Вы находитесь на странице: 1из 147

Product Manual

1HYB 800001-52 Rev. A

EDF SKS 1-1


with operating mechanism
Type FSA
Product Manual
1
HIGH VOLTAGE CIRCUIT-BREAKER-TYPE
ED 1 H Y B 8 0 0 0 0 1 - 2 6

FUNCTIONAL VALUES
1 H Y B 8 0 0 0 0 1 - 53
2
LUBRICANTS
1HYB800001-28
3
LOCKING LIQUID FOR THREADS
1HYB800001-29
4
GENERAL INSTRUCTIONS FOR
MAINTENANCE, TRANSPORT & STORAGE
1HYB800001-30
5
GOODS MARKING AND TRANSPORT
1HYB800001-31
6
STORAGE PRIOR TO ERECTION
1HYB800001-32
7
INFORMATION
SF6 GAS AND GAS MIXTURES
1HYB800001-33 8
SAFETY REGULATIONS
1HYB800001-35
9
DISPOSAL AND RECYCLING
1HYB800001-36
10
INSTRUCTIONS FOR ERECTION,
OPERATION AND MAINTENANCE
1 H Y B 8 0 0 0 0 1 - 54
11
INSTRUCTIONS FOR OPERATION
AND MAINTENANCE OPERATING
MECHANISM TYPE FSA -
1HYB800001-38
12
1HYB800001-26 Rev. A
Page 1

HIGH VOLTAGE CIRCUIT-BREAKER TYPE ED


The high voltage circuit-breaker type ED is a detached SF6 circuit-breaker for outdoor
erection in open substations.

The circuit-breaker is built up of three separate poles, which consist of three main
parts. At the bottom, the mechanism housing is made of aluminium. The hollow post
insulators, through which operating insulators run and on top, the breaking units.
Each breaking unit consists of a hollow insulator which together with an upper and a
lower flange constitute the casing and a lower and an upper current path with a
contact system. The moving contacts are assembled on the lower current path
whereas the fixed contacts are assembled on the upper one.

The circuit-breaker poles to ED SK are permanently filled with SF6 - gas, normally to
the pressure 0.7 MPa absolute at 200C. For monitoring the pressure the circuit-
breaker is equipped with a density monitor. The poles are mounted on a common
supporting frame, consisting of a front and a rear pole beam. The latter is mounted
on two supports which are anchored to the foundations. The beams and supports are
hot-dip galvanized.

The pressure rise and gas flow which are necessary for extinguishing the arc during
the course of breaking are produced partly by compression of the gas, partly by the
energy given from the arc.

At the opening operation, the moving contact is pulled downwards over the fixed
piston and the confined quantity of gas is compressed and at high speed forced out
through the springs in the upper end of the cylinder. At the same stage the arcing
contacts are separated and an arc occurs. A specially formed nozzle leads the
outflowing gas towards the arc. The gas is allowed to pass both downwards through
the moving arcing contact and upwards past the fixed arcing contact.

For the continuous current there are separate contacts which are not affected by the
arc at breaking.

At closing operation, the moving contact is pushed upwards at which time the con-
tacts engage and the cylinder is filled with gas again.

The ED SK circuit-breaker is operated by a motor-operated spring closing device


type FSA.
1HYB800001-53 Rev. A
Page 1

Functional Values
SF6 BREAKER TYPE ED-SKS 1-1 (72.5 kV) WITH OPERATING DEVICE TYPE FSA 1

Closing time max. 60 ms


Opening time max. 35 ms
ON-OFF time *) max. 40 ms

Demand of time difference between poles.

Unearthed capacitor bank.

Pole C1 Pole B1 Pole A1


Closing time 50 Hz ts ts ± 0.5 ts + 5.0 +1.0/-0.5
Closing time 60 Hz ts ts ± 0.5 ts + 4.2 +1.0 -0.5

Earthed capacitor bank.


Pole C1 Pole B1 Pole A1
Closing time 50 Hz ts ts +3.3 ±0.7 ts + 6.7 ±0.7
Closing time 60 Hz ts ts +2.8 ±0.7 ts + 5.6 ±0.7

Resistance of the main circuit across a breaking unit: Max. 50 at rated current 2000
A/1600 A.

*) ON-OFF time means the time during which the main contacts are closed at a
closing operation when the tripping impulse is connected in simultaneously, via
the auxiliary contact.
1HYB800001-28 Rev. A
Page 1

Types of Lubricants for Switching Devices


As a guide to the selection of Lubricants and oils, a description is given below of the
range of applications.
Oil “A” :
Thin lubricating oil for precision parts in operating mechanisms and air-blast circuit-
breakers. Also for relubricating of bearing, which can not be lubricated with grease
G without dismounting -e.g. links and link gears. Viscosity at 400C: 62-65 cSt.
Oil “C”:
Circuit-breaker oil with viscosity~17 cSt at +200C. Suitable only for temperature > -
100.
Oil “D” :
Circuit-breaker oil with viscosity~6.0 cSt. at +20 0C. Shall also be used as oil in
dashpots. For dashpots with the letter “S” stamped on the cover - oil “S” shall be
used.
Oil “S” :
Silicon oil intended for oil dashpots in heavy operating mechanisms. Only dashpots
with the letter “S” stamped on the cover shall be filled with this oil.
1HYB800001-28 Rev. A
Page 2

Grease “G” :
Low temperature grease for all types of bearings, gears and worm gears as well as
valves in air-blast circuit-breakers. Also suitable for lubrication of silverplated con-
tacts in air (e.g. contacts in disconnectors).
Also used when greasing O-rings made from nitrile rubber and as a crevice corrosion
prevention.
Grease “N” :
For lubrication of moving contacts in SF6-insulated circuit breakers (e.g. puffer
cylinders). A very thin layer of the grease shall be rubbed on the sliding surface of
the contacts.
Grease “L” :
Low temperature grease specially suitable for lubricating of fine mechanics-e.g. catch
devices in operating mechanism which shall operate in strong cold.
Grease “M” :
Low temperature grease for long-duration and permanent lubrication of worm gears
and other machine elements. Prevents wear and corrosion.
Grease “P” :

Vaseline for treatment of contact surfaces in current conductor joints.

Grease “R” :

EP-grease for heavily-loaded roller bearings, slide bearings, cam discs and catches
(Lithium grease. Solvent refined mineral oil with lithium soaps and molybdenum
disulphide) in operating mechanisms type FSA.

Grease “S” :

Fluoro-silicone grease for greasing of O-ring made from EPDM and as a corrosion
prevention of gaps in circuit-breakers type ED.

Grease “SV”

Grease for lubricating moving contacts, silver plated connections and brushed
aluminium surfaces in fixed joints outdoors.
1HYB800001-28 Rev. A
Page 3
1HYB800001-29 Rev. A
Page 1

Locking Liquid For Threads


As a guide to selection of locking liquids, a description is given below of the range of
applications.

Pre-treatment of surfaces : The surfaces shall be free from oil, grease, wax, paint and
rust-preventive. Locking Liquids “A”, “B” and “C” are designed for use in only surfaces
also.

Locking Liquid “A” : Weak locking and setting of set screws.

Locking Liquid “B” : Medium strong locking of threads and sealing of screws and
nuts.

Locking Liquid “C” : Strong locking and sealing of studs and bolts up to M36.
Difficult to dismantle.

Locking Liquid “D” : Locking of fasteners after assembly or adjustment. Sealing


of porous weld joints, castings and sintered materials. The
sealing is very resistant against pressure, solvent and
chemicals. Can be used only on clean, dry surfaces. Oily
goods to be washed with trichloroethylene, preferably steam-
washing.

Locking Liquid “E” : To pre-treat PTFE at locking of a thread connection PTFE/


metal

LOCTITE Ltd.

LOCTITE Ltd.
1HYB800001-30 Rev. A

General Instructions for Maintenance,


Transport & Storage

Contents :

1. Safety precautions
2. Cleanliness
3. Cleaning
4. Waste disposal
5. Emptying of gas
1HYB800001-30 Rev. A
Page 1

1. Safety precautions
Follow the local high-voltage safety regulations. Put the breaker in the “OPEN”
position.
Disconnect and earth the high voltage side.
Disconnect the operating and heating voltage.
Work on the insulators of the breaker or live parts as well as transport and
dismounting of complete breaking poles may not be done before the breaker is
emptied to a max. pressure of 0.15 MPa abs. Before the opening of the normally
pressurised vessel, it shall be emptied completely to atmospheric pressure. If the
gas is emptied into the free air, this shall be done through a dust and absorption filter.
See under clause “Emptying of gas”.

2. Cleanliness
Very high dielectric requirements are placed on the SF6 gas and on the insulating
parts and correspondingly also on their cleanliness and dryness.
On all work on the open circuit breaker, be aware that not only dirt but also air
moisture and hand perspiration are deleterious.
If for any reason gas spaces or parts thereof are exposed to air for longer than 24
hours, the gas spaces are to be closed temporarily and filled with SF 6 gas to Pabs =
120 kPa (1.2 bar). Single parts are to be sealed in plastic bags and kept in storage.
Unused SF6 gas is non-poisonous, odourless and colourless. However, it is heavier
than air and with substantial outflow, it gathers easily in low situated spaces like
cable trenches, tanks and such.
With large amount of SF 6 in these spaces, there is a risk of suffocation due to lack
of oxygen.
- Perform overhaul work only with adequate room ventilation.
- The decomposition products which are formed in the breaking elements are in
combination with humidity corrosive and can cause skin, eye and mucous
membrane irritation. During the opening and internal cleaning of the breaker, a
close fitted mask with a filter against fine dust and acid gases, protective
plastic or rubber gloves and a long sleeved overall shall be used.
The dust (decomposition products), that is formed in the breaker, shall be sucked
with a vacuum cleaner provided with a dust filter and wiped off with a cloth that is
sprinkled with ethanol or toluol.
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear
protective gloves.
Drying cloths, protective gloves and vacuum cleaner bags shall be rinsed carefully
with plenty of water.
1HYB800001-30 Rev. A
Page 2

3. Cleaning
A. Insulator with paint-treated plastic outside surface, silicon rubber sheds or porce-
lain insulator.
Rinse the outside surfaces thoroughly with water and let it dry well before the
breaker is opened.
The end and inside surfaces are cleaned with a non fluffy drying cloth soaked with
ethanol.
Cleaned insulators must be touched only with clean protective gloves (plastic or
rubber).
Cover the end surfaces of the insulators with a strong plastic foil to protect from
recontamination.
B. Single parts
Vacuum immediately after disassembly with a vacuum cleaner with a fine dust
filter. Wipe off persistent dust with a non fluffy cloth.
Remove stubbornly adhering dust with a cloth soaked with ethanol.
Cover cleaned details with plastic foil or put in plastic bag.
Details from spaces not filled with SF6 shall be cleaned with ethanol and then left
to dry in air. Then they are packed in plastic bags.

4. Waste disposal
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear protective
gloves.

5. Emptying of gas
The breaker is evacuated by means of the gas treatment equipment, that purifies and
compresses the gas, so that it can be reapplied.

Mixed gas - SF 6 + N2 - can only be reapplied if the mixing conditions are under
control.

After the evacuation, the breaker is filled with nitrogen up to atmospheric pressure
and after this, evacuated again. In this way, the eventual free drifting dust in the
breaker is removed.

Finally the breaker is filled again with dry nitrogen up to atmospheric pressure after
which it is ready for dismounting and transport to the workshop.

NOTE

If work on the circuit-breaker only affects the outside of the breaker, for example
cleaning of the insulators, it is sufficient to empty the breaker down to a pressure of
0.15 MPa abs, normal working pressure.
1HYB800001-31 Rev. A
Page 1

GOODS MARKING AND TRANSPORT


General
Each case is marked with markings as per Packing list.
In addition they are marked with following :

- Glass, porcelain, handle carefully

- Up

- Put the lifting slings here

DO NOT TILT - It is not allowed to tilt the transport unit more than 45 degrees
MORE THAN 45”

- Centre of gravity

- Must be protected from moisture and rain

Figure 1 Transport unit

The circuit-breaker should be transported in their transport units, and particularly


never be transported unpacked. While choosing conveying equipment, the
following should be observed :

• Packing case markings


• The distance and road conditions

The units should be transported in such a way that they are

- Prevented from standing in water


- Not exposed to rough handling and damages
- Covered by at least tarpaulin, protected against water

Every transport unit must be fixed during the transport. The tying must be so
arranged that the transport units can not move in any direction. Velocity should be
adapted to the road conditions. Violent acceleration or retardation can cause damage
to the contents without damaging the packing.
1HYB800001-31 Rev. A
Page 2

Lifting
Before lifting, the symbols on the transport unit (such as centre of gravity, weight
etc.) should be observed. The transport units should be lifted with a lifting machine
provided with forks of slings (see fig. 2). If a crane is utilised slings should be used.
The units may not be rolled or dropped from the conveying or lifting equipment.

Figure 2 Lifting a transport unit

Lifting the operating mechanism out of the transport unit

The operating mechanisms FSA should be lifted by the lifting devices on top of the
cubicle. Lifting slings should never be used around the operating mechanism (see fig.
3)

Figure 3 Lifting the operating mechanism

Lifting the breakers out of the transport units

Lifting the breakers out of the transport units is only necessary just before erection
(see product information, which can be found in the cubicle of the operating
mechanism). If they are going to be stored, see “Storage prior to erection”.
1HYB800001-31 Rev. A
Page 3

Stacking
Transport units with different widths may not be stacked (the pressure may break the
cover of the lower transport units. It should be noted that stacking causes sideways
instability, and therefore the load has to be fixed, i.e. prevented from dropping, rolling
or falling. It is not allowed to stack more than three transport units.

Figure 4 Stacking
1HYB800001-32 Rev. A
Page 1

Storage prior to erection


General

Circuit breakers intended for outdoor operation are generally delivered in units which
are determined for transport reasons. Intermediate storage of these units should be
avoided. If it is not possible to avoid intermediate storage, they should be stored
indoors or under a roof. They must also be stored above ground level to prevent
water damage. On arrival, it is important that plastic sheets are removed in order to
prevent corrosion by condensate water (except for the spare parts).
Storage in a humid climate without proper ventilation may lead to discoloration of the
galvanised surface. This discoloration is commonly known as “white rust”, consisting
mainly of zinc oxide and zinc hydroxide and is a result of a chemical process
between the pure zinc on the surface and moisture.
The long term corrosion protection is not influenced, since the iron-zinc layer below
the surface remains unaffected. The presence of white rust is no reason for rejection
of goods.
On arrival, each unit should be checked in the following way :
- delivery is in accordance with order and delivery documents
- any damage in delivery, and material loss
In cases where damages are detected or suspected, the units should be opened and
damages should be photographed. Both damages and shortages should be reported.
All details should be rationally stored so that they are always available. In general, all
material should be stored in an approved storage (note 1), exceptions are given in
the text below. The ambient air should not be heavily contaminated by dust, smoke,
corrosive or combustible gases, vapours or salt, otherwise the equipment has to be
cleaned before erection.
For storage the original transport unit may be used, but the plastic sheeting should
be removed. The coupling joints of the assemblies, as well as all connections, are
fitted with transport covers or protective caps which shall not be removed until
immediately before erection.
Operating mechanism (for circuit breakers)
The operating mechanism should be unpacked on arrival. If it is not going to be
stored in an approved storage (note 1), the heating elements must be connected and
supplied permanently with power to protect the control equipment from corrosion or
freezing damages.
Circuit Breakers
The breakers should be stored in their original transport unit, where they are well
protected from damages. The units shall be prevented from standing in water. The
breakers may be stored outdoors, except for the EDI-breaker, which should be stored
in an approved store. If the breakers are stored outdoors they should be covered with
a tarpaulin. (Note 1)
1HYB800001-32 Rev. A
Page 2

The tarpaulin should not be placed directly on the galvanised surface. An air gap
should be left to prevent condensation. Condensation that may occur should be self-
draining.

For the outdoor breakers, the minimum ambient temperature allowed is -300C. For the
indoor breakers, the minimum ambient temperature allowed is -50C.

Spare parts

The spare parts shall be stored indoors in an approved storage (note 1), in their
original units. This is in particular valid for rubber parts (sealings etc.), which also
have to be protected against light and sun, in order to prevent them from ageing.
Gaskets can be stored only for limited periods, so avoid storage of these parts.
Structures may be stored outdoors.

Notes 1 :

We define an approved storage as a storage with

- roof
- solid ground
- relative humidity less than 50%
- temperature 20 0C (+/-100C)
1HYB800001-33 Rev. A

Information on SF6 Gas and Gas mixture types SF 6/CF4


and SF 6/N2 when used as breaking and insulation media

Contents :

1. Introduction
2. Thermal and dielectric breaking capacity
3. Chemical reactions in Circuit Breakers
4. Criteria for choice of mixed gas
5. Filling mixed gas
6. Measuring gas mixing proportions
7. Technical data for SF 6, CF4 and N2 gases
8. Safety regulations
8.1 Safety regulations for SF 6 gas
8.2 Safety regulations for CF4
8.3 Safety regulations for SF6 and CF 4 gases which
are exposed to arcs
9. Environmental effect.
1HYB800001-33 Rev. A
Page 1

1. Introduction
SF6 gas has become the predominant breaking and insulation media for circuit-
breakers of puffer and Auto-PufferTM types.

At low ambient temperatures, below - 300 or -400C (depending on filling pressure),


there is a risk of condensation of SF6 gas resulting in drastic density changes. The
temporary condensation at low temperatures is not dangerous but can cause
problems in density monitoring and, temporarily, some reduction of breaking capacity.
One way of avoiding this is to fill sulphur hexafluoride SF6 to a lower density and fill
up to rated density with nitrogen N2 or tetrafluormethane CF4.

Information on characteristics and regulations for SF6 gas, N2 gas and CF4 gas is
stated in this product information.

2. Thermal and Dielectric Breaking Capacity


When breaking short-circuit currents the circuit-breaker must withstand two separate
stresses at somewhat different times, See Figure A.

2. Dielectric region

Figure A.
Stress on a circuit-breaker at breaking moment

Gas flow

Figure B.
Cooling SF6 arc by cold gas mixture
1HYB800001-33 Rev. A
Page 2

These stresses are :

1. Thermal range

At current zero the hot arc channel shall be cooled down quickly to a temperature
which makes it electrically non-conductive, Figure B. Cooling capacity depends on
how quickly the current decreases towards zero, di/dt, and on the rate-of-rise of the
recovery voltage after current zero, du/dt, Figure A.

2. Dielectric range

After current zero the circuit-breaker must, for a short moment, withstand the full top
value of the transient recovery voltage without dielectric breakdown.

Breaking of terminal fault often gives low rate-of-rise of the recovery voltage and is
often a problem in the dielectric range.

Breaking of distance fault is a problem usually concentrated to the thermal area.

SF6 is an electronegative gas of high density with good characteristics in both the
thermal and dielectric ranges.

Mixed gas filling of SF6 and N 2 gives a somewhat deteriorated thermal breaking
capacity as well as a slightly deteriorated dielectric breaking capacity compared with
only SF6 gas filling. Mixed gas filling with nitrogen often results in a reduction of
breaking capacity, e.g., a rated breaking current of 40 kA is reduced one step to 31.5
kA. The deteriorated dielectric characteristics can be compensated by nitrogen gas
filling to a slightly higher pressure than with only SF6 gas.

Mixed gas filling of SF6 and CF6 results in practically unchanged thermal and
dielectric breaking characteristics. A mixed gas filled circuit-breaker with SF 6/CF4
often retains its breaking capacity down to the lowest ambient temperature.

3. Chemical Reactions in Circuit-Breakers


When an arc burns in the arc chamber, part of the SF 6 gas decomposes but is
quickly restored to SF6 gas when the temperature falls. Heat from the arc added to
gas, contact material, nozzle material, as well as small amounts of moisture residue,
give chemical reactions. The most important of these are :

Arc in teflon nozzle

Teflon is degraded to pure carbon and CF 4 gas.

heat
CF3-(CF 2)N - CF3 ➞ CF 2 (1)
heat
2CF2 ➞ C + CF 4 (2)

Arc in SF 6 gas
heat
SF 6 ➞ S + 6F (3)
1HYB800001-33 Rev. A
Page 3

The carbon which is formed according to (2) reacts with fluorine atoms which are
produced according to (3) and form CF4 gas, whereby the carbon is bound and
carbonisation is avoided.

4F + C ➞ CF 4 (4)

CF 4, which is an electronegative gas, is therefore formed when the arc affects the
teflon nozzle and SF 6 gas.

Chemical reactions between gas formation and possible moisture residue on surfaces
in breaking units.

SF 4 + 2H 2O ➞ SOF2 + 2HF (5)


SOF 2 + H2O ➞ SO 2 + 2HF (6)

Reactions between hydrofluoric acid and porcelain

SiO 2 + 4HF ➞ SiF4 + 2H2O (7)

Reactions at copper-tungsten contacts

heat
SF6 + Cu ➞ SF 4 + CuF2 (8)

heat
3SF6 + W ➞ 3SF4 + WF6 (9)

Degraded gases which can appear in SF6 breakers after a number of years’ service
are SOF2, CF4, SiF 4 and SO2.

The powder which remains in the breaker poles consists of formation of fluorides.

In the gas analysis of mixed gas circuit-breakers with SF6/N2 and SF6/CF4 no other
degraded products than the above mentioned have been identified.

4. Criteria for choice of mixed Gas


By mixed gas is always understood a mixture of SF6 and nitrogen gas or SF6 and CF4.
Nitrogen gas and CF4 are both easily available at gas suppliers. CF4 is comparatively
expensive but it is a natural choice since this gas is formed already when the arc
erodes teflon nozzles in SF6 circuit-breakers. See formulae (2) and (4).

Criteria for choice of gas :

SF6 gas is chosen for ambient temperatures down to -300C or -400C

Gas Lowest Filling pressure at +200C Breaking data


ambient absolute pressure
temperature

SF 6 -300C 0.7 MPa Depends on type of circuit-


SF 6 -400C 0.5 MPa breaker
1HYB800001-33 Rev. A
Page 4

Mixed gas is chosen for ambient temperatures down to -550C

Gas Lowest Filling pressure at +200C Breaking data in


mixture ambient absolute pressure comparison
temperature with SF6 filling

SF6/N2 -550C 0.36 MPa SF6+0.34 MPa N2=0.7 MPa Reduction one
breaking current step

SF 6/CF4 -550C 0.36 MPa SF6+0.34 MPa CF4=0.7 MPa Retains breaking capacity

This table is only for information. It is always the relevant product information for
respective circuit breakers which is valid.

5. Filling mixed Gas


Mixed gas is always filled in such a sequence that SF6 is filled first and then CF4 or
nitrogen gas is filled up to rated pressure at +20 0C according to the rating plate.

By filling SF 6 first a satisfactory gas mixture, without layers of gas, is always


obtained. Otherwise, the mixing process takes a long time since it is based on
diffusion and convection. At gas loss, for example due to leakage, refill with correct
mixing proportions and always with SF 6 gas first.

6. Measuring Mixing Proportions


Mixing proportions for mixed filling can be measured by DILO “SF6 Percentage
Measuring Device 3-027”.

The instrument measures the sound velocity of the gas mixture and it is calibrated for
SF6/N2 gas. The instrument shows directly on the display the volume of the SF6 part.

If the instrument is used to measure SF6/CF4 gas mixture, the result shown on the
display must be corrected according to figure C. (Example: If 51% is read on the
instrument, the SF 6 part is 0% and the CF4 part 100%)

100
SF6 (%)
In 90
SF6/CF4
80

70

60

50

40

30

20

10 DILO

0
50 60 70 80 90 100 DISPLAY
Figure C.
SF 6 part in SF6/CF4 gas as a function of
the shown result on the display of DILO 3-027.
1HYB800001-33 Rev. A
Page 5

7. Technical Data for SF 6, CF4 and N2 Gases


General SF 6 CF4 N2
information: Max. bottle pressure
at 200C 2.3 MPa 13.7 MPa 20 MPa

Valve thread (local G5/8A-RH CGA580 G5/8A-RH


& national deviations
can occur)

Material recom- No re- Avoid None


mendation strictions zinc
magnesium

Hygienic limit: 1000 ppm - -

Characteristics: No colour No colour No colour


or smell or smell or smell

Health risks : Suffocating Suffocating Suffocating

Transport: ADR ADR ADR


Class 2.5(a) Class 2.1(a) Class 2.1(a)

Storage: - Group 1A Group 1A

Physical data: Molecular weight 146.05 88.01 28.01

Boiling point
at 1.013 bar 0C -63.8 -127.94 -195.8

Density
(1.013 bar 150C)kg/m3 6.25 3.74 1.185

Vapour pressure
at 00C MPa 1.26 - -

Vapour pressure
at 200C MPa 2.3 - -

Combustible Non-combust. Non-combust. Non-combust.


range in air

Specific volume m 3/kg


(1.013 bar, 150C) 0.160 0.268 0.844

Critical temperature 0C 46

Critical pressure MPa 3.7


1HYB800001-33 Rev. A
Page 6

8. Safety Regulations
8.1 Safety Regulations for SF 6
“SAFETY REGULATIONS FOR SULPHURHEXAFLUORIDE”

HEALTH RISK

Sulphurhexafluoride is considered to be an inert gas.

INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.

SPECIAL CHARACTERISTICS AND RISKS

At high temperatures degraded products, which cause irritation, can be formed.

PREVENTIVE MEASURES

Good ventilation.
Safeguard gas bottles with chains.

PERSONAL PROTECTIVE EQUIPMENT

Inhalation apparatus for use at suffocating gas content.

FIRST AID

Inhalation: fresh air, rest

SPILLAGE AND DEGASSING

Airing

MEASURES AT FIRE

Gas containers near the fire must be removed immediately or cooled with
water.

8.2 Safety Regulations for CF 4 gas


“SAFETY REGULATIONS FOR TETRAFLUORMETHANE”

HEALTH RISK

Tetrafluormethane is considered to be an inert gas.

INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.

SPECIAL CHARACTERISTICS AND RISKS

At high temperatures degraded products, which cause irritation, can be formed.

PREVENTIVE MEASURES

Good ventilation.
Safeguard standing gas bottles with chains.
1HYB800001-33 Rev. A
Page 7

PERSONAL PROTECTIVE EQUIPMENT

Inhalation apparatus for use at suffocating gas content.

FIRST AID

Inhalation: fresh air, rest.

SPILLAGE AND DEGASSING

Airing

MEASURES AT FIRE

Gas containers near the fire shall be removed immediately or cooled with
water.

8.3 Safety Regulations for SF6 and CF4 gases which are exposed to arc
HEALTH RISK

Air humidity together with degraded products can cause irritation of skin,
eyes, and mucous membranes.

INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.

SPECIAL CHARACTERISTICS AND RISKS

Since the gas has been exposed to high temperatures degraded products,
which cause irritation, have been formed.

PREVENTIVE MEASURES

Good ventilation.
Gas from circuit-breakers can be recovered in gas treatment equipment and reused.

PERSONAL PROTECTIVE EQUIPMENT

Fresh air mask or mask with filter against fine dust and gases with acid content.
Plastic or rubber gloves.
Overalls with long sleeves.
Vacuum cleaner with filter for fine dust.

FIRST AID

Inhalation: fresh air, rest.

Skin and eyes: rinsing with water.


1HYB800001-33 Rev. A
Page 8

SPILLAGE AND DEGASSING

Airing
Dust and filters shall be stored sealed and handled as chemical refuse according to
local regulations.

MEASURES AT FIRE

Gas containers near the fire must be removed immediately or cooled with
water.

9. Environmental Effect
SF6 and CF4 gases can leak out into the surrounding environment due to leakage in
the circuit-breaker.

CF 4 and SF6 are very stable gases and make no detectable contribution to ozone
destruction and photochemical smog, and they have negligible influence on the green
house effect. The latter applies especially when used in circuit-breakers where, from
the global point of view, gas volumes are small.
1HYB800001-35 Rev. A
Page 1

Safety Provision and Assembly Instructions for Circuit-


Breakers with Operating Device.
Read carefully the entire Assembly Instruction before starting assembly work.

WARNING TEXTS

Warning texts are stated in 5 different degrees of urgency which should be carefully
observed. These are described below :

DANGER indicates an immediate risk situation that can lead to death or serious
personal injury if not avoided.

DANGER

Warning indicates a risk situation that can lead to death or serious personal injury if
not avoided.
Warning

Caution indicates a risk situation that can lead to small or moderate damage.

Caution

Note Note is used when there is danger that can lead to equipment damage only.

Important Important indicates an operation or a suggestion for handling.


1HYB800001-35 Rev. A
Page 2

1. Safety Regulations
When working on high-voltage circuit-breakers the below-mentioned risks must be
taken into consideration and corresponding safety measures taken.

RISK MEASURE

1. Work next to high-voltage Warning plate placed inside the door to the
operating device

Disconnect and earth near the workplace. If work


must be carried out near energized parts of the
plant, it has to follow local safety regulations of the
organisation responsible for the circuit-breaker.

2. Work on ladders and platforms The work shall follow the directions of the Authority
for occupational safety and health. Avoid work in
severe weather conditions which entails a great
deal of climbing for short periods.

3. Work with low-voltage. Do not connect control or heating voltage until all
Both D. C. and A. C. voltage may have been connection work is completed.
connected on the operating device.

4. Squeezing risk in operating device and Warning plate is placed on the supporting frame.
link system.
No work must be carried out unless the closing and
The spring operated device has energy opening springs are uncharged and the circuit-
stored in the closing spring. The opening breaker in position OFF “O” disconnect voltage to
spring, which is on the mechanism housing of the motor.
pole C1, or on every pole for one-pole
- The operating device must not be operated
operation, has energy stored. The device can
unless it is connected to the circuit-breaker
be activated by heavy vibrations or
and the electric cables are connected. The
unintentional slight touch on mechanical latch
circuit-breaker shall be filled with SF 6 gas to
parts.
a pressure of 0.7 MPa. The closing springs
should for safety reasons be uncharged
during transport and when the circuit-breaker
is off duty.

5. Work on pressurized porcelain insulators. Work close to the insulators of the circuit-breaker,
Normally, the work pressure is up to 0.7 MPa. which entails risk to damage the porcelain, must
Damage in the porcelain can cause the not be carried out until the gas pressure has been
porcelain to break, lowered to 0.125 MPa absolute pressure.
1HYB800001-35 Rev. A
Page 3

2. Unpacking
Place the case hoizontally on a flat surface before opening the cover.

Check that all parts are included in the delivery. Check-off on the accompanying
packing list.

Check that no parts have been damaged during transport, especially the porcelain
insulators.

Report any faults immediately to the ABB Representative.


1HYB800001-36 Rev. A

Disposal and Recycling

Information

The information in this document is subject to alteration without prior notice and should not be regarded as an
undertaking from ABB Limited. ABB Limited takes no responsibility for errors that can occur in the documen-
tation.

ABB Limited is not responsible for damage incurred due to the misuse of this document.

The document, or parts thereof, may not be reproduced or copied without prior permission from ABB Limited.
It may not either be imparted to third pary or otherwise be used without authorisation. Infringement hereof will
be subject to action in accordance with applicable laws.

© ABB Limited
1HYB800001-36 Rev. A

Contents

1. Disposal and recycling


1.1 General
1.2 Taking care of spent equipment
1.3 The circuit-breaker’s component parts
1.4 SF6-gas
1.5 Porcelain
1.6 Electronics
1.7 Metals
1.8 Plastics
1.9 Oils and greases
1.10 Rubber
1.11 Other materials
1HYB800001-36 Rev. A
Page 1

1. Disposal and recycling


1.1 General

ABB Limited attempts to minimize environmental impact during the entire product’s
service life. Environment aspects are held in focus during technical and product
development. We always try to consider the eco-cycle while the material’s impact on
the environment and possibilities of recycling are observed. Manufacturing processes
are selected that are as gentle as possible on the environment.

1.2 Taking care of spent equipment


Spent products should be taken out of service in an environmentally correct manner
according to the following instructions.

When discarding used equipment a great deal of material and the energy content of
the material can, after sorting and cleaning, be recycled. The degree of material that
can be recycled varies depending on the technical resources and experience
available in respective countries.

Non-recyclable components shall be left at an approved recycling centre for


destruction or disposal.

1.3 The circuit-breaker’s component parts


A circuit-breaker contains approximately 30 weight % metal, primarily iron, steel and
aluminium. Rubber and different plastics make up approximately 0.5% each and
chemicals and gas less than 0.5%. The greatest weight share in a circuit-breaker,
virtually 70%, is made up of porcelain.

1.4 SF 6-gas
The SF6-gas must be emptied before discarding a circuit-breaker. Care shall be
exercised in accordance with applicable regulations with all handling of SF 6-gas, to
prevent gas leakage. The gas can be taken care of in different ways depending on
the circumstances :

● Regenerated on site, and reused in other equipment


● Sent to a gas supplier for regeneration
● Sent for destruction at a special waste disposal centre

In those cases where the circuit-breaker is filled with mixed gas, the SF6-gas is
separated from the mixture for continued handling as set out above. Alternatively, the
gas mixture can be sent for destruction without being separated.

ABB Limited will willingly take care of the gas when the circuit-breaker is to be
discarded.
1HYB800001-36 Rev. A
Page 2

1.5 Porcelain

Porcelain can, after cleaning, be left for disposal or used for other purposes, for
example, as a filling material.

1.6 Electronics

Leave electronic equipment at an approved recycling company or sort out its


component parts and take care of them accordingly.

1.7 Metals

Sort metals according to type and surface finish and leave at an approved recycling
company. After the removal of any paint or other surface treatment, the metal can
generally be melted down and used in new products. Many iron, steel and aluminium
parts are large and easy to identify, for example, the frame and mechanism housing.

ABB Limited aims for a reduction in the use of noble metal, or with discharge
environmentally hazardous metals. Recycling of these is extremely important.

Noble metals such as copper and silver are expensive and only occur is small
quantities in the earth’s crust. Copper is primarily used in the current paths, puffer,
contactors and cables. Silver plating of contactors can occur. Some metals can cause
damage if discharged. This applies, among others, to copper, but also to zinc and
nickel which are used sparingly in the form of surface treatment.

1.8 Plastics

Separate different types of plastic and leave at an approval recycling centre or


recycling company. The energy content in thermoplastics and thermosetting plastics
can frequently be recovered through combustion in purpose built installations.
Generally, thermoplastics can be melted down and used again without degrading
quality too much. Composites can be fractionised and used as filling agent in other
materials or be left for disposal.

Composites found in small quantities in isolators, pipes and cable glands consist of
thermosetting plastic. Thermoplastics can be found in components such as guide
rings, belts bushings and support rings. Thermoplastic in ferrules, nozzles, pipes and
collars contains fluorine and is not suitable for recycling, however, it can be disposed
of without the risk of leaking hazardous substances.
1HYB800001-36 Rev. A
Page 3

1.9 Oils and greases

Empty oils, grease and the like before discarding and leave at an approved recycling
centre or at a recycling company. Oil waste can be separated into oil, water and
different contamination through the use of gravimetric forces. In many cases the oil
can be reused. Alternatively, the oil’s energy content can be recovered through
combustion in purpose built installations.

Oil can be found in dashpots and grease is used as a lubricant.

1.10 Rubber

Rubber can be left at an approved recycling centre either for disposal or reused for
different purpose.

Rubber can be found in seals.

1.11 Other materials

Sort and leave other materials at an approved recycling centre.


1HYB800001-54 Rev. A

SF6 CIRCUIT-BREAKER type EDF SKS 1-1


Rated voltage 52-72.5 kV
With operating mechanism type FSA 1(F)

INSTRUCTIONS FOR ERECTION,


OPERATION AND MAINTENANCE

CONTENTS

1. GENERAL
2. DESIGN
3 . FUNCTION
4. ERECTION
5. COMMISSIONING
6. TROUBLESHOOTING
7. MAINTENANCE
8. SPARE PARTS AND MATERIAL FOR OVERHAUL
11 APPENDIX
1HYB800001-54 Rev. A

Contents Page 7.7 Tools, Jigs, Fixtures & Accessories 26


7.8 Maintenance Procedures 26
1. GENERAL 1 7.9 Preparation for overhaul 26
7.9.1 Taking Circuit Breaker out of Service 26
1.1 Validity 1
7.10.1 Dismantling of SF6 gas lines 26
1.2 Type designation 1
7.10.2 Removal of breaker poles & mechanism
1.3 Technical data 1
housing 26
1.4 Masses 1
7.11.1 Disassembly of breaker pole B1 27
1.5 Storage 1
7.11.2 Disassembly of fixed contact 28
7.11.3 Disassembly of moving contact 28
2. DESIGN 2
7.11.4 Cleaning 28
2.1 Breaker pole 2 7.12 Overhaul of component groups 28
2.2 SF6 gas system 2 7.12.1 Overhaul of fixed contact 28
7.12.2 Overhaul of moving contact 29
3. FUNCTION 2 7.12.3 Overhaul of link gear 30
3.1 Control and monitoring 2 7.13 Assembly of breaker pole 30
3.2 Switching operations 3 7.14 Erection of breaker poles 32
3.2.1 Starting conditions 3 7.15 Overhaul of spring operating mechanism 33
3.2.2 CLOSING operation 3
8. SPARE PARTS AND MATERIAL
3.2.3 OPENING operation 3
FOR OVERHAUL 33
4. ERECTION 3 8.1 General 33
4.1 General 3 8.1.1 Important directions 33
4.1.1 Preparation for erection 3 8.1.2 Ordering spare parts and material
4.2 Erection procedure 4 for overhaul 33
4.2.1 Fitting motor-operated 8.2 Spare part lists for overhaul 33
spring-closing mechanism 4 8.2.1 Set of contacts for one breaking unit 33
4.2.2 Fitting the connecting rod 4 8.2.2 Set of gaskets, springs, fasteners for one
4.2.3 Fitting density monitor and cables 4 breaker pole 33
4.2.4 High-voltage connections 4 8.2.3 Complete set of gaskets for gas
monitoring system 34
5. COMMISSIONING 5 8.2.4 Set of gaskets for one link gear 34
8.2.5 Spare parts for FSA-1 34
5.1 Starting conditions 5 8.2.6 Overhaul tools for EDP SK 35
5.2.1 Filling SF6 gas to rated pressure 5 8.2.7 Gas filling equipment 35
5.2.2 Filling “mixed gas” to rated pressure 6 8.2.8 Safety disc unit 36
5.3 Function test 6
5.3.1 Trial switching operations 7 11. APPENDIX 37
5.3.2 Anti-pumping device 7
11.1 Figure sheets 37
5.3.3 Control of heater 8
5.4 Concluding work 8
5.5 Checklist for Assembly and Commissioning 9

6 TROUBLESHOOTING 13
6.1 SF 6 gas system 13
6.2 Control circuits 13
7. MAINTENANCE (OVERHAUL) 14
7.1 Maintenance Summary 15
7.2 Maintenance category A 16
7.3 Maintenance category B 17
7.4 Maintenance category C 19
7.5 Maintenance category D 24
7.6 Table of parts to be serviced 25
1HYB800001-54 Rev. A
Page 1

1 GENERAL
1.1 Validity
This document covers high-voltage circuit-breakers, type EDF SKS.

Type designation EDF SKS means that the circuit-breaker has been adapted to
synchronous coupling. The adaptation is carried out in the mechanical arm and link
system in the circuit-breaker mechanism housing, so that there is a time difference in
contact closing or contact opening.

When connecting capacitor stacks, for example, the following time differences can occur.

Earthed capacitor stack

Pole A1 Pole B1 Pole C1


+6.66 ms +3.33 ms 0 for 50 Hz
(after pole C1) (after pole C1)

Unearthed capacitor stack

Pole A1 Pole B1 Pole C1


+5 ms 0 0 at 50 Hz
(after poles Bl and C1)

1.2 Type designation E D F SK S 1 - 1


SF 6 gas insulation

Generation

Outdoor design

Type of arcing chamber

Synchronous coupling

Circuit-breaker design
Insulation BIL Rated voltage
1 ~ 325 kV ~ 52/72.5 kV
Number of breaker chambers

1.3 Technical data


Technical data can be seen in order-related documentation and rating plate (fig.1/1). The
diagrams in this instruction are mainly intended to explain the functional principles.

1.4 Masses
Information about masses for a three-pole circuit-breaker can be found in the order
documentation and delivery documents. For internal transport, see fig. 1/2.

1.5 Storage
The circuit-breakers intended for outdoor operation are usually dismantled in suitable
units for delivery. Before erection, these units should as far as possible be stored
indoors or under roof. If the units are to be stored outdoors, they shall be blocked up so
that they do not stand in water. If the units are to be stored outdoors for a long time,
they should be covered with tarpaulins and have their heating elements switched on.
1HYB800001-54 Rev. A
Page 2

2 DESIGN (fig. 2/1)


- Circuit-breaker type EDF SKS 1-1 is a three-pole SF6 circuit-breaker.

The circuit-breaker consists mainly of:

- three breaker poles 10171 with rating plates A1, B1 and C1


- support frame 10172
- control cubicle with spring operating mechanism and connecting rod 10173
- density monitor 10112
- breaker support 10174

2.1 Breaker pole (fig. 3/la, b:1,2,3)


The breaker pole consists mainly of:

- upper terminal flange 10099 *)


- breaker chamber insulator 10106
- fixed contact compl. 10030
- moving contact compl. 10013
- lower terminal flange 10108
- post insulator
- link gear 10185

*) On this flange there is a cover which can easily be exchanged by a safety disc
unit, if the customer so wishes.

The poles are filled with SF6 gas (transport pressure) and connected to a header
block via tubes (fig. 4/la,c).

2.2 SF 6 gas system (fig. 4/1a,c)


The gas system consists of:

- an SF6 gas density monitor 10112 with header block 10118


- check valve 00112 (fig. 7/5)
- SF6 connection line L10177/a, L10177/b and L10178

3 FUNCTION
3.1 Control and monitoring (Fig. 3/2)

The electrical principle drawing shows how the switching commands enter the control
circuit of the circuit-breaker, the monitoring units which are built in to sense any
interference which might occur, and the signals which are then triggered.

The control circuit itself can be seen in the order-related circuit diagram.

Monitoring unit:

- Gas density
The density monitor 10112 (temperature compensated pressure monitor)
monitors the insulation gas pressure in the breaker poles and sends, via its
auxiliary contactor, the signal “filling of SF6 gas” if gas losses have occurred. If
the gas pressure decreases to a value below that shown in the blocking
pressure curve, fig. 5/1, the CLOSE and OPEN operations are blocked and
simultaneously an alarm signal is given.
1HYB800001-54 Rev. A
Page 3

3.2 Switching operations (fig. 3/1a, b)


3.2.1 Starting Conditions

- SF6 gas is filled to the rated pressure


- The operating mechanism is in breaking position b2 (fig. 2/1), i.e. closing spring
charged and in OPEN position.

3.2.2 CLOSING operation (fig.3/1b)

- The switching command is issued via a control element “CLOSE”. The


operating mechanism is then tripped and operates the moving contacts upwards
via the mechanical transmission. Thereby first arc contact “g-h” is closed and,
thereafter, the rated current contact “k-l”.

3.2.3 OPENING operation (fig. 3/1a)

- The switching command is issued via a control element “OPEN”. The


operating mechanism is then tripped and operates the moving contacts
downwards via the mechanical transmission. Thereby, first the operating current
contact “k-l” is opened and, thereafter, the arc contact “g-h”. During this
movement the piston compresses the gas in the cylinder. The arc which rises
between the contacts increases the compression pressure. In the zero current
area a gas flow occurs, which blows intensively on the arc and extinguishes it.

4 ERECTION
4.1 General
- All adjustments have been carried out in the works.

All moving parts which shall be assembled together have already been adjusted
and fixed in correct position in the works.

- Transport packing for breaker poles should be suitably kept to facilitate transport,
if necessary, at later overhaul.

- Breaker poles are filled with insulation gas Pabs. = 150 kPa (~ 1.5 bar) in order to
prevent any moisture absorption.

4.1.1 Preparation for erection


The following shall be prepared and procured before erection:
- Crane with a lifting capacity of approx. 850 kg and a hoist height of at least 4 m
above floor level.
- Lifting ropes
- Dimension drawing, erection drawings and circuit diagram.
- Circuit-breaker material according to erection drawings.
- Torque wrench 6...200 Nm with socket 24 mm (connection 3/8").
- Open-end/ring type wrenches for M6-16 and 1/2" UNC as well as open-end wrench
for 36 mm.
- Normal thermometer for ambient temperature.
- Gas filling equipment and an SF6 gas cylinder
- SF6 leak detection instrument
1HYB800001-54 Rev. A
Page 4

4.2 Erection procedure


- Lift the completely assembled circuit-breaker by crane according to fig. 4/2.

- Check the SF 6 gas pressure by pressing the disc of the check valve inwards
with a ø 5 pin. A distinct blow-off sound from the pole shall be heard. If there is no
blow-off sound, the pole has a leak which must be repaired.

Place frame support 10174 on the foundation. The top supporting surfaces, where the pole
beam is mounted, must be at the same level (horizontally). Screw the frame support to the
foundation. Observe tightening torque MD, fig. 2/1. The exact location is shown on the
installation layout. Observe the location of the holes for the earthing clamp (fig. 2/1).

Mount the frame 10172, with assembled poles 10171, on the support 10174 with
screw, nut and washer, 49069, 49622 and 89027. Observe the tightening torque
MD=190 Nm, fig. 4/1a:1, 2.

4.2.1 Fitting motor-operated spring closing mechanism (fig. 4/1a:1,2)

Place the mechanism on a wooden structure in correct position for mounting between
the frames.

- Lift up the operating mechanism by the four upper eyes, place the bolts for the
operating mechanism in the holes intended for them and fasten with enclosed
fasteners “h” (note the MD). Make sure the middle pole is not damaged by the sling.

CAUTION

During lifting the upper joint head of the connecting rod must be fitted into the fork on
the actuating lever 10154.

4.2.2 Fitting the connecting rod

- Starting condition: Indication of circuit-breaker position and spring charging shows


positions “b1” and “uncharged”, respectively, (fig. 2/1).

- Couple the operating mechanism and circuit-breaker to each other in OPEN


position, i.e. turn the actuating lever on the circuit-breaker towards the operating
mechanism until the actuating lever, 10154, stops and the hole in the connecting
rod, f, correspond (fig. 4/1b).

- However, if holes do not correspond, the operating rod length must be adjusted.

- This is done by releasing the lower fasteners “g” (fig. 4/1a) and by lowering the cubicle.

- Release locknuts “h” and “k” of the operating rod (fig. 4/1b) , turn operating rod to
adjust length. Tighten locknuts by holding the operating rod (Observe MD)

4.2.3 Fitting density monitor and cables

Connect the density monitor 10112, density monitor cables and pressure gauge, if
any, according to fig. 2/1, 4/1:1,2.

4.2.4 High-voltage connections (fig. 4/1:1,2)

The assembly parts for high-voltage connections consist of screw M12 (8.8) and at
least 1 washer 13/28x3 mm, 1 locking washer 13.5/28x1.6 mm on each side of the
screw. (Observe the tightening torque MD)
1HYB800001-54 Rev. A
Page 5

5. Commissioning
All data which are checked or measured are to be entered in a commissioning record
and preserved for comparisons.

The SF 6 gas pressure can be seen on the circuit breaker nameplate.

5.1 Starting conditions


The erected circuit breaker is isolated from the high-voltage system and earthed accord-
ing to regulations. The control current circuits are connected to the low-voltage system.

5.2.1 Filling of SF 6 gas to nominal filling pressure (Fig. 5/1)

As the circuit-breaker poles are delivered vacuum processed and filled with SF6 gas
at a transport pressure of 0.150 MPa abs (200C), during commissioning only one
filling of SF6 gas is required, to top up pressure up to the filling pressure given on the
rating plate.

It is appropriate to carry out pressuring directly from an SF 6 gas bottle. In order to


avoid risks at the first filling, due to possible transport damages to the porcelain, the
gas bottle with filling equipment shall be placed as far from the circuit-breaker as
possible, and preferably behind some shield. Pole columns are connected to the
header block by pipes. Connect the hose from the gas filling equipment to the SF 6
gas filling valve on the header block L10118 (Fig. 4/1c).

- SF6 gas filling (Fig. 4/1d)

● Place gas cylinder (1) in a protected area.


● Check the filling pressure and any gas mixture (at ambient temperature lower
than -300C) on the circuit breaker’s rating plate.
● Fit the regulator (3) on the gas cylinder using appropriate coupling (2) supplied
with gas filling device. Use the pressure gauge (9) for filing gas in circuit breaker.
● Lubricate the sealing rings supplied with density monitor (7) with grease “G”.
● Fit the density monitor on the gas valve (8) on the breaker.
● Connect coupling (4) supplied loose with gas filling bag to the non-return valve
on the hose of gas filling device.
● Connect above assembly to the circuit breaker’s gas valve (5).
● Open regulator to fill gas in circuit breaker to rated pressure as per fig. 5/1.
● Allow the pressure to stabilise in the circuit breaker for some time. Check the
pressure and adjust if necessary.
● Dismantle the hose coupling assembly from the gas valve on the circuit breaker.
● Close the valve on the gas cylinder.
● Disconnect regulator with hose from gas cylinder. Breaker is now ready for
functional test as per section 5.3.

In the filling process the dependence of the nominal pressure on temperature (Fig. 5/
1) must definitely be taken into account. After a temperature equalization period of
approx. 1 hour, check the pressure and correct if necessary by adding or releasing
gas. Check all sealing joints on the breaker poles and the gas supply system for
leaks with a leak detector. Repair any leaks found according to chapter 6.
1HYB800001-54 Rev. A
Page 6

5.2.2 Filling “mixed gas” to rated pressure

When the circuit-breaker is erected in a climate with temperatures below -30°C, fill
“mixed gas” instead of pure SF6.

In order to avoid condensation at temperatures below -30°C, mix the SF6 gas
with CF4 (carbon tetrafluoride) or N2 (nitrogen gas). The CF 4 gas has good breaking
capabilities, like SF6, while N2 gas often reduces the breaking capacity.

Choice of gas mixture:

Gas mixture Breaking data Network frequency


Rated breaking
current

SF6/N2 25 kA 50 Hz
20 kA 60 Hz

SF6/CF4 25 kA 50 Hz
25 kA 60 Hz

The rating plate states the total filling pressure for mixed gas. The breaker poles are
delivered vacuum processed or filled to pressure 0.15 MPa abs. (20°C). When
commissioning, first fill the SF 6 gas proportion, 0.36 MPa abs. at 20°C, and there-
after N2 or CF4 proportions up to the total filling pressure according to the
rating plate.

Normally, gas filling is:

with SF6/N2 at 20°C


0.36 MPa SF6 + 0.34 MPa N2 = 0.7 MPa abs.

with SF6/CF4
0.36 MPa SF6 + 0.34 MPa CF4 = 0.7 MPa abs.

When filling gas after possible leakage, refill with SF6 and N2 or CF4, respectively,
in the proportions stated above. For example, leakage to blocking level 0.6 MPa
abs. entails refilling with SF6/N2.

SF6 gas 0.36 • 0.1 ~ 0.051 Mpa SF6 at 20°C


0.7
N2 gas 0. 34 • 0 .1~ 0 . 04 9 Mpa N2 at 20° C
0.7
At gas filling observe the influence of temperature on pressure. Fig. 5/1, curve 4, for
SF6 filling, and continued filling up to curve 1 for N2 or CF4 gases.

5.3 Function test


Before function testing, check with order-related circuit diagram. Check also the
connections. Thereafter, trial switching can be run from a sheltered place.

This trial switching shall take place only if:

- the circuit-breaker is disconnected from the high-voltage network and earthed


according to regulations

- SF6 gas or mixed gas pressure is at rated pressure

- spring charging indicator on the spring operated mechanism is in position “b2” (fig.
2/1) “charged”
1HYB800001-54 Rev. A
Page 7

5.3.1 Trial switching operation (fig. 5/2a,b)

Measure the function times. Fig. 5/2a shows the principle diagram for such a
measurement. Thereby, each breaker pole has its own measuring circuit. The time
diagram in fig. 5/2b is solely intended as an explanation of the time expression used.

- CLOSING operation (C) (fig. 5/2b) Closing time “t1. ≤ 60 ms is the time from
switching command issue to contact closing in the arcing chamber. This shall be
measured on each breaker pole.
The time differences between the poles are:
For earthed capacitor stack
Pole A1 Pole B1 Pole C1
+6.66 ms +2/-0.5 ms 3.33 ms ±1 ms 0
(after pole C1) (after pole C1).

For unearthed capacitor stack

Pole A1 Pole B1 Pole C1


+5 ms +2/-0.5 ms 0 ±1 ms 0
after pole C1 after pole C1
or depending on the application.
- OPENING operation (O) (fig. 5/2b)
Opening time “t2”≤ 35 ms is the time from switching command issue to contact
opening in the arcing chamber. This shall be measured on each breaker pole.
The time differences between the poles are:
For earthed capacitor stack:
Pole A1 Pole B1 Pole C1
+6.66 ms +2/-0.5 ms 3.33 ms ±1 ms 0
(after pole C1) (after pole C1)
For unearthed capacitor stack:
Pole Al Pole B1 Pole C1
+5 ms +2/-0.5 ms 0 ms ±1 ms 0
after pole C1 after pole C1
or depending on application.
- CLOSE-OPEN switching (C-0) (fig. 5/2b)
Close-Open time “t3” ≤ 40 ms is the time from contact closing to contact
opening in the arcing chamber at a switching cycle CLOSE-OPEN.
For measuring, short-circuit terminals “K1” and “K2” on the close-open switch
“M3” (fig. 5/2a).
- Rapid reclosing (O-C-O)
Rapid reclosing can only be controlled together with the monitoring equipment
for the plant.
5.3.2 Anti-pumping device (fig. 5/2a)
- CLOSE command is issued by connecting control voltage to terminal 2. The
voltage prevails.
- OPEN command is issued by connecting control voltage to terminal 6.
The circuit-breaker is in position OPEN and despite the prevailing CLOSE command
remains in position OPEN.
1HYB800001-54 Rev. A
Page 8

5.3.3 Control of heater

- Measure the resistance or apply voltage and measure the current.

- When the thermostat controlled additional heater is installed, check the thermostat
setting.

5.4 Concluding work


- Remove all test and measuring equipment.

- Connect the circuit-breaker to the high-voltage network.

- Check that the safety regulations are followed. Put the circuit-breaker into service.
1HYB800001-54 Rev. A
Page 9

5.5 Checklist for assembly and commissioning


1 DATE :
2 PLATE OF INSTALLATION :
SERIAL NUMBER
3 NAME PLATE DETAILS :
Circuit breaker type : e.g. EDF SKS 1-1
Rated voltage : kV Normal Current A
Sr No : Gas Pressure SF6 / 20 deg.C. (abs): bar
Lightning Impulse withstand voltage : kV
Short circuit breaking current : kA
Short time withstand current 3s kA
Line charging breaking current : A
Closing & Opening supply voltage : VDC
Operating sequence : O - 0.3 s - CO - 3 min - CO
First pole to clear factor : 1.5

STORAGE YES NO
1 a Complete material is available as per packing list ?
If NO mention the shortages :
b Instruction manual available ?
c G.A. and erection drawing available ?
d Schematic drawing available ?
2 a Operating drives box stored indoor ?
b Accessories box stored indoor ?
c Was the outdoor equipment stored above HFL (Highest flood level ) ?
d Any equipment damaged during re-transportation / unloading at site ?

ERECTION YES NO
1 Is foundation and location of equipment as per G.A. drawing ?
2 STRUCTURE ERECTION
a Is length of the foundation bolts (projecting outside) sufficient to put checknuts ?
b Is there levelling nut available below structure ?
c Is the top side of the structure base plate as per G.A.. Drawing ?
d Is direction of the structure as per G.A. drawing ?
e Is the structure levelled in x , y and z axis as per G.A. drawing ?
X = Pole to pole distance (Measuring tape)
Y = Structure Height (Water tube level)
Z = Alignment of all the structures in one line (Line thread)
f Tightness of the nuts and checknuts done ?
g Are the foundation bolts filled with mortar ?
h Are the serial nos. of all the equipment matching with the serial numbers
mentioned in the packing list ?
1HYB800001-54 Rev. A
Page 10

3 BREAKER POLES ERECTION : YES NO


a Is there any chipping on the sheds of insulators ?
If YES what is the size of chipping ?
Can erection work proceed further ?
DO NOT PROCEED FURTHER , IF CHIPPING IS UNACCEPTABLE
b Is 0.5 bar positive pressure verified in the breaker poles?
Verification to be done by pressing the gas valve after opening the cover.
c Any damage observed on gas pipe while mounting the breaker poles
on the structure ?
d Any washers left in between the breaker pole channels and the structure ?
DO NOT PROCEED FURTHER BEFORE REMOVING THE WASHERS
e Application of Torque on all the mounting bolts ?
If YES , mention the values :
1. Foundation bolts Nm
2. Structure hardware Nm
3. Pole mounting bolts Nm
4 FIXING OF OPERATING MECHANISM
a Is there any ingress of water found inside the mechanism?
If YES : DO NOT PROCEED FURTHER BEFORE OVERHAULING OF THE MECHANISM.
b Is following procedure adopted for fixing the mechanism?
● Ensure that breaker poles are in fully OPEN position.

● Lift the mechanism and fix the 04 mounting bolts with the pole beam.

● Match the Eye-bolt of the mechanism connecting rod with the lever on pole.

● Apply thin layer of grease on the pin before inserting in the eye bolt.

● After insertion of pin, tighten the locking screw with locking washers.

6 GAS FILLING AND LEAKAGE TEST :


Prerequisite for SF6 gas filling :
● Thermometer

● Temperature v/s pressure chart

● SF6 gas cylinder

● Gas filling kit

● Suitable right / left adaptor (Gas cylinder)

● Spanners

● Cloth

● Cleaning agent

a Presence of positive pressure checked in breaker poles.


If NO , Fill the pressure in that particular pole upto 2.0 bar absolute and sniff
all the pole including gas pipe with the leak detector and find the leakage.
If no leakage is found , continue gas filling and if any leakage is found ,
first ATTEND the leakage point before proceeding further.
b Is the gas monitoring system fixed as per G.A. drawing ?
c CALIBRATION OF DENSITY MONITOR / SWITCH.
AMBIENT TEMPERATURE AT SITE DURING CALIBRATION OF
DENSITY SWITCH & SF6 GAS FILLING IN POLES> DEG.C.
IS THERMOMETER AVAILABLE?
IS GAS FILLING KIT AVAILABLE?
BLOCKING DEBLOCKING

CONTACT / SETTING VALUES IN ABS.BAR


1HYB800001-54 Rev. A
Page 11

REFILL ALARM
OP. BLOCK –I
OP.BLOCK – II
TIME AT WHICH CALIBRATION DONE : AM / PM
e SF6 GAS PRESSURE FILLED AFTER CALIBRATION OF DENSITY SWITCH
● SF6 gas filled in the breaker : Bar
● Temperature at which gas filled . degree C
● Time at which gas filled AM / PM
f SF6 GAS LEAKAGE TEST : YES NO
● Is Leak detector available?
● If NO , do not proceed further till leak detector is arranged.

● Is the complete SF6 gas system in the breaker (which includes pole,

gas pipes & density switch / monitor ) free from any SF6 gas leakage ?
● If NO , describe leakage found from which joints :

7 COMMISSIONING :
a Connection of density switch cables :
●Density switch cable
closing circuit terminals : &__
trip 1 circuit terminals : &__
trip 2 circuit terminals : &__
b Control coil resistance :
CLOSE COIL : W
TRIP COIL - 1 W
TRIP COIL - 2 W
c Requirement of DC control voltage in ideal condition : dc
Measured control voltage dc
SWITCH “ ON “ AC / DC supply.
d Local operation of the breaker ( electrically) :
Local closing operation OK
Local tripping operation for trip coil 1 OK
Antipumping function OK
* Open command provided directly on terminal number :
e Remote operations :
Close command given on terminal number :
Open command (T1) given on terminal number :
Open command (T2) given on terminal number :
f SPARE CONTACTS OF AUXILIARY SWITCH :
● Position of the breaker : TRIP
● Serial number of contacts found NC :

● Serial number of contacts found NO :

● Position of the breaker : CLOSE


● Serial number of contacts found NC :

● Serial number of contacts found NO :

g BREAKER OPERATING TIMES

OPERATION LIMIT PHASE Measured value

CLOSING < 60 milliseconds A ms

B ms

C ms
1HYB800001-54 Rev. A
Page 12

OPENING ( T1 ) < 35 milliseconds A ms

B ms

C ms

OPENING ( T2 ) < 35 milliseconds A ms

B ms

C ms

CO ( through T1 ) < 40 milliseconds A ms

B ms

C ms

CO ( through T2 ) < 45 milliseconds A ms

B ms

C ms

h Are all the space Heaters in operating mechanism working? YES NO


I Tightness of all the electrical terminals verified?

j Is GAS leakage once again verified after timing and operation?

SF6 GAS PRESSURE AFTER COMPLETION OF JOB : BAR


TIME AT WHICH THE FINAL PRESSURE NOTED : AM / PM

k Operational counter readings as on DATE :

l Are insulators, operating mechanism, pole beam thoroughly cleaned and free
from dust and dirt?
* If NO , clean it thoroughly with dry cloth , before charging.

Check carried out by :

If points 1-7 as set out above have been completed, the circuit-breaker
can be commissioned.
1HYB800001-54 Rev. A
Page 13

6 Troubleshooting
Before any activity is started, the circuit breaker has to be isolated from the high-
voltage system and earthed according to regulations. The control and heating
currents are to be interrupted.

6.1 SF 6 gas supply system


- When the signal “Replenishment of SF6 gas” is given the gas pressure has to
be checked and insulating gas added. The correction can also be done while
the breaker is in service. If the density monitor responds inspite of nominal
pressure being present, the density monitor has to be checked.
- If leaks are suspected in the SF6 system, proceed as follows :
- SF6 gas lines :
Check all screwed and brazed joints with a leak detector. Replace faulty
brazings and fittings. Tighten leaking screwed connections.
- Casing details (mechanism housing, flanges etc) :
In the case of minor leaks all sealing joints are to be checked with a leak
detector. In the case of major leaks, it is recommended that the leaks are
located using soapy water.
- Crank Mechanism seals :
Leaking crankshaft seals must be replaced according to section 7.12.3.
- Check SF 6 gas humidity (dew point).

6.2 Control Circuits


If a switching command is delayed, or executed only partially or not at all, proceed
as follows:
- Switch off control and auxiliary current circuit.
- Check the electrical terminals in the control circuits for tightness and proper
connection.
- Compare wiring with wiring diagrams and correct if necessary.
- Check coils of solenoid valve 10006, 10007 and if necessary change defective
coils. The cause of the overload has to be established and eliminated.
- Switch on and check control voltage.
- Switching or blocking occurs in the wrong pressure range.
- Check the function of the circuit breaker when the density monitor is
disconnected. When it is confirmed that the density monitor is defective, it has
to be replaced.
1HYB800001-54 Rev. A
Page 14

7. Inspection intervals
Important checkpoints, acceptable tolerances, certain functional values for
adjustments, and recommended inspection intervals can be found in the following
inspection chart.

In corrosive or polluted air and in climates with a high relative humidity, it can be
necessary to halve the inspection intervals.

The specified inspection intervals should be considered as recommended guide


values, which can be increased or decreased depending on local conditions.
1HYB800001-54 Rev. A
Page 15

7.1 Maintenance summary

Condition of Com-
Explan- circuit- petence
Type of measure Inspection interval
ation breaker require-
during work ments
A Ocular inspection 1-2 years a1 a2
B Preventive maintenance
Intermediate inspection
• Operation testing including 3-6 years, 2 000 mech. 1) b1 b2
time checks oper.
• Heat measurements

C Preventive maintenance After 15 years or 5 000 1), 3) b1 b2


• General inspection of the mech. oper.
circuit-breaker and
operating mechanism.
D Overhaul
• Overhaul of the breaker 2) c1 c2
chamber
• Line breaker ΣnxI2=8 000
• Transformer breaker ΣnxI2=8 000
• Capacitor battery breaker
Reactor breaker
Filter breaker
• Non-synchronised 2 000 el. oper.
• Synchronised 4 000 el. oper.
• Complete overhaul. after 30 years or
10 000 mech oper.

Explanation:
1) Mech. oper. =Mechanical Close-Open operations.
2) El. oper.= Close-Open operations with electrical load
3) Special demands on resistance inspections for circuit-breakers operated
> 100 Close and Open operations/year.
1HYB800001-54 Rev. A
Page 16

Condition of the circuit-breaker during work :


a1) Circuit-breaker in operation.
b1) Closing spring untensioned, circuit-breaker open, disconnected and earthed.
Circuit-breaker poles removed and transported indoors.
c1) Closing spring untensioned, circuit-breaker open, disconnected and earthed.
Poles/breaking unit dismantled and transported to the workshop.
d1) Closing spring untensioned, circuit-breaker open, disconnected and earthed.
Complete circuit-breaker including operating mechanism transported to the
workshop.

Competence requirements :
a2) Substation personnel with no special training.
b2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work.
c2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work. In certain cases, with instructions from ABB.

7
1HYB800001-54 Rev. A
Page 17

See Maintenance of the operating


mechanism
1HYB800001-54 Rev. A
Page 18
1HYB800001-54 Rev. A
Page 19

7
1HYB800001-54 Rev. A
Page 20
1HYB800001-54 Rev. A
Page 21
1HYB800001-54 Rev. A
Page 22
1HYB800001-54 Rev. A
Page 23
1HYB800001-54 Rev. A
Page 24

4
1HYB800001-54 Rev. A
Page 25

7.6 Table of parts to be serviced


Inspection / Maintenance
Part Part which see Activity after*)
No. must be section number of
Inspected/ switching
replaced operations
Breaker pole type EDF
10036 Lockwasher 7.11.1 replace
10038/1 Sealing ring 7.11.1 replace
10038/2 Sealing ring 7.11.1 replace
10038/3 Sealing ring 7.11.1 replace
10038/4 Sealing ring 7.11.1 replace
10045 Alumina container 7.11.1 replace
10047 Lockwasher 7.11.3 replace
10056 Fixed contact pin 7.12.1 replace
10059 Finger, complete 7.12.1 replace
10060✪ Piston 7.11.3 inspect
10061✪ Flow direction tube 7.11.3 inspect
10064✪ Lockwasher 7.11.1 replace
10065✪ Contract ring 7.12.2 replace
10066✪ Insulating nozzle 7.12.2 replace
10067✪ Auxiliary nozzle 7.12.2 replace
10068✪ Erosion finger 7.12.2 replace
10072 Compression spring 7.12.2 replace
10073✪ Piston guide ring 7.12.2 replace
10074 Multi-contact ring 7.12.2 replace
10076 Cylinder 7.11.3 inspect
10077 Cylinder guide ring 7.12.2 replace
10082 Sealing ring 7.12.3 replace
10090 Sealing ring 7.12.3 replace
10091 Sealing washer 7.12.3 replace
10182 Sealing ring 7.12.3 replace
Spring stored-energy actuator FSA-1(F)
10006 Coil “OPEN” inspect
10166 Motor brushes inspect
10167 Switching element inspect
10168 Switching element inspect

*) Number of switching operations according to Fig. 7/1 of these instructions.


✪ Parts marked as ✪ can be replaced by piston assembly 1HYN400069R1,
which is the part of moving contact (part no. 10013, fig. 7/4)
- Replace means :
As a general rule replace the part when the permissible number of switching
operations according to fig7/1 of these instructions has been reached.
- Inspect means :
Inspect the part thoroughly for wear and replace if necessary. It is not
necessary to replace the part if at the endangered points it exhibits no or only
slight wear and if silver plating is not damaged.
1HYB800001-54 Rev. A
Page 26

7.7 Tools, jigs, fixtures and accessories


Besides tools for erection according to section 4.1.1 the following are required:

- Circlip pliers C8 (straight)

- Open end wrenches 10-43 mm

- Set of hexagon sockets 5-10 mm ((connection 3/8") and special tools, jigs and
fixtures as per fig 7/2b.

7.8 Maintenance procedure


7.8.1 General

Maintenance includes inspection and overhaul according to that described in sections


7.1 to 7.5 of this Instruction. Maintenance work in general, and contact overhaul in
particular, shall be carried out in closed and as dust-free premises as possible.

In principle, all sealing units, spring washers and locking rings which are dismantled
during maintenance work shall be replaced by new such parts.

7.9 Preparation for overhaul


7.9.1 Taking the circuit-breaker out of service

- Operate the circuit-breaker to position “b1” (uncharged and position OPEN) (fig. 2/1).
- Open the disconnectors on both sides of the circuit-breaker.
- Switch off control, signal, motor, and heating voltages.

- Earth the high-voltage cables on both sides of the circuit-breaker according to


local regulations and disconnect them from the circuit-breaker.
- Disconnect control, signal, motor and heater circuits.
- Reduce the SF6 gas pressure to pabs = 150 kPa (= 1.5 bar) before transport to
the assembly shop.

7.10 Removal of breaker poles


7.10.1 Dismantling SF, gas lines

Loosen the fastening bolts of the gas system so that it can be moved lengthwise.
Remove the cap nuts on the check valves so that the groove in its threads is
visible. Move the gas tube as far as possible to the side so that it comes against the
cap nut. In this position, all three check valves are closed and the cap nuts can be
completely loosened while moving the tube system further to the side.

7.10.2 Removal of breaker poles (10171) and mechanism housing

Remove outer poles:

- Fasten lifting ropes under the upper flange of the breaker chamber insulator and
tension them slightly. Remove screw, washer and nut, 49621, 49063, 89026 (fig. 4/
1a:1,2).

- Move out the breaker poles to the side. Thereby, the coupling shaft 10005 (fig. 4/
1:1,2) slides out of its coupling sleeve 10180. Transport the breaker poles to the
assembly shop and place them on an assembly block (supplied by the customer).
1HYB800001-54 Rev. A
Page 27

Dismantling middle pole:

- Pull out the coupling shaft 10005.

- Dismantle connecting rod “f” (fig. 4/la:1,2).

- Fasten the lifting rope under the flange and tension it slightly. Remove screw,
washer and nut, 49621, 49063, 89026.

- Lift the breaker pole upwards and transport it to the assembly shop.

7.11 Disassembly of breaker poles 10171 (fig. 7/2:1, :2, :3)


- Clean the breaker poles on the outside.

- Empty SF6 gas through a connected dust filter.

- Observe meticulous cleanliness in all following work.

- Parts from the various poles must not be interchanged. This is important since
parts in the arm and link systems are not identical.

7.11.1 Disassembly of breaker pole B1

The following description applies for pole B1, shown in fig. 7/2a:2. All poles are
disassembled in the same way.

- Place the breaker pole on the assembly table. Fastening points are the post and
breaker chamber insulator’s upper flanges and the adapter plate 10098.

Remove screws 49756/2 and the washers 89026/1 and lift the cover 10056/1.

Then lift out the desiccant container. Treat this according to prevailing local
regulations.

Remove screw, nut and washers 49756, 49621/2, 89026/2, and carefully lift off the
flange 10099/2 with the fixed contact.

- Place the flange on a sturdy base taking care of the O-ring groove.

- Support the mechanism housing, included in the link gear 10185/2, with a suitable
wooden base. Unscrew and pull it out as far as possible.

- Hold firmly the socket of the operating insulator 10042/2 with wrench SW28, loosen
the locking nuts 49695/1, 49586, and turn the set screw 10041/2, until the operating
insulator socket 10042/2 and the linkage joint 10043/2, are free. Take out the
mechanism housing completely. Remove O-rings 10038/3 and 10038/4.

- Disassemble the screw joint which holds together the support and breaker
chamber insulator, with the intermediate connector flanges (49333, 49621, 89026/
2) Lift off the breaker chamber insulator 10106

- Now lift off the moving contact and place it on a wooden base.

- Remove the pin 10050 and operating insulator socket 10042/2 from the operating
insulator 10049.

- Thread off the set screw in 10051 with its locking nut 49505 from adjusting ring
10053.

- Knock out the flow direction tube base with dismantling rod and adapter 00104 (fig.
7/2b). Remove pin 10029.
1HYB800001-54 Rev. A
Page 28

- Unscrew the post insulator from the adapter plate 10098.

- Do not damage the sealing surfaces on the insulators and mechanism housing. Be
careful also with the O-ring grooves in the flanges.

7.11.2 Disassembly of fixed contact 10030 (fig. 7/3)


- Remove screw 49756/2 with washer 89006/2 and separate the flange from the
contact holder.
- Loosen hexagon screws 10057 from contact finger cage 10058. Lift off the finger
cage. Thereby, the fingers 10059 fall out.
- Unscrew the fixed contact pin 10056 with socket wrench 00103.
- As a general rule, change the fixed contact pin 10056, countersunk screws 10057,
and all contact fingers 10059 .

7.11.3 Disassembly of moving contact 10013 (fig. 7/4)

- Remove screw 49332 and lift off the flange.


- Carefully take out the moving middle part.
- Clamp the piston 10060 in wooden jaws or prisms. Push flow direction tube base
10054 out of flow direction tube 10061 and unscrew the piston base 10062 with the
special torque wrench 00106 (fig. 7/2b).
- Remove the socket head screw 49318 and lock washer 10064. Take out the
contact ring 10065 with nozzle 10066 and disassemble them.
- Unscrew sleeve 10067.
- Unscrew erosion finger 10068 with torque wrench socket 00102.
- Remove the long screw 10069 from the cylinder base 10070, and pressure relief
flap 10071 with compression springs 10072.
- Check the piston 10060, flow direction tube 10061 and cylinder 10076, with regard
to damage.
- Replace all piston guide rings 10073, cylinder guide ring 10077, multi-contact rings
10074, compression springs 10072, insulating nozzle 10066, auxiliary nozzle
10067, erosion finger 10068, contact ring 10065 and spring washers 10064.

7.11.4 Cleaning

- All parts shall be cleaned according to prevailing Maintenance and Storage


Instructions 1HYB800001-30.

7.12 Overhaul of component groups


7.12.1 Overhaul of fixed contact 10030 (fig. 7/3)

- Treat the contact surfaces of the fixed contact pins with polishing cloth and grease
“N”, and the contact fingers with grease “N’ but no polishing cloth.

- Screw the fixed contact pin 10056 with hexagon wrench 00103 (fig. 7/2b) and
secure with locking fluid “B” (see 1HYB800001-29). Observe the tightening torque.

NOTE
Only the last two threads of the fixed contact holder 10097 are to be treated with
locking fluid. There must be no locking fluid on the contact surfaces, see fig. 7/3, 2*).
1HYB800001-54 Rev. A
Page 29

- When changing contact fingers, proceed as follows:

Slide the finger cage 10058 over the fixed contact holder 10097 up to 15 mm
before the end position. Insert fingers 10059, including springs, and then push the
finger cage to the end position. Screw in the countersunk screws 10057 and
secure with locking fluid “B”. NOTE: Only on the last four threads. Observe the
tightening torque.

- Screw the assembled contact 10030 to the connection flange and do not forget to
lubricate the contact surface at 3*) (fig. 7/3) with grease “N”.

7.12.2 Overhaul of moving contact 10013 (fig. 7/4)

NOTE
- Clamp the piston 10060 in wooden jaws or prisms.

- Treat the fixed contact surfaces on erosion finger and piston with polishing cloth
and grease “N”, 2*.

- Mount the erosion finger 10068 by special wrench 00102 (fig. 7/2b) and secure
with locking fluid “B”. Observe the tightening torque.

Apply fluid “E” on the thread on sleeve 10067. Mount by hand and secure with
locking fluid “C”.

Note
Only the last thread shall be treated with locking liquid (fig. 7/4, *).
Remember to remove the inside catch piece of the special wrench 00102.

- Clean and grease the fixed contact surfaces between the contact ring 10065
and piston 10060 with grease “N”. Mount the contact ring, including insulating
nozzle 10066, screw and washer, 49318, 10064, on the piston. Observe the
tightening torque and locking.

- Mount the piston base 10062 with torque wrench 00106 (fig. 7/2b) and secure with
locking fluid “B “

NOTE
Apply locking agent to the last two threads only.

- Replace cylinder guide rind 10077 in the cylinder base 10070, piston guide rinds
10073, and multi-contact rings 10074 in the piston 10060. Observe, when doing so,
the direction of the multi-contact firings.

- Clean and grease the moving contact surface on cylinder 10076 and the piston in
the area of the multi-contact rings with grease “N”, see 2*) (fig. 7/4).

- Insert carefully the assembled middle part into cylinder 10076 and flow direction
tube 10061, in cylinder base 10070. Note that there shall be an angle of 90° between
the flow direction tube window and the cylinder base window. Thereby, the middle part
must not be turned, but if so happens only in the direction of the arrow.

- Mount the long screws 10069, with pressure relief flap 10071 and compression
springs 10072. Secure with locking fluid “B”. Observe the tightening torque.
1HYB800001-54 Rev. A
Page 30

7.12.3. Overhaul of link gear 10185/2 (fig. 4/1a:2, 7/5:2)

- Remove screw and washer 49705 and 89025, or 49701 and 89154, with shaft
guard 10179 , and disassemble completely. Pull out the crankshaft 10083 and
lever 10084/2 with linkage joint 10085/2. Unscrew socket head screw 10086
with washers 10088 and 89004, and pull out the joint pin 10087.

Replace the following parts:

O-ring 10090.
X-ring10081
Sealing ring 10182

- Clean the metal parts that are not changed. Reassemble in reverse order. Grease
X-rings 10081 with grease “S”and sealing ring 10182, pack with grease “G” (Mobile
Grease 28). Be careful that the sealing rings are not damaged by the splines.
Apply grease “G” on joint pin 10087.

Observe the tightening torque.

NOTE

For the relative positions of the punch marks, see “e” in fig. 7/5:2. Apply
grease (fluor-silicone grease) “S” on the outer diameter “c” and assembly surface
“a” on shaft guard 10179 10179.

7.13 Assembly of breaker pole (fig. 7/2a)


Mounting the operating insulator 10049 on the moving contact:

- Place the snap ring 10055 in the groove on the flow direction tube base 10054.

- Push in the flow direction tube base 10054 and retaining ring 10055 so far into the
flow direction tube 10061 that the pin 10029 can be inserted.

- Push in the ring 10053 over flow direction tube 10061.

- Slide the operating insulator 10049 with screen 10095 over the flow direction tube.
Insert pin 10029 so that the bore in the bolt is in line with the centre-line of
the operating insulator. Insert the flow direction tube base 10054 through the
bore in pin 10029 until it reaches stop. Check that the rear blow-off hole is com-
pletely open.

- Place the ring 10053 so that the set screw 10051 can be screwed into the bore in
the flow direction tube 10061. Insert set screw 10051, tighten lock nut 49505 and
secure with locking fluid “B”. Observe the tightening torque.

- Assemble the operating insulator socket 10042 and pin 10050 on the operating
insulator. At this assembly the bore in the pin must be in line with the centre-line
of the operating insulator.

Assembly of the moving contact 10013 on the terminal flange 10108:

- Clean the contact surface on the terminal flange. Rub the fixed contact surface on
the cylinder base with a polishing cloth. Apply grease “N” on the rubbed surfaces.
Mount with screw and washers, 49332, 10047 and 89006/1, and secure with
locking fluid “B”. Observe the tightening torque.

- Apply grease “N”, Fomblin, on the marked moving contact surface of contact ring
10065 (fig. 7/4).
1HYB800001-54 Rev. A
Page 31

- Apply grease “S”, fluor-silicone grease on 0-rings 10038/1 and 10038/2 and the
grooves for the terminal flanges 10108. Place the O-rings in the grooves.

- Place the breaker chamber insulator on the flange and thereby try to locate the
moving contact as far as possible in the middle of the insulator.

Place the post insulator over the operating insulator and screw both the insulators
to the flange with screw, nut and washers, 49333, 49621 and 89026/3 (fig. 7/2a:2)

- Apply grease “S” on the O-rings and the groove for these in the adapter plate, and
put the O-rings in the groove.

- Screw the adapter plate against the flange on the post insulator with screw and
washer, 49726/1 and 89026/1.

Determination of the adjusting measurement “A” between the operating insulator


socket 10042 and linkage joint 10043 (fig. 7/2c:2):

- Place the depth gauge 00109 on the flange 10016 of the breaker chamber
insulator. Push the operating insulator 10049 upwards to stop. Place the straight
edge 00114 on the lower insulator flange. Measure the “X” measurement.

- Calculation formula for the measurement “A”: A = X + 32.5 mm (~ 45.5)

- Set the measurement “A” on compass 00115.

- Remove the depth gauge 00109 and straight edge 00114.

The setting values of the two remaining poles are measured in the same manner but
the calculation formula for the measurement “A” is:

for pole marked A1: X - 29 mm (~ 51.5 mm)


for pole marked C1: X - 14 mm (~ 66.5 mm)

At unearthed capacitor stack, the circuit-breaker consists of one pole marked A1(Fig.
7/2a:1), and two poles, marked B1 and C1 (7/2a:3). B1 and C1 have the same setting
value A.

For assembly of the complete fixed contact 10030, see fig. 7/2a:2.

- Apply grease “S” in the 0-ring groove on the upper terminal flange 10099/2 and the
two O-rings, before placing them in the groove.

- Now mount the contact 10030 with flange on the upper flange of the breaker
chamber insulator and try to place the contact as far as possible in the middle of
the insulator. Use screw, washers and nut, 49756, 49621/2 and 89026/2.Observe
tightening torque 79 Nm.

- Install the desiccant container filled with desiccant (see fig. 7/2a:1,2,3).

- Finally, treat the O-rings and groove on the upper connection flange with grease
“S” and mount the cover 10056/1 with screw and washer 49756/2 and 89026/2.
(MD = 45 Nm).

Assembly of link gear 10185/2 (fig. 7/2a:2):

- Move the operating insulator 10049 to position OPEN.

- Apply “S” grease in the O-ring groove of the adapter plate and on the O-rings.
Place the O-rings in their grooves.
1HYB800001-54 Rev. A
Page 32

- Place the link gear 10185/2 at a distance of 50 mm in front of the lower flange on
the post insulator.

- Place the adjusting screw 10041/2 (with only one tightening turn), with hexagon
nuts 49586 and 49695 fully backed off on their threads, on the operating insulator
socket 10042/2 and the linkage joint 10043/2.

- Tighten the adjusting screw 10041/2 to the measurement “A” by means of pre-set
compass 00115, according to fig. 7/2c:2, and secure on both sides with locking
fluid “B”. Observe the tightening torque.

- Apply grease “S” (fluor-silicone) on the sealing surfaces.

- Mount the link gear 10185/2 with hexagon nuts 49621/2 and 89026/2 and secure
as above. Observe the tightening torque 79 Nm.

- Filling gas :

After the circuit-breaker has been dismantled for overhaul or repair it shall (before
trial switching operation) be filled with SF6.

Evacuate down to the pressure 1 mbar and continue to pump at least one hour
after that pressure has been reached.

Stop evacuating and fill the circuit-breaker with dry and pure nitrogen gas to the
atmospheric pressure. Let it stand two hours at this pressure.

Evacuate again to 1 mbar and fill with pure SF6 gas to 0.15 MPa abs. Observe
thereby the safety regulations for gas filling.

7.14 Erection of breaker poles (fig. 4/1a,b)


- Set the middle breaker pole at max. OPEN position, and place the actuating lever
10154 in correct position according to punch marking “a” (fig.4/ib). Lower the pole
on support frames 10161 and place the connecting rod joint head in the actuating
lever fork. The operating mechanism must be in position OPEN. Insert the
hexagon screws 49063. Fit nut 49621 with washer 89026 and tighten slightly so
that the pole can be turned easily. Apply grease “G” ( Mobile Grease 28 ) on joint
pin 10158. Mount the spring washer, spacer and hexagon screw, 10064, 89224 and
49215. Place coupling shaft 10005 in the coupling sleeve and actuating lever.
Apply grease “G” on the splines.

- Set the outer poles in OPEN position and push them from the outside with
coupling sleeves as far as possible over the coupling shafts. Insert the hexagon
screws 49063, fit the nuts 49621 and spacers 89026, and then tighten after
adjusting the breaker poles into correct position. The joint heads on the connecting
rod must be moveable, and the coupling shafts must be moveable axially.

- Apply grease “G” (Mobile Grease 28, see 1*), (fig. 4/lc), on the flange surfaces of
the gas nipples.

Clean the gas system by blowing SF6, gas via the. header block for approx. 3 min.
Allow the gas to continue to flow while the system is connected to the check
valves of the mechanism housing, according to fig. 4/1c. Screw on all cap
nuts up to the groove. Then tighten all cap nuts fully while moving the com-
plete tube system to the side. Lock all fastening bolts. If the connections of the
gas system to the header block have been dismantled, they shall be secured
with locking fluid “B” when re-installed. Observe the tightening torque 45 Nm.
Fill with pure gas to normal working pressure 0.7 MPa abs. After conclusion of
gas treatment, fit the nut and , O-ring L10112/c.
1HYB800001-54 Rev. A
Page 33

7.15 Overhaul of spring operating mechanism 10173 (fig.7/6)


- Clean the transfer roller “A” shaft, worm wheel “G”, and worm screw “H”, and apply
grease on the machined surfaces without dismantling.

- Clean and grease sparingly the transfer cam disc “B”, latches “C” and “D”, levers
“E” and “F”. Use grease “G”.

- After 5000 switching cycles, the spring operating mechanism shall be overhauled.
Contact ABB.

8. Spare parts
8.1 General
8.1.1 Important notes
- Replace all uncovered sealing rings of the insulating gas space.
- Unpacking : shortly before use.
8.1.2 Ordering of spare parts
For ordering, the following data are essential :
- Order no 1......... See order documentation
- Type designation See nameplate
- Serial number See nameplate
- Publication number See end paper
- Part number See spare parts list
- Part designation See spare parts list

8.2 Spare parts


8.2.1 Set of contacts for 1 breaking unit
Comp. No. Art No. Name of Item Fig. Number
10056 HATH408148R1 Fixed contact pin 7.3 1
10059 HATH401095R1 Finger Compl. 7/3 27
10065 HATH306969P3 Contact Ring 7/4 1
10066 HATH307413P1 Insulating Nozzle 7/4 1
10067 HATH407749P1 Auxiliary Nozzle 7/4 1
10068 HATH307654R1 Erosion finger 7/4 1
10074 HAGS301276P24 Multi-contact Ring 7/4 1
10073 HATH408678P1 Piston guide Ring 7/4 2
10077 HATH408677P1 Cylinder guide Ring 7/4 1
10045 HAMT401304R1 Desiccant Cont. 7/2a 1
8.2.2 Gaskets, springs, fasteners for 1 breaker pole.
Comp. No. Art No. Name of Item Fig. Number
10038/2 1HML400410P170 O-ring 7/2a 5
10038/3 1HML400063P145 O-ring 7/2a 1
10038/1 1HML400410P610 O-ring 7/2a 6
10047 MT430575P14 Disc Spring 7/2a 16
10057 STD430017P2205 Countersunk screw 7/3 2
10064 1HYN400575P1 Disc Spring 7/4 12
10072 HATH407739P2 Compression Spring 7/4 3
1HYB800001-54 Rev. A
Page 34

8.2.3 Complete set of gaskets for gas supervision


Comp. No. Art No. Name of Item Fig. Number
L 00110/a 1HML400063P20 O-ring 4/1c 10
L 10112/c 1HML400063P28 O-ring 4/1c 3
L 10118 1HML400063P40 O-ring 4/1c 12
L 00110/b 1HML400063P16 O-ring 4/1c 6
L 10112/b SWT431154P1 Gasket 4/1c 1
8.2.4 Set of gaskets for 1 crank mechanism
Comp. No. Art No. Name of Item Fig. Number
10081 1HYN400061P1 X-ring 7/5 4
10090 AG434301P52 O-ring 7/5 4
10091 1HML400063P25 O-ring 7/5 1
10182 HAMT400593P6 Sealing ring 7/5 2
8.2.5 Spare parts for spring operated mechanism FSA -11
Comp. No. Art No. Name of Item Fig. Number
10166 -- Motor brushes motor 7/6 2
10168 HAGT444559P2 Limit switch 7/6 1
10168 HAGT444559P5 Limit switchT 7/6 1
10066 Close / Tripping as per table given below
10020 Motor as per table given below
1HYB800001-54 Rev. A
Page 35

8.2.6 Tools for EDF SK

8.2.7 Gas Equipment


Gas filling equipment 1HYN300349R3
Gas filling and evacuation equipment 1HYN300189R1
Gas leak detector LS790A
1HYB800001-54 Rev. A
Page 36

8.2.8 Safety Disc Unit

1 2 3

Item No. Qty. Name of Item Article No.

1 1 Safety Disk Unit 1HYN400578P1


2 1 O-ring 1HML400063P75
3 1 O-ring 1HML400063P90
1HYB800001-54 Rev. A
Page 37

11. Appendix
11.1 Figures
Fig. Designation
1/1 Nameplate
1/2 Tabulated masses
2/1 Circuit breaker
3/1a:1,2,3 Breaker Pole (“OPEN” Position)
3/1b:1,2,3 Breaker Pole (“CLOSED” position)
3/2 Schematic control diagram
4/1a:1,2 Circuit breaker, complete
4/1b Connecting rod securement
4/1c SF6 gas line
4/1d Gas filling with SF6
4/2 Transport instructions
5/1 SF6 filling pressure diagram
5/2a Measurement layout for function tests
5/2b Simultaneity monitoring
7/1 Admissible switching cycles for contact overhaul
7/2a:1,2,3 Breaker pole, complete
7/2b Tools and overhaul tools
7/2c:1,2,3 Length adjustment of moving contact
7/3 Fixed contact
7/4 Moving contact
7/5:1,2,3 Link Gear
7/6 Spring stored-energy actuator
1HYB800001-54 Rev. A
Page 38

Fig. 1/1
1HYB800001-54 Rev. A
Page 39

Type EDF
Mass per citruit breaker (net)

Designation kg (approx.) lb (approx.)

Operating mechanism incl. control 160 396

Breaker poles, pole supports 475 1045


with actuator transmission

Total mass including 815 1793


Supports

Supports 180 352

Mass per pole

kg lb

Breaker pole, complete 125 275

Fig. 1/2
1HYB800001-54 Rev. A
Page 40

Legend to Fig. 2/1

10112 Density monitor

10126 Density monitor cable, compl.

10170 Circuit breaker, type EDF

10171 Breaker pole

10172 Support frame

10173 Control cubicle with stored-energy spring operating mechanism and connecting rod

10174 Support

b Position indicator “CLOSED-OPEN”

b1 Breaker position “OPEN” and springs untensioned (not ready for switching)

b2 Breaker position “OPEN” and springs tensioned (ready for CO switching)

b3 Breaker position “CLOSED” and springs tensioned (ready for O-CO Switching)

C Earthing connection
Fig. 2/1
1HYB800001-54 Rev. A
Page 42

Legend to Fig. 3/1a,b:1

10013 Moving contact

10017 Cover

10030 Fixed contact

10041/1 Adjusting screw

10049 Operating insulator

10098 Adapter plate

10099 Upper terminal flange

10106 Insulator for breaking chamber

10108 Lower terminal flange

10171 Breaker pole

10185/1 Link gear

g-h Arcing contact

k-l Main current contact

O Circuit breaker in “OPEN” position

C Circuit breaker in “CLOSED” position


10017

10099

10106

10030

10165 k-l
g-h
10013

O C
10108
10171

10049

10157

10041/1

10098

10185/1

Fig. 3/1a:1 Fig. 3/1b:1

Fig. 3/1 a,b:1


1HYB800001-54 Rev. A
Page 44

Legend to Fig. 3/1a,b:2

10013 Moving contact

10017 Cover

10030 Fixed contact

10041/2 Adjusting screw

10049 Operating insulator

10098 Adapter plate

10099 Upper terminal flange

10106 Insulator for breaking chamber

10108 Lower terminal flange

10171 Breaker pole

10185/2 Link gear

g-h Arcing contact

k-l Main current contact

O Circuit breaker in “OPEN” position

C Circuit breaker in “CLOSED” position


10017

10099

10106

10030

10165 k-l
g-h
10013

O C
10108
10171

10049

10157

10041/2

10098

10185/2

Fig. 3/1a:2 Fig. 3/1b:2

Fig. 3/1 a,b:2


1HYB800001-54 Rev. A
Page 46

Legend to Fig. 3/1a,b:3

10013 Moving contact

10017 Cover

10030 Fixed contact

10041/3 Adjusting screw

10049 Operating insulator

10098 Adapter plate

10099 Upper terminal flange

10106 Insulator for breaking chamber

10108 Lower terminal flange

10171 Breaker pole

10185/3 Link gear

g-h Arcing contact

k-l Main current contact

O Circuit breaker in “OPEN” position

C Circuit breaker in “CLOSED” position


10017

10099

10106

10030

10165
k-l
g-h
10013

O C
10108
10171

10049

10157

10041/3

10098

10185/3

Fig. 3/1a:3 Fig. 3/1b:3

Fig. 3/1 a,b:3


1HYB800001-54 Rev. A
Page 48

Legend to Fig. 3/2

10006 Opening coil “OPEN”

10007 Closing coil “CLOSE”

10008 Auxiliary switch (S1)

10009 Auxiliary switch (K1 or K2)

10018 Motor limit switch (S3)

10019 Motor operated spring closing mech.

10020 Spring tensioning motor

10112 Density monitor (F2)

10171 Breaker pole

F3 Miniature circuit breaker

F12 Selector switch

S13 Control switch “CLOSE-OPEN”

1) Remote control
10171 10171
10171

S13

Fig. 3/2
1HYB800001-54 Rev. A
Page 50

Legend to Fig. 4/1a:1


10005 Coupling Shaft
10112 Density monitor
10118 Header block
10126 Density monitor cable compl.
10154 Actuating Lever
10161 Support frame
10173 Operating mechanism
10174 Support
10176 Coupling Shaft
L10177 SF6 gas pipe
L10178 SF6 gas pipe
10179 Shaft guard
10180 Coupling Sleeve
10182 Sealing ring
10183 Cover
49063 Hex screw M12x45 mm
49069 Hex screw M16x50 mm
49621 Hex nut M12x0.8D
49622 Hex nut M16x0.8D
49701 Socket head screw M10x20 mm
49705 Socket head screw M10x40 mm
89025 Washer
89026 Washer
89027 Washer
89154 Washer
D High-Voltage terminal:
Per screw fastener at least
1 washer13/28x3 and
1 Lock washer 13.5/28x1.6
on each side of the fastener
E Coupling, coupling sleeves
F Coupling shaft and guard
f Connecting rod (component of sping
operated mechanism)
g Fasteners
h Fasteners
MD Torque

Nm ft. lbf

13 10
45 33
79 58
190 141
Installation of breaker poles with grounded capacitor bank
A1, B1 and C1 are markings of
Fig 7/2a:1 Fig 7/2a:2 Fig 7/2a:3
respective pole mechanisms
A1 B1 C1

49705
D 89025
MD=79Nm MD=38 Nm

10176

10179

10154 10005 49063


L10177/a 49621
10112 89026
h E MD=79Nm
MD=190Nm
F
10118 10161

10180 10182 101


L10177/b
L10178
f
49069
49622
89027
10173

49701
10126 89154
10183

g g

10174

C
OPE

A-A

*) Rotation by 1800

Fig. 4/1a:1
1HYB800001-54 Rev. A
Page 52

Legend to Fig. 4/1a:2


10005 Coupling Shaft
10112 Density monitor
10118 Header block
10126 Density monitor cable compl.
10154 Actuating Lever
10161 Support frame
10173 Operating mechanism
10174 Support
10176 Coupling Shaft
L10177 SF6 gas pipe
L10178 SF6 gas pipe
10179 Shaft guard
10180 Coupling Sleeve
10182 Sealing ring
10183 Cover
49063 Hex screw M12x45 mm
49069 Hex screw M16x50 mm
49621 Hex nut M12x0.8D
49622 Hex nut M16x0.8D
49701 Socket head screw M10x20 mm
49705 Socket head screw M10x40 mm
89025 Washer
89026 Washer
89027 Washer
89154 Washer
D High-Voltage terminal:
Per screw fasterner at least
1 washer13/28x3 and
1 Lock washer 13.5/28x1.6
on each side of the fastener
E Coupling, coupling sleeves
F Coupling shaft and guard
f Connecting rod (component of sping
operated mechanism)
g Fasteners
h Fasteners
MD Torque

Nm ft. lbf

13 10
45 33
79 58
190 141
Installation of breaker poles with ungrounded capacitor bank
A1, B1 and C1 are markings
Fig 7/2a:1 Fig 7/2a:3 Fig 7/2a:3 respective pole mechanisms
A1 B1 C1

49705
D 89025
MD=79Nm MD=38 Nm

10176

10179
E
10154 10005 49063
L10177/a 49621
10112 89026
E MD=79Nm
h
MD=190Nm 10118
F

10161

10180 10182 1
L10177/b
L10178
f
49069
49622
89027
10173
E

49701
89154
10126 10183

g g

10174

A-A
*) Rotation by 1800

Fig. 4/1a:2
1HYB800001-54 Rev. A
Page 54

Legend to Fig. 4/1b

10064 Lockwasher

10083 Crankshaft

10154 Actuating lever compl.

10158 Joint pin

49215 Hex screw M 6 x 10 mm

89224 Washer

a Location of punch marks

c Installation location

d Rubber collar *)

e Clamp *)

f Connecting rod, compl. *)

g Punch mark unimportant for type EDF

h,k Locknuts

* Operating mechanism component

MD Torque

Nm ft. lbf

6 4
c=360
h

Fig. 4/1b
1HYB800001-54 Rev. A
Page 56

Legend to Fig. 4/1c

L 00110/a O-ring 15.3 x 2.4

L 00110/b O-ring 12.3x2.4

L 10177/a SF6 gas pipe

L 10177/b SF6 gas pipe

L 10178 SF6 gas pipe

L 10164 Non-return valve

L 00111 Washer

L 10118 Header block

L 10112/a Density monitor

L 10112/b Manometer *)

L 10112/c Hex. nut and sealing ring

*) At request of customer

1 *) To be greased with greases G,

Mobil Grease 28
Fig. 4/1c
1HYB800001-54 Rev. A
Page 58

Legend to Fig. 4/1d

1 SF6 Gas cylinder

2 Coupling

3 Regulator

4 Coupling

5 Gas Valve

7 Density Switch

8 Gas Valve

9 Pressure Gauge
Fig. 4/1d
1HYB800001-54 Rev. A
Page 60

Legend to Fig. 4/2

10186 Pole support with poles

a Supporting timber
Fig. 4/2
1HYB800001-54 Rev. A
Page 62

Legend to Fig. 5/1

1 Nominal filling pressure curve

2 Replenishment pressure curve (signal “Replenish SF6 gas”)

3 Blocking pressure curve (Signal “OPEN operation blocked”)

4 Filling of SF6 gas at mixed gas filling

Conversion of pressure units


100 kPa = 14.5 lbf/in2 = 1 bar

Conversion of :
Pabs (kPa) to Pe (gauge) lbf/in2
Pabs - 100 x 0.145 (kPa) = Pe (gauge) lbf/in2

Example : Rated filling pressure 1 at 200C (=680F) according to


table = 700 kPa (700-100) x 0.145 = 87 (gauge) lbf / in2
bar ibf/in2 kPa


Pabs Pabs

1000

9 130.5 900 1
8 116 800
2
7 101.5 700 3

6 87 600

5 72.5 500

4 58 400 4

3 43.5 300

2 29.0 200

100

0
-30 -20 -5 0 10 20 30 40 50 60 70 80

Pabs t0C
kPa -30 -20 -5 0 10 20 30 40 50 60 70 80
1 500 580 625 640 670 700 730 760 790 820 850 880

2 490 520 555 570 590 620 650 670 700 730 750 770

3 470 500 540 550 580 600 630 650 680 700 720 750

4 290 300 330 340 350 360 370 380 400 420 430 440

Pabs t0C
bar -30 -20 -5 0 10 20 30 40 50 60 70 80
1 5.0 5.8 6.2 6.4 6.7 7.0 7.3 7.6 7.9 8.2 8.5 8.8

2 4.9 5.2 5.6 5.7 5.9 6.2 6.5 6.7 7.0 7.3 7.5 7.7

3 4.7 5.0 5.4 5.5 5.8 6.0 6.3 6.5 6.8 7.0 7.2 7.5

4 2.9 3.0 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.3 4.4

Pabs t0C / F
lbf/in2 -30/-22 -20/-4 -5/23 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158 80/176
1 72.5 84.1 90.7 92.3 97.2 101.5 105.9 110.2 114.5 118.9 123.3 127.6

2 71.1 75.4 80.5 82.7 85.6 89.9 94.3 97.2 101.5 105.9 108.8 111.2

3 68.2 72.5 78.4 79.3 84.1 87.0 91.4 94.3 98.6 101.5 104.4 108.8

4 42.1 43.5 47.9 49.3 50.8 52.2 53.7 55.1 58.0 60.9 62.4 63.8

Fig. 5/1
1HYB800001-54 Rev. A
Page 64

Legend to Fig. 5/2a,b

Fig. 5/2a Measurement layout for function tests

10171 Breaker pole

Y2, Y3 Coils OPEN

Y1 Coil CLOSE

Q Auxiliary switch

1 Terminal 1 in control cubicle

2 Terminal 2 in control cubicle

3 Terminal 3 in control cubicle

4 Terminal 4 in control cubicle

5 Terminal 5 in control cubicle

6 Terminal 6 in control cubicle

A,B,C Pole coluomn

M1 Time recorder

M2 Main switch of test gear

M3 Control switch of test gear

K1 Terminal 1 on M3

K2 Terminal 2 on M3

UM Measurement voltage

US Control Voltage

C CLOSED

O OPEN

Fig. 5/2b Time diagram of CLOSE-OPEN operation

A,B,C Pole column

I Coil current

t1 Closing time

Dt 1 Closing tolerance of the pole column

t2 Opening time

Dt 2 Opening tolerance of the pole column

t3 Close-open time
Fig. 5/2b

Fig. 5/2a,b
1HYB800001-54 Rev. A
Page 66

Legend to Fig. 7/1

I Breaking current

n Number of switching operations


Fig. 7/1
1HYB800001-54 Rev. A
Page 68

Legend to Fig. 7/2a:1


10056/1 Cover
10013 Moving contact
10099/2 Upper terminal flange
10029 Pin
10030 Fixed contact, compl.
10038/1 O-ring
10038/2 O-ring
10038/3 O-ring
10038/4 O-ring
10041/1 Adjusting screw
10042/1 Operating socket insulator
10043/1 Linkage joint
10045 Desiccant container
10047 Lock washer
10049 Operating insulator
10050 Pin
10051 Set screw
10053 Adjusting ring
10054 Flow direction tube base
10055 Retaining ring
10061 Flow direction tube
10095 Screen
10106 Insulator for breaking chamber
10108 Lower terminal flange
10171 Breaking pole
10172 Support frames
10098 Adapter plate
10185/1 Link gear
49017 Socket screw M 6 x 20 mm
49332 Socket screw M 10 x 50 mm
49333 Hex screw M 12 x 70 mm
49505 Hex nut M 8x0.5D
49586 Hex nut M 16x0.5D
49621/2 Hex nut M 12 x 0.8 D
49695/1 Hex nut M 16 x 0.8 D
89006/1 Washer M 12 x 40 mm
49726/2 Hex screw M 12 x 50 mm
49756/2 Hex head bolt M 10 x 30 mm
89026/2 Washer
49756 Hex Head bolt M 12x60
49333 Hex Head bolt M 12x70
49726/1 Hex Head bolt M 12x45
89006/2 Washer 10.5x20x2
MD Torque
Nm ft. lbf
6 4
20 15
45 33
79 58
10056/1
49756/2 10038/1
89006/2 10038/2
49756
10099/2 89026/2

10016 49621/2

10045

10030

10106

10013

10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
M D =79Nm 10029
10095
89006/1
10047
49332 10049
MD =40Nm

10050
10042/1

10038/1
49695/1 10038/2
10041/1 49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/1 49621/2
89026/2
10185/1

10172

Fig. 7/2a:1
1HYB800001-54 Rev. A
Page 70

Legend to Fig. 7/2a:2


10056/1 Cover
10013 Moving contact
10099/2 Upper terminal flange
10029 Pin
10030 Fixed contact, compl.
10038/1 O-ring
10038/2 O-ring
10038/3 O-ring
10038/4 O-ring
10041/2 Adjusting screw
10042/2 Operating socket insulator
10043/2 Linkage joint
10045 Desiccant container
10047 Lock washer
10049 Operating insulator
10050 Pin
10051 Set screw
10053 Adjusting ring
10054 Flow direction tube base
10055 Retaining ring
10061 Flow direction tube
10095 Screen
10106 Insulator for breaking chamber
10108 Lower terminal flange
10171 Breaking pole
10172 Support frames
10098 Adapter plate
10185/2 Link gear
49017 Socket screw M 6 x 20 mm
49332 Socket screw M 10 x 50 mm
49333 Hex screw M 12 x 70 mm
49505 Hex nut M 8x0.5D
49586 Hex nut M 16x0.5D
49621/2 Hex nut M 12 x 0.8 D
49695/1 Hex nut M 16 x 0.8 D
89006/1 Washer M 12 x 40 mm
49726/2 Hex screw M 12 x 50 mm
49756/2 Hex head bolt M 10 x 30 mm
89026/2 Washer
49756 Hex Head bolt M 12x60
49333 Hex Head bolt M 12x70
49726/1 Hex Head bolt M 12x45
89006/2 Washer 10.5x20x2
MD Torque

Nm ft. lbf
6 4
20 15
45 33
79 58
10056/1
49756/2 10038/1
89006/2 10038/2
49756
10099/2 89026/2
49621/2
10016

10045

10030

10106

10013

10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
M D =79Nm 10029
10095
89006/1
10047
49332 10049
MD=40Nm

10050
10042/2

10038/1
49695/1 10038/2
10041/2 49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/2 49621/2
89026/2
10185/2

10172

Fig. 7/2a:2
1HYB800001-54 Rev. A
Page 72

Legend to Fig. 7/2a:3


10056/1 Cover
10013 Moving contact
10099/2 Upper terminal flange
10029 Pin
10030 Fixed contact, compl.
10038/1 O-ring
10038/2 O-ring
10038/3 O-ring
10038/4 O-ring
10041/3 Adjusting screw
10042/3 Operating socket insulator
10043/3 Linkage joint
10045 Desiccant container
10047 Lock washer
10049 Operating insulator
10050 Pin
10051 Set screw
10053 Adjusting ring
10054 Flow direction tube base
10055 Retaining ring
10061 Flow direction tube
10095 Screen
10106 Insulator for breaking chamber
10108 Lower terminal flange
10171 Breaking pole
10172 Support frames
10098 Adapter plate
10185/3 Link gear
49017 Socket screw M 6 x 20 mm
49332 Socket screw M 10 x 50 mm
49333 Hex screw M 12 x 70 mm
49505 Hex nut M 8x0.5D
49586 Hex nut M 16x0.5D
49621/2 Hex nut M 12 x 0.8 D
49695/1 Hex nut M 16 x 0.8 D
89006/1 Washer M 12 x 40 mm
49726/2 Hex screw M 12 x 50 mm
49756/2 Hex head bolt M 10 x 30 mm
89026/2 Washer
49756 Hex Head bolt M 12x60
49333 Hex Head bolt M 12x70
49726/1 Hex Head bolt M 12x45
89006/2 Washer 10.5x20x2
MD Torque

Nm ft. lbf
6 4
20 15
45 33
79 58
10056/1
49756/2 10038/1
89006/2 10038/2
49756
10099/2 89026/2
49621/2
10016

10045

10030

10106

10013

10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
MD=79Nm 10029
10095
89006/1
10047
49332 10049
MD=40Nm

10050
10042/3

10038/1
49695/1 10038/2
10041/3
49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/3 49621/2
89026/2
10185/3

10172

Fig. 7/2a:3
1HYB800001-54 Rev. A
Page 74

Legend to Fig. 7/2b

00100 Guide pin

00102 Special Wrench

00103 Socket Wrench

00104 Disassembly Rod with adapter

00105 Set of Wrenches

00106 Special torque Wrench

00107 Measuring kit

00109 Depth Gauge

00114 Straight edge

00115 Compass

00117 Torque wrench


Fig. 7/2b
1HYB800001-54 Rev. A
Page 76

Legend to Fig. 7/2c:1

00109 Depth gauge

00114 Straight edge

10016 Upper flange

10049 Actuating rod

10185/1 Link gear

49621 Hex nut M12x0.8D

49756 Socket head screw M12x70 mm

89026/2 Washer

89026/3 Washer

A Setting dimension x-29 mm=A (~51.5) for compass 00115 (Fig. 7/2b)

d Upper Limit stop

x Actual dimension from actuating rod to outer edge of straightedge

mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621

001
00109

10185/1
10043/1
A
10042/1

Fig. 7/2c:1
1HYB800001-54 Rev. A
Page 78

Legend to Fig. 7/2c:2

00109 Depth gauge

00114 Straight edge

10016 Upper flange

10049 Actuating rod

10185/2 Link gear

49621 Hex nut M12x0.8D

49756 Socket head screw M12x70 mm

89026/2 Washer

89026/3 Washer

A Setting dimension x+32.5 mm=A (~45.5) for compass 00115 (Fig. 7/2b)

d Upper Limit stop

x Actual dimension from actuating rod to outer edge of straightedge

mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621

0
00109

10185/2
A 10043/2

10042/2

Fig. 7/2c:2
1HYB800001-54 Rev. A
Page 80

Legend to Fig. 7/2c:3

00109 Depth gauge

00114 Straight edge

10016 Upper flange

10049 Actuating rod

10185/3 Link gear

49621 Hex nut M12x0.8D

49756 Socket head screw M12x70 mm

89026/2 Washer

89026/3 Washer

A Setting dimension x-14 mm=A (~66.5) for compass 00115 (Fig. 7/2b)

d Upper Limit stop

x Actual dimension from actuating rod to outer edge of straightedge

mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621

00109

10043/3 10185/3
A
10042/3

Fig. 7/2c:3
1HYB800001-54 Rev. A
Page 82

Legend to Fig. 7/3

10099/2 Upper terminal flange

49756/2 Hex head bolt

89006/2 Washer

10030 Fixed contact

10056 Fixed contact pin

10057 Countersunk screw M 6 x 16 mm

10058 Finger cage

10059 Finger complete

10097 Fixed contact support

10188 Finger spacing

MD Torque

*) Thread turns (2 turns) to be treated with locking agent

2*) Contact sufrace which must remian free of locking agent

3*) Contact surfaces, greased with grease “N”

Nm ft. lbf
6 4
26 19
49 36
10099/2

10097

10059

Fig. 7/3
1HYB800001-54 Rev. A
Page 84

Legend to Fig. 7/4


10108 Lower terminal flange
49332 Socket screw, M10x40
10047 Disk spring
89006/1 Washer
10013 Moving contact
10060 Piston
10061 Flow direction tube
10062 Piston base
10064 Lock washer
10065 Contact ring
10066 Insulating nozzle
10067 Auxiliary nozzle
10068 Erosion finger
10069 Long screw
10070 Cylinder base
10071 Pressure relief flap
10072 Compression spring
10073 Piston guide ring
10074 Multi-contact ring
10076 Cylinder
10077 Cylinder guide ring
49318 Socket head screw M6x25 mm
MD Torque
* Inside thread (2 turns) to be treated with locking agent
2 *) Contact surface which must remain free of locking agent
3 *) Contact surface, greased with grease “N”
A Note ! Observe carefully that the direction of rotation given in the figure is kept. If it is not
followed, the lamella of the multi-contact will be destroyed.

Nm ft. lbf
6 4
11 8
79 58
Fig. 7/4
1HYB800001-54 Rev. A
Page 86

Legend to Fig. 7/5:1

00112 Non-return valve

10080 Ball bearing

10081 X-ring

10083 Crankshaft

10084/1 Lever

10085/1 Linkage joint

10086 Socket head screw

10087 Joint pin

10088 Washer

10090 Sealing ring

10091 Sealing ring

10092 Gas connection

10182 Sealing ring

10183 Cover

10185 Link gear

49701 Socket head screw M10x20 mm

49705 Socket head screw M10x40 mm

89004 Washer

89025 Washer

89154 Washer

MD Torque

a....e See section 7.7.3

Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
b 89025
MD=45Nm
10090 10081

10183

10080
10182

10083
C

89154
49701 00112
10092

10091
d

Fig. 7/5:1
1HYB800001-54 Rev. A
Page 88

Legend to Fig. 7/5:2

00112 Non-return valve

10080 Ball bearing

10081 X-ring

10083 Crankshaft

10084/2 Lever

10085/2 Linkage joint

10086 Socket head screw

10087 Joint pin

10088 Washer

10090 Sealing ring

10091 Sealing ring

10092 Gas connection

10182 Sealing ring

10183 Cover

10185 Link gear

49701 Socket head screw M10x20 mm

49705 Socket head screw M10x40 mm

89004 Washer

89025 Washer

89154 Washer

MD Torque

a....e See section 7.7.3

Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
89025
b MD=45Nm
10090 10081

10183
10080
a
10182

10083
C

89154
49701 00112
d 10092

10091

Fig. 7/5:2
1HYB800001-54 Rev. A
Page 90

Legend to Fig. 7/5:3

00112 Non-return valve

10080 Ball bearing

10081 X-ring

10083 Crankshaft

10084/3 Lever

10085/3 Linkage joint

10086 Socket head screw

10087 Joint pin

10088 Washer

10090 Sealing ring

10091 Sealing ring

10092 Gas connection

10182 Sealing ring

10183 Cover

10185 Link gear

49701 Socket head screw M10x20 mm

49705 Socket head screw M10x40 mm

89004 Washer

89025 Washer

89154 Washer

MD Torque

a....e See section 7.7.3

Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
b 89025
MD=45Nm
10090 10081

10183
10080

10182

10083
C

89154
49701 00112
10092

10091
d

Fig. 7/5:3
1HYB800001-54 Rev. A
Page 92

Legend to Fig. 7/6

10006 Coil “CLOSE”, “OPEN” (Y1,2,3)

10020 Spring tensioning motor

10144 Hand crank

10166 Motor brushes

10167 Switching element (S1)

10168 Switching element (S3)

A Transmission roller

B Transmission cam

C Locking pawl

D Locking pawl

E Level

F Lever

G Worm wheel

H Worm

Possible breaker positions according to Fig. 2/1a...c

a Lubricating points of spring retaining pin


10144

Fig. 7/6
1HYB800001-38 Rev. A

Operating mechanism type FSA 1

Instructions for Operation


and Maintenance

Contents :

1. General
2. Construction
3. Function
4. Erection
5. Commissioning
6. Maintenance
7. Spare Parts
8. Appendix
1HYB800001-38 Rev. A
Page 1

Contents Page
1. GENERAL 1
1.1 Validity 1
1.2 Specification 1
1.3 Masses 1

2. CONSTRUCTION 1
2.1 Operating mechanism cubicle 1
2.2 Drive mechanics 1
2.3 Driving units 2
2.4 Electrical components 3

3. FUNCTION 3
3.1 Functions of the basic mechanism 3
3.2 Charging the closing spring 3
3.3 Closing - operation 4
3.4 Opening - operation 5

4. ERECTION 5
4.1 Delivery 5
4.2 Installation 5

5. COMMISSIONING 5
5.1 Function tests 5
5.1.1 Manual operation 5
5.1.2 Motor operation 5

6 MAINTENANCE (Overhaul) 6
6.1 Duty-related overhaul 6

7 SPARE PARTS 7
7.1 Storage instructions 7
7.2 Spare parts list 7

8 APPENDIX 8
8.1 Figures 8
1HYB800001-38 Rev. A
Page 2

1. General
1.1 Validity

This operating instruction applies for stored-energy spring operating mechanisms to


SF 6 circuit-breakers of type EDF
- Operating mechanism type FSA 1 (outdoor)

1.2 Specifications

Specifications are contained in the order documentation and on the rating plate.

1.3 Masses
The masses (kg/lb) can be obtained from the order documentation and the shipping
documents. For internal transport and assembly see the instructions for erection and
operation of the circuit breaker, Fig. 1/2

2. Construction
The stored-energy spring operating mechanism comprises the following main parts :

- Operating mechanism cubicle compl.


- Basic mechanism
- Driving unit
- Electrical components

2.1 Operating mechanism cubicle (Fig. 2/1)

In the operating mechanism FSA 1 (outdoor), the electrical components and the
basic mechanism are placed in the operating mechanism cubicle EV 11851.

There is a door with an inspection window for reading the position indicator
EV11825 and the spring charge indicator EV11824 on the operating mechanism
front. The door can be locked with a padlock. When the door is opened, the
electrical panel with its electrical components becomes accessible and the hand
crank can be inserted.

The operating mechanism cubicle is designed so that the basic mechanism and the
electrical components are hermetically protected against the effects of the weather.

The outdoor circuit breaker type EDF has the cubicle mounted below the pole
beams of the breaker. The connecting rod projects upwards.
1HYB800001-38 Rev. A
Page 3

2.2 Drive mechanics (Fig. 2/1, 7/1)

The basic mechanism EV 11852 is assembled in a chassis EV 11855 in which the


shaft bearings, the spring suspension points and the switchgear panel are fastened.

Their major parts are :


- Main shaft EV 11815
- Output shaft EV 11816
- Motor EV 11843 with reducer gear EV 11842
- Worm gear EV 11819
- Closing spring EV 11813
- Opening spring EV 11814
- Opening unit EV 11810
- Closing unit EV 11811
- Auxiliary switch EV 11838
- Hydraulic shock absorber EV 11840

2.3 Driving units (Fig. 2/1, 7/1)

Stored-energy spring operating mechanism type FSA 1 (outdoor)

- Lever EV 11848 is located on the output shaft and when it rotates, it transmits
the rotary movement to the connecting rod.

- Connecting rod compl EV 11822 (FSA 1) constitutes the connection between


the operating mechanism and the circuit breaker. Bellows EV 11781 seals the
operating mechanism cubicle at the connecting rod.

2.4 Electrical components

In the operating mechanism, the auxiliary switches EV 11838, microswitches EV


11826 (motor limit switches), counters EV 11860 and CLOSE and OPEN magnet
coils are integrated in the basic mechanism.

In the mechanism type FSA 1, the electrical control and monitoring elements
necessary for the control of the circuit breaker are additionally arranged on the
switchgear panel.

These are essentially :


- LOCAL-REMOTE selector switch
- ON-OFF-switch
- Motor protection switch
- Auxiliary contacts
- Miniature circuit breakers

The operating mechanism is equipped with a permanently turned-on heating resistor


to avoid the condensation inside the operating mechanism.

If the operating mechanism is to be stored outdoors for periods longer than four
weeks, the heater should be connected.
1HYB800001-38 Rev. A
Page 4

3. Function
3.1 Function of the basic mechanism (Fig. 7/1)
- The main shaft EV 11815 serves as the drive shaft for charging the closing spring.

- By means of lever EV 11848, the output shaft EV 11816 transmits the closing
or opening movement to the connecting rod, and hence to the circuit breaker.

- The motor EV 11843 with reducer gear EV 11842 charges the operating
mechanism mechanically (tensions the closing spring). The motor limit switch,
EV 11826, opens when the closing spring is tensioned.

- Hand crank EV 11812 (FSA 1) is used to charge the closing springs by hand
(e.g. on power failure).

- On discharging, closing spring EV 11813 release uses the energy to charge


the opening spring via the output shaft, at the same time closing the breaker.

- On discharging, opening spring EV 11814 release uses the energy to open the
breaker.

- Closing unit EV 11811 holds the closing spring in the charged condition or it
releases it on command electrically via the CLOSE magnet coil or
mechanically (by hand).

- Opening unit EV 11810 holds the opening spring in the charged condition or
releases it on command electrically via the OPEN magnet coil or mechanically
(by hand).

- Hydraulic shock absorber EV 11840 is double acting. It assures a dampened


opening and closing operation.

- Auxiliary switch EV 11838 is controlled by the position of the circuit breaker.


CLOSE and OPEN magnet coils are controlled by its contacts, i.e. the
commands for charging or discharging of the springs are tripped. They also
prevent the CLOSE magnet coils from being excited when the circuit breaker
is closed or the closing spring is not fully charged, or they prevent the OPEN
magnet coils from being energized when the circuit breaker is opened.

- Heater EV 11854 (Fig.2/1) is provided in operating mechanism. The heating


resistor prevents condensation in the operating mechanism cubicle. The
heating resistor remains permanently turned on.

3.2 Charging the closing spring (Fig. 7/1)


In Fig. 7/1 the basic mechanism is shown with the circuit breaker in the position
OPEN (“O”) and with the springs in the discharged condition.

The closing spring EV 11813 is charged electrically by motor EV 11843 with


flanged-on reducing gear EV 11842, leading via coupling shaft EV 11841 to worm
gear EV 11819. The hand crank coupling EV 11817 prevents the hand crank from
turning during the electrical charging of the spring. The motor EV 11843 is also
decoupled (by coupling shaft EV 11841) when the spring is charged by hand.
1HYB800001-38 Rev. A
Page 5

As an emergency charging feature the closing spring EV 11813 is charged with hand
crank EV 11812 via bevel gear EV 11818 and worm gear EV 11819 by turning the
main shaft EV 11815. The main shaft EV 11815 is turned via worm wheel and pull
hook EV 11830 which engages the coupling ring EV 11829.
For charging the closing spring approx. 30 rotations of the hand crank are necessary.
On a 1800 rotation the crank EV 11828 runs through top dead center.
The pawl on the control disk EV 11820 is held by lever EV 11832, and the blocking
hook EV 11834 of the closing unit.
The switching cam of crank EV 11828 simultaneously reaches the motor limit switch
EV 11826 and cam follower lever EV 11827 is lifted.
The following functions are thereby initiated :
- Turning off the power supply to the motor by the motor limit switch.
- Preparation of the closing operation by the motor limit switch.
- Spring charge indicator indicates “Spring charged”.
Time necessary for charging the spring at nominal tension : < 15 seconds.

3.3 Closing-operation (the circuit breaker is closed)

When the engagement lever EV 11837 or the closing coil EV 11839 are actuated by
hand or electrically, the lever 11832 and the blocking hook EV 11834 of the closing
unit release the control disk pawl EV 11820.

By releasing the closing spring EV 11813, the main shaft EV 11815 rotates in the
direction shown on fig. 7/1 and in turn the control disk EV 11820 transmits the
rotational movement to the cam follower EV 11836 and operating lever EV 11835.
The output shaft EV 11816 is thereby rotated and the circuit breaker is closed via
operating lever EV 11848 and connecting rod compl. EV 11780/EV 11822.
Simultaneously, opening spring EV 11814 is charged.

When the output shaft has rotated by 60 o, the control disk pawl passes over the cam
follower EV 11836 and then the output shaft is released and can rotate in the
opposite direction.

However, this is not possible as long as holding cam EV 11847 is held by lever EV
11832 and blocking hook EV 11834 of the opening unit. The closing spring EV
11813 is automatically recharged again.

At power failure the closing spring can be recharged by hand with hand crank EV
11812 (FSA 1).
In this position the following indications are visible :
- Position indicator : “I” (circuit breaker in closed position)
- Spring charge indicator : “Spring charged”
1HYB800001-38 Rev. A
Page 6

The operating mechanism is ready for another rapid closing operation but the
interlock hook EV 11833 prevents the execution of a closing operation, while the
circuit breaker is closed. Both springs (EV 11813 and EV 11814) remain charged
and both shafts are blocked by the two blocking units (EV 111810 and EV 11811).

3.4 Opening-operation (the circuit breaker is open)


The holding cam EV 11847 is released from lever EV 11832 and the opening unit
blocking hook EV 11834, when disengagement lever EV 11845 and opening coil EV
11846 and/or EV 11839 are actuated manually or electrically.
By discharging the opening spring EV 11814, the output shaft EV 11816 rotates 600,
thereby opening the circuit breaker via the connecting rod.
The interlock hook EV 11833 of the closing block is released at the end of the
opening operation and a new closing operation can be executed.

4. Erection
4.1 Delivery
Each circuit breaker is delivered with its corresponding operating mechanism which
is packed separately or already mounted on the circuit breaker pole beams. At
delivery, both springs are uncharged and the circuit breaker is in open position.

4.2 Installation (Fig. 2/1)


If the operating mechanism is delivered separately, the following must be noted :

Mount the operating mechanism or operating mechanisms (which 1-pole operating


mechanism type) on the circuit-breaker pole beams. Make sure that the number of the
circuit breaker corresponds with the number on the operating mechanism rating plate.

The operating mechanism must be mounted on the circuit breaker according to the
instruction for erection and operation of the circuit breaker.

Connect electrical connections according to valid circuit diagram.

Never operate the operating mechanism if it is not connected to the circuit breaker (filled
with SF6-gas to 0.7 MPa) and the electrical connecting lines are not connected.

5. Commissioning
5.1 Function tests
Function tests are performed after the commissioning work and immediately before
the circuit breaker is taken into service, as well as after overhaul work.
Function tests may only be performed with the circuit breaker disconnected from the
high-voltage system and filled with SF6-gas to 0.7 MPa (abs).
5.1.1 Manual operation
For this purpose hand crank EV 11812 is used for charging the closing spring. When
the closing spring has reached the desired tension, it automatically uncouples the
pull hook (EV 11830) of the main shaft, thereby releasing the hand crank.
During these trial switching operations, the position indicators (EV 11824 and EV
11825) and the counter must be tested for proper functioning.
1HYB800001-38 Rev. A
Page 7

5.1.2 Motor operation

The motor should be turned on only after the hand crank has been removed, even
though it is uncoupled automatically when the motor is started.

The charging of the closing springs starts as soon as the motor supply is switched
on. The supply of power to the motor is turned off automatically (by microswitch EV
11826) when the closing spring is adequately charged.
- Proper functioning of the operation mechanism should be tested by several
CLOSE and OPEN switching operations.
- Also a test for correct functioning of the selector switch LOCAL-REMOTE
should be performed.
- Motor running time for charging springs at rated voltage : < 15 seconds.

6. Maintenance
6.1 Duty-related overhaul (Fig. 7/1)
After 2000 CO Switching operations, the following parts must be cleaned and
lubricated without being disassembled :
- Cam follower EV 11836 with roller shaft, greased with grease G, (Mobile
Grease 28*)
- Worm gearing EV 11819 (worm and worm wheel), grease G (Mobile Grease 28)
- Rollers of levers EV 11832 of closing and opening units, grease L (Aseol
Sylitea 4-018)
Clean and lubricate the machined surfaces of the following cams :
- Control disk with pawl EV 11820, grease L (Aseol Sylitea 4-108)
- Holding cam EV 11847, grease L (Aseol sylitea 4-108)
Treat the worm surfaces of the following pins or cranks with :
- Crank pin EV 11853, grease L (Aseol sylitea 4-108)
- Spring fixation pin EV 11856, grease L(Aseol sylitea 4-108)
- Spring fixation pin EV 11857, grease L(Aseol sylitea 4-108)
- Crank with switching cams EV 11828, grease L(Aseol sylitea 4-108)
Change the following details of the connection rod if required (Fig. 2/2):
- Rod end joint EV 11858 or EV 11782 (in case of obvious wear)
- Bellows EV11781 when there are cracks in material, leaks.

Treat rod end joint with grease G (Mobile Grease 28)

Disassembly and assembly as described in the instructions for erection and


operation of the circuit breaker.

No work is allowed to be carried out until the closing and opening springs are
discharged, and the circuit breaker is in the OPEN “O” position. The power to the
motor must be disconnected.

After 5000 CO switching operations, a general overhaul must be performed by


specialized staff. Please contact the manufacturer or his representative.

*As an alternative to Mobile Grease 28, Molykote Long term 2 plus or Aseol Sylitea
4-108 may be used.
1HYB800001-38 Rev. A
Page 8

7. Spare parts
For ordering, the following data are essential :
- Order number See order documentation
- Type designation See rating plate
- Serial number See rating plate
- Publication number See spare parts list
- Part number See spare parts list
- Design Outdoor
- Part designation See spare parts list

7.1 Storage instruction


Before the erection, the operating mechanisms shall be stored indoors or under a
roof as long as possible. If the units are stored outdoors, they must be prevented
from standing in water pools. With outdoor storage for long periods, the units shall be
covered with tarpaulin and the heating elements of the operating mechanism shall be
connected.

7.2 Spare parts list


Overhaul parts :
Part No. Part designation Number/Type of operating mechanism Figure
FSA 1 (1) FSA 1 (F)

EV 11781 Bellows - 1 2/1,2/2a,b


EV 11782 Rod end joint - - 2/1,2/2b
EV 11858 Rod end joint 1 1 2/1,2/2a
EV 11859 Motor brush 2 2 7/1

Reserve parts :

Part Number Part designation Number/type of operating mechanism Figure/section


FSA 1 (1) FSA 1 (F)

EV 11810 Opening unit 1 1 7/1 (legend)/3.1


EV 11811 Closing unit 1 1 7/1 (legend)/3.1
EV 11813 Closing spring 1 1 7/1
EV 11814 Opening spring 1 1 7/1
EV 11823 Pin 1 1 7/1
EV 11826 Motor limit switch 2 2 7/1
EV 11836 Cam follower 1 1 7/1
EV 11838 Auxiliary switch 1 1 7/1
EV 11839 Coil “CLOSE”, “OPEN 1” 1 1 7/1
EV 11840 Hydraulic shock absorber 1 1 7/1
EV 11842 Reducer gear 1 1 7/1
EV 11843 Motor 1 1 7/1
EV 11844 Switching element (yellow) 2 2 7/1
EV 11846 Coil “OPEN 2” 1 1 7/1
EV 11854 Heater 1 1 2/1
1HYB800001-38 Rev. A
Page 9

8 Appendix
8.1 Figures
Fig. Title

2/1 Stored-energy spring operating mechanism compl. FSA 1

2/2a Connecting rod compl. FSA (outdoor)

7/1 Drive mechanics (schematic representation)


1HYB800001-38 Rev. A
Page 10
1HYB800001-38 Rev. A
Page 11

Legend to Fig. 2/1


EV 11781 Bellows
EV 11812 Hand crank (FSA 1)
EV 11822 Connecting rod compl. (FSA 1)
EV 11824 Spring charge indicator
EV 11825 Breaker position indicator
EV 11849 Rotational movement lever
EV 11851 Drive assembly cubicle compl.
EV 11854 Heater
EV 11855 Chassis
EV 11858 Rod end joint (FSA 1)
b Breaker position indicators
b1 Breaker position OPEN “O”, springs
“discharged” (not ready for switching)
b2 Breaker position OPEN “O”, springs
“charged” (ready for CO Switching operation)
b3 Breaker position CLOSED “I”, springs
“charged” (ready for O-CO switching operation)
11812

Fig. 2/1
1HYB800001-38 Rev. A
Page 13

Legend to fig. 2/2a


EV11781 Bellow
EV11822 Connection rod compl. (FSA 1)
EV11858 Rod end joint (FSA 1)
84638 Hex nut M20 x 1.5 mm/0.5d
MD Torque
Fig. 2/2a
1HYB800001-38 Rev. A
Page 15

Legend to fig. 7/1


EV11812 Hand crank (FSA 1)
EV11813 Closing spring
EV11814 Opening spring
EV11815 Main shaft
EV11816 Output shaft
EV11817 Handcrank coupling
EV11818 Bevel gearing
EV11819 Worm gearing
EV11820 Control disk with pawl
EV11822 Connecting rod compl. (FSA 1)
EV11823 Pin
EV11824 Spring charge indicator
EV11825 Position indicator
EV11826 Microswitch (motor limit switch)
EV11827 Cam follower lever
EV11828 Crank with switching cams
EV11829 Coupling ring
EV11830 Pull hook
EV11831 Adjusting screw
EV11832 Lever (closing/opening block)*),2*)
EV11833 Interlock hook*)
EV11834 Blocking hook*),2*)
EV11835 cam follower lever
EV11836 Cam follower
EV11837 Engagement lever (closing lever)*)
EV11838 Auxiliary switch
EV11839 Coil “CLOSE”, “OPEN 1”*),2*)
EV11840 Hydraulic shock absorber
EV11841 Coupling shaft
EV11842 Reducer gear
EV11843 Motor
EV11844 Switching element (yellow)
EV11845 Disengagement lever (opening lever)2*)
EV11846 Coil “OPEN 2”, 2*)
EV11847 Holding cam
EV11848 Rotational movement lever (FSA 1, outdoor)
EV11850 Auxiliary switch lever
EV11852 Drive mechanism
EV11853 Crank pin
EV11856 Spring fixation pin
EV11857 Spring fixation pin
EV11859 Motor brush
EV11860 Switching operation counting meter

*) Part of closing block EV11811


2*) Part of opening block EV11810
Fig. 7/1
1HYB800001-52 Rev.A

ABB Ltd.
Maneja, Vadodara
Gujarat, (INDIA)
Tel. : +91 265 2642141
Fax : +91 265 2638918, 2638911
visit us at : www.abb.com

Вам также может понравиться