Вы находитесь на странице: 1из 3

INSULATING MATS FOR ELECTRICAL PURPOSES IS:15652-2006 (Latest)

Insulating Mats for Electrical Purposes


IS:15652-2006 (Latest)

Insulating Mats for Electrical Purposes are used as Floor covering for the protection & prevention of workers from Electric-

Stock while working in Electricity generation, Transmission & its distribution or any other related work on AC and DC

installations. Synthetic Insulation Mats or Poly Electro Safe Mats are available both for H.T & LT Voltage Panels with the

system voltages up to 66 kV ac and 240 V dc-

Insulating Mats are laid down on floors in & around following area for the safety of worker working on it from Electric Shock.

Electricity Control Panels

High Voltage & Low Voltage Panels

Power Transformers

Energy Sub Stations,

Power Control Rooms,

Labs involved in Electric related Operations.

Classification:
Electrical Insulation Mats as per BIS Standard 15652-06 are divided in to three classes depending upon Voltage Ratings.
The three classes varies in terms of Thickness of Mats, Voltage Grade, Proof Voltage & their break down voltage.

VOLTAGE RATEINGS

Class Thickness Grade KV Proof voltage B/Down voltage

A 2.0 mm 3.3 10KV/3 minutes 30 KV

B 2.5 mm 11 22KV/3 minutes 45 KV

C 3.0 mm 33 36KV/3 minutes 65 KV

Construction: Made from Highly Electrical resistant Elastomers, free from any insertions. "Elastomer" (a generic term that

includes rubbers, Latex and elastomeric compounds that may be natural synthetic or a mixture or a combination of both).
High Voltage Resistant Electrical Insulation Matting is made up of 100% virgin compound.
Colour: Any colour without metallic derivatives.

Surface:Anti-skid (rough on top & smooth at bottom to avoid slippery effects).

Size: Can be in standard size- 1mtr x 2mtr or in Long rolls form.

Working Temperature Range: -10°C to +60°C.

Marking: Mats should be marked with Class, Lot No. and Manufacturer Identity.

Packing: : Should be packed in Gunny /Jute /Hessian /HDPE bags to avoid any mechanical damage to the mats.

Silent Features of Insulating Mats:-

 High Di-Electric Strength up to 65KV.

 Complies to IS:15652-2006 (latest).

 Insulation Resistance Up to 1494000 Mega Ohm.

 Superseding the Rubber mats for Electrical Purposes IS:5424.

 Resistant to Fire.
 Hold Excellent Physical Properties so that can withstands movement of instrument involved in Electrical Equipment &

Foot Traffic. Resistant to wide range of Acids, Alkalis & Oils.

 Withstands both AC & DC electrical installations.

 Can be Pasted/Installed on Floor if required, not mandatory. Water & moisture proof.
 Exhibit good Elongation & Tensile Strength Properties.

TECHNICAL SPECIFICATION IS:15652-2006

S
Characteristics Standard Values
No.

1 Thickness 2.0mm 2.5mm 3mm

Tensile Strength(N/mm²)
2 15 15 15
(N/mm²)

3 Elongation (%) 250 250 250

Insulation Resistance with


4 1,000,000MO 1,000,000MO 1,000,000MO
water at 500V

5 Leakage Current at 11KV 10mA 10mA 10mA

6 Dielectric Strength 30KV 45KV 65KV

7 Flame Retardance 5.0sec 5.0sec 5.0sec


Effect to Acid, Alkali,

Transformer Oil % Change from % Change from % Change from


8
Acid: Tensile Str.(N/mm²) Original Value Original Value Original Value

Elog(%)

Alkali: Tensile Str.(N/mm²) Tensile Strength 20% Tensile Strength 20% Tensile Strength 20%

Elog(%) Elongation 20% Elongation 20% Elongation 20%

Diesel: Tensile
9
Str.(N/mm²)

Elog(%) T.Oil: Tensile

Str.(N/mm²) Elong.)

Ageing Properties at70 ±1


% Change from % Change from % Change from
(°C) for 168 hrs.
10 Original Value Original Value Original Value
Tensile Strength
T.S 25% T.S 25% T.S 25%
(Elongation %)

-:STOCKIST:-

SPOT TRADING CO
3443, GALI BAJRANG BALI, CHAWRI BAZAR, DELHI-110006

PH: 011-23255999, 30114769, 65172292 * T.FAX: 011-23266999 * MOB: 9311123460

E-MAIL: spottradingco@gmail.com, Web: www.spottrading.in

Вам также может понравиться