.0 (3/11)
KE0110P1-DEQ/7004 Rev.0 (4/11)
KE0110P1-DEQ/7004 Rev.0 (5/11)
T
ESTR
EPO
RTO
FTH
REEP
HAS
EIN
DUC
TIO
NMO
TOR
三相誘導電動機検査成績表 F
ujiE
lec
tri
cCo
.,L
td.

C
ust
ome
r
御注文主名 P
T.S
UPR
E!!
E ENERGYMUARA LABOH
W
or
ki
ng
.No
.
K
KSN
o. A!L01LCA21APOOH!Ol 製番 S1KE0110M040
S
or
ialNo
.o
r D
at
eofT
es
t
M
ach
ineN
o
. 1803J556NS1 試験日 2018-04-06
念 乎

A
ppl
ica
tio
n A
ppr
ove
dby P
rep
are
dby
用途
Motor for Hotwell Pump(
A) 承 認 =
l.
'.
J:
.心迅’

成 :災.尻グ
T
ype F
ram
e P
ole
s
型式 !
ILA
756
ED 枠番 560
I 930 k
l『
1
2 極

I I .I
-
l Cl
ass
6300 V
olt
s 50 H
z 1
28 A
mp 490 mm 耐熱クうス 155(
F)
R
a
定ti
n
格g S
ec
.V. S
ec.
A. S
tan
dar
d
CONT 二次電圧 二次電流 規格 IEC60034-1(
201
0)
C
har
act
eri
sti
csT
est
特性試験
W
ind
in
線gR
esi
sta
nce N
oLo
adT
est L
ock
edR
oto
rTe
st
巻 抵抗 (Q) Amb
.
. H
z . P
ol
os
無負荷試験 拘束試験
T
em
p S
ec
.V
S
tat
or R
oto
r 周温
固定子 回転子 (
℃)
周波数 V
olt
s A
mp 鼻 W
att
s V
olt
s A
mp
. W
att
s 二次電圧 極

0
.361 1
8 50 6300 6
4.8 24000 1
661 1
28 75330 1
2

25 900 1
28 53630

戻紐n 4-;/l3r :
-
IJ
.
W
i
[R
,
t
n
v
e
s
i
,
s叫
w,
d

IQ
A
ui
iE
Y
!●
.Sc
u
tr
iw
c
,Co
.,L
td.
L
oadC
har
act
eri
sti
cs
負荷特性 等価回路法による byEquivalent Circuit !
!et
hod :JEC-2137(
200
0)

50 H
z, 6300V
, 1
2P, H
z, V
, P
,
L
oad
負荷率 (
%) 2
5 5
0 7
5 1
00 1
25 25 5
0 7
5 1
00 1
25
C
urr
ent 2
.,
::
,/宕
電流 (
A) 7
0.0 8
3.1 1
02 1
25 1
52 D
戸A
¥T
WE
<l
T 3
oo
,昴
c ソ

nf
tl
/,r
.v
,r
.w
r.
n
E
ffi
cie
ncy
効率 (%) 8
9.7 9
3.5 9
4.2 9
4.1 9
3.6 /,三
S ピ

P
owe
rFa
cto
r(% ONB
Eii
AL
FOF
3
3.9 5
4.8 6
6.6 7
2.5 7
5.l
力率 )
1
otV如 J 乙 如<
11
5/

S
lip
滑り (
%) 0
.49 0
.99 1
.52 2
.10 2
.76
S
tat
or R
oto
r V
ibr
ati
onT
es
t
固定子 回転子 振動試験 (
P-P
)
I
ns
ul
.Re
sis
tan
ce M
ax
絶緑抵抗 1000 MO MO 最大 1
.8 μm
B
roa
kdo
wnT
orq
uo k
V I
ns
pe
ct
ionofAp
po
ar
anc
o
最大トルク (%) 208 b
y I・0M
egg
er C
on
st
ru
cti
on& O
t1
tl
in
o-
mo
D
. n
s1

.o
n造: G o
od
L
oc
ko
dRo
tor
Tor
quo D
iel
ect
ricT
es
t 外観・ ・寸法検査:良
最小始動トルク (%) 1
74 酎霞圧試験 13600 V V S
pac
eH e
ate
r
L
ock
edR
oto
rCu
rre
nt(
A
) 1
00M Oby,
051
;
VMog
go
r
637 (
A. CG
O
!f
afo
rI日i
n
) G
ood
最大始動電流 2
000 VG
oo
d
Temperature Rise Vibrationtest( M
ax.
)
Velocity :0
.94mm/s
ec(
RMS
)
C
ond
iti
ono
fTe
st Temperature Rise K
Noise test dB(
A)
Co
oling Windings Frame Bearings
Average :7 8.3 B
.G.N :6
5.0
byEm
bedd
ed
Load Air
. t l
1e
nno
mc
term
eth
od byThe
rmo
meterMethod Rotationdirectionch
eck
% ℃ Sta
torR otor D
-Ed N
n -E
nd Thrust CC
IVas viewedfromth
edr
ive side
Natural frequency
100 24 *72 45 29 21 1
3
Terminal boxdirection :19.8Hz
*67KbybyResistanceMethod Directionperpendicular
tot het ermina
l box :2
3.5Hz
I
I
K C
539
l92
KE0110P1-DEQ/7004 Rev.0 (6/11)
MeasurementofRTD'sresistance

KKSN
o. ML01LCA21AP001-M01 S
er.N
o. : 1803J556NS1

M
easur
ed
M
eas
uri
ngp
oin
ts va
,ue
(Q)
u 1
06.
8
V 1
07.
1
w 1
06.
9
U
' 1
07.
0
RTD'sf
orw
ind
ing V
' 1
07.
2
W' 1
06.
7
U" 1
06.
9
V
'' 1
07.
2
W" 1
06.
7
D
riv
e-E
nd 1
07.
5
RTD'sf
orb
ear
ing N
on-
dri
ve-
End 1
07.
4
T
hru
st 1
07.
3
Amb.Temp: 1
8 ℃

DATE:r
あ舟杓江{
J
応 ?tl /d う
笠 l饂芯
:::
ふd □W
ITN
ESS
ED 団R
EVI
E¥V
ED
~ ';J.~伽嘉一 ポ今字
QAY.S
uwa加
F
ujiE
le
ctr
icC
o.,L世 ON BEHALF OF

和 vN,
孤 な 釦<
es
/q

D
ate : 2018/3/28

A
ppr
ove
d by: ぷ 年 砂 磁

P
rep
are
dby : J
:
.
.~

F
uj
iEl
ect
ricC
o.,L
td.

KE0110P1-DEQ/7004 Rev.0 (7/11)


CONSTRUCTIONANDDIMENSIONINSPECTION
構造・寸法検査
(Refert
otheo
utl
inedrawing 外形図参照)

S
eri
alNo
, D
ateo
fIn
spe
cti
on
:1803J556NS1 2018/4/6
機番 検査日

Approved
KKS N
o. ・ML01LCA21AP001-M01 点名研磁・
承認

A
ppl
ica
tio
n I
nspe
cte
d
:Motorf
orH
otw
ellPump(A) S.Terao
用途 検査

Construction 構造
It
em 項目 R
esu
lt 結果 Cri
ter
ia 判定基準
Name p
lat
e Ac
cor
dingt
onamepl
atedra
win
g
: Good 銘板図による ( Z
D.18
03J55
6N1-2
)
銘板
P
ain
tin
gco
lor
Good RAL501O
(Bl
ue)
塗装色
Appearance M
anu
fact
ure
r'ss
tan
dar
d
: Good
外観 製作者基準

Dimensioni
nm m 寸法 m m
Item A
ctu
al 測定値 Cr
ite
ria
項目 1803J556NS1 判定基準

H
eig
htfromf
oun
dat
ionf
lan
ge
3937 3930 + 40
フランジ面からの高さ
D
ist
ancebetweens
haf
tce
nte
randc
ool
er
c
over 1605 1610 土 20
軸中心から冷却器枠までの距離
F
lan
geo
ute
rdi
ame
ter
¢1600 ¢1600 + 1
8

ランシ
・タH至
D
ist
anc
ebe
twe
enf
oun
dat
ionf
lan
gea
nds
haf
ten
d
2
85.
0 285 + 1
.5
フランジから軸先端までの距離
P
itc
hci
rcl
edi
ame
tero
ffl
ang
efo
und
ati
onh
ole ¢1500 ・2.0
r
/,1
500
.0 十
フランジ据付穴の PCD
Boreo
ffo
und
ati
onh
oleo
ffl
ang
e +
0.5
2
¢28.00 ¢28


フランヅの据付用穴の内径
D
iam
ete
roff
lan
ge打x
er
¢1400,00 ¢1400 +0.039
フランジいんろうの直径
S
haf
tdi
ame
ter +
0.040
¢160.035 ¢160
軸の直径 +0
.01
5
キー
Ke溝wの
y 幅
ayw

Keywayd
e
i
d

p
t

t
h
h 3
9.

1
3
9
6

.
0

0
9
40

1
3
-
0.
+
0
0
.
6
3
2


キー溝の深さ
L
eng
tho
fsh
afte
xte
nsi
onf
roms
hou
lde
r
2
80.
0 280 + 0
.5
軸端長さ
Screwsp
eci
fic
ati
ono
fth
evi
bra
tio
nde
tec
ter
Gaugemat
chi
ng
fo
rs e
at MS、P1
Good
振動計取付座ネジ仕様

Note:C
rit
eri
aar
edependont
he
作 の
者ap
p基r
ov
準eddr
awi
ngandm
anu
fac
tur
er'
sst
and
ard DATE:
IE
IS
J
S的-
1冗訴訟
E
VI即
?
1 ED
注:判定基準は承認図及び製 による
□WITN
片ふ滋
罠?訊畷足ェ叶虚
13雷
悶ごぷd 亡 11 I
r C:1 Cf"¥Tl:)J("¥ r,,.n IT n
ONB
EHA
LFO
F

F
QA
uj
iE
Yl
.e
S坦
c
uw吐
a恥辿 L
td.

KE0110P1-DEQ/7004 Rev.0 (8/11)


REPORTOFRUSTPREVENTION & PAINTINGWORK
Therustprevention& p
ain
tin
gworkhavebeenc
arr
iedouts
ati
sfa
cto
ryasb
ell
ow.
12-Apr-18
F
ujiE
lec
tri
cCo.,Ltd

CUSTOMER PT.SUPREME ENERGY MUARA LABOH

WORKINGNa S1KE0110M040 MACHINEN~ 1803J556NS1

WORKINGPLACE OUTDOOR
三 WORKINGCOMPLETION 11-Apr-2018

WORKINGENVIRONMENT FINE RAINY


三 TEMPERATURE: 19℃ HUMIDITY: 70%

SURFACE INSTRUMENT SHOTBLASTANDSANDBLAST

SSPCNo.

『文ン
~-
SSPC-SP-10(NEAR-WHITEBLASTCLEANING)

-vI ‘
b ",u ’
ノ□R
I evi
ewd
CLEANINGCONDITION (SOLVENT) LACQUERTHINNER .傘 峰
'
;
J
_ '
FuQ
i
iA
EY
l.
eS
cu
tr
iw
c
abC
o
e.
,Ltd. 三 NOGOOD

INTERNAL EXTERNAL

No.OF D.
F.T
. No.OF D
.F.
T.
NAMEOFPAINT NAMEOFPAINT
COAT (μm) COAT (μm)
Epoxyr
esi
npri
mer.
PRIMER SPEC 1 20
(MPPRIMER6000)

COAT RESUL DITTO 1 25

Organiczincr
ichp
ain
t.
UNDER SPEC 1 75
(NIPPEZINKY8000HB)

COAT RESUL" DITTO 1 75

Epoxyr
esi
npri
mer
.
FINISH SPEC 1 100
(HI-PON30MASTICPRIMER)

COAT RESUL" DllTO 1 105

Polyurethaner
esi
nfi
nis
hcoat
FINISH SPEC 1 75
(Hl-PON50FlNlSHGOA)

COAT RESUL" o
rrr
o 1 80

TOTAL SPEC 20 250


DRYFILM
THICKNESS RESUL" 25 260

FINISH SPEC MunsellN5 RAL501O(Blue)

COLOR RESUL
― DITTO DITTO

REMARKS

DA
WT
IE
TN
:パ
E
I`
S
SS
'
ふE
AJD '
R
約凌凹
, 2
.E
V
0
7
/I
E1
/
3'
疋D
QUALITYCONTROLSECTION

D.F.T : DryFilmThickness. APPROVED

PAINTMAKER : KANSAlPAlNTCO.,LTD.
ONBEHALFOF 〖公.沼•砂成
7
吸 J
v'
rn
cI噌C匹 免
(
KKSNo.:ML01LCA21AP001-M01 CHECKED
]二昴ク[

KE0110P1-DEQ/7004 Rev.0 (9/11)


MEASURING A
PPA
RAT
US L
IST
侭 Z
fJ
Jo う饂:
-峠 l 古
グ5
↑ バ グdr /
K
KSN
o. :M
L01
LCA
21A
POO
H!O
l
QAY.S
uwa加
F
ujiE
le
ctr
icC
o.,L
td
. S
eri
alN
o. :1
803
J55
6NS
1

Valid
Manufacture R
ate orMo
del A
ppara
tus
N
o. ApparatusName Calibration
Name N o
. N
o.
Period
D
igi
talp
owe
r 3
101 D
ec.
-20
18
1 Y
OKO
GAW
A 0~10oov;o~20A
m
ete
r
2 M
egg
er Y
OKO
GAW
A 500V/1000MQ 5
190 D
ec.
-20
18

3 M
egg
er Y
OKO
GAW
A 1
000
V/2
000
MQ 5
171 D
ec.
-20
18

4 D
iel
ect
rict
est K
OA 0~30kV 7
541 D
ec.
-20
18

D
igit
al t e
mpe
rat
ure
5 i Y
OKO
GAW
A o~soo゜C(J) 9
570 J
an.
-20
19
n
dica
tor

6 D
oub
leb
rid
ge Y
OKO
GAW
A o
.oorn~non 5
256 D
ec.
-20
18

7 V
ibr
ati
onm
ete
r I
MV 10~1000µm(P-P) RH1184 D
ec.
-20
18

8 N
ois
ele
velm
ete
r R
ION 27~130dB(A) 7
118 D
ec.-
201
8

, T
e
r
e
m
c
p
o
e
r
r
a
d
e
t
r
u
re
F
UJI
-
200℃ ~+uoo℃
(
J) 9
695 J
ul.
-20
18
T
empe
ratu
re
1
0 r F
UJI 0~400℃ /PTlOOQ 9
735 J
ul.-
201
8
e
cord
er( f
orR
TD)
1 S
1 topw
atc
h S
EIK
O o~30min 2
84 F
eb.-
201
9
0~750/lOOOV
2 D
1 igi
talm
ult
ime
ter I
-
I
IOK
I 1
706
115
76 J
un.-2018
/O~lOA

3 V
1 ern
ierc
ali
per M
ITU
TOY
O 0~3oomm 1
88 S
ep.
-20
19

4 V
1 ern
ierc
ali
per M
ITU
TOY
O O~l500mm 0
06 S
ep.
-20
19

5 V
1 ern
ierc
ali
per M
ITU
TOY
O 0~2ooomm 0
02 S
ep.
-20
19

6 O
1 uts
idem
icr
ome
ter M
ITU
TOY
O 125~150mm 0
53 J
un.-2019

7 O
1 uts
idem
icr
ome
ter M
ITU
TOY
O 150~175mm 0
50 J
un.-2019

8 I
1 nsi
dem
icr
ome
ter M
ITU
TOY
O 25~50mm 0
20 J
an.
-20
19

9 T
1 apem
eas
ure K
YOT
ODO
KI o~5500mm 0
03 S
ep.
-20
19
C
oat
ing
2
0 t M
ITU
TOY
O o~500µm 5
23 M
ar.-2019
hic
kne
ssg
aug
e
1 T
2 hre
adg
aug
e K
URO
DA M
S,P
l.0 N
l00
38-
12 S
ep.
-20
18

IDATE:S
/S

EDA E
V
I
げ面四r
EI
g
V I
fN
E ED
)(ぷ如冴
KE0110P1-DEQ/7004 Rev.0 (10/11)
-----~--------~~---------------------------;=--


TESTCERTIFICATE 試 験 証 A闊itsubishiSteelM u0 anInc. 『 『
QUALITYASSURANCESECTIO

)
.
.
Q叫 ;
ty心 '
"ra
n"'脳 p
art
mon
t,M,
rnra
n

注文主 M
ess
rs 乖萎宗 P
urc
has
er オーダー O
rde
rNo
.

"ユ M,,Jt.JI一品ふ成• ..A A.
t
.
r 殿 血畜ー S卒~^心 殿 """qワ OAq
特約店 納入先 溶番 H
eatN
o.

品名 T
ypeo
fst
ee
l
殿 "
'
..
.,
.
'震
C
o

n

d
i

t

i
on
土 ヰ 匹 上 ヽ ‘ ”
Cer
tif
ica
teNo.
11A?177
発行日 Da
te
殿
形状DS~hopeI 寸法 S
I匹 訥入状態 試験証明杏ぬ
Q?F;(' D i
,,;r.nn<JllA 1~n~n~
""" nn
化 学 成 分 Ch
emicalC o
mposi
tio
n (%)
項 目 C 当抵 D I 値
C S
i Mn p s N
i c
, Mo Cu
I
tem
s NI+CR Ce
q. DI
X
lQO X
100 x
100 X
!OO
O X
l00
0 X
l00 X
100 X!OO XlO
O Y1nn
規 格 MAX. MAX.
Sp
ec. 22
~a - 1 ~,;
5 Rn MAX;n MAX社
- 30 MAX;0 MAX.
?n ~n ~~

成 績
Res
ult
s n~ 1ワ Aワ ワ 1A ,
. 1只 1 1?
捩 械 的 性 貨 M
ech
anic
alP
rop
ert
ies 供 試 材 熱 処 理
項 目 引張政さ 伸び 絞り 硬さ 衝 撃 値 曲げ試験 Sampling H
eatTreatment
降伏点
I
tem
s T
ens
ileS
tr. E
lon
gat
ionR
el.
ofA
re
aHa
rdn
ess I
mpa
ctV
a1u
e BendTe
st Condi
tion ℃
Y
IE.
,L1
1
D11
1Pq• % 1s
o
・ Materia
l T D
ll'""" % unw
規 格 MIN. MIN. MIN. 123
,
-
Sp
ec. qa~ AAn "ワ -1A~ N T.P.
A.C. ・
成 拭 860- 910
Res
項目 I
u
lts
t
e m
s
•a• 吋• I•" R1

1A0
入 性(一端焼入法) H
ard
ena
bil
ity(
EndQ
uen
chi
ngM
eth
od)
ann• P

規 格
S
pec.
成 絨
Res
ult
s
非 金 屈 介 在 物 詰晶位度 地 き ず 脱炭 製品硬さ 硬さ 記事 Remarks
項 月
N
on-・
Met
all
icInc
lusio
n G
rai
nSi
ze Macro D
a書
c
ar
・ BodyHard
ness H
ard
nes
s ULTRASONIC INSPECTION:GOOD
I
tem
s マクロ組様
Stre
akFlaw 切ri
,at
io
n
M四 O ;

『 ヘ


『:
規 格 St
ruc
tur
e DATE I~·、:、:,·
'
S
pec
.
心^多



-o4-I


二? □W
IT :
E
IS
/み
SED
Ar屯
v
:,RE
砂V/
/!
J
EV
ED [

ぶ. -
'"-'-. _
,
'
.
-....、
.. .

.
、、 -
成 Ii
i r
i
F埠iE
Y.S
犀 u
血w1C
匹o
.,L
td. I $碕 ヤ',--1''-へ,,'''~" ~ ?ぐ:ぅ ('j ~,


c
;
;
,_
,,
'.
Res
ult
s m,AO cnc I

-.'-''・-, ,
'



;
,
,
.,

.c
/
.
d
,
' ヽ/ .
,;ふ'ふ.. .
心ンッコ

臼畑
,
._


.
.r.
.
.,1 J
, ヽ -_
, ヽ 1-
∼^
I
tisherebyc
ert
ifi
edt
hutt
heabover
esu
ltsa
ret
rueandc
orr
ecti
neveryd
eta
ils
. ,.........、ィ
上記の成絞は要求事項を満足していることを証明します。
Manager.Q
ual
ity年 suranceS
ect
ionMuro
ranWorks.
Rr,q~fi,UU_..R 且,.4n1 n-liL r
.in
1n

弘a.~-t ,
/t
03
JS
:ダ&
Nfl
KE0110P1-DEQ/7004 Rev.0 (11/11)
Attachment 10 : Vacuum Pump Motor
(3) Engineering Design
Attachment 10 : Vacuum Pump Motor
(4) FAT Report
Witness Test Record for Motor of Vacuum Pump
Document No : Origin Rev No. Contract No :

ML-PRD01-QAC-CRPT-7007 FH 0 14000011-OS-10101

Table of Contents
Table of Contents ............................................................................................................................................2

Witness Test Record for Motor of Vacuum Pump................................................................................... 3~16

Page 2 of 16

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


KE0110P1-DEQ/7011 Rev.0 (3 / 16)
KE0110P1-DEQ/7011 Rev.0 (4 / 16)
KE0110P1-DEQ/7011 Rev.0 (5 / 16)
KE0110P1-DEQ/7011 Rev.0 (6 / 16)
KE0110P1-DEQ/7011 Rev.0 (7 / 16)
KE0110P1-DEQ/7011 Rev.0 (8 / 16)