Вы находитесь на странице: 1из 7

Annexure I

BILL OF QUANTITIES FOR CONSTRUCTION OF INDUSTRIAL BUILDING FOR M/s PHOENIX COTACT INDIA Pvt.
Ltd, Prithla, Haryana.
FIRE PROTECTION WORKS

TOTAL INSTALATION
S.No DESCRIPTION UNIT
QTY
RATE AMOUNT
1 Installation and fixing Ball Valve (brass) of approved quality
complete. (High or low pressure with plastic floats).
25 mm nominal bore Each 6 0
2 Installation & erection of ISI marked portable Fire Extinguishers,
wall mounted type, wall brackets complete in all respect as per
standard item with all accessories, delivery hose & nozzle
whereever required, including fixing on walls as per the directions
of Engineer-in-charge.
Water CO2 type. 9 Lt.capacity (IS:940) Each 45 0
CO2 gas type. 4.5 kg. Capacity (IS:2878) Each 45 0
3 Installation & fixing of 4 nos. G.I. round bottom Fire Buckets of
9.5 liters capacity filled with sand including proper supporting /
mounting arrangements in MS angle iron frame, painted by fire
red colour over two coats of red oxide paint and written with white
paint "FIRE" complete in all respects as per the directions of
Engineer-in-charge.
Set 3 0
4 Installation, erection and testing of ISI marked M.S. pipes (Class
C - heavy duty) and specials etc. (as per IS:1239) for above
ground laying for hydrants system including transportation of
materials upto the worksite, cutting the pipes to required length,
edge preperation, welding, fixing / erection of pipes including
specials i.e. bends, tees, reducers, flanges, expansion joints
wherever required, washers, nuts, bolts etc. in proper position
including all supports at maximum 3 meter spacing by 3 mm thick
G.I. hangers / clamps / Tie rod supports with G.I. nuts, bolts,
anchor fastner and washer for hydrant / sprinkler piping, jointing
by welding, aligning the pipe line, painting with two primer coat by
zinc chromate primer and two coats of synthetic enamel fire red
colour, providing tapping for pressure gauges and for other
instruments etc. Hydrostatic testing of system as specified,
flushing & cleaning by water etc. complete as per drawings &
direction of the Engineer-in-charge.

The pipes and accessories will be provided with all type of


supports (Maximum Support spacing = up to 25 mm dia @ 2 m,
32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by
minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie
rod supports with G.I. nuts, bolts, anchor / dash fastner and
washer for hydrant / sprinkler piping, for 100 & 150 mm dia pipe
the support will be through 50x50x6 mm painted / pre galvanized
MS angle iron along with G.I. U clamp, nuts, washers, anchor
fasteners etc as the case may be.

upto 40mm dia. pipe threaded forged fittings and threaded joints
shall be provided and for 50mm dia & above pipes welded joints
with MS / malleable iron fittings shall be used.
25 NB Meter 1670 0
32 NB Meter 635 0
40 NB Meter 525 0
50 NB Meter 200 0
65 NB Meter 90 0
80 NB Meter 90 0
100 NB Meter 320 0
150 NB Meter 1025 0

Page 1
5
Installation, laying & jointing of ISI marked Mild Steel pipes
(class C - heavy duty) (as per IS : 1239) including all fittings i.e.
reducer, elbows, tees, flanges, washers, nuts, boltsetc. below
ground including transportation of all materials to work site, earth
work in excavation in all kinds of soil upto 1.50 meter depth, edge
preparation, jointing by welding, laying the pipes in trenches in
proper alignment, providing 150 mm thick fine sand layer above
pipe, back filling the trenches in layers of 20 cms, consolidation of
Each deposited layer, watering, ramming, disposal of surplus earth
within a lead of 200 m and as directed, hydrostatic testing of the
complete pipe work, providing 1:2:4 concrete thrust blocks of
suitable size at all bends, tees and junctions with form works,
completing the work in all respect as per drawings & direction of
the Engineer-in-charge.

The rates will include providing and laying 4 mm thick "Pypkote"


tar based polymeric corrosion protection tape over two coat of zinc
chromate primer as per manufacturers specs, as directed and as
per IS:10221.
100 MM NB Meter 25 0
150 MM NB Meter 85 0
200 MM NB Meter 18 0
6 Same as in item above but of G. I. Class B - medium duty for
Drainage Pipe.
80 NB Meter 85 0
7 Installation & fixing neoprene rubber single arch Expansion Joint
(anti vibration bellow) as per manufacturers specifications. Tested
to a pressure of 16 Kg/Cm2 including all necessary fittings
complete as required.
80 mm dia. Each 0 0
150 mm dia. Each 2 0
200 mm dia. Each 0 0
8 Installation & fixing in position ISI marked cast iron double flanged
Butterfly Valves (PN 20 MPa) as per IS:13095, with SS disc,
shaft, seating rings, internal fastening, nuts, bolts including
transporting to worksite, 3 mm thick rubber gaskets etc. including
testing, Complete as per drawings & directions of the Engineer-in-
charge.

80 MM NB Each 12 0
100 MM NB Each 9 0
150 MM NB Each 14 0
200 MM NB Each 1 0
9 Installation & fixing in position ISI marked cast iron double flanged
dual plate type Non Return Valves (PN 1.6 Mpa)
80 MM NB Each 0 0
150 MM NB Each 3 0
10 Installation of ISI marked Single headed 63 mm dia. Stainless
steel Hydrant Valve, (PN 20), 80 mm dia flanged inlet with 63 mm
female instantaneous outlet confirming to IS : 5290 on the fire wet
riser/down comer, including making 80 NB pipe connection with
riser, fixing the landing valves in proper positions, including supply
of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and
completing the work in all respect as per directions of the
Engineer-in-charge.
Each 17 0
11 Installation, testing and commissioning of Yard Hydrant
comprising of the following (as per IS:908). (MAKE : Newage /
Safeguard / Padmini / Getech )
1 no single headed C.I. stand post type hydrant.
1 no C.I.flange riser and duck foot bend
1 nos taper connection from main line. Each 17 0

Page 2
12 Installation, testing & commissioning of 20 mm bore and 30 meter
long Hose (high pressure rubber braided hose pipe as per IS:444)
and Hose reel suitable for 10 kg/sqcm operating pressure for first
aid fire fighting conforming to IS : 884, with 180 o full swing drum,
fixing brackets, shut off gun metal nozzle, 40 mm dia. hand lever
operated isolating ball valve, connecting directly from the riser
through 40 mm dia. G.I.pipe with sockets, elbows, nipples etc.
including providing operating instructions on a metal plate and
fixing it near hose reel. The system shall be complete in all
respects as per drawings and directions of Engineer-in-charge.

Each 17 0
13 Installation of Stainless steel ISI marked 63 mm. dia. male
Instantaneous pattern short Branch Pipes with 20 mm dia. Nozzle
as per IS : 903, suitable for 10 kg/sqcm operating pressure and
suitable for interconnections to hose pipe coupling as required.
Each 34 0
14 Installation of ISI marked RRL (IS : 636, type-A) Fire Hose pipe
15 meter long and 63 mm dia with ISI marked (IS : 903)
Stainless steel male and female coupling bound and rivetted to
hose pipes with copper rivets and copper wire complete as
required.
Each 68 0
15 Installation & fixing standard carbon steel Fireman Axe with
rubber insulated handle tested to 20000 Volts. Each 17 0
16 Installation of 25 mm dia Air release Valve with forged brass
body full way ball valve type isolating valve, flanges / union,
suitable for sprinkler / wet riser / down comer system with all
necessary connections complete in all respects.
25 mm dia air release valve Each 7 0
17 Installation of C I body flanged S S strainer fabricated out of 1.6 mm
thick Stainless Steel 304 sheet with 3 mm dia hole complete.

150 mm dia Each 2 0


200 mm dia Each 1 0
18 Installation of stainless steel Orifice Plates at appropriate places
to restrict the pressure up to 3.5 Kg/ Cm2 at different floors on the
wet riser system and yard hydrant. It shall be inserted between the
flange and hydrant valve. The size of plate being 100 mm or 80
mm (as the case may be), the hole not less than 50 mm. and the
plate thickness shall not be less than 6 mm.

Each 17 0
19 Installation of electrically operated water Flow Switches (Vane
type) for sprinkler system including accessories, junction box
complete as required, with potential free contact with 2 NO / 2 NC
suitable for fixing on fire pipe. (Make : System sensor)

for 100 mm diameter pipe Each 8 0


for 150 mm diameter pipe Each 3 0
20 Installation of testing & commissioning of C.P. bronze / gun metal
Sprinklers as per IS : 9972, comprises of 15mm dia conventional
pattern, 68oC, quatzoid bulb type pendent / upright sprinklers,
UL / FM listed / approved. The installation shall be complete as
per the drawings with positioning of sprinklers as per final
coordinated plan and requirement of IS : 15105, local fire service
& Engineer-in-charge.
(MAKE : HD / Tyco / Globe)

Each 1080 0
21 Installation of testing & commissioning of 25 mm dia inspecting
and testing assembly with gun metal valve, sight glass, by pass valve
and connection to the drain line as required to complete the system.
Each 12 0
22 Installation of dial Pressure Gauge complete in all respects.
(Make : H Guru / FIBIG)

Page 3
for 80 mm diameter pipe Each 0 0
for 150 mm diameter pipe Each 8 0
for 200 mm diameter pipe Each 0 0
23 Installation and testing of cylindrical type flanged Pressure
Vessel Tank, 450 mm dia, 2 m long and of 10 mm thick M.S.,
common for a set of fire pumps including flanged connection,
suitable supporting legs etc. The air vessel tank shall be provided
with air release valve, stop cock, safety valve, pressure gauge, 50
mm dia drain valve, suitable pressure switches to operate main
pumps and jockey pumps, tested to min 25 KG/cm2 complete
including painting with synthetic enamel paint of approved shade
with all accessories as per direction of the Engineer-in-charge.

Each 1 0
24 Installation of cast iron body 150 mm dia Draw out connection in
Under ground water storage tank with heavy class MS suction
pipe of required length, foot valve, suction coupling in conformity
with local regulations complete in all respects. (MAKE : Newage /
Safeguard / Padmini )
Each 2 0
25 Installation of standard fire Hose Cabinet (900 / 1000 / 1200 mm x
2000 mm x 450 / 600 mm) Indoor Type suitable for accomodating internal
hydrant, hose reel made of not less than 16 SWG MS sheet having full
fronted glass hinged door (5 mm thick glass) including necessary locking
arrangement with handle for housing two nos. 15 meter long fire hose
pipes, 30 meter long hose reel, branch pipe and hydrant valve as required
as per drawings, including brackets for mounting accessories, painting
(one coat primer and two coat of fire red colour). The cabinet shall be
mounted on suitable raised platform. The words "FIRE HOSE" to be
painted on the box.

Each 17 0
26 Installation of weather proof standard Fire Hose Cabinet (900 mm
x 600 mm x 450 mm) outdoor type made of not less than 14
SWG MS sheet having glassed hinged door (5 mm thick glass)
including necessary locking arrangement with handle for housing
hydrant valve, two nos.15 meter long fire hose pipes, branch pipe
as required as per drawings, including brackets for mounting
accessories, painting (one coat primer and two coat of fire red
colour). The cabinet shall be mounted on self standing mounted
type painted MS Angle iron frame as required. The words "FIRE
HOSE" to be painted on the box.

Each 17 0
27 Constructing brick masonary chamber 90 x 90 x 120 cm inside with
FPS brick work in cement mortar 1 : 5 (1 cement : 5 fine sand) for sluice
valve with S.F.R.C. cover and frame (heavy duty HD-20 grade
designation), 560 mm internal diameter confirming to IS:12592, total
weight of cover and frame to be not less than 182 Kg in cement concrete
1:2:4 and RCC top slab 1:2:4 mix (1cement : 2 coarse sand : 4 graded
stone aggregate 20 mm nominal size ) necessary excavation, foundation
concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40
mm nominal size) and inside plastering with cement mortar 1:4 (1
cement : 4 coarse sand) 12 mm thick finished with a floating coat of neat
cement complete as per standard design .

Each 1 0
28 Installation, testing and commissioning of electrically driven
high pressure centrifugal fire hydrant /sprinkler pump, suitable
for automatic operation consisting of the following:

Each 1 0
29 Installation, testing & commissioning of MS air cushion tank on
top of each riser fabricated from 6mm thick MS plate, 200 mm in
diameter and 1.2 m in height with dished ends fabricated from
8mm thick MS plate. Each 8 0

Page 4
30 Installation, testing & commissioning of U.L.listed/ FM approved
corrugated SS-304 unbraided flexible sprinkler pipe droplet for 12
kg/ sq. cm. working pressure with 1/2" BSP threaded outlet & 1"
BSP threaded inlet with reducer nipple, snap, clamp, T-bar bracket
etc. with necessary fitting complete as required.

1000 mm long. Each 276 0


31 Installation of Control Valve with turbine type automatic Alarm
Gong to be connected with control valve, drain & test valve and all
other necessary components as per manufacturer's
specifications complete as required.
150 mm dia. Each 2 0
100 mm dia. Each 3
32 Installation of GM fire brigade connection consisting of 4 No. 63
mm dia instantaneous type male couplings with built-in check
valves, 150 mm dia flanged outlet complete with bolts, nuts and
rubber insertions as required and as per IS standards
Each 2 0
33 Rosset plate adjustable type power coated for pedent sprinkler on
follceling area. Each 276 0
34 Fixing standard type pressure switch (for operation at 0-15
Kg./sqcm) with required fittings and accessories complete etc. as
required. Each 1 0

35 Fabrication & Erection Wall Bracket Support for External Hydrant


Systems Each 200 0

36 Making AS Built Drawing. Soft copy only. lot. 1 0

37 Providing and Laying of R.C.C. pipes NP2, for (storm water


drain) with collars jointed with stiff mixture of cement
mortar in the proportion of 1:2 (1 cement : 2 fine sand)
including testing of joints etc. complete embedding in
concrete as per specifications. 300 mm dia

rm 50
B CIVIL WORKS
1
Earth work in excavation in all type of soils by
mechanically/manually for depth of 1.5m including removal
of vegetation etc cutting and dressing of sides in slopes,
ramming of bottom, dewatering of accumulated water from Cum 500
any source and disposal of stacking of excavated material
within 200 m as directed including providing temporary
supports to existing service lines etc all complete.
2
Backfilling to proper grade and level with selected material
from excavated earth including breaking of clods, laying in
all depths and levels in layer of thickness 15 cm , watering, Cum 350
ramming to achieve 95 % laboratory max dry density
dressing, trimming etc.

Page 5
3
Providing and Laying plain cement concrete concrete 1:4:8
(1 cement:4 coarse sand: 8, 40mm and downsize coarse
aggregate) up to plinth in foundations, drains, fillings, non
suspended floors, pavements& ramps or any other works
Cum 40
including shuttering, tamping, ramming, vibrating,
curing,etc.all as specified in any thickness & finishing the top
surface as per direction of engineer in-charge. (Cement
supplied by owner)
4
Providing and Laying REINFORCED CEMENT
CONCRETE of M-25 grade with 20mm and down size
graded crushed stone aggregates/gravel in sub structure of
all types of e.g. foundations rafts beams slabs, retaining
walls, counter forts buttresses trenches manholes, pipe
encasement, catch pits, drains RCC pits
equipments/machines foundations pedestals, columns,
Cum 150
suspended floors, staircases, landings, stabs, brackets etc.
Including cost of admixtures if used, providing pockets,
openings, recesses, chamfering etc. Wherever required
vibrating tamping, curing and rendering if required to give a
smooth and even surface for all depths below and up to
plinth level in any shape, position and thickness etc. all
complete as specified. (Cement supplied by owner )

5
Placing in position HIGH STRENGTH DEFORMED
STEEL BARS REINFORCEMENT (conforming to IS :1786
grade fe 500D) for RCC work transporting the same for
store/issue points to site of work, straightening, cleaning de-
coiling ,cutting ,bending with required shapes and lengths as
per details, binding wire at every intersection , supplying and MT 13
placing with proper cover blocks, supports, chairs, overlaps,
welding, spacers, fan hooks etc. (return for all unused /
scrapped/ reconciliation of material) for all heights and depth
etc. all complete as directed . (Steel reinforcement supplied
by owner)

6
Providing and fixing CENTERING AND SHUTTERING in
foundations, raft ,beams, slabs, retaining walls, counter-forts
, buttresses, trenches, equipment foundations pedestals,
abutments, slabs, beams, staircases, landings, steps, etc. for
all depths below and up-to & inclusive of plinth level ,
strutting, bracing , propping etc. keeping the same position Sqm 610
during concreting and removal of the same after specified
period etc. for straight/ inclined shuttering, keeping necessary
provision for inserts, projecting dowels, anchor bolts or any
other fixture etc. all complete as specified, shown and
directed.

7 Supplying ,Fabricating and fixing of insert plates & angle


with lugs, NB pipe , as per drawing in position including
MT 2
leveling, preparation of template strutting, shuttering etc.
complete and direction of Engineer-in-charge
8 Dismantling manually /by mechanical means RCC Road and
disposal of materials outside the PLANT area up-to all lead.
Cum 15

Page 6
Note - above quantity of materials are for considering the work of FIRE SYSTEM to be
executed on item basis , actual quantity of material will be calculated at site during works.

Note:
1 Dismantling of any Equipment/ piping etc. claim
@50% of Erection rate

Page 7