Вы находитесь на странице: 1из 11

Indoor Selectable-

Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert® Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.

Features The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
• Plug-in design with minimal intrusion into the back box
With white and red plastic housings, wall and ceiling mounting
• Tamper-resistant construction options, and plain and FIRE-printed devices, SpectrAlert Advance
• A
 utomatic selection of 12- or 24-volt operation at can meet virtually any application requirement.
15 and 15/75 candela
Like the entire SpectrAlert Advance product line, wall-mount horns,
• F
 ield-selectable candela settings on wall units: 15, 15/75,
strobes, and horn strobes include a variety of features that increase
30, 75, 95, 110, 115, 135, 150, 177, and 185
their application versatility while simplifying installation. All devices
• Horn rated at 88+ dBA at 16 volts feature plug-in designs with minimal intrusion into the back box,
• Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
• Universal mounting plate for wall units

• M
 ounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction
device installation damage, SpectrAlert Advance utilizes a universal mounting plate
• Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
• Compatible with MDL3 sync module

• Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.

Agency Listings

7125-1653:186 (indoor strobes)


7125-1653:188 (horn strobes,
S4011 (chimes, horn strobes, horns) 3023572 MEA452-05-E chime strobes)
S5512 (strobes) 7135-1653:189 (horns, chimes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or
double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-
wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.

Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.

Horn Strobe Combination


The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.

Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)
Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)
Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D)

Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS) UL Max. Horn Current Draw (mA RMS)
8–17.5 Volts 16–33 Volts 8–17.5 Volts 16–33 Volts
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR
Standard 15 123 128 66 71 Temporal High 57 55 69 75
Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69
Range 30 NA NA 94 96 Temporal Low 38 44 44 48
75 NA NA 158 153 Non-temporal High 57 56 69 75
95 NA NA 181 176 Non-temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 NA NA 228 207 Coded Medium 44 51 56 69
Candela 150 NA NA 246 220 Coded Low 40 46 52 50
Range 177 NA NA 281 251
185 NA NA 286 258
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts 16–33 Volts
DC Input 15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
16–33 Volts 16–33 Volts
DC Input 135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262

Horn Tones and Sound Output Data


Horn and Horn Strobe Output (dBA)
8–17.5 16–33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 75 75 80 80 86 86 96 96
3 Temporal Low 71 71 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 73 74 81 81 88 84 96 92
7† Coded High 82 82 88 88 93 92 101 101
8† Coded Medium 78 78 85 85 90 90 97 98
9† Coded Low 74 75 81 81 88 85 96 92
Settings 7, 8, and 9 are not available on 2-wire horn strobes.

8-Inch Dual Voltage
Speaker for Fire and
General Signaling
Systems
The SPCW8 8-inch ceiling speaker with listed enclosure
has field selectable tap setting from 1/8 to 8 Watts. SPCW8 8” speaker provides a solution for ceiling mount
applications for tap setting range between ¹/8 watt to 8 watts.
Providing a solution for almost any voice need.
Features
• For use with separately sold tile support bracket: SB-SPC8 System Sensor offers seven different tap settings ranging from
• Flush and ceiling tile mounting with use of ceiling tile bracket ¹/8 to 8 watts providing a solution for life safety and general signaling
requirements. The high dB output reduces the number of speakers
• Voltage and speaker tap settings via jumper connection
required for sound and intelligibility. The SPCW8 is designed for high
• F
 ield selection of speaker voltage (25 and 70.7 Vrms) efficiency sound output with low total harmonic distortion to offer high
and power settings (¹/8, 1/4, 1/2, 1, 2, 4, and 8 watts) fidelity sound output.
• UL and ULC listed
Its clear audibility is designed to meet life safety needs from fire
• Broad temperature range 32°F to 120°F
to emergency communication messages. With its wide frequency
• Accepts wire up to 12 AWG range it can also be used for general signaling such as paging and
• Speaker ships with included back can background music. The SPCW8 speaker is listed to ANSI/UL 1480,
CAN/ULC S541 and CSA C22.2. No. 205 requirements for public
mode and general signaling applications as well as ANSI/UL 2043
Dimensions plenum rated. Speaker is suitable for indoor and damp installations.

The SPCW8 can be surface mounted with the included back can
or flush mounted with optional accessory, SB-SPC8. The SB-SPC8
(sold separately) offers support for ceiling tile installations and
3/4 inch knockouts are provided for conduit entry and are compatible
with plenum rated cable and plenum whip flex conduit.

Surface Mounting

Agency Listings

A0510-00

S4048 7320-1653:0500 Ceiling-Mount Speaker with Back Can and SB-SPC8 tile bridge
Speaker and Speaker Strobe Specifications
Architectural/Engineering Specifications
The System Sensor SPCW8 8-inch dual voltage speaker and enclosure shall mount using SB-SPC8 mounting bracket, sold separately. The
SPCW8 can be flush mounted with supplied back can or ceiling mounted with back can and SB-SPC8 tile bridge.

The speaker shall be a SPCW8 dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms with field selectable tap
settings from ¹/8 to 8 Watts. It should be listed to ANSI/UL 1480, CAN/ULC S541 and CSA C22.2 No. 205 requirements for public mode and
general signaling applications as well as ANSI/UL 2043 plenum rated. Speaker is suitable for indoor and damp installations. The speaker shall
have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power
taps and voltage that are selected by jumper connection.

Physical Specifications
Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Dimensions, Ceiling-Mount
Diameter Depth
SPCW8 Speaker with Grill 12.8 in., 325.1 mm 2.7 in., 68.6 mm
SPCW8 Speaker with Back Can 12.8 in., 325.1 mm 4.2 in., 106.7 mm
Length Width Diameter Opening
SB-SPC8 Tile Support Bracket: Length 23.75 in., 603.3 mm 4.125 in., 104.8 mm 10.75 in., 273.1 mm
Electrical/Operating Specifications
Nominal Voltage (speakers) 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage (speakers) 50 VDC
Operating Voltage Range (includes fire 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
alarm panels with built in sync)
Frequency Range 400 to 4,000 Hz (Fire Alarm),
200Hz - 15KHz (General Signaling)
Power ¹/8, 1/4, 1/2, 1, 2, 4, 8 watts
Input Terminal Wire Gauge 12 to 18 AWG

UL Current Draw Data


Sound Output
UL Reverberant (dBA @ 10 ft.) ¹/8 W 1/4 W 1/2 W 1W 2W 4W 8W
SPCW8 75 78 81 84 87 90 93
UL Anechoic (dBA @ 10 ft.)
SPCW8 82 85 87 91 94 97 100

Ordering Information
Speaker
White Description
SPCW8 8 Inch Dual Voltage Speaker
Accessories
White Description
SB-SPC8 Tile Support Bracket, 4-Pack

3825 Ohio Avenue • St. Charles, IL 60174 ©2017 System Sensor.


Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
www.systemsensor.com AVDS86101 • 03/17
INTELLIKNIGHT FIRE ALARM CONTROL PANEL

IntelliKnight® 5808
Single Loop Addressable
Fire Alarm Control System
The convenience of an addressable fire
alarm control panel in a cost-effective
easy to use package.

IntelliKnight Model 5808 is a 127 point class leading single loop addressable fire alarm control/communicator
system. 5808 provides you with the revolutionary value and performance of addressable sensing technology
combined with exclusive, built-in digital communication, distributed intelligent power, easy to use interface.
Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from
Silent Knight.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-328-0103.

Description
The basic 5808 system can be enhanced by adding
modules such as 5860 remote annunciator, 5824
serial/parallel printer interface module (for printing system
reports), and 5496 intelligent power module. 5808 supports
SD or SK protocol devices. 5808 also features a powerful
built-in dual line fire communicator that allows for reporting
of all system activity to a remote monitoring location.
Features
• Built-in support for up to 99 SK detectors and 99 SK
modules.
• Built in support for 127 SD devices.
• Up to 125 zones and 125 output groups.
• Uses standard wire—no shielded or twisted pair required
• Built-in digital communicator. Model 5808
• Central station reporting by point or by zone • Plex-2 door option combines a dead front
• Supports Class B (Style 4) and Class A (Style 6 or 7) cabinet door with a clear window, limiting
configuration for SLC. access to the panel while providing single
• Distributed, intelligent power. button operation of the reset and silence
• Drift compensation. functions.
• 13 pre-programmed output cadences, (including ANSI- • Integrated dead front panel protects operator
3.41), and 4 programmable outputs.
from exposure to electrical components.
• Notification circuits can be configured as 2 Class A
(Style Z) or 4 Class B (Style Y), or auxiliary power for • The FACP enclosure features a Plexiglass®
resettable, constant, or door holder power. viewing window to protect annunciator.
• Built-in annunciator with 80-character LCD display. • Acknowledge function allows operator to keep
• RS-485 bus provides communication to system track of event status.
accessories.
• Built-in RS-232 and USB interface for programming Installation
via a PC. The 5800 can be surface or flush mounted.
• Upload or download programming, event history, or
detector status via remote or direct connection. Compatibility
• Improvements in SKSS deliver five times faster The 5808 signal line circuit (SLC) supports
upload/downloads. multiple device types of the same protocol:
• Built-in synchronization for appliances from AMSECO, • SK
Gentex®, Faraday, System Sensor®, and Wheelock®. • SD
• One Form C trouble relay rated at 2.5A at 27.4 VDC and You cannot mix SD and SK SLC devices on a
two Form C programmable relays rated at 2.5A at 27.4 FACP.
VDC.
INTELLIKNIGHT FIRE ALARM CONTROL PANEL

5496

5808

Specifications Protected Premises Unit; & Water Deluge Miscellaneous Accessories


Electrical Releasing Service. Suitable for automatic,
5660 Silent Knight Software Suite
manual, waterflow, sprinkler supervisory
Primary AC: 120 VRMS at 50/60 Hz, PC-base software for FACP
(DACT non-coded) signalling services.
2.75A programming. Upload and view panel
UL Listed
Total Accessory Load: 6A @ 27.4 CSFM 7165-0559:0142; account information, event history, and
VDC MEA 429-92-E Vol. XIV detector status.
Notification Power: 6A @ 27.4 VDC, OSHPD (CA) OSP-0065-10 5670 Silent Knight Software Suite
power-limited
S-BUS Accessories End-user facility management software
Standby Current: 170 mA allows viewing of detector status and
Alarm Current: 365 mA 5860/R Remote Fire Annunciator event history via modem or direct
Notification & Auxiliary Circuits: Features the same 80 character backlit connection.
3A @ 27.4 VDC per circuit,power- LCD display keypad and firefighter's key
limited switch as the 5808. 5860 is gray and Plex-2 Door
Battery Charging Capacity: 5860R is red. Dead front cabinet door with clear
7.0-35 AH window to limit access to the FACP.
5496 Intelligent Power Module
Battery Size: 18 AH max. allowed in A 6 amp notification power expander that RBB
FACP. Larger capacity batteries can provides four additional power-limited Remote Battery Box Accessory
be housed in an RBB accessory notification appliance circuit outputs. Cabinet. Use if backup batteries are
cabinet too large to fit into FACP cabinet.
5880 LED/IO Module Dimensions: 16” W x 10” H x 6” D
Physical Features 40 LED outputs, 8 normally open (406 mm W x 254 mm H x 152 mm D)
Flush Mount Dimensions: dry contact inputs and one piezo output.
14.5” W x 24.75” H x 3.5” D SK-SCK
(36.8 W x 62.9 H x 8.73 D cm) 5865-3 and 5865-4 Seismic Compliance Kit
Remote LED Annunciator
Overall Dimensions: Features 30 programmable LED (15 red SD and SK Devices
16" W x 26.4" H x 4.65" D and 15 yellow) outputs and a piezo See the specification sheets listed
(40.6 W x 67 H x 11.8 D cm) sounder. The 5865-4 adds a silence and below for a complete listing of the SD
Weight: 28 lbs. (12.8 kg) reset switch to the package. and SK devices.
Color: Red 5824 Serial/Parallel Printer 53624 SD Devices data sheet
Telephone Requirements: Interface Module 53623 SK Devices data sheet
FCC Part 15 and Part 68 approved Provides one parallel and one RS-232
Type of Jack: RJ31X (two required) serial port for connecting a printer to 5808.
Approvals Use to print a real-time log of system
NFPA 13, NFPA 15, NFPA 16, NFPA events, detector status reports, and event
70, & NFPA 72: Central Station; history.
Remote Signalling; Local Protective 5883 Relay Board IntelliKnight & JumpStart are Registered
Features 10 general purpose Form C Trademarks of Silent Knight Flexput is a
Signalling Systems; Auxiliary
relays. Used with 5880 module. Trademark of Silent Knight

This document is not intended to be used for installation purposes. We try to MADE IN AMERICA
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are 350386 Rev. L
subject to change without notice. For more information, contact Silent Knight © 2013 Honeywell International Inc.
12 Clintonville Road, Northford, CT 06472-1610. Phone: (800) 328-0103,
Fax: (203) 484-7118. For Technical Support, Please call 800-446-6444.
www.silentknight.com
PP2611/2018/Issue 1
Page 1 of 2

XP95
Heat Detector
Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24 V, 25°C and 50% RH unless otherwise stated.

Detection principle Linear approximation over


temperature range 25OC to 90OC
Sensor Single NTC thermistor
Sampling frequency Continuous
Sensitivity 90 OC: 55 counts
Supply Wiring Two wire supply, polarity insensitive
Terminal functions L1 & L2 Loop in & out positive
+R Remote indicator positive
connection (internal 2.2 kΩ
resistance to supply +ve)
Product overview –R Remote indicator negative
connection (internal 2.2 kΩ
Product Heat Detector - A2S resistance to supply -ve)
Part No. 55000-400 Supply voltage 17 V to 28 V dc
Digital communication XP95, Discovery and CoreProtocol
Product Heat Detector - A2S
compatible
Part No. 55000-420 Modulation voltage 5 V - 9 V peak to peak
Product Heat Detector - CS Quiescent current 300 µA
Power-up surge current 1mA
Part No. 55000-401
Duration of power-up surge 0.3 seconds
Digital communication XP95, Discovery and current
CoreProtocol® compatible Max power-up time 4 seconds
Analogue value at 25ºC 25 ± 5 counts
Compliance* Alarm indicator Red light emitting diode (LED)
Alarm LED current 4 mA
Remote LED current Internal 4.5 k to +ve line (5 mA max)
Storage temperature -30°C to +80°C
Operating temperature -20°C to +70°C
Humidity (no condensation 0% to 95% RH)
or icing
Note: *
Effect of atmospheric None
55000-400; CPR, LPCB only
pressure
55000-420; CPR, LPCB, VdS, BOSEC, SBSC, CCMG, FG
55000-401; CPR, LPCB, BOSEC, CCMG, SBSC, only Effect of wind speed None in fixed temperature use
Vibration, impact and shock To EN 54 - 5
Product information IP Rating IP54
The XP95 Heat Detector monitors temperature by using a Standards and approvals* EN54, CPR, LPCB, VdS, BOSEC, SBSC,
single thermistor which provides a count output proportional CCMG, FG
to the external air temperature. Dimensions 100mm diameter x 42 mm height
Weight 105 g
• Ideal for environments that are dirty or smoky under
normal circumstances Material Housing: White flame retardant
polycarbonate
• Unaffected by wind or atmospheric pressure Terminals: Nickel plated stainless
steel

All information in this document is given in good faith but Apollo


36 Brookside Road, Havant Tel: +44 (0)23 9249 2412 Email: sales@apollo-fire.com Fire Detectors Ltd cannot be held responsible for any omissions or
Hampshire, PO9 1JR, UK. Fax: +44 (0)23 9249 2754 Web: www.apollo-fire.co.uk errors. The company reserves the right to change the specifications
of products at any time and without prior notice.

MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2018
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2611/2018/Issue 1
Page 2 of 2

Operation
XP95 Heat Detector dimensional drawing
The XP95 Heat Detector has a common profile with the XP95
optical smoke detectors but has a low air flow resistance
case made of white polycarbonate.
The device monitors heat using a single thermistor network
which provides a voltage output proportional to the external
air temperature.

Electrical description
The Heat Detector is designed to be connected to a two wire
loop circuit carrying both data and a 17 V to 28 V dc supply.
The detector is connected to the incoming and outgoing
supply via terminals L1 and L2 in the mounting base. A
remote LED indicator requiring not more than 4 mA at 5V
may be connected between the +R and -R terminals. An
earth connection terminal is also provided. The detector
is calibrated to give an analogue value of 25±5 counts at
5OC. This value increases with rising temperature. A count
of 55 corresponds to the EN 54 alarm sensitivity level.
When the detector is energized the ASIC regulates the flow
of power and controls the data processing. The thermistor
provides an output over normal operating ranges that is
proportional to the external air temperature. The voltage
output is processed in the analogue to digital converter and
stored by the communications ASIC. It is transmitted to the
control equipment when the device is interrogated. When a
count of 55 is exceeded the alarm flag is initiated and the
device address is added to the data stream every 32 polling
cycles from its last polling for the duration of the alarm
level condition, except when an alarming device is being
interrogated. This can provide a location identified alarm
from any device on the loop in approximately two seconds.

Environmental characteristics
The XP95 Heat Detector range is unaffected by wind or XP95 Heat Detector sectional diagram
atmospheric pressure. Standard detectors operate over the
temperature range -20°C to +70°C.
Address Buttons Thermistor Bead Case Moulding
EMC Directive 2014/30/EU
The XP95 Heat Detector complies with the essential
requirements of the EMC Directive 2014/30/EU, provided that
it is used as described in this datasheet.
A copy of the Declaration of Conformity is available from Apollo
upon request.
Conformity of the XP95 Heat Detector with the EMC Directive, PCB Lid Moulding
does not confer compliance with the directive on any apparatus
or systems connected to it. LED LED

Construction Products Regulation 305/2011/EU Heat Shrink Sleeving


The XP95 Heat Detector complies with the essential
requirements of the Construction Products Regulation
305/2011/EU.
A copy of the Declaration of Performance is available from
Apollo upon request.
SLV-24 PHOTOELECTRIC SMOKE DETECTOR

APPLICATIONS
The Hochiki SLV-24 can be used in al areas where Photoelec-
tric Smoke Detectors are required. The Patented smoke
chamber makes the SLV-24 well suited for fires ranging from
smoldering to fast-flame fires.
NS-4 Series, NS-6 Series, HSC-4R or HSC-xxxR Style bases
may be used with the SLV-24. Current interchangeable/
compatible devices are the SIJ-24 ionization detector, the
Shown without base
SLR-24H photoelectric detector with heat sensor, and the
STANDARD FEATURES DCD-135/190 heat detectors.

 Low profile - only 2.0” high (with base) All NS conventional devices are mechanically compatible with
Hochiki America HSB, HSC, and YBA type bases which may
 2 or 4 wire base compatibility (relay base available) have been used in previous installations. Please check indi-
vidual panel listings for compatible bases.
 Highly stable operation, RF/Transient protection
 Two built-in power/alarm LEDs
OPERATION
 Non-directional smoke chamber
The SLV-24 photoelectric smoke detector utilizes two bicol-
 Vandal resistant security locking feature ored LEDs for indication of status. In a normal standby condi-
tion the LEDs flash GREEN every 3 seconds. When the de-
 Removable smoke labyrinth for cleaning or replacement tector senses smoke, and goes into alarm the status LEDs
with latch on RED.
 Backward compatible with Hochiki SLK/SLR-24 and SIH
detectors The detector utilizes an infrared LED light source and silicon
photo diode receiving element in smoke chamber. In a normal
 Highly resistant to nuisance alarms caused by steam standby condition, the receiving element receives no light
 Automatic Sensitivity window verification function meets from the pulsing LED light source. In the event of a fire,
outlined requirements in NFPA 72, Chapters 2 & 7 inspec- smoke enters the chamber and light is reflected from the
tions, testing and maintenance smoke particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference level, and
SPECIFICATIONS when two consecutive signals exceeding the reference level
are received within a specific period of time. The time delay
Light Source GaAIAs Infrared Light Emitting Diode circuit triggers the SCR switch to activate the alarm signal.
Rated Voltage 17.7 - 30 VDC The status LEDs light continuously during the alarm period
Working Voltage 15.0—33 VDC
Nominal Voltage 24 VDC
Maximum Voltage 42 VDC
Supervisory Current 45μA @ 24VDC
Surge Current 160μA @ 24VDC
Alarm Current 150mA @ 24VDC
Air Velocity range 0—300 fpm
Ambient Temperature 32°F to 100°F (0°C to 38°C)
Color and Case Material Bone PC/ABS Blend
Sensitivity Range 0.5—3.8%/ft
Refer to NS Conventional PRODUCT LISTINGS
Mounting
Detector Base Data Sheet
California State
Fire Marshal
7272-0410:0174
S1383 3033131
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com F0077 11/2016
SLV-24 PHOTOELECTRIC SMOKE DETECTOR
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install Hochiki's SLV-24 Photoelectric Smoke Detectors as indicated on the plans. The detector
head and twist lock base is UL Listed and it’s compatible with an UL Listed fire alarm control panel.
The base permits direct interchange with the Hochiki SLR-24H combination photoelectric smoke/heat detector, SIJ-24 ionization
type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-lock
base NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLV-24 may be used in
conjunction with, or as a replacement for, Hochiki detectors (SLK-24, SLK-24FH and the SIH-24) on most HSB and HSC base
applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the
LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating
the control panel reset switch. The sensitivity of the detector shall be capable of being measured. To facilitate installation, the
detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed in the detector to minimize
false alarm potential. Auxiliary SPDT relays shall be installed where indicated. The vandal-resistant, security locking feature shall
be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required.

TYPICAL WIRING DIAGRAMS