Вы находитесь на странице: 1из 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/224400789

Effects of harmonics on distribution transformers

Conference Paper · January 2009


Source: IEEE Xplore

CITATIONS READS
23 8,799

2 authors:

Dalila Mat Said K.M. Nor


Universiti Teknologi Malaysia Perundingan KMN
42 PUBLICATIONS   343 CITATIONS    104 PUBLICATIONS   1,122 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

wind energy View project

power system operation optimisation View project

All content following this page was uploaded by K.M. Nor on 02 June 2014.

The user has requested enhancement of the downloaded file.


Effects of Harmonics on Distribution
Transformers’
D.M. Said* and K.M. Nor**
Faculty of Electrical Engineering, Universiti Teknologi Malaysia, 81310 Skudai Johor, Malaysia.
*dalila@fke.utm.my, **khalidmn@fke.utm.my

Abstract| - Proliferation of harmonics in power distribution that are affected by the harmonic current loadings are the
systems, which are using increased nonlinear loads, have I2R loss, eddy current loss and the stray losses.
become a power quality problem for both customers and
suppliers. The harmonic power losses not only cause an A. Harmonic current effect on ohmic losses
increase in operational costs but also create additional
heating in power system components, which in turn will
The ohmic losses ( I 2 R ) are the losses due to
reduce their life expectancy. This happens especially in primary and secondary distorted currents flowing through
commercial buildings, where usage of nonlinear loads is very the windings. If the root mean square value of the load
high. In general the cost of power quality and in particular current is increased due to a harmonic component, the I2R
the aging costs due to harmonic losses in transformers will loss will be increased accordingly [8].
increase since harmonics will affect all power system
equipment. This study examines the effect of harmonic B. Harmonic current effect on eddy current loss
distortion on power transformers when supplying non-
sinusoidal load currents. The Malaysian Standards are used The transformer core eddy-current loss ( PEC ) in
in the findings for comparison. For this research, the the power frequency spectrum is proportional to the
harmonic problem can be analysed with simulations, real square of the load current and the square of frequency.
measurements and assessments. The results show that an This characteristic will cause excessive core losses
increase in the current harmonic distortion can increase thereby creating abnormal temperature rise in
transformer losses and decrease its life expectancy.
transformers when supplying non-sinusoidal load
I. INTRODUCTION currents[8].

Power quality problems in Malaysia have been C. Harmonic current effect on other stray loss
identified and recognized as far back as in the early Other stray loss ( POSL ) in the core, clamps, and
1990’s but however progress in managing the problems structural parts will also increase at a rate proportional to
nationally has been rather slow. Higher harmonics the square of the load current, but these losses will not
distortion can cause excessive losses leading to abnormal increase at a rate proportional to the square of the
temperature rises. If a transformer cannot be operated up frequency, as transformer core eddy-current losses.
to its stipulated standard lifetime expectancy, the Studies by manufacturers and other researchers have
phenomena would definitely cause an economical loss. shown that the eddy-current losses in bus bars,
The theory proves that the losses on power connections and structural parts increase due to the
transformer increases with the presence of harmonics. A harmonic exponent factor of approximately 0.8 or less [8].
more serious effect of harmonic loads served by For dry-type transformers temperature rise in these
transformers is due to an increase in eddy current losses. regions are less critical than in the windings but it has to
The eddy current losses increase appears as the square of be properly accounted for transformers that are liquid
the current in the conductor and the square of its filled.
frequency. The increase in transformer eddy current loss
due to harmonics has a significant effect on the operating D. Effect on top oil rise
temperatures of the transformers. The other stray losses in The top oil rise (θ TO ) , will increase as the total
the core, clamps and other structural parts are found to be load losses increase with harmonic loading for liquid-
proportional to the square of the load current and filled transformers. Any increase in other stray loss will
frequency to the exponent factor of 0.8. Several measures primarily affect the top oil rise [8].
and development works on the effect of harmonics on
losses of life of power transformers have been conducted II. TRANSFORMER LOSSES IN NONSINUSOIDAL
[1-8]. However, these works did not take in consideration CONDITION
the standards of harmonics. In this study, harmonic data of
distribution transformers at commercial buildings is Transformers are usually the interfaces between
measured. This study examines the loss of life of supply and most non-linear loads [1]. Transformers are
transformers where the Malaysian Standards on the designed to deliver the required power to the connected
limitation of harmonics is being used as a reference. loads with minimum losses at a fundamental frequency.
One of the major effects of harmonic distortion is Transformer losses are generally classified into no load
the increasing transformer losses [2]. Component losses losses and load losses as shown in (1) [2, 9-13].

2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-107 page 1
PT = PNL + PLL (1) The eddy current loss is increased by the factor FHL and
the other stray losses are increased by a factor FHL-STR in
the presence of harmonics.
Where,
PT = total loss, watt,
PNL = no load loss, watt,  =   + '(.  + '(. !


PLL = load loss, watt (10)


These factors are calculated by the following equation [8]
2
The no load loss or excitation loss are the losses due to the  Ih  2
h = hmax

voltage excitation of the core and are due to magnetic ∑   h


h =1  I 1 
hysteresis and eddy currents. The load loss or impedance FHL = (11)
2
loss is subdivided into I2R loss and stray loss caused by
h = hmax
 Ih 
electromagnetic flux in the windings, core, core clamps, ∑  
h =1  I 1 
magnetic shield, enclosure or tank walls, etc [2,9]. Thus, 2
the total stray loss is subdivided into winding stray loss  I h  0.8
h = hmax

and stray loss in components other than the windings ∑   h


h =1  I 1 
FHL −STR = (12)
( POSL ). The windings stray loss includes winding h = hmax
 Ih 
2

conductor strands and loss due to circulating currents ∑  


h =1  I 1 
between strands or parallel winding circuits. The total
load loss can be stated as follows. Where,
PLL = PI 2R + PEC + POSL (2) FHL = harmonic factor for eddy current loss,
Where, FHL-STR = harmonic factor for other stray loss
PI2R = loss in the winding
PEC = eddy current loss The per unit load losses and rated per unit eddy current
POSL = other stray loss loss is given by the expression [8],

 
The rated losses of a transformer can be calculated by )* =  (+,) × ∑23245
23 / 0 1 (13)
using the data provided but first the rated currents at the 

primary and secondary parts are calculated as follows; .7(


89:;<=>? )
  )* = .@(  (14)
:;<=>? ) 

( )
 = (3)
√ 
Where,

( ) h = harmonic order
 = (4) hmax = maximum harmonic order
√ 
I1 = rms current of fundamental component
The I2R losses is the following form [8], pu = per unit quantities

 = [   +    ] (5) III. TRANSFORMER’S LOSS OF LIFE


CALCULATION
Where
K = 1.0 for single-phase transformers Harmonic losses occur in the form of increased
= 1.5 for three-phase transformers heat dissipation in the windings and skin effects. Both are
a function of the square of the root mean square current;
 =   +  (6) as well as from eddy currents and core losses [14]. This
extra heat can have a significant impact in reducing the
 =   + ! (7) operating life on the insulation of a transformer. The
estimation of transformer loss of life is based on the
Where, deterioration rate achieved by insulating materials [2, 4,
I1 = current in primary side of transformer, and 5]. About 50% of a transformer loss of life is caused
I2 = current in secondary side of transformer by thermal stresses which are produced by the non-linear
R1 = primary dc resistance load currents [4]. The hottest spot winding temperature is
R2 = secondary dc resistance [15];
PTSL = total stray loss A( = A + ∆A( (15)

Based on the IEEE Standards [8] for the dry type Where,
transformer the eddy current loss can be assumed to be θA = ambient temperature,
about 0.67 of the total stray losses. θHS = is the hottest-spot winding temperature, in °C,
  = 0.67 (8) θHS = is the hottest-spot winding temperature rise
above ambient, in °C.
! =  −   (9)

2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-107 page 2
The relative aging factor, the loss of life and actual real active power, reactive power, apparent power, voltage
life of this transformer can be expressed in the following harmonic, current harmonic, true power factor and
manner [16]; displacement power factor.
Table I shows the specifications of the
@EEE @EEE
' = CD+ / 7
−F 1 (16) distribution transformers and Table II shows harmonic
G HI currents for transformer loads which are compared to the
MNN × ×EE
standards. The total harmonic distortion for Case 1 and
%KLK = (17) Case 2 are 51.91% and 18.36% respectively. The daily
OPQRST UOVWTSXUPO TUYZ
curve or load per unit of the transformers is shown in
`aaa Fig.1. The usage of the loads in the building is based on
( )
K[\C(+,) = 9.8 × 107 C bG cde (18) the duration of working hours at the buildings which is
from 8.00 am to 5.00 pm. Maximum per unit load that is
Real life = Life (pu) x normal insulation life (19) achieved by the transformers is about 0.5 per unit and 0.7
or per unit for Case 1 and Case 2 respectively.
Real life = normal insulation life/ FAA (20)
Where, V. RESULT AND ANALYSIS
FAA = relative aging factor
%LOL = lost of life in percent From the harmonic data Case 1 in Table II,
t = given time period harmonic loss factor for eddy current loss and harmonic
factor for other stray losses are calculated using (11) and
IV. POWER QUALITY MEASUREMENT (12) as follows,
FHL = 7.1222
The power quality analyzer is used to log the FHL-STR = 1.5418
harmonic data. This equipment is used for two different In this case, the transformer loading, is considered 0.5 per
cases of load types. The first case is at the computer unit. The total load loss of the transformer being used(13)
centre building and the second case being the office and is,
lecture hall buildings. The difference here is that the )* = 0.3174 pu
number of computers connected to the first case is much The load losses are also calculated considering
higher than that of the second case. However for both the actual load and the effects of harmonic. The total eddy
cases, the type of load connected include personal current loss and other stray loss are also determined using
computers, fluorescent lamps, air conditioners, printers, harmonic loss factor for eddy current loss and harmonic
photocopy machines and LCD projectors.
factor for other stray losses. The result of this calculation
At the computer centre building the burnt
is then summarized in Table III. The result shows that the
transformer was replaced in 2001 with a 2500 kVA rated harmonic load current can be detrimental on the power
power. The old transformer with the rated power of 2000 transformer. The relative aging factor and real life of this
kVA had been used since 1985, so the life of this transformer are as follows,
transformer had been reduced to 16 years from a life
expectancy of 20.55 years or the percent of loss of life FAA = 0.002
being 0.2214%. As for the transformer in Case 2, the %LOL = 0.00015%
transformer was used since 1988, and the life expectancy Real life = 20.55 years
of this transformer is twenty years. For both cases the data
was logged for one week with intervals of five-minute. With the 0.5 per unit loading, the aging acceleration factor
Optical cable for USB and Power Log Software was used is less than 1. This means that the life of the transformer
to transfer the data stored in the instrument to the
will not be less than its normal expected life. However,
computer. The data was set to measure the quantities such with the same harmonic levels, 30 ᴼC ambient
as frequency, voltage, current, total harmonic distortion, temperature and reference temperature of 110 ᴼC, if the
load is increased to 0.7 per unit, the aging acceleration
TABLE I: DISTRIBUTION TRANSFORMER CHARACTERISTICS factor will be 2.53 and the real life expectancy of this
CASE 1 CASE 2 transformer decreases from 20.55 to about 8.12 years. Fig.
2 shows that for the total harmonic distortion of 51.91%,
No Load Losses 2500 W 1600 W the transformer will have a normal life with a loading
Load Losses 25000 W 14570 W smaller than 0.60 per unit because its aging factor is less
Power (kVA) 2500 1500 than 1. When the standard limits are applied for this case,
Primary Voltage 11000 V 11000 V as Fig.3 shows the curve of transformer’s real life
Secondary Voltage 433 V 433 V reduction, but if the load exceeds 90%, the real life of the
transformer will decrease to about 28% for each 1%
Winding Temperature increase in load. For Case 2, from the simulation results,
Rise 100 ᴼC 65 ᴼC Fig.4 shows that the transformer still maintains its normal
Ambient Temperature 30 ᴼC 30 ᴼC life with the higher load but if the load exceeds 98%, the
Normal Insulation Life 20.55 years 20.55 years transformer’s real life expectancy will decrease
dramatically, which is about 12% for each 1% increase in
load.

2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-107 page 3
VI. CONCLUSION This will involve some expenses on consumers to
compensate for the loss of life of the transformers. The
The study of harmonic impact on power simulation results of harmonic effects on transformers
transformers is important because power transformers are show that higher the loads, the lower will be the life of
among the most expensive equipment and the most transformer due to current harmonics generated by the
critical plant equipment in electric utilities especially in electrical devices. The harmonic standard shows that
transmission and distribution network. In Case 1 the harmonic currents need to be monitored. These maximum
transformer will not be less than its normal life limits of MS 1555:2002 which correspond to IEC TR
expectancy until the loading exceeds 0.6 per unit. 61000-3-4:1998 should be used as a guide for both
However for Case 2, the transformer will maintain its real customer and suppliers facing the highest total harmonic
life expectancy for a higher loading. In this case it is not distortion to protect power systems equipment that could
sufficient to apply the standards. Even if the IEC TR be affected by high harmonic currents and raise the
61000-3-4:1998 Standards are applied for both the cases; quality of power supply. By conducting this research, a
there will still be a loss of life at a higher loading because better understanding could be gained about these
the lifespan will be maintained only at 90% of the load. harmonic problems and harmonic contents.

TABLE II: HARMONIC DISTORTION FOR A TRANSFORMER LOAD COMPARE WITH THE
STANDARD
Maximum Limit of MS
Harmonic Measured data (A) Measured data (A) 1555:2002(IEC TR 61000-3-
No. (Case 1) (Case 2) 4:1998)
1 100 100
3 33.83 13.2 21.6
5 29.62 10.16 10.7
7 19.35 5.66 7.2
9 14.7 4.1 3.8
11 6.81 2.1 3.1
13 5.07 1.78 2.0
15 3.25 1.8 0.7
THD% 51.91 18.36 25.72

Figure 1: Daily load cycle for the transformer

TABLE III: THE BREAKDOWN OF LOSSES IN DISTRIBUTION TRANSFORMER


Rated Load losses Harmonic Corrected losses
Type of loss losses(W) (W) multiplier (W)
No load 2500.000 2500.000 2500.000
I2R 12500.252 3967.000 3967.000
Eddy current 8374.800 2658.000 7.1222 18930.000
Other stray 4124.900 1309.000 1.5418 2018.000
Total losses 27499.952 10434.000 27415.000

2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-107 page 4
25
ACKNOWLEDGMENT
The authors gratefully acknowledge the Ministry of Higher
20
Education (MoHE) for the financial support of this project.

REFERENCES
Real Life (year)

15
[1] Delaiba, A.C., de Oliveira, J.C., Vilaca, A.L.A. and Cardoso,
J.R. (1996). The Effect of Harmonic on Power Transformer
10
Loss of Life. Proceedings of the 38th Midwest Symposium on
Circuits and Systems.13-16 August. Rio de Janeiro: IEEE, 933 –
936.
[2] Radmehr, M.; Farhangi, S.; Nasiri, A. (2006). Effect of Power
5
Quality Distortion on Electrical Drives and Transformer Life in
Paper Industries: Simulation and Real Time Measurements.
Pulp and Paper Industry Technical Conference, 2006. 18-23
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 June 2006. Iran: IEEE, 1 - 9.
Load(pu) [3] Emanuel, A.E. and Xiaoming Wang. (1985). Estimation of Loss
of Life of Power Transformers Supplying Nonlinear Loads.
Figure 2: The transformer life versus loading in presence IEEE Transactions on Power Apparatus and Systems. March
of harmonic using measured data for Case-1 .628 – 636.
(THD=51.91%) [4] Samesima, M.I., Wilson Resende, J., and Araujo, S.C.N. (1995).
Analysis of transformer loss of life driving nonlinear industrial
loads by the finite elements approach. IEEE Industry
Applications Conference, 1995. Thirtieth IAS Annual Meeting,
25 IAS '95. 8-12 Oct. 1995. Orlando, FL: IEEE, 2175 – 2179.
[5] Pierrat, L., Resende, R.J. and Santana, J. (1996). Power
transformers life expectancy under distorting power electronic
20 loads. Proceedings of the IEEE International Symposium on
Industrial Electronics. ISIE '96. 17-20 June. Warsaw: IEEE,
578 – 583.
[6] Marzband, M. and Shaikholeslami, A. (2006). A program for
Real Life (year)

15
harmonic modeling of distribution network transformers and
determination of loss in the transformers and the amount of
10
decrease of their life. International Conference on Power
Electronics, Drives and Energy Systems, 2006. PEDES '06. 12-
15 Dec. New Delhi: IEEE, 1 – 6.
5
[7] Elmoudi, A.,Lehtonen, M. and Nordman, H. (2006). Effect of
harmonics on transformers loss of life. Conference Record of
the 2006 IEEE International Symposium on Electrical
Insulation, 2006. 11-14 June. Espoo, Finland: IEEE, 408 – 411.
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 [8] IEEE Std C57.110-1998 “IEEE Recommended Practice for
Load(pu) Establishing Transformer Capability When Supplying Non-
Figure 3: The transformer life versus loading by using sinusoidal Load Currents”.
[9] Jayasinghe, N.R., Lucas, J.R. and Perera, K.B.I.M. (2003).
the maximum limit of MS 1555:2002.( IEC TR 61000-3- Power System Harmonic Effects on Distribution Transformers
4:1998) and New Design Considerations for K Factor Transformers.
IEEE Sri Langka Annual Sessions. September 2003. Sri Lanka:
[10] Tofoli, F.L., Sanhueza, S.M.R. and Oliveira, A. (2006). On the
25
Study of Losses in Cables and Transformers in Nonsinusoidal
Conditions. IEEE Transaction Power Delivery. April 2006.
Uberlandia, Brazil: IEEE, 971-978.
[11] Masoum, M.A.S. and Fuchs, E.F. (1994). Transformer
20
Magnetizing Current and Iron-Core Losses in Harmonic Power
Flow. IEEE Transactions on Power Delivery. January 1994.
Boulder, CO, USA: IEEE, 10 – 20.
Real Life (year)

15 [12] Sharifian, M.B.B., Faiz, J., Fakheri, S.A. and Zraatparvar, A.


(2003). Derating of Distribution Transformers for Non-
Sinusoidal Load Currents Using Finite Element Method. ICECS
10 2003. Proceedings of the 2003 10th IEEE International
Conference on Electronics, Circuits and Systems. 14-17
December. Iran: IEEE, 754 – 757.
5 [13] Owen. C. G. (2005). The Impact of Harmonic Distortion on
Power Transformers Operating Near the Thermal Limit. Master
Dissertation. University of Johannesburg.
[14] De La Rosa, F. (2006). Harmonics and Power Systems. (1st ed.).
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 Boca Raton, London NY: Taylor & Francis Group.
Load(pu) [15] IEEE C57.96, Guide for Loading Dry-Type Distribution and
Figure 4: The transformer life versus loading in presence of Power Transformer.
[16] IEEE Std C57.91-1995, Guide for Loading Mineral-Oil-
harmonic using measured data for Case-2 (THD=18.36%) Immersed Transformers.

2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-107 page 5

View publication stats

Вам также может понравиться