Make sure provision Nozzle

for pressure transmitter in


the future the sizing meet
Note 3 in the Dwg No.
L44-C-POR-A3-10-003.
1.5m, Class 1, Div 1

P-03 P-02 P-01


3m, Class 1, Div 2

Make sure each of discharge line


arranged the spool pipe provision for
Make sure the lenght of spool
the future flow meter require, the
pipe that provision for mounting
pipe spool length at least 500mm &
SDV in the future the spool pipe
meet Note2 in the Dwg No. Cement Pad
length required 400mm at least,
L44-C-POR-A3-10-003.
See Note 5 in the Dwg No.
L44-C-POR-A3-10-003.
Safety Zone area for WOrkover Rig Operation.

Cement Pad Roof

VFD-P03 VFD-P-02 VFD-P-01

General Notes:
Mud Pit
-Make sure that provided the nozzle for procress indicator meet Dwg No. L44-C-POR-A3-10-003.
-Electrical facilities installation Hazardous area classified meet or exceed API 500, NEC (NFPA-70) Edition 2002, article 500.