CIVIL / STRUCTURAL CONSTRUCTION NOTES

I. GENERAL NOTES III. NOTES ON REINFORCEMENT VII. NOTES ON BEAMS AND GIRDERS
1. IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN AND 1. UNLESS OTHERWISE INDICATED, THE YIELD STRENGTH OF REINFORCING STEEL BARS (RSB) SHALL BE: 1. UNLESS OTHERWISE NOTED IN PLANS, CAMBER ALL BEAMS AND GIRDER AT LEAST 6 mm
DISTANCES OF SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. A. 12-mmØ AND BELOW fy = 276 MPa (40,000 psi) FOR EVERY 4.50 m OF SPAN , EXCEPT CANTILEVERS FOR WHICH THE CAMBER SHALL BE
B. 16-mmØ AND ABOVE fy = 420 MPa (60,000 psi) AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER BUT IN NO CASE LESS THAN
2. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS 20 mm FOR EVERY 3.0 m OF FREE SPAN.
IN FLOOR SLABS, OPENINGS IN THE WALLS AND SLABS, INTERIOR PARTITIONS, LOCATION 2. ALL RSB SIZE 10-mm Ø OR BIGGER SHALL BE DEFORMED IN ACCORDANCE WITH
OF DRAINS, ETC. 2. IF THE BEAM RSB END IN A WALL, THE CLEAR DISTANCE FROM THE RSB TO
ASTM A 615. RSB SMALLER THAN 10-mm Ø MAY BE PLAIN.
THE FARTHER FACE OF THE WALL SHALL NOT BE LESS THAN 25 mm. EMBEDMENT LENGTH SHALL
3. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS, AND ELEVATIONS BETWEEN BE AS SHOWN IN A TABLE 'A' FOR TENSION BARS AND TABLE 'B' FOR COMPRESSION BARS
3. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL BE LAPPED OR EXTENDED
THE STRUCTURAL PLANS AND ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOTIFY UNLESS SPECIFIED IN PLANS. TOP BAR SHALL NOT BE SPLICED WITHIN THE COLUMN OR
BOTH THE STRUCTURAL ENGINEER AND THE ARCHITECT. IN ACCORDANCE WITH TABLE A & TABLE B (TABLE OF LAP SPLICE & ANCHORAGE LENGTH)
WITHIN A DISTANCE TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN. AT LEAST
UNLESS OTHERWISE INDICATED, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. TWO STIRRUPS SHALL BE PROVIDED AT ALL SPLICES.
4. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI 318-11 BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE, AND STRUCTURAL STEEL 3. IF THERE ARE TWO OR MORE LAYERS OF RSB USE 25-mm Ø BAR SEPARATORS
ACCORDING WITH AISC SPECIFICATION (9th EDITION), IN SO FAR AS THEY DO NOT CONFLICT
WITH THE LOCAL BUILDING CODE REQUIREMENTS. IV. NOTES ON STRUCTURAL STEEL SPACED AT 1.0 m O.C. IN NO CASE SHALL THERE BE LESS THAN TWO (2) SEPARATORS
BETWEEN TWO LAYERS OF BARS.
5. ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC TO AMERICAN INSTITUTE OF STEEL 1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE SHALL
CONSTRUCTION, AND ASTM TO AMERICAN SOCIETY FOR TESTING MATERIALS. 4. MINIMUM CONCRETE CONCRETE COVER FOR RSB FOR BEAMS & GIRDERS SHALL BE 40 mm.
COMPLY WITH ALL THE PERTINENT PROVISION OF AISC SPECIFICATION FOR THE DESIGN,
6. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDING, 9TH EDITION.
INDICATED OR NOTED MODIFIED TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. 2. ALL STRUCTURAL STEEL SHAPES SHALL BE ASTM A36 STRUCTURAL STEEL UNLESS 5. WHEN A BEAM CROSSES A GIRDER, REST BEAM ON TOP OF GIRDER RSB, BEAM RSB
OTHERWISE INDICATED. SHALL BE SYMMETRICAL ABOUT CENTER LINE WHENEVER POSSIBLE.
7. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS CONNECTED.
MISCELLANEOUS IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGINEER'S 6. GENERALLY, NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING STRESSES
APPROVAL PRIOR TO FABRICATION. 4. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A325 BOLTS. OCCUR. SPLICES WHERE SO PERMITTED SHALL BE INDICATED IN THE "TABLE A" AND "TABLE B".
5. USE E70XXX ELECTRODES FOR ALL WELDED CONNECTIONS. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125 % OF THE SPECIFIED YIELD
8. THE CONTRACTOR SHALL TAKE NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, STRENGTH OF THE RSB. NOT MORE THAN 50% OF THE RSB AT ANY ONE SECTION IS
EQUIPMENTS AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, ALLOWED TO BE SPLICED THEREIN.
ELECTRICAL, AND MECHANICAL DRAWINGS.
V. NOTES ON FOOTINGS AND WALLS BURIED IN SOIL 7. NO LAPS IN TOP AND BOTTOM TO OCCUR WITHIN A DISTANCE 2D FROM FACE OF SUPPORT.
9. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS, AND STRUCTURAL 1. ASSUMED SOIL BEARING CAPACITY: 150 kPa (3123 PSF) GIRDER. JOINT IN GIRDERS SHALL BE OFFSET A MINIMUM DISTANCE OF TWO TIMES THE WIDTH OF
STEEL MUST BE NOTED AND APPROVED BY THE STRUCTURAL ENGINEER. LAP SPLICES ARE ALLOWED ONLY WITHIN L/2 FOR TOP BARS, AND L/5 FOR BOTTOM BARS.
FOR THIS PROJECT. CONTRACTOR SHALL REPORT
TO THE ENGINEER, IN WRITING, SOIL CONDITIONS, UNCOVERED AND CONFIRM 8. CONSTRUCTION JOINT SHALL BE LOCATED WITHIN THE MIDDLE THIRD OF SPAN OF THE BEAM /
(IF APPLICABLE) ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE.
II. NOTES ON CONCRETE MIXES & PLACING 2. MAINTAIN 75-mm MINIMUM CONCRETE COVER FOR RSB FOR WALLS AND FOOTINGS INTERSECTING BEAMS.
1. ALL CONCRETE SHALL DEVELOP A MININUM COMPRESSIVE STRENGTH AT THE END OF TWENTY 9. WHERE JOINT IS AT POINT OF STRESS, PROVIDE SHEAR RODS WITH ENGINEER'S APPROVAL.
EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE AGGREGATE AND SLUMPS AS FOLLOWS: INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL. PROVIDE 50-mm GRAVEL BEDDING
UNDER COLUMN FOOTINGS, AND 100-mm GRAVEL BEDDING UNDER MAT FOOTINGS.
LOCATION 28 DAYS STRENGTH MAX. SIZE OF MAX. SLUMP
AGGREGATE VIII. NOTES ON STIRRUPS
SLABS, WALLS 3000 PSI (21 MPa) 20 mm 150 mm VI. NOTES ON CONCRETE SLABS 1. ALL REINFORCEMENT SHALL BE BENT COLD UNLESS OTHERWISE PERMITTED BY THE
FOOTINGS, COLUMNS, BEAMS 3000 PSI (21 MPa) 20 mm 150 mm
1. MAINTAIN 20-mm MINIMUM CONCRETE COVER FOR RSB FOR SLAB STRUCTURAL ENGINEER.
2. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION. RE-HAND- INDICATED IN PLANS. NO SLAB ON-GRADE SHALL REST ON FILL.
WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM 2. REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FILLED BENT, EXCEPT
HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT 2. CONSTRUCTION JOINTS SHALL BE LOCATED WITHIN THE MIDDLE THIRD OF THE SPAN OF THE SLAB. AS SHOWN IN THE DESIGN DRAWINGS OR PERMITTED BY THE STRUCTURAL ENGINEER.
EXCEED SIX (6) METERS IN AGGREGATE LENGTH. 3. TIES & CLOSE STIRRUPS MUST BE BENT AT 135°.
3. WHERE A CONSTRUCTION JOINT IS TO MADE, THE SURFACE OF CONCRETE SHALL BE CLEANED
3. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS. AND ALL LAITANCE AND STANDING WATER REMOVED.
UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS, AND ONLY FOR UNUSUAL CONDITIONS
WHERE VIBRATIONS IS EXTREMELY DIFFICULT TO ACCOMPLISH.
IX. NOTES ON COLUMNS
4. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED 1. PROVIDE EXTRA SETS OF TIES AT 100 mm O.C. FOR TIED COLUMN REINFORCEMENT.
AND SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. ABOVE AND BELOW THE BEAM - COLUMN CONNECTION FOR A DISTANCE FROM THE FACE
OF THE CONNECTION SHALL BE EQUAL TO THE GREATER OF THE:
7. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) CONSECUTIVE DAYS (a) OVERALL THICKNESS OF COLUMN (b) 1/6 THE CLEAR HEIGHT OF COLUMN (c) 450 mm.
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP FOG SPRAYING, CURING
COMPOUNDS, OR OTHER APPROVED METHODS. 2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST
MONOLITHICALLY WITH THE CORE WITH THE MINIMUM THICKNESS OF 40 mm.
8. STRIPPING OF FORMS AND SHORES:
3. WHERE COLUMNS CHANGE IN SIZE , VERTICAL REINFORCEMENTS SHALL BE OFFSET
FOUNDATION 24 HRS. AT A SLOPE OF NOT MORE THAN 1:6 AND EXTRA 10-mmØ TIES AT 100 mm SHALL
SUSPENDED SLAB EXCEPT WHEN ADDITIONAL LOADS ARE IMPOSED 8 DAYS BE PROVIDED THROUGHOUT THE OFFSET REGION.
4. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR COLUMN REINFORCEMENTS
SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND THE SPLICE
BEAMS 14 DAYS LENGTH SHALL NOT BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED
COLUMNS 21 DAYS MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS
ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL DISTANCES
9. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600 mm.
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST FOUR (4) DAYS PRIOR TO THE
POURING FOR APPROVAL.

10. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS SHORINGS UNTIL THE
X. NOTES ON CONCRETE HOLLOW BLOCK WALLS
CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. 1. UNLESS OTHERWISE INDICATED IN PLANS, ALL CONCRETE HOLLOW BLOCKS (CHB)
SITE LOCATION FROM SHALL BE REINFORCED AS SHOWN IN THE SCHEDULE OF CHB REINFORCEMENT.
2 NEAREST FAULTLINE 2. UNLESS OTHERWISE INDICATED IN PLANS, PROVIDE 150-mm x 300-mm STIFFENER COLUMN
REINFORCED WITH 4-12 mm Ø WITH 6-mm Ø TIES AT 150 mm O.C. WHERE CHB TERMINATES
S-1 AND AT EVERY 3.0 m LENGTH OF CHB WALLS.

PROJECT: OWNER: SHEET CONTENTS: SHEET NO.:


RA 545 SEC. 25-4

DRAWING AND SPECIFICATIONS DULY SIGNED STAMPED OR SEALED, AS AN 1. CIVIL / STRUCTURAL CONSTRUCTION NOTES
ALEXANDER VINCENT B. POLICARPIO
CIVIL ENGINEER
INSTRUMENT OF SERVICE ARE THE INTELLECTUAL PROPERTIES AND
DOCUMENTS OF THE ARCHITECT, WHETHER THE OBJECT FOR WHICH THE
PROPOSED TWO STOREY MS. BECKY BUENAVENTURA 2. SITE LOCATION FROM NEAREST FAULTLINE

NO.12 UGNAYAN ROAD PHASE 2 PACITA COMPLEX 1 SAN PEDRO LAGUNA PRC REG. NO. : 0088536 VALIDITY : 07 / 27 / 2020
ARE MADE IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL FOR ANY PERSON
WITHOUT WRITTEN CONSENT OF THE ARCHITECT OR AUTHOR OF THE SAID
DOCUMENTS TO DUPLICATE OR MAKE COPIES OF SAID DOCUMENTS FOR USE
RESIDENTIAL HOUSE
PTR NO. : 7012447 DATE : 01 / 18 / 2018 IN THE REPETITION OF AND OTHER PROJECTS OR BUILDINGS, WHETHER RES. CERT. NO.: DATE ISSUED: DRAWN BY: AVBP DATE: 08 / 22 / 18
EXECUTED PARTLY OR IN WHOLE.
PLACE ISSUED : MANILA TIN NO. : 211 636 081 LOCATION : BLK. 6 LOT 6 SEVILLE ST.BF HOMES PARANAQUE TIN NO. : PLACE ISSUED: SCALE: AS SHOWN REMARKS: REVISION NO.: