1 2 3 4 5 6 7 8 9 10 11 12

A A

GALV. DROP-IN GRATE FINAL RISER DIA. TO SUIT


50 MIN.
(NOTE 3 & 4) PRE-CAST CONCRETE GALV. AIR VALVE NOM. DIAMETER
150 MAX. 50 MIN.
SURROUND DROP IN GRATE
150 MAX. (NOTE 3)
F.S.L.

PRE-CAST GRC OR RC CHAMBER

600 MAX.
600 MAX. (NOTE 7)

375 MIN.
(NOTE 2)

600 MAX. (NOTE 7)


PRE-CAST GRC OR RC CHAMBER

DIM "H"
(NOTE 2) DIM "D2"
900 MAX.

AIR VALVE 80 DRAIN HOLE ON LOW SIDE

900 MAX.
B (NOTE 5) B
FLANGED BALL VALVE AIR
F.S.L.
OR WAFER LUGGED VALVE
BUTTERFLY VALVE
(BALL VALVE SHOWN) FLANGED BALL VALVE OR
WAFER LUGGED
BUTTERFLY VALVE
(BUTTERFLY SHOWN) BEDDING AND BACKFILL TO BE SITE/
CONCRETE SUPPORT LOCATION SPECIFIC

CONNECTION TO
NEARBY DRAIN
BEDDING AND BACKFILL INLINE RISER DIM "D1"
REQUIRMENTS (SUPPLY MAIN NOM. DIA)
C C
TO BE SITE SPECIFIC
TYPE B - AIR VALVE INSTALLATION
INLINE OR OFFSET CONNECTION
(RURAL AREAS) DETAIL A - IN LINE CONNECTION
TYPE A - AIR VALVE INSTALLATION SCALE: 1 : 10 SCALE: 1 : 10

(URBAN AREAS, UNPAVED)


SCALE: 1 : 10
DIM "D2"

AIR VALVE CHAMBER DETAILS DIM "D1"


(SUPPLY MAIN NOM. DIA)

D D

DETAIL B - OFFSET CONNECTION


(FOR MAINS DN250 AND SMALLER)
SCALE: 1 : 5

NOTES:
E E
FINAL PIPE DIA. TO SUIT
CHAMBERS AIR VALVE NOM. DIAMETER

1. “TYPE A” INSTALLATION TO BE USED IN NON-TRAFFICABLE URBAN AREAS. “TYPE B” INSTALLATION TO BE USED IN RURAL
AREAS.

2. CHAMBER CONSTRUCTED FROM PRECAST GRC OR RC PITS AND RISERS TO SUIT REQUIRED DEPTH. APPROVED MINIMUM SIZE
IS 900x900 (INTERNAL DIMS.) RISERS TO COME WITH "SWIFT LIFT" LIFTING ANCHORS OR SIMILAR.

3. GALVANISED GRATE TO BE PAD-LOCKABLE AND BOLTED IN PLACE USING KEEPER PLATES TO PREVENT UNAUTHORISED ACCESS.
32kg MAX. WEIGHT, CAPABLE OF MAX. MIDSPAN DEFLECTION OF 5mm @UDL = 2.5kPa

F 4. TOP OF COVER TO SIT 25-35mm ABOVE FINISHED GROUND LEVEL. F


DIM "H"
5. CHAMBER MUST BE SELF DRAINING. DRAIN HOLE MUST BE SITUATED BELOW THE AIR VALVE INLET/OUTLET NOZZLE,
TO AVOID AIR VALVE BEING MADE INOPERABLE DUE TO FLOODING. DIM "D2"

6. CHAMBERS TO BE LOCATED A MINIMUM CLEARANCE OF 6.0m AWAY FROM ROADWAYS. SEEK ADVICE FROM ICON WATER
PRINCIPAL ENGINEER IF THIS CLEARANCE IS NOT ACHIEVABLE.

7.IF ISOLATION VALVE HANDLE TIP EXCEEDS MAXIMUM DIMENSION STATED, ISOLATION VALVE WITH GEARBOX SHALL BE
INSTALLED. COVER TO INCLUDE A BANDED HOLE TO ALLOW AN EXTENSION SPINDLE TO MANUALLY OPERATE THE VALVE. IF THIS DIM "D1"
IS NOT PRACTICAL LOCATE THE VALVE SO THAT A “TYPE C” INSTALLATION CAN BE EMPLOYED. (REFER WSS-076 AND WSS-077 (SUPPLY MAIN NOM. DIA)
FOR “TYPE C” DETAILS).

G CONNECTION TO SUPPLY MAINS


DETAIL C - OFFSET CONNECTION G
(FOR MAINS DN300 AND LARGER)
8. NOMINAL RISER DIAMETER “D2” SHALL BE A MINIMUM OF HALF THE SUPPLY MAIN DIAMETER “D1” EXCEPT WHERE “D1” SCALE: 1 : 10

EXCEEDS DN750, THEN “D2” SHALL BE DN300.

9. DIM “H” SHALL BE A MINIMUM OF HALF OF THE SUPPLY MAINS NOMINAL DIAMETER.
AIR VALVE CONNECTION TO SUPPLY MAIN
DETAILS
Drawn: Date: Drawing Type:
M. Matusiak 27/07/2016 STANDARD DRAWING
Designed:
K. Danenbergsons
Standard Drawing
A ISSUED FOR USE AND TRANSITION TO WSAA CODES 28/10/2016 I. McRae P. Language Drawing Status:
Engineering
I. McRae
H B AMENDMED VALVE ANNOTATION AND CHAMBER NOTES 5/01/2017 K. Danenbergsons K. Danenbergsons
Checked:

Verified:
4/11/2016 VALVE CHAMBER TYPE A AND TYPE B AND CONNECTION TO SUPPLY MAINS
Current H
No. DESCRIPTION DATE ENG CHECKED VERIFIED DESIGN AUTH
AIR VALVES
Rev
The information contained within this drawing & associated electronic file shall remain the property of Icon Water and shall not be copied or used for any other
purpose without express written permission from Icon Water. © Icon Water. 2016
Design
Authority: P. Language 9/11/2016
DETAILS A1 WSS-078 B