Академический Документы
Профессиональный Документы
Культура Документы
STAMP:
COMMON
220/66/11kV New Doha B Super Substation, 220/66/11kV Abu Hamur Super Substation
220/66/11kV Ain Khalid Super Substation, 220/66/11kV Lusail Development Super 3 Substation
CONTRACTOR NAME
2. DESIGN INPUT
1) Technical Specification, Volume 3, Section 3.3.6 ‘LV Service Equipment’
2) Technical Schedule, (PH10-1C-10-60-T003)
3) LVDC Single Line Diagram, (PH10-1C-51-60-5001, PH10-1C-52-60-5001,
PH10-1C-81-60-5001, PH10-1C-82-60-5001)
4) LVDC DB Schematic Diagram, (PH10-1C-51-60-5003, PH10-1C-52-60-5003,
PH10-1C-81-60-5003, PH10-1C-82-60-5003)
5) LVDC Battery Charger Schematic Drawing, (PH10-1C-10-60-2002)
3. ASSUMPTION
1) Power Factor of 0.85 considered
2) Ambient Air Temperature is considered as 50°C
4. DESIGN CRITERIA
1) Low Voltage DC Basic Technical Values
- Nominal System Voltage: 110V
2) Study of selectivity and setting of protection is valid on four mode of operation as follows;
- Float Mode for trickle charging the batteries under normal DC loading condition.
- Equalizing Mode for periodic topping up of battery capacity and to correct the irregularities
of cell voltage and specific gravity. Selection shall be both auto and manual.
- Boost Mode for manual charging of batteries following a deep discharge or prolonged
absence of AC supply. This mode shall permit charging of the batteries only by manual mode
with auto – manual isolation of DC loads connected to the charger.
- Manual Charging Mode for commissioning of batteries.
2 OF 41 PH10-1C-10-60-7001_R0
5. SELECTIVIY PRINCIPAL
CHARGER 1 CHARGER 2
T4S320_320A
BATTERY 1 BATTERY 2
SBLE1600AH X 2: AHS, AKS, LDS-3 155.9kVA
SBLE1500AH X 2: NDBS
1000A
~ 110V ~
850A
BAT. CHAR.
1000A
1000A
NH4 800A gG
800A
K1 400A K2 400A
400A
K3
DIODE
A FUSE
PANEL
NH2 400A gG
DIODES
400A
DCDB
Total full load current (374.53A)
Note*
B INCOMING
T5N400_400A
C COUPLER
T5N400_320A
D3 D2 D1 D4 D5
iC60L_32A iC60L_63A NS160DC iC60L_25A iC60L_10A
FEEDERS 160A
E
160A
3 OF 41 PH10-1C-10-60-7001_R0
Selectivity :
- Between A & B : a selectivity is not necessary because there is no differences on the system if it’s the first or
the second which is tripping.
- Between A & C : a selectivity is necessary because in the case of fault downstream a feeder, it should keep the
busbar supplied.
- Between A & D : a selectivity is necessary because in the case of fault downstream a feeder, it should keep the
busbar supplied.
- Between B & C : a selectivity is necessary because in the case of fault a bus zone, it should keep the other
busbar supplied.
- Between C & D : a selectivity is necessary because in the case of fault downstream a feeder, it should keep the
busbar supplied.
- Between C & E : a selectivity is necessary because in the case of fault downstream a feeder, it should keep the
busbar supplied.
- Between D1 & E : a selectivity is not necessary because there is no differences on the system if it’s the first or
the second which is tripping.
6. LIST OF FEEDERS
Protection Device
No. Feeder Description Type Setting
/ Trip Device
A FUSE 400A NH2 gG 400A Fuse
4 OF 41 PH10-1C-10-60-7001_R0
7. SELECTIVITY BETWEEN CHARGER FUSE & DCDB INCOMER
BREAKERS :
There is not necessity to guarantee selectivity between A & B, however resetting of MCCB is much
easier, faster, cheaper and safe than replacement of fuses. Therefore it is better to guarantee selectivity
between the two.
Overload Zone
Please note that the maximum full load is 41,198 W.
Therefore, max. full load current = 41,198/110 = 374.53A (see below Table-1 on page 6)
The overload pickup of the incomer is 400A (400A x 1.0 setting). From the above curve, please note
the incomer breaker will trip first for the overload current starting from 400A up to 1023A. Therefore,
the breaker and fuse are well coordinated for the overload condition.
5 OF 41 PH10-1C-10-60-7001_R0
Short-circuit Zone
The through fault current of the battery is 21.82kA. This fault current is about 12.25kA in the LVDC
board after cable length between the battery and LVDC board. (Refer to attached short-circuit
calculation at DCDB on page 35-37) The overlapping between NH4-800A fuse and DC incomer
breaker occurs at over 20kA which is more than maximum fault current. Therefore 800A fuse is not
blown by the DCDB short-circuit fault, NH2-400A fuse or incomer breaker will trip first to block fault
current.
[Table-1]
6 OF 41 PH10-1C-10-60-7001_R0
8. SELECTIVITY BETWEEN CHARGER FUSE & DCDB COUPLER
BREAKER :
Overload Zone
Please note that the maximum one DC bus load is 34,107 W.
Therefore, max. full load current = 32,653/110 = 296.85A (see above Table 1on page 6)
The overload pickup of the coupler is 320A. From the above curve, please note the coupler breaker
will trip first for the overload current starting from 320A up to 1357A. Therefore, the breaker and fuse
are well coordinated for the overload condition.
Short-circuit Zone
The through fault current of the battery is 21.82kA. This fault current is about 12.25kA in the LVDC
board after cable length between the battery and LVDC board. (Refer to attached short-circuit
7 OF 41 PH10-1C-10-60-7001_R0
calculation at DCDB on page 35-37) The overlapping between NH4-800A fuse and DC incomer
breaker occurs at over 20kA which is more than maximum fault current. Therefore 800A fuse is not
blown by the DCDB short-circuit fault, NH2-400A fuse or coupler breaker will trip first to block fault
current..
8 OF 41 PH10-1C-10-60-7001_R0
9. SELECTIVITY BETWEEN CHARGER FUSE & DCDB OUTGOING
FEEDERS :
Overload Zone
In the overload zone, the load side breaker must trip more rapidly than the supply-side fuse because
there is no overlapping between two time-current curves.
Short-circuit Zone
In the short-circuit area, a selectivity is guaranteed by fuse E (160A). 160A fuse must trip rapidly more
than supply side 400A fuse. Therefore, selectivity is in order.
9 OF 41 PH10-1C-10-60-7001_R0
10. SELECTIVITY BETWEEN DCDB INCOMER BREAKERS & DCDB
COUPLER BREAKER :
Discrimination Between : B-C
Supply side: MCCB – ABB_T5N400 400A (Thermal: 1.0, Magnetic: 10x In) (Icu=36kA)
Load side: MCCB – ABB_T5N400 320A (Thermal: 1.0, Magnetic: 10x In) (Icu=36kA)
Overload Zone
Please note that the maximum one DC bus load is 34,107 W.
Therefore, max. full load current = 32,653/110 = 296.85A (see above Table 1on page 6)
The overload pickup of the coupler is 320A. From the above curve, please note the coupler breaker
will trip first for the overload current starting from 320A up to 400A, above which the incomer breaker
shall pick up in order to clear the fault. Therefore, the breakers are well coordinated for the overload
condition.
Short-circuit Zone
Short circuit discrimination is not possible between incomer and coupler breaker. These are only
guaranteed faults which occur up to 3.2kA by current discrimination.
10 OF 41 PH10-1C-10-60-7001_R0
11. SELECTIVITY BETWEEN DCDB COUPLER BREAKER & DCDB
OUTGOING FEEDERS :
Supply side: ABB_T5N400 320A (Thermal: 1.0, Magnetic: 10x In) (Icu=36kA)
Load side: Schneider_NS160 DC 160A (Thermal: 1.0, Magnetic: 8xIn) (Icu=100kA)
Overload Zone
Please note that the total UPS load is 18.6kVA. ie 18600 VA x 0.85 pf = 15810 W
Therefore, the max. full load current = 15810/110 = 143.73 A
The overload pickup of the UPS feeder is 160A. From the above curve, please note the UPS feeder
breaker will trip for the overload current starting from 160A up to 336.3A, above which the coupler
breaker shall pick up in order to clear the fault. Therefore, the breakers are well coordinated for the
overload condition.
11 OF 41 PH10-1C-10-60-7001_R0
Short-circuit Zone
In the short-circuit area, load side breaker will trip faster than coupler breaker however the gap of the
time is small to secure selectivity. So that a selectivity is guaranteed by load side 160A fuse. See the
below curve;
Coupler breaker trip time is 15ms in short-circuit condition, but 160A fuse is faster than 10ms.
Therefore 160A load side fuse must trip rapidly more than coupler breaker fuse.
12 OF 41 PH10-1C-10-60-7001_R0
2) Circuit Breaker 63A D2 (iC60L-C curve)
Supply side: ABB_T5N400 320A (Thermal: 1.0, Magnetic: 10x In) (Icu=36kA)
Load side: Schneider_iC60L In63 C curve (Thermal: Fixed, Magnetic: Fixed) (Icu=25kA)
Overload Zone
In the overload zone, the load side breaker must trip more rapidly than the supply-side breaker because
there is no overlapping between two time-current curves.
Short-circuit Zone
In the short-circuit zone, the load side breaker must trip more rapidly than the supply-side breaker
because there is no overlapping between two time-current curves.
13 OF 41 PH10-1C-10-60-7001_R0
3) Circuit Breaker 32A D3 ((iC60L-C curve)
Overload Zone
In the overload zone, the load side breaker must trip more rapidly than the supply-side breaker because
there is no overlapping between two time-current curves.
Short-circuit Zone
In the short-circuit zone, the load side breaker must trip more rapidly than the supply-side breaker
because there is no overlapping between two time-current curves.
14 OF 41 PH10-1C-10-60-7001_R0
4) Circuit Breaker 25A D4 ((iC60L-C curve)
Overload Zone
In the overload zone, the load side breaker must trip more rapidly than the supply-side breaker because
there is no overlapping between two time-current curves.
Short-circuit Zone
In the short-circuit zone, the load side breaker must trip more rapidly than the supply-side breaker
because there is no overlapping between two time-current curves.
15 OF 41 PH10-1C-10-60-7001_R0
5) Circuit Breaker 10A D5 ((iC60L-C curve)
Overload Zone
In the overload zone, the load side breaker must trip more rapidly than the supply-side breaker because
there is no overlapping between two time-current curves.
Short-circuit Zone
In the short-circuit zone, the load side breaker must trip more rapidly than the supply-side breaker
because there is no overlapping between two time-current curves.
16 OF 41 PH10-1C-10-60-7001_R0
ANNEXURE
17 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
Low Voltage Selectivity Theoretical Outline
18 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
19 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
20 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
21 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
22 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
23 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
24 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
25 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
26 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
27 OF 41 PH10-1C-10-60-7001_R0
ANNEX 1. LV Selectivity Theoretical Outline
28 OF 41 PH10-1C-10-60-7001_R0
ANNEX 2. Protection Discrimination
29 OF 41 PH10-1C-10-60-7001_R0
ANNEX 2. Protection Discrimination
Protection Descrimination
30 OF 41 PH10-1C-10-60-7001_R0
ANNEX 3. Fuse Time-Current Curves
Time-Current Trip Curve
31 OF 41 PH10-1C-10-60-7001_R0
ANNEX 3. ABB_T5N Time-Current Curves
32 OF 41 PH10-1C-10-60-7001_R0
ANNEX 3. Schneider_NS100DC to NS250DC Time-Current Curves
33 OF 41 PH10-1C-10-60-7001_R0
ANNEX 3. Schneider_iC60L Time-Current Curves
34 OF 41 PH10-1C-10-60-7001_R0
ANNEX 4. Short-Circuit Analysis
SHORT-CIRCUIT ANALYSIS
35 OF 41 PH10-1C-10-60-7001_R0
ANNEX 4. Short-Circuit Analysis
36 OF 41 PH10-1C-10-60-7001_R0
ANNEX 4. Short-Circuit Analysis
37 OF 41 PH10-1C-10-60-7001_R0