Вы находитесь на странице: 1из 1

SIZE & INCOMING CABLE : 4Cx25mm² XLPE/SWA/PVC CU CABLES

Poject: Al Shauiba Residential Complex Project, Al Ain Feed From : LV PANEL Main Breaker : 63 A TP Isolator
Adress/Location : ELECTRICAL SUBSTATION No. OF OUTGOING: (4 + 2) WAY
DISTRIBUTION BOARD No: DB - 1
PHASE & CONNECTED CIRCUIT LOAD WATTS CIRCUIT LOAD
BUSBAR MCB EARTH CABLE
CKT NEUTRA NO. OF LOAD PER DIVERSITY AFTER
INCOMER SECTION / RATING SIZE RATING CIRCUIT NAME / POINT REFERENCE
REF. NO L SIZE POINTS POINT R Y B FACTOR DIVERSITY
RCD (AMPS) mm² A(Kw)
mm² (WATTS) (WATTS)
R1
Y1 40 4C×6mm² * 45 (26.65) AC CONTROL PANEL - SPILIT A/C UNIT-1 1 4061 1,354 1,354 1,353 0.90 3655
B1
100mA RCD 40A 4P

R2
AC CONTROL PANEL - SPILIT A/C UNIT-2
Y2 40 4C×6mm² *
Section-2

(FUTURE)
B2
63A TP ISOLATOR

R3
Y3 40 SPARE
B3
R4 10 SPARE
Y4 10 2.5 1.5 24.0(4.7) L1 - L8 8 100 800 0.75 600
B4 10 2.5 1.5 24.0(4.7) L9 - L14 6 100 600 0.75 450
30mA RCD 40A 4P

R5 16 4 2.5 32.0(6.3) PS1 - PS2 2 200 400 0.50 200


Y5 16 4 2.5 32.0(6.3) PS3 - PS4 2 200 400 0.50 200
Section-1

B5 16 SPARE
R6 10 "
Y6 10 "
B6 10 "
TOTAL LOAD IN WATTS 4,661 1,754 2,554 1,953 5105
* NOTE: AC CONTROL PANE - EARTHING 35²mm
TOTAL DIVERSIFIED LOAD 5105 (91.30%)

Вам также может понравиться