dseGenset

dse7450
ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for

DC GENERATOR CONTROLLER the Industrial Environment


BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
The DSE 7450 is a control module Application specific needs can also The DSE7450 module is BS EN 60950
Safety of Information Technology Equipment,
designed to control DC generators be achieved by combining the compatible with both electronic including Electrical Business Equipment
in supplying both a load and/or the standard and embedded safety (CAN) and non-electronic engines
TEMPERATURE
charging of batteries. features for generator control and and offers a comprehensive BS EN 60068-2-1
the configurable discrete I/O. number of flexible inputs, outputs Ab/Ae Cold Test -30 oC
Specific attention has been given to and extensive engine protections. BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
ensure this module has the The DSE7450 will annunciate This means the system can be
necessary features to be warnings, shutdown and engine easily adapted to meet the most VIBRATION
BS EN 60068-2-6
configured for many different and status information on the back-lit demanding industry requirements. Ten sweeps in each of three
challenging applications. Owing to LCD screen, illuminated LEDs, The modules can be easily major axes
the large number of monitoring remote PC, audible alarm and via configured using the DSE 5 Hz to 8 Hz at +/-7.5 mm,
8 Hz to 500 Hz at 2 gn
points and the built in SMS text alerts. Parameters can be Configuration Suite Software via an
programmable logic controller, a adjusted using the LCD and tactile A to B USB cable. HUMIDITY
BS EN 60068-2-30
wide number of operating modes rubber silicon 5 key menu Db Damp Heat Cyclic 20/55 oC
can be realised. This provides the navigation. PIN code protection at 95% RH 48 Hours
user with the ultimate flexibility in ensures that only authorised BS EN 60068-2-78
Cab Damp Heat Static 40 oC
the engine control of the generator persons can access these features. at 93% RH 48 Hours
to ensure battery life optimisation,
SHOCK
reduce engine maintenance/ The module includes USB, RS232, BS EN 60068-2-27
replacement and fuel usage. RS485 & Ethernet ports as well as This data sheet refers to V2+ Three shocks in each of three major axes
dedicated terminals for system controllers. For V1 controllers 15 gn in 11 mS
expansion. please refer to the Operator DEGREES OF PROTECTION
Manual. PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF


GEN-SET APPLICATIONS
MODEM MODBUS PC
DSE2130
DSE2131
DSE2133 10 6 4
DSE2152
DSE2157
DSE2548 232 485

DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V

ETHERNET
+

DEUTZ
DSE7450 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) N/O VOLT GENERATOR CHARGE FUEL & CRANK ELECTRONIC
N/C VOLT ENGINES &
SENSING VOLTS CURRENT SENSING FREE OUTPUT SENSING ALTERNATOR OUTPUTS
FREE OUTPUT MAGNETIC
FLEXIBLE WITH CAN
PICK-UP

VOLTS CHARGE SHUNT LOAD SHUNT


VOLTS D+
W/L +

1ph 1 1 1ph
2ph 2ph
3ph 3ph
N N

ISSUE 1
®

dseGenset

dse7450
SPECIFICATION

DC SUPPLY
CONTINUOUS VOLTAGE RATING

DC GENERATOR CONTROLLER 8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


260 mA at 12 V, 130 mA at 24 V

MAXIMUM STANDBY CURRENT


120 mA at 12 V, 65 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J


2 A DC at supply voltage

GENERATOR
VOLTAGE RANGE
KEY FEATURES • Fault condition notification to KEY BENEFITS 15 V to 150 V AC (L-N)
• Configurable inputs (10) designated PC • Programmable characteristics to
FREQUENCY RANGE
• Configurable outputs (8) • Engine Protection influence charging operation and 3.5 Hz to 75 Hz
• Configurable maintenance alarms • Five key menu navigation for LCD extend battery life
(3) display (PIN protected) • Optimise generator running time MAINS (UTILITY)
VOLTAGE RANGE
• Configurable battery • Engine speed detection via CAN, to reduce fuel usage, reduce 15 V to 333 V AC (L-N)
maintenance alarms (3) magnetic pick-up or alternator maintenance and extend engine
• Configurable alarms and timers sensing and battery lifetime FREQUENCY RANGE
3.5 Hz to 75 Hz
• Automatic or Manual start with • Fuel usage monitor and low level • Automatic start/stop according to
configurable start and stop timers alarms configured settings and battery MAGNETIC PICK UP
• 2 DC shunt inputs (Configurable • Charge alternator failure alarm condition. VOLTAGE RANGE
+/- 0.5 V to 70 V
0-250mV and 0-5000 A) • Manual fuel pump control • Engine start/stop can be adjusted
• AC & DC voltage measurement • ‘Protections disabled’ function to maintain desired battery charge FREQUENCY RANGE
• Mains (utility) failure detection • Manual/Automatic load transfer level 10,000 Hz (max)
• Dedicated load test button • Fully configurable & remote • DSENet® connection for system BUILT-IN AVR BIAS

1000 Ω
• kW overload alarms SCADA monitoring via DSE expansion modules MINIMUM LOAD IMPEDANCE
• Comprehensive electrical Configuration Suite PC Software • Ability to implement application
Fully isolated
protection • Start & stop capability & specific logic and customise
• USB, RS232, RS485, Ethernet advanced SMS messaging operation. BIAS VOLTAGE
0 V to 10 V DC
and Modbus RTU/TCP (additional modem required) • Allows measurement of Battery Fully isolated
communication • Additional display screens to help current, Load current and Total
• PLC functionality using program with modem diagnostics current. DIMENSIONS
OVERALL
editor within PC configuration • DSENet® expansion 240 mm x 172 mm x 57 mm
suite • Battery & Load monitoring 9.4” x 6.8” x 2.2”
• Multi event exercise timer • DC alarms for overcurrent &
PANEL CUTOUT
• Back-lit LCD 4-line text display short circuit 220 mm x 160 mm
with multiple languages possible • Battery temperature monitor 8.7” x 6.3”
• Audible alarm • Battery charge remaining display
MAXIMUM PANEL THICKNESS
• Fixed and user defined LED • Battery depth of discharge This data sheet refers to V2+ 8 mm
indicators display controllers. For V1 controllers 0.3”
• Real time clock and event log • AVR bias control please refer to the Operator Manual.
OPERATING TEMPERATURE RANGE
(250 events). -30 oC to +70 oC

STORAGE TEMPERATURE RANGE


RELATED MATERIALS -40 oC to +85 oC
TITLE PART NO’S
DSE7450 Installation Instructions 053-143
DSE7450 Operator Manual 057-170
DSE7450 PC Configuration Suite Manual 057-169

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-142/02/16 (2)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457