Dissertation Report on

Seismic Analysis of High-Rise RCC Structures with Steel


Outriggers and Belt Truss System
Submitted
in partial fulfillment of the requirement for the degree of
Master of Technology
in

Civil Structural Engineering


By

SAWANT VAIBHAV DINKAR


Roll No: 17221214
Under the guidance of
Prof. V.M.BOGAR

DEPARTMENT OF CIVIL ENGINEERING


M-TECH CIVIL – STRUCTURAL ENGINEERING
GOVERNMENT COLLEGE OF ENGINEERING, KARAD.
(An Autonomous Institute of Government of Maharashtra.)

Affiliated to Shivaji University, Kolhapur.


CERTIFICATE
This is to certify that the dissertation entitled “Seismic Analysis of High-Rise RCC Structures
with Steel Outriggers and Belt Truss System”, which being is submitted herewith for the
award of the ‘Master of Technology’ in Structural Engineering’ of Government College of
Engineering, Karad (An Autonomous Institute of Government of Maharashtra.). This is the
result of the original research work and contribution by ‘Mr. Sawant Vaibhav Dinkar’ under
my supervision and guidance. The work embodied in this dissertation has not formed earlier for
the basis of the award of any degree or compatible certificate or similar title of this for any other
diploma/examining body or university to the best of knowledge and belief..

Dr.Y.M. Ghugal Prof. V.M. Bogar

H.O.D. Guide
Applied Mechanics Department Applied Mechanics Department

Dr. A.T. Pise

Principal
Government college of Engineering

P a g e | ii
DISSERTAION APPROVAL SHEET
Mr. Sawant Vaibhav Dinkar has done the appropriate work for the award of Master of Technology
in Structural Engineering of Government College of Engineering ( An Autonomous Institute of
Government of Maharashtra ), affiliated to Shivaji University, Kolhapur (M.S. India)

Date :

Place :

Examiner

Name

Signature

Guide

Name

Signature

P a g e | iii
DECLARATION
I declare that this report reflects my thoughts about the subject in my own words. I have
sufficiently cited and referenced the original sources, referred or considered in this work. I have not
misrepresented or fabricated or falsified any idea/data/fact/source in this my submission. I understand
that any violation of the above will be cause for disciplinary action by the Institute.

Date :

Place : Sawant Vaibhav Dinkar

P a g e | iv
ACKNOWLEDGEMENT
I take this opportunity to express my deep sense of gratitude towards my guide Prof. Mrs.
V. M. Bogar, of Applied Mechanics Department, Government College of Engineering, Karad &
Dr. Y.M. Ghugal, Head of Department, Applied Mechanics Department, Govt. college of
Engineering, Karad, for their well formulated and indispensable guidance and also for extending all
kinds of cooperation during the course and in completion of this report, without which this work
would not have been possible.

I am also thankful to all supporting staff of Applied mechanics Department and Library of Govt.
College of Engineering, Karad.

I am extremely grateful to my family and friends for their constant inspiration and motivation
during the course.

Lastly, I am thankful to all those who have helped me directly or indirectly to complete this
dissertation work.

Date :

Place : Sawant Vaibhav Dinkar

P age |v
ABSTRACT
During the last few decades several buildings have been built utilizing belt truss and
outrigger system for the lateral loads transfer (throughout the world). This system is very
effective when used in conjunction with the composite structures especially in tall buildings.
The optimum location of outriggers and belt truss system provided at various positions along
the height of building using Linear and Non- Linear Analysis is the main scope of this research.
The key parameters discussed in this paper include lateral deflection, story drifts and base shear.
Nine different models were prepared for different positions of outrigger system along the height
and by providing X and V types of bracing systems results have been compared. Analysis of
RCC building provided with 1,2 and 3 outriggers are separately carried out using finite element-
based software (ETABS) following guidelines of revised IS: 1893 (Part 1)-2016 Seismic loads
are consider as per IS: 1893- 2016. The results indicate that lateral displacement and maximum
storey drift gets reduced by and respectively compared to conventional building when X-type

bracing outriggers are used.

P a g e | vi
CONTENTS

Certificate ii

Dissertation Approval Sheet iii


Declaration iv
Acknowledgement v
Abstract vi
Content vii
List of Figures x

List of Tables xii

Nomenclature xiii

Abbreviation xiv

Chapter 1: INTRODUCTION ................................................... Error! Bookmark not defined.

1.1Background- ........................................................................Error! Bookmark not defined.

1.2Concept of Outrigger- .......................................................... Error! Bookmark not defined.

1.3Outrigger Structural System ................................................. Error! Bookmark not defined.

1.4Advantages of Outrigger systems: ........................................Error! Bookmark not defined.

1.5 Disadvantages of outrigger systems: ....................................Error! Bookmark not defined.

1.6 Outline of Project Report .................................................... Error! Bookmark not defined.

1.7 Closure: ..............................................................................Error! Bookmark not defined.

Chaper 2: LITERATURE REVIEW ........................................ Error! Bookmark not defined.

2.1 Introduction: .......................................................................Error! Bookmark not defined.

2.2 Review of previous studies: ................................................. Error! Bookmark not defined.

2.3 Summary of Literature: ....................................................... Error! Bookmark not defined.

P a g e | vii
2.4 Gaps in Literature: .............................................................. Error! Bookmark not defined.

2.5 Objectives of present work: ................................................. Error! Bookmark not defined.

2.6 Closure: ..............................................................................Error! Bookmark not defined.

Chapter 3: METHODOLOGY ADOPTED .............................. Error! Bookmark not defined.

3.1 Introduction: .......................................................................Error! Bookmark not defined.

3.1.1 Linear Dynamic Method:...........................................Error! Bookmark not defined.

3.1.2 Non-linear time history analysis method: ................... Error! Bookmark not defined.

3.2 Problem statement: .............................................................. Error! Bookmark not defined.

3.2.1Input Data of Building: ...............................................Error! Bookmark not defined.

3.2.2Material properties: .................................................... Error! Bookmark not defined.

3.3.1 Details of model: ....................................................... Error! Bookmark not defined.

3.3.2 Ground motion data considered for non-linear time history analysis:Error! Bookmark
not defined.

3.3.3 Criteria for selection of suitable steel bracing section for outriggers:Error! Bookmark
not defined.

3.4 Closure: ..............................................................................Error! Bookmark not defined.

Chapter 4: MODELING AND ANALYSIS .............................. Error! Bookmark not defined.

4.1 Introduction: .......................................................................Error! Bookmark not defined.

4.2 Modeling of Buildings: ....................................................... Error! Bookmark not defined.

4.2.1 Software modeling of G+45 conventional building: ...Error! Bookmark not defined.

4.2.2 Software modeling of G+45 story building with outriggers using V and X-type
bracings located at top storey: ............................................Error! Bookmark not defined.

4.2.3 Software modeling of G+45story building with outriggers using V and X-type
bracings located at top and 35th storey: ............................... Error! Bookmark not defined.

P a g e | viii
4.2.4 Software modeling of G+45 story building with outriggers using V and X-type
bracings located at top and 35th storey: ............................... Error! Bookmark not defined.

4.2.5 Software modeling of G+45 story building with outriggers using V and X-type
bracings located at top, 15th and 31st storey: ....................... Error! Bookmark not defined.

4.3 Lateral displacement limitation: ..........................................Error! Bookmark not defined.

4.4 Provision of hinges: ............................................................ Error! Bookmark not defined.

4.5 Validation of software: ........................................................ Error! Bookmark not defined.

4.5.1 Manual problem statement: .......................................Error! Bookmark not defined.

4.5.2 Analysis of above problem using ETABS software: ..Error! Bookmark not defined.

4.6 Closure: ..............................................................................Error! Bookmark not defined.

Chapter 5: RESULTS AND DISCUSSION .............................. Error! Bookmark not defined.

5.1 Introduction: .......................................................................Error! Bookmark not defined.

5.3 Results from non-linear time history analysis: ..................... Error! Bookmark not defined.

5.4 Comparative results:............................................................ Error! Bookmark not defined.

5.4.1 Lateral displacement: ................................................Error! Bookmark not defined.

5.4.2 Storey Drift: .............................................................. Error! Bookmark not defined.

5.4.3 Base shear: ................................................................ Error! Bookmark not defined.

5.5 Closure: ..............................................................................Error! Bookmark not defined.

Chapter 6: CONCLUSIONS AND FUTURE SCOPE ............. Error! Bookmark not defined.

6.1 Conclusion: .........................................................................Error! Bookmark not defined.

6.2 Future scope:.......................................................................Error! Bookmark not defined.

REFERENCES .......................................................................... Error! Bookmark not defined.

P a g e | ix
List of Figures
Fig. No. Title ........................................................................................................... Page No
Figure 1. 1 : Interaction of core and outrigger............................ Error! Bookmark not defined.
Figure 1. 2 : Outrigger system with a central core and offset coreError! Bookmark not defined.
Figure 1. 3 : Building with outrigger and belt truss system ........Error! Bookmark not defined.
Figure 1. 4 : Building with conventional outrigger system .........Error! Bookmark not defined.
Figure 1. 5 : Building with virtual outrigger system................... Error! Bookmark not defined.

Figure 3. 1 : Plan of G+45 storied RCC building ....................... Error! Bookmark not defined.
Figure 3. 2 : Elevation of G+45 storied conventional building ...Error! Bookmark not defined.
Figure 3. 3 : Imperial Valley ground acceleration ...................... Error! Bookmark not defined.

Figure 4. 1 : Conventional frame model with Outriggers ...........Error! Bookmark not defined.
Figure 4. 2 : G+45 building with outriggers using V and X-type bracing located at top storey
.................................................................................................Error! Bookmark not defined.
Figure 4.3 : G+45 building with outriggers using V and X-type bracing located at top and 35th
storey ........................................................................................ Error! Bookmark not defined.
Figure 4. 4 : G+45 building with outriggers using V and X-type bracing located at top and 23rd
storey ........................................................................................ Error! Bookmark not defined.
Figure 4. 5 : G+45 building with outriggers using V and X-type bracing located at 15th and 31st
storey ........................................................................................ Error! Bookmark not defined.
Figure 4. 6 : Plastic hinge mechanism of G+45 storey building .Error! Bookmark not defined.
Figure 4. 7 : Hinge response plot against moment ..................... Error! Bookmark not defined.
Figure 4. 8 : Building configuration for validation..................... Error! Bookmark not defined.
Figure 4. 9 : Design seismic force .............................................Error! Bookmark not defined.
Figure 4. 10: Plan and elevation of building in ETABS softwareError! Bookmark not defined.

P age |x
Figure 5. 1 : Comparison of lateral displacement from linear dynamic analysisError! Bookmark
not defined.
Figure 5. 2 : Comparison of lateral displacement from non-linear time history analysis ....Error!
Bookmark not defined.
Figure 5. 3 : Comparison of storey drift from linear dynamic analysis ..... Error! Bookmark not
defined.
Figure 5. 4 : Comparison of storey drift from non-linear time history analysisError! Bookmark
not defined.

P a g e | xi
List of Tables
Table No Title Page No
Table 4. 1 : Lateral load distribution ..........................................Error! Bookmark not defined.
Table 4. 2 : Free Vibration Properties of the building for vibration in theError! Bookmark not
defined.
Table 4. 3 : Calculation of modal mass and modal participation factorError! Bookmark not
defined.
Table 4. 4 : Lateral load calculation by modal analysis method .Error! Bookmark not defined.
Table 4. 5 : Base shear at different storeys ................................ Error! Bookmark not defined.
Table 4. 6 : Storey shear using ETABS software ....................... Error! Bookmark not defined.

Table 5. 1 : Lateral displacement from linear dynamic analysis .Error! Bookmark not defined.
Table 5. 2 : Storey drift from linear dynamic analysis ...............Error! Bookmark not defined.
Table 5. 3 : Lateral displacement from non-linear time history analysisError! Bookmark not
defined.
Table 5. 4 : Storey drift from non-linear time history analysis ...Error! Bookmark not defined.
Table 5. 5 : Maximum lateral displacement from linear dynamic analysisError! Bookmark not
defined.
Table 5. 6 : Maximum lateral displacement from non-linear time history analysis ............Error!
Bookmark not defined.
Table 5. 7 : Maximum storey drift from linear dynamic analysisError! Bookmark not defined.
Table 5. 8 : Maximum storey drift from non-linear time history analysisError! Bookmark not
defined.

P a g e | xii
Table 5. 9 : Maximum base shear from linear dynamic analysis Error! Bookmark not defined.
Table 5. 10 : Maximum base shear from non-linear time history analysisError! Bookmark not
defined.

NOMENCLATURE
x, y, z Cartesian coordinate system for a laminate (Global coordinates)

Es Modulus of Elasticity of steel

Ec Modulus of Elasticity of concrete

K Stiffness factor

rmin Minimum radius of gyration

λ Slenderness Ratio

Ah Design horizontal seismic coefficient

g Gravitational acceleration

Z Seismic zone factor

I Importance factor

R Response reduction factor

Sa/g Design acceleration coefficient

VB Design base shear

P a g e | xiii
Wi Seismic weight at ith floor

Mk Modal mass at kth mode

Pk Modal participation factor at kth mode

Qik lateral load acting at ith floor in the kth mode

T Fundamental time period

ABBREVATIONS

RCC Reinforced Cement Concrete

SRSS Square Root of the Sum of Squares

ETABS Extended Three-Dimensional Analysis of Building System

FE Finite Element

IS Indian Standard

SDOF Single Degree of Freedom

P a g e | xiv
P a g e | xv