Вы находитесь на странице: 1из 11

TM

NICHIAS OMEGA FLOOR


TM
Panel

Lock plate

Lock base

NICHIAS OMEGA FLOOR is a safe and secure


TM
Large protrusion
Small protrusion

raised access floor system that provides excellent


Pedestal
Cushioning material:
head

Pedestal
Two-tiered protrusion rubber gasket

performance and has a proven track record of


Stopper screw

installation in many buildings. Base plate

1. Proven track record of installation 2 .High-strength panel using 3 .Solid walking feel 4 .Raised access floor system with
in many buildings reinforcing bars and laths without rattling excellent cost performance
Since its release in 1990, NICHIAS OMEGA FLOORTM has A unique reinforcing bar structure and laths are used in The panel lock system incorporates a two-tiered Offers various excellent properties at low cost,
been installed in many buildings and built a solid track record. concrete to prevent crack, thus realizing a tough and protrusion rubber gasket which absorbs rattles that creating a comfortable office environment at
Renowned for its ease of installation, excellent performance high-strength concrete panel while providing solid walking have plagued conventional raised access floor reasonable cost.
and economy, the raised access floor system boosts a proven feel that is comparable to walking on a concrete slab systems and reduces squeaking noise and hollow
record of installations on many sites including buildings in floor. sound. This structure also ensures a natural,
large-scale re-development areas. comfortable walking feel and reduces foot fatigue
for office workers.

*“TOMBO” is a registered trademark or trademark of NICHIAS Corporation.


*“OMEGA FLOOR” and “NICHIAS SIGMA FLOOR” are trademarks of NICHIAS Corporation.

NICHIAS OMEGA FLOOR TM 1


Product Catalog Basic Items

Panels

The base material is reinforced with steel bars and laths. Type "0 (zero)" and
type "PKC" with cutouts for wiring can be freely combined.

■Standard panel Type 0 (zero) ■Standard panel Type PKC

Standard grommet cover lid


for type PKC
C70 C72 R35
12 (mm)

7 (mm) 7 (mm) Examples of wiring outlet


Panel specifications
Model No. Type Design concentrated load (N) Size (mm) Thickness (mm) System weight (kg/m2) Note 1 Panel weight (kg/panel)

0 (zero) (500 mm finish size module) (Side center)


M300A 3,000 48 11.5
497.5×497.5 29
PKC

0 (zero) (500 mm finish size module) (Side center)


HG Note 2 5,000 52 12.5
497.5×497.5 31.5
PKC
Note 1: For pedestal height of 100 mm. Not including floor coverings.
Note 2: OMEGA FLOORTM HG is a made-to-order product.

Pedestals

A full lineup of finish floor height from 60 to 1,000 mm


Finish floor height from 300mm to1,000mm are mede to order. Consult NICHIAS for details.

【Field pedestal】 Pipe stud type 【Perimeter pedestal】 Pipe stud type
D-50 D-80 DL-100 D-200 150-square E-50 E-60 EL100 E-200 100-square
Flat base Flat base Flat base Flat base Bowl-shaped Flat base Flat base Flat base Flat base Floor type
plate type plate type plate type plate type base plate type plate type plate type plate type plate type

【Types of pedestals】 Pedestal type


Field pedestal Perimeter pedestal
Finish height
60mm D-50 flat base type E-50 flat base type

80mm D-80 flat base type E-80 flat base type

100mm DL-100 flat base type EL-100 flat base type

125mm DL-125 flat base type EL-120 flat base type

150mm DL-150 flat base type E-150 flat base type

200mm D-200 flat base type E-200 flat base type

150-square bowl-shaped 100-square floor


300mm
base plate type type
Lock type field pedestal Perimeter pedestal

2 NICHIAS OMEGA FLOOR TM


Optional Items Product Catalog

Optional panel Installation of outlet box

■Optional panel Type PK


If an outlet box is installed:
Install the outlet box on a custom panel (option).

Custom panels are made of


calcium silicate boards
(NICHIAS phoduct: NICHIAS
SIGMA FLOOR™).
* I nstall a special attachment on a
pedestal. (See page 7.)
* R einforcing pedestals may be
Cover lid for 8.8 (mm) required depending on the panel
optional panel shape.
* The photo shows an optional panel
example.
FK-44

Up outlet

Manufacturer : TERADA ELECTRIC WORKS Co.,Ltd. (NAS70000)

Pedestal types Grill


Pedestals are made to order. Consult NICHIAS for details. Grills are mede to order. Consult NICHIAS for details.

There are a variety of grills that have various materials, sizes


【Security system】 【Whisker prevention】 and open rates. Appropriate grills can be selected according
to office applications.
Panels are locked using To prevent the formation of
special screws. This system zinc whiskers (Note 1), the
enhances security since the p e d e s t a l h a s s t a n d a rd
panels cannot be opened nickel plating.
or closed with an ordinary Note 1: Zinc whiskers are hair-like
screwdriver or Allen wrench. conductive crystals that are formed
on zinc-plated electrical parts. These (GP-40) (GP-41)
whiskers adversely affect computers
and electronic devices.

(GP-64)

Product Size Open rate Material Remarks

GP-40 500×500mm 75% Steel

GP-41 500×500mm 0 to 62% Steel With damper

GP-64 500×250mm 39% Steel Bolt pedestal

NICHIAS OMEGA FLOOR TM 3


Performance test Performance Items

Concentrated load test

A floor panel is supported with four supports for static load


Center of floor panel
パネル中央 testing. A load is applied using a load tester and a loader of
50 mm diameter.
Static load test
Model Loading point Maximum load Deformation volume
2 mm or less
M300A 9,000 or more
Center of at 3000 N
panel 2 mm or less
HG 10,000 or more
at 5000 N
In-house standard
Displacement meter
Load Each of four corners of a floor panel is supported with a
pedestal, and load is applied using a load tester and a loader
of 50 mm diameter.
Static load test (Test method: JIS A 1450)
Spherical seat
Specified Loading Deformation volume Residual
Model load point accompanied with specific load deformation volume

M300A 3000 N
Weakest
5 mm or less 3 mm or less
points
HG 5000 N
Indenter

In-house standard
(Source: JIS A 1450) *The weakest points are the point where the largest deformation is
caused when the specific load is applied and the point where the largest
residual deformation is caused. (The two points may coincide.)

Rolling load test


A urethane-covered caster (diameter of 150 mm, width of 40
mm, hardness of 85 HS or higher) with a specified load is
rolled.
Establishment of zero point Loading Measurement of deformation
(before loading) (after loading)
Weight

Surface finishing Load Rolling load test (Test method: JIS A 1450)
material Wheel
Specified Loading Residual
Model Visual damage
load point deformation volume

M300A
Weakest
1000 N None 3 mm or less
point
HG
(Source: JIS A 1450)

In-house standard
*The weakest point is the point where the largest deformation is caused
by the rolling load.

Impact test

A sand bag of 30 kg (with a bottom diameter of 220 mm) is


Establishment of zero point Impacting Measurement of deformation dropped from a height of 250 mm.
(before impacting) (after impacting)
Sandbag
Weight
Surface finishing
material  Impact test (Test method: JIS A 1450)
Impactor Impact Visual Residual
Model Impactor
height point damage deflection

M300A
Sandbag with a Weakest 3 mm or
250mm None
mass of 30kg point less
(Source: JIS A 1450) HG

In-house standard
*The weakest point is the point with the largest deformation caused by
impact.
JIS: Japanese Industrial Standards

4 NICHIAS OMEGA FLOOR TM


Performance Items Performance test

Leakage resistance test


Measuring instrument
Resistance between the panel top and ground is measured.
Electrode ( M e a s u re m e n t c o n d i t i o n s : a p p l i e d vo l ta g e : 5 0 0 V;
temperature: 20±5°C; humidity: 30±10% RH)
Cushioning plate

Adhesive Leakage resistance test (Test method: JIS A 1450)

Model Floor panel surface Leakage resistance (Ω)

M300A
Bare finish
1×10 6 or more
(without covering)
Copper plate Earth HG

Concrete flat plate, etc. Rubber insulating plate In-house standard

(Source: JIS A 1450)

Electrostatic propensity test Combustion test

The maximum charge potential between the panel top and Fuel is burnt below a panel, and the time is measured from
ground, and the time for reduction by half are measured when the fuel is burnt out until when flames on the panel
using a measuring instrument specified in JIS A 1455. The U disappear.
Surface finishing material
value is determined using the formula specified in JIS A 1455.
Space between test specimen
and fuel canister Fuel canister
Measuring instrument
Cork board
Surface finishing material
30±1

Adhesive

Supporting
table
Copper
plate
Earth Base
Concrete flat plate, etc. Rubber insulating plate

(Source: JIS A 1450) (Source: JIS A 1450)

Electrostatic propensity test (Test method: JIS A 1450) Combustion test (Test method: JIS A 1450)
Model Floor panel surface U value Model Afterflame time

M300A Bare finish M300A


0.6 or more 0 seconds
HG (without covering) HG

In-house standard In-house standard

Vibration test

A weight of 350 kg is placed on a test piece, and a sine-wave Note: The pedestal type varies depending on the applied load.
vibration of 2 Hz is applied 3 times. Vibration test(Test method:JIS A 1450)
2,500 Model Load mass Result
500
M300A Floor panels should
200kg/350kg
HG not come off.
Motor
Testing organization: Floor Materials and Construction Research Institute
1,000

Mass of Underfloor
Applications
specified weight strength
The case where setting of a lightweight 3000N/㎡
150kg fixture and furniture is assumed
Accelerometer (e.g. ordinary offices)
Concrete flat plate, etc. Surface finishing material The case where setting of a common
book shelf and fixture and furniture is
200kg
500 assumed
Weight (e.g. ordinary offices)
Highly rigid material The case where setting of heavy load
such as a large book shelf and equipment
350kg
including a pint-sized server is assumed
(Heavy-duty zone) 5000N/㎡

Notes
- Specified load is not related to underfloor strength. These data items
are given here for reference considering the current usage.
Accelerometer - Data source: "Performance Assessment of Raised Access Floor
(Source: JIS A 1450) System" by Japan Access Floor Association
NICHIAS OMEGA FLOOR TM 5
Standard Installation Method Examples of Perimeter Work

Cross section

Covering

Cut panel

Field pedestal Perimeter pedestal

Drywall partition (separate work)


A drywall partition can be secured with Drywall partition
screws by drilling screw holes in NICHIAS Covering
OMEGA FLOORTM panels.

Tapping screw for concrete

* Fire-resistant drywall partitions cannot be installed on NICHIAS OMEGA FLOORTM panels.

Fascia (wood base) Fascia (stainless steel)

Screw Screw

Cut panel Cut panel

Tapping screw Perimeter pedestal Field pedestal Tapping screw Perimeter pedestal Field pedestal
for concrete for concrete

Ramp (wood base)

Screw Covering
Covering Wood base for ramp

Cut panel

Tapping screw Ta p p i n g s c rew Perimeter pedestal Field pedestal


for concrete for concrete

Ramp (steel base)

Screw Covering
Covering Steel base for ramp

Cut panel

Tapping screw for concrete Ta p p i n g s c rew Perimeter pedestal Field pedestal


for concrete

6 NICHIAS OMEGA FLOOR TM


Perimeter Work Standard Installation Method

Working on perimeters

When panels of the same material Installation example 1


are used
Cut and install NICHIAS OMEGA FLOORTM (Type 0)
panels.
- Use perimeter pedestals in places close to a wall.
- Install the panels, leaving a clearance of 2 to 4 mm from the wall.
- Panels are cut while pouring water on them. Water supply is required in
the work place and appropriate measures are required to prevent the
surrounding area from becoming dirty.

Field panel Covering cut panel

Field pedestal Perimeter pedestal

Installation example 2
Lock type field pedestal Perimeter pedestal

When using calcium silicate boards


Cut special panel(Calcium silicate board) to the appropriate
size for installation.
- Install a special attachment on the pedestal to adjust the panel thickness.

Field panel Covering Special panel


Special attachment

Special attachment

Field pedestal Perimeter pedestal

Ramps and fascias

Fascia (wood base) Fascia (stainless steel)

Ramp (wood base, steel base) Ramp (wood base, steel base)
NICHIAS OMEGA FLOOR TM 7
Standard Installation Method Installation Procedure

Installation Procedure

STEP1 STEP5
Mark the reference lines on When the installation of the
the concrete floor in pedestals is complete, immediately
accordance with the put the floor panels (type 0 or type
building standard marks PK) on the pedestals according to
and the working drawings. the layout plan, then tighten with
lock plates.

STEP2 STEP6
Adjust the height of the Install the floor panels at
reference pedestals with a the perimeters.
leveler, etc.

(mm) 500 250 500

STEP3 STEP7 Tile carpet

500
Adjust the height of other Install car pet tiles or other
pedestals to the reference coverings. (Be sure to install floor

250
pedestals with a long bar, coverings immediately after
etc., then fix the height installing the floor panels.)

500
Floor panel
with the stoppers. *T he recommended quantity of carpet bond
(peel-up type adhesive) to be applied is 30 to 60
g/m2. Refer to the installation specifications of
the manufacturer for detailed instructions.
Applying too much carpet bond may damage the
Floor panel
carpet due to excessive joint
viscosity.
Reference line (joint) of tile carpet
STEP4
A p p ly a d h e s i ve to t h e 【Layout example of tile carpet】
bottom of the base plate of (mm) 500 250 500 (mm) 500
70 or more
500

each pedestal with a lock


Tile carpet
base, then install the
500

500
pedestals according to the Tile carpet

ADHESIVE
70 or more

reference lines.
250

*W h e n a p p l y i n g p a i n t t o t h e c o n c r e t e s l a b , c o n s u l t t h e p a i n t
500

manufacturer regarding the slab conditions for applying the paint, the Floor panel
500

Floor panel
curing time before bonding pedestals, etc.

Floor panel joint Floor panel joint


Reference line (joint) of tile carpet Reference line (joint) of tile carpet

70 or more
(mm) 500 500
500

Tile carpet
70 or more
500

Floor panel

Floor panel joint


Reference line (joint) of tile carpet

Prohibitions
● Do not use NICHIAS OMEGA FLOORTM for applications other than raised access floors. ● Do not install floor panels upside down because this reduces their strength.
● Do not cut or modify panels or pedestals based on your own judgment because cutting or modifying panels or pedestals may reduce their strength and cause the
panels to break or fall. (Please be sure to contact us.) ● Do not install or move equipment exceeding the design concentrated load on panels. ● Do not leave or use
installed floor panels without laying a floor covering for more than six months. ● Do not use it with a panel lifter.

Please contact us if you have any questions.

8 NICHIAS OMEGA FLOOR TM


Maintenance Standard Installation Method

Maintenance

Installation precautions
● Reinforcement is required when a custom panel is installed or moved. Be sure to contact us. ● Be sure to cover openings in floor panels with the
grommet cover lids. ● The raised access floor system has grommets for power outlets. The joint line of the carpet needs to be shifted at least 70 mm
from the joint line of the floor panels. ● An unusual smell might be generated in case of reaction between the plasticizer of the backing rubber of the
carpet tiles and alkaline water contained in the floor panels. Ventilate the room sufficiently after installing carpet tiles. The recommended quantity of
carpet bond (peel-up type adhesive) to be applied is 30 to 60 g/m2. Refer to the installation specifications of the carpet manufacturer for detailed
instructions. Applying too much carpet bond may damage the carpet due to excessive viscosity. ● Store panels and accessories in a place where they
will not come in contact with water. ● Comply with your local regulations concerning industrial waste when disposing of floor panels.

Precautions on handling panels after installation


1 2 3

Pull up a corner of the floor covering Remove the lock plate with a Remove the grommet cover lid.
(such as tile carpet) and remove the hexagonal wrench.
four sheets of covering that cover the
floor panel to be opened and closed.
* S ince the floor covering has a specific direction, record
its position and direction for reinstalling it later.

4 5 6
If heavy objects exceeding 300 kg or construction ① I f load is concentrated on a single
materials are carried on carts, avoid excessive floor panel, put a steel plate or frame
localized load on floor panels by reinforcing the on the panel.
panels along the route with wooden board ② W hen equipment that generates
according to the following standards. repetitive loading or vibration such as
Heavy object Reinforcing method a mobile rack or large rotary press is
Plywood panel or vinyl used, install it on a mount secured to
300 kg or less
sheet about 2 mm thick the concrete floor to isolate the floor
Wooden board 9 mm panels from the equipment.
300 to 500 kg
thick
Hold the panel with both hands and Wooden board 20 mm
③ If there is equipment that could topple
500 to 1000 kg over, secure it to the concrete floor or
lift it straight up. thick
* R
 ecord the position and direction of the * Make sure the joints of the floor panels and reinforcing materials do not load-bearing walls. Do not secure the
panel for reinstalling it later. overlap. (The joints would be dislocated.) equipment to the floor panel or
* Slowly carry carts by human power. Be careful not to cause an impact
pedestals.
load when hydraulically operating equipment such as a hand fork-lift.

7 8 9
【Maintenance of panel surface】 【Precautions on changing the layout】 【Other precautions】
■Tile carpet Please contact us when modification ●A heavy object falling on the floor or
① For daily maintenance, clean the carpet of panels or replacement of floor excessive impact could damage the panels
with a large vacuum cleaner for business materials is required due to a layout or cause them to fall off. If the panels are
use or a home vacuum cleaner. change or wiring work. used in such a situation, check that the
② For periodical maintenance, clean panels are not damaged after each
the carpet using cleaning powder. incident, and replace them if necessary.
*B  e careful not to spill water or chemicals on ●D o not open the floor panels unless
floor panels. unavoidable. If panels are removed, be
* Consult a cleaning company or surface finish
careful not to stumble or fall.
material manufacturer for details on how to
clean powder or remove stains. ●Be careful not to allow water to splash
onto wiring equipment during cleaning.

Please contact us if you have any questions.

NICHIAS OMEGA FLOOR TM 9


E38 Issued in Feb. 2019

Printed in Japan E38-1902-01-PA-SH-RE-1510