Вы находитесь на странице: 1из 66

Tulkarem Hospital

-BOQ-

Construction of the third floor in Tulkarem Hospital

-BOQ-

1 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

1 Preliminary works prior to the construction of the new floor

* The contractor shall, when pricing the rates of this bill, take
into consideration to include and allow for the costs or
expenses of all requirements stipulated herein below or in
the preambles, drawings and the specification of the
tender.
* The contractor should visit the site to verify the amount of work
and consider all other works for the proper construction of the
new floor.
* The disposal& demolished materials shall be carried out from
the construction zones through special arrangements to external
hospital yards to avoid disturbances/ noises or dust spreading
down the floors or neighboring areas. the contractor is
responsible for the disposal of all demolished and removed
materials from the site to a dump site approved by the
municipality.
* The contractor should coordinate with the client for any possible
material or elements that need to be preserved and handed over
to the client stores.
* The preserved elements such as steel doors& widows, steel
grills, steel hand rails, steel steps and metal protections for fans
shafts& service openings shall be re installed for the new
construction as directed by the engineer. while the other
materials should be handed over to the client stores.

* The contractor should take all measures to protect the hospital


belongings from any damage or disturbance to it’s functioning
systems and to ensure the safety of the hospital users during
the construction stage,
The contractor shall protect the underneath floors from leakage
or penetration of rain water from the roof above which the new
floor will be constructed.
Therefore, special arrangement and prtection zone shall be
erected in full coordination with the hospital directorate and the
engineer.
* The contractor should also protect all existing mechanical,
drainage systems and electrical networks . This include the
conduct of any necessary arrangements to ensure continuous
functioning of these systems during construction stage.

* The contractor should also take all necessary shoring measures


to protect the existing building elements during all stages of
work until safely completing all new construction work.

* The contractor should submit a clear methodology for the


proposed stages of work and protection and shoring methods
for the Engineers approval prior to commencement of works.

* Careful demolishing and reinstatement of existing structural


elements for proper construction of the new floor works; all as
sown in the demolishing plan and in accordance with the
engineer's instructions. The work includes but not limited to :
1.1 Demolishing and removal of all elements covering the steel LS 1
reinforcement for the columns starters on the existing roof, such
concrete, blocks, stone, filling materials....etc, including the
preserving and cleaning of steel reinforcement for proper
erection of the new columns (this is true for all existing columns
including perimeter columns).

2 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

1.2 Demolishing the existing concrete roof slab for the machinery M2 250
room located on the existing roof. The unit price shall include
dismantling and removal all the utilities and finishing layers
above the slab including the sloped light weight concrete, water
proofing layers. All as directed by the Engineer.

1.3 Demolish concrete slabs of the existing staircases, including M2 60


protection and preservation of the existing finishing works such
as, staircase steps, landings, tilling, steel doors, handrails
aluminum windows, walls finish and all other electrical&
mechanical utilities, fittings and equipments. …etc. the voids for
the staircases shall be protected by rigid and safe formwork or
scaffolding through out the construction stage.

1.4 Demolish and removal of concrete roof slabs for existing M2 100
elevators shafts (roof& floor) including the protection and
preservation of all existing finishing works, steel doors, steel
steps& handrails, grills--etc, and all other electrical& mechanical
utilities, fittings and equipments, machines. …etc. the work also
includes cuttings/ making new openings for elevators doors
through the existing concrete walls to match the new proposed
locations of the elevators and perform concrete filling/
patching/adjustment of the existing doors openings at the roof.
the voids for the elevators shall be protected by rigid formwork
or scaffolding through out the construction stage.

1.4 Demolishing and removal of the existing concrete or block M2 500


partitions, or external stone walls, this shall include demolishing
of the other wall finshes in the machinery room at the existing
roof level. The unit price shall include dismantling and
preserving the existing windows and doors . All as directed by
the Engineer.

1.5 Demolishing and removal the finishing layers on top of the M2 300
existing roof slabs including the sloped light weight concrete,
and machine foundations. All as directed by the Engineer.
(provisional)

1.6 Careful dismantle and preserve the doors of staircases at the LS 1


existing roof level, windows, steel hand rails& landing,
machinery protections& coverings, shafts sheets covering…etc.
the price includes re- installtion of the same dismantled units or
structures. Hence all parts and elements shall be preserved and
maintained in good condition. All as directed by the Engineer.

3 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

1.7 Careful dismantle, demolish and removal of the existing sky light L.S 1
structure (between grids10-13&H-J) including all elements that
blocks the construction of new design layout. The price includes
the re-installtion of the same dismantled sky light and the steel
structure at the new roof level. Hence all parts and elements of
the sky light such as transparent sheets, metal sections&
profiles, plates, anchors, sheets, flashing.......etc should be
carefully dismantled and reserved in good condition. the void for
the sky light shall be protected by rigid and safe formwork or
scaffolding throughout the construction stage. The price shall
include also cuttings in concrete walls for new windows
openings and treming the concrete wall to fit the details as
shown in drawings.

1.8 Dismantle and demolish parts of the existing stone roof parapet, M2 100
circular parts and parts of the chimney walls, including the
preservation of stone courses.

1.9 Careful removal of existing coping for the stone parapet and MR 245
preservation for use in the construction of new stone parapet.
All as directed by the Engineer.

Total of preliminary works carried to summary sheet

4 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

2 Concrete Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the tender.
All concrete works includes the supply of ready mix concrete,
placing& casting, formwork & supports, reproping, shuttering,
vibration, curing, testing and whatever needed for the
completion of the works all in accordance to the standards,
codes, specifications and as details shown in drawings.

2.1 Supply and cast reinforced concrete B300 for columns of M3 70


various dimensions and locations, maximum size of aggregate
20mm as shown on drawings.
2.2 Supply & cast concrete B300 for 31cm thick ribbed slabs M2 1700
including Light weight block "EYTONG" and drop beams as
shown on drawings. The rate includes casting the slab in stages
by providing several construction joints in order to allow for
lifting the existing chillers, machines and equipments before
completing the work. the rate also includes the special
treatments of the construction joints in accordance to the
construction codes and standards.

2.3 Ditto, but for 49cm thick ribbed slabs. M2 200


2.4 Ditto, but for 15 cm thick solid slabs. M2 95
2.5 Ditto, but for 18 cm thick solid slabs. M2 95
2.6 Supply and cast reinforced concrete B300 for staircase flights, M3 25
steps, landings and machine foundations of various sections.

2.7 Supply and cast reinforced concrete B300 for walls of various M3 145
thickness, dimensions and different locations.

2.8 Supply and cast concrete B300 behind stone walls for backing M3 200
the stone work and for windows and door lintels and where
needed; all in accordance with the engineer instructions.

2.9 Deformed high yield steel bar reinforcement of various TON 130
diameters, characteristic strength FY=420N/mm2 for concrete
reinforcement, as shown on drawings and according to
specifications.

Total of Concrete Works carried to civil summary

5 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

3 Stone Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs and expenses of
all requirements stipulated in the preambles, drawings and
technical specification of the contract. The price includes
scaffolding, formworks, supports, cutting, trimming, chamfering,
galvanized anchors& pins, angles as specified and flush
pointing works composed of white cement and sand (1/2) with
approve additive for better workability, tightness and water
proofing. The stone finishing and dressing for the new stone
works shall be similar to that rendered at the lower floors of the
existing hospital building. The unite rate shall also include cost
of all required stone pieces, (such as windows and doors
jambs, sills, lintels, corners, key stones, any other special stone
pieces etc..); all as per the stone works rendered in the lower
floors of the existing hospital and to the engineer instructions.
Accordingly, no separate cost allowance for the stone pieces.
The unit rate shall also include the cost of pointing the stone
work.

3.1 Supply and install 5 cm thick 25 cm wide Taltish stone courses M2 950
from first quality Jama'en as shown on drawings. The unit rate
shall include cost of 10cm hollow concrete blocks and anchors
for the stone walls as per drawings.

3.2 Ditto, but 4 cm thick stone cladding. The rate includes cost of M2 40
B200 concrete backing, anchors and 6 mm steel mesh. The rate
includes all anchoring details as shown on drawings.

3.4 Supply and install 8 cm thick stone coping , 36 cm wide a stone MR 100
roof parapet copping made from Jama'en stone . The price
includes stone pointing.

3.5 Re-install stone copping which was dismanteled and preserved MR 150
from the existing parapet.

Total of Stone Works carried to civil summary

6 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

4 Block Work:
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
4.1 Supply and construct 10cm hollow concrete block in cement and M2 2200
sand mortar (1:4) for internal portion walls, the price includes
cost of cutting, anchors, bonding, jointing, utilities openings
complete as per drawings, specifications and as directed by the
engineer.

4.2 Ditto, but 20 cm hollow concrete block . M2 1050

4.3 Ditto, but 7 cm hollow concrete block around column starters on M2 100
the new roof including sand cement mortar fill.
Supply and cast B300 concrete lintels or griddles above block M3 40
works at door or window level across the whole length of block
walls and in places as directed by the engineer. The price
including shuttering and the supply & installation of steel
reinforcement 4nos of 12mm dia. and with stirrups 8mm @ 20
cm c/c
4.4 Supply and install 3 cm "Randopan" extruded polystyrene M2 930
boards for external stone walls, of density 24 kg/m3 as shown
on drawings.

Total of Block Works Carried to Summary Sheet

7 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

5 Plastering Works:
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
5.1 Supply and install internal plastering for walls, columns, arches M2 5200
drop beams, softies of slabs & beams, shaft walls etc
,composed of 3 coats, a bond coat 1:1, base coat 1:4, and finish
coat 1:5 as specified. The price includes the corner beads,
casing beads, metal lath, scaffoldings, shuttering, bonding
agents and the requirements as specified .

5.2 Ditto, but supply and install internal plastering for ceiling M2 900

5.3 Ditto but supply and install external plastering for parapet wall, M2 800
external walls or shafts and wherever needed composed of 3
coats a bond coat 1:1, a base coat 1:4 and a finish coat 1:2 with
water proofing materials all as specified.

Total of Plastering Works carried to Summary

8 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

6 Flooring and Covering Works:


The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
6.1 Supply and install 30x30x3cm Terrazzo floor tiles similar to M2 890
Halonim # 75 or equally approved. Rate includes 30cm x 10cm x
1 cm skirting, 3 cm cement sand mortar (1:3 ), sand fill
materials, cuttings, fittings, trims, grouting with white cement
and polishing, all in accordance with the specifications and
applicable Standards.

6.2 Supply and install 20x20cm glazed ceramic class (A) tiles for M2 900
walls cladding of different colours. The tiles shall be laid and
fixed to the walls in patterns, style and forms of grouting&
jointing as directed by engineer using approved adhesive
materials. The price also includes the cost of surface
preparation to receive tiles, which shall include two coats of
cement plaster (scratch and float coat), approved adhesive
materials, grouting, aluminum protection angles as approved by
the engineer.

6.3 Ditto, but 30x30cm ceramic tiles class (A) "Negev" model # M2 1500
9001 or equivalent for walls cladding of different colours. The
tiles shall be laid and fixed to the walls in patterns, style and
forms of grouting& jointing as directed by the engineer using
approved adhesive materials. Price includes the cost of surface
preparation to receive tiles, which shall include two coats of
cement plaster (scratch and float coat), approved adhesive
materials, grouting, protection angles as approved by the
engineer.

6.4 Ditto, but anti bacteria ceramic 20x20cm class (A) closured wall M2 130
tiles for surgery& sterile stores using special adhesive materials
and anti fungus grouting materials as per manufacturer
instructions and in accordance with the MOH requirements and
related Standards.
6.5 Supply and install non slip ceramic floor tiles class (A) M2 200
20x20*0.8cm of different colours, the price includes the mortar
(1:3) with water proofing materials, the sand cement fill,
cutting& trimming around floor utilities and pointing as specified.
the tiles shall be laid and fixed in patterns, style and forms of
grouting& jointing as directed by the Engineer.

6.6 Ditto, but 30*30*0.8 cm granite porcelain floor tiles of different M2 900
colours as made by TAU ceramic, Matt finish or equivalent, the
tiles shall be laid and fixed in patterns, style and forms of
grouting& jointing as directed by the Engineer.
6.7 Ditto but 2cm thick Perlato marble for elevator walls, the rate M2 50
include cuttings, recesses for utilities, cut pieces, rounding,
jointing& polishing, anchoring& all fixing accessories. The work
covers the cladding of elevator door sides and lintels.

6.8 Supply and install 3cm thick, 10.5 cm wide local polished cut MR 120
stone for window thresholds with mitered edge as shown on
drawings.

9 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

6.10 Supply and install 3cm thick "Perlato" marble for stair No. 75
treads(155*34*3 cm) polished one face & edge with chamfered
edges matching the existing material . The treads should be
bedded on 3cm mortar (1:3), a sand bed and pointing works.
The rate includes an edge piece for water stop.

6.11 Ditto but 2cm thick riser(155*14 cm). No. 74


6.12 Ditto but 3 cm thick 30 cm wide for staircase landing. M2 50
6.13 Ditto but 2cm thick for steps skirting. No. 75
6.14 Ditto but 1cm thick 7cm high for landing skirting. MR 75
6.15 Supply and install Anti static PVC flooring type "Teraclean", M2 200
2mm thick or equivalent for surgery room, sterile stores and as
directed by the engineer. The price includes the installation of
skirting and copper mesh under tiles every 30cm using 1cm
wide copper strip. This mesh should be connected with the earth
system of the building. The pvc flooring should be fixed using
conductive adhesive and complete seal of joints all in
accordance to manufacturer instructions and MOH regulations
standards. The Installations for pvc flooring, skirting,
terminations with walls/outer& inner corners shall be strictly
implemented by professional and in accordance to the
manufacturer's recommendation.

6.16 Ditto, for sterile area but with out copper strips. M2 100

6.17 Supply and install VINYL Anti static flooring type Armstrong M2 30
2mm thick or equivalent for surgery rooms, sterile stores and as
directed. The price includes the installation of skirting and
copper mesh under tiles every 30cm using 1cm wide copper
strip . This mesh should be connected with the earth system of
the building. The pvc flooring should be fixed using conductive
adhesive and complete seal of joints all in accordance to
manufacturer instructions and MOH standards.

6.18 Ditto, for sterile area but with out copper strips. M2 30

Total of wall and floor cladding Works carried to Summary


Sheet

10 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

7 Water Proofing
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
7.1 Supply and install roof water proofing membrane 5mm thick M2 2300
covered with quartz granules, Pazkar or equivalent, for main
roof, machines roofs, stairs roofs, parapet walls and where
required the price includes the application of primer coat GS474
at a rate of 25 kg /m2, installation of 15*15cm angle fillet,
grooves, groove sealant, groove cover, joints over lapping,
backing sheets or pieces all around external& internal corners,
roof drains, machines foundations or up stands, roof door
thresholds and silver paints along the joints and all necessary
material and workmanship to complete the works as shown in
the drawings and as per manufacturer instructions and codes of
practice.
7.2 Supply and apply three coats of bitumen (25/75) at rate of M2 270
500g/m2 for each layer with two layers of fiberglass in opposite
directions including primer coat GS474. The price includes
5*5cm angle fillet with smooth sand cement mortar(1:3) and
5cm thick sand cement screed with water proofing agent as
surface layer before applying the water proofing coats.

7.3 Supply and install a sloped light weight foam concrete of density M2 2050
1000kg/m3 on the roof ( the thickness to meet the level and
slopes shown on drawings). The rate includes cost of applying
2 cm cement screed layer above the light weight concrete.

Total of Water Proofing carried to summary Sheet

11 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

8 Carpentry Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
8.1 Fabricate, supply and install the following wooden doors
complete with the metal frames, all necessary fixing
accessories, glazing, heavy duty roller hinges, stoppers,
louvers, grills, the required hydraulic closures, hardware,
protection panels and ironmongery , painting of the frame and
the exposed wooden surfaces of the door panels, the unit rate
shall also include all the works described herein below:

* The wooden door leaf shall be 45mm thick with required filling, 5
mm thick class A plywood facing on each side, the exposed
surfaces of the door panel shall be hard wood "Zan" 52*35 mm
tongued and grooved in the internal wooden fillings, sealing
strips around door panel, and door closure German made where
shown and required on the drawings, all as shown on the
drawings.
* Supply and install of heavy duty hinges, locks, cylinders are
"Yardini" or equivalent. locks to toilets-vacant/ occupied "Yardini
" type 7008 all doors shall be provided with master key system.
The hierarchy shall be specified before the supply of lock sets.

* Door handles shall be steel handles similar to Hewi type


zg1113bb and type fbg 1113 or equivalent. The colour to be
selected by the Engineer.
* Supply and installation of formed galvanized steel frame 1.5mm
thick of required width according to the wall thickness, buckets
for cylinders& locks, recess for hinges with backing plates ,
rubber knobs, side anchoring& bottom bracing and concrete
filling as specified in drawings. The frames shall be fabricated
and assembled by specialized manufacturer with all required
accessories.
* Door protection 2mm stainless steel U shape for the both sides
as shown on drawings.
* Door protection where needed as per drawings of 2mm
"Decosheet" (SPM ) or equivalent including all necessary
fittings & fixings complete as per manufacture
recommendations, the colour will be as per Eng. approval.
* Supply and installation of PVC inflammable 'Taraflex' or
equivelant 2mm thick cladding on both sides of the door panels.

* All exposed edges , louvers and door frames are" Zan" wood
and should be painted with 3 coats of liquor paint. the metal
doors frames shall be painted with primer coat of meginol
special gray 270-004 and two coats of polyour matt oil. the
colour shall be selected by the engineer.
* Door filling material should not be less than 80%.
* Rate for smoke proof doors include 100% filling , sealing strips
around door panel including the bottom of panel.
8.1.1 D01 ( 1.20 * 2.10 m) No. 23
8.1.2 Ditto, but D01G ( 1.20 * 2.10 m) with grills No. 3
8.1.3 D02 ( 1.10 * 2.10 m) No. 3
8.1.4 D03 ( 0.95 * 2.15 m) No. 21
8.1.5 D04 ( 0.95 * 2.10 m) No. 12

12 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

8.1.6 Ditto, but D04G ( 0.85 * 2.10 m) with grills No. 7


8.1.7 D05 ( 0.95 * 2.15 m) No. 2
8.1.8 D06 ( 0.85* 2.15 m) No. 9
8.1.10 D07 ( 0.85 * 2.15 m) No. 3
8.1.11 D08 ( 1.60 * 2.10 m) operate electrically and manually with inter- No. 3
come system
8.1.12 D09 ( 1.70 * 2.10 m) No. 1
8.1.13 D10 ( 1.70 * 2.10 m) operate electrically and manually with inter No. 2
come system
8.1.14 D11 ( 270 * 2.10 m) operate electrically and manually with inter No. 1
come system
8.1.15 D12 ( 1.60 * 2.10 m) located in the Children day room No. 1
8.2 Nurse station , desks and cabinets
Fabricate, supply and install the following units, as in drawings
with all fixing accessories, drawers, shelves, hardware, and
ironmongery with a master key and made of:
18mm thick plywood for wall hung and lower cabinets, plastic
laminated " top quality from outside and laminated with regular
Formica from inside, 12mm thick sandwich panel for shelves
laminated with regular Formica. For dimensions refer to detailed
drawings.
8.2.1 kitchen lower and upper cabinets ( 120 cm length) Room No. 72 No. 1
including granite counter top "Tiger eye" with top& bottom
skirting, beads, polishing, routings, jointing…etc and all
preparatory woks for the installation of the required sink and
sanitary fixtures.
8.2.2 Ditto, but 125cm length for Room No. 28 No. 1
8.2.3 Ditto, but 130cm length for Room No. 22,32 and 65. No. 3
8.2.4 Ditto, but 135cm length for Room No. 59 No. 1
8.2.5 Room No. 31 working station, lower& upper cabinets. No. 1
8.2.6 Room No.37 working station, lower& upper cabinets. No. 1
8.2.7 Room No. 64 working station, lower& upper cabinets. No. 1
8.2.8 Room No. 97 utility working station, lower& upper cabinets. No. 1
8.2.9 Nurse station C1 No. 1
8.2.10 Nurse station C2 No. 1
8.2.11 Nurse station C3 No. 1
8.2.12 Nurse station C4 No. 1
8.2.13 Electrical cabinets of different sizes. No. 5

Total of Carpentry Works Carried to Summary Sheet

13 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

9 Suspended ceiling
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract. Rates for all suspended
ceilings works includes suspension system with anchors to the
structure, L& Z, main& main profiles, omega profiles. clips,
gaskets and all necessary fittings in accordance to the
manufacture technical data and related standards covering this
type of works, The rate includes also cutting and preparation for
installing lighting fixtures, ceiling recess, maintenance
openings, grills, ceiling utilities... etc.

9.1 Supply and install suspended ceiling for bathroom, utilities and M2 200
wet areas made from 30cm non perforated formed galvanized
metal trays of 0.6mm thick and 45mm high. The trays should be
supplied pre painted and oven cured. The unit rate shall also
include acoustic rock wool mats, 25mm thick and 25kg/m3
density, wrapped in black non inflammable dust proof sags in
accordance with specifications and the related Standards.

9.2 Ditto, but perforated sheets(12%-20%) perforation and of 40cm M2 600


wide. The unit rate shall include cost of the of 25mm thick rock
wool.
9.3 Ditto, but 60*60cm perforated sheets for the waiting area with M2 220
approved acoustic material "Soundex " or equivalent in
accordance to the related safety standards, rules and
regulations.
9.4 Supply and install 60*60cm suspended ceiling for operating M2 150
room, ECOPHONE HYGINE Type Protect "A" (non perforated).
The price should include galvanized suspension system with
anchors to the structure, bacterial resistant, moisture resistant,
with standing relative humidity up to 95% at 30c fire resistant
tiles, including access panels, fittings, fixing, installation of a
closed cell gasket between the grid and panel including
retention clips to insure good seal , complete all as
specifications and drawings.

9.5 Ditto, but for clean room areas type "Clima Plus USG" class M2 300
100 ceilings or equivalent.
9.6 Ditto, but 60x60cm acoustic tiles suspended ceiling, type M2 100
Armstrong Georgian drop type or equivalent.

9.7 Supply and install vertical and horizontal gypsum boards 12mm M2 250
thick for walls and ceiling cladding and for other decorative
works. The price shall include all decorative beams, edges,
recessed slab, squares, cuts, suspension& structural profiles--
etc to any shape and patterns to complete the works as
approved by the engineer.

Total of Suspended Ceiling Works carried to Summary


Sheet

14 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

10 Painting Works:
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
Type of paint shall be in accordance with the specification and
the applicable Standards. The contractor should allow in his
pricing that the engineer will use as many different colours or
combination of colours to meet an approved colour scheme.

All paint works should conform to manufacturer instruction


regarding number of coats , rate of application or drying time
10.1 Supply and apply cement sand filling layer to the ceiling and M2 500
walls above false ceiling level. (provisional)
10.2 Supply and apply emulsion paint on plastered walls composed M2 2100
of two coats of putty and 3 coats of " supercryel " emulsion
paint.

10.3 Supply and apply polysid paint. M2 830


10.4 Supply and apply oil paint for walls composed of two coats of M2 600
putty, one coat of under coat and 2 coats of " polyour".
10.5 Supply and apply oil paint for metallic surfaces "Superlac" of M2 80
including surface preparation.

Total of Painting Works carried to Summary Sheet

15 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

11 Metal Works:
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.
11.1 Aluminum Works
Fabricate supply and install the following powder coated
aluminum doors & windows Napco or equivalent, complete
with double glazing ,sekurit, silicone, handles, locks and oplite
fly screen. Shop drawings must be submitted. All as shown in
drawings and approved by the Engineer .

11.1.3 W1(1.56 * 0.90 m) No. 40


11.1.4 W2 (1.30 * 0.90 m) No. 4
11.1.5 W3 (1.56 *1.00 m) No. 3
11.1.6 W4 (0.90 *1.82 m) No. 4
11.1.7 W5 (1.56 *4.13 m) No. 1
11.1.8 W6 (1.56 *3.05 m) No. 2
11.1.9 W7 (1.56 *1.00 m) No. 3
11.1.10 W8 (1.04 * 0.60 m) No. 3
11.1.11 W9 (0.87 * 3.00 m) No. 3
11.1.12 W10 (0.87 * 2.00 m) No. 2
11.1.13 Wooden glass windows for the Children day room and MR 20
Incubators, the price shall include 6mm glass, the Ironmongery
and carpentry works as per drawings.

11.2 Steel Works


Fabricate supply and install the following steel doors complete
with all accessories such as heavy duty roller hinges, water
flushing, master key, Yale cylinder locks, approved handles,
glazing and all fixing accessories. Door frames are made of
RHS profiles 80/40/32 mm cladded with two 1.5 mm metal
sheets. The price includes steel frame made of bent steel sheet
2mm thick and the required louvers made of 15mm thick bent
sheet metal. Shop drawings must be submitted and approved
before fabrication.

11.2.1 D12 ( 1.10 * 2.10 m) multi lock smoke proof doors similar to " No. 3
Raf Barih" or equally approved
11.2.2 Ditto, but D13 ( 0.90 * 2.10 m) No. 1
11.2.3 D14 (1.00 * 2.10 m) No. 4
11.2.4 D15 (1.35 * 2.10 m) No. 1
11.2.5 D16 (0.80 * 2.10 m) No. 1
11.2.6 D17 (1.50 * 2.10 m) No. 2
11.2.7 D17 (2.20 * 2.10 m) No. 1
11.3 Fabricate supply and install steel handrails, similar to the MR 45
existing handrail in the staircase and as shown on drawings,
including fixing accessories, matching the . The rate includes
panting the hand rails with 2 coats of anti rust primer and oil
paint.

Total of Metal works carried to summary sheet

16 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

12 Other Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allow for the costs or expenses of all
requirements stipulated in the preambles, drawings and
technical specification of the contract.

12.1 Supply and install Avis curtain rail as per detailed drawing, Mr. 295
complete with all fixing accessories, Aluminum carrier main
profile and locks.

12.2 Supply and install wall guard rail similar to the existing rails Mr. 100
rendered at the second floor or equivalent with all fixing
accessories. The rate includes the stop ends and external
corners, colour to be selected by the Engineer.

12.3 Corner protection similar to the existing rendered at the second No. 150
floor or equivalent(2.10 m) height.

12.4 Supply& install 2mm "Decosheet" panel wall protections at the M2 50


beds level cut to size according to the site requirements as
made by (SPM ) or equivalent, including all necessary fittings &
fixings complete as per manufacture recommendations, the
colour will be as per Eng. approval.

12.5 Supply and install a wooden wall guards for corridors with all Mr. 300
fixing accessories as per the detailed drawings and engineer
instructions. colour to be selected by the Engineer.

12.6 Supply& install 2mm "Decosheet" hand plates protections No. 20


around door handles according to the site requirements as
made by (SPM ) or equivalent including all necessary fittings &
fixings complete as per manufacture recommendations, the
colour will be as per Eng. approval.

Total of Other Works carried to Summary Sheet

17 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

13.0 Important Notes: All materials and accessories to be used shall


be according to the Approved Manufacturer List attached to the
electrical specifications (see attachent # 1)
Sec. 13.1) - Electrical Points.
The electrical power supply from electrical switchboard to first
point in circuit shall be included in the unit price of that point (by
means of wires, cables or leads in self extinguishing conduits
and cables). All as per specifications and as required.

13.1.1 Supply, install and connect standard lighting point internal or Comp. 354
external, in slab or over false ceiling, to include a 16 mm
diameter conduit, 1.5 or 2.5 sq.mm cross-section leads or cable,
and, as required single , double, two way or push button lighting
switch , and outlet for luminaries with junction box and terminals.

13.1.2 Ditto but for emergency lighting point Comp. 80

13.1.3 Supply, install and connect a 16A wall socket point - to include a Comp. 65
16 mm dia. Conduit, (3x2.5) sq.mm cross-section leads or
cables, and as required 16 A wall socket .
13.1.4 Ditto as item 13.1.3 but double socket. Comp. 36
13.1.5 Ditto as item 13.1.3 but with water proof socket. Comp. 66
13.1.6 Ditto as item 13.1.4 but with water proof cover. Comp. 13
13.1.7 Supply, install and connect a three-phase (5x16) A, single-circuit Comp. 1
wall socket point, to include a 23 mm diameter conduit, (5x2.5)
sq.mm cross section leads or cables and a (5x16) single-circuit
wall socket accessory .
13.1.8 Supply, install and connect Intercom connection point (Price Comp. 36
includes 16 mm diameter conduit with a standard Intercom
cable, leading from point to the Intercom section in LV box).

13.1.9 Supply, install and connect Public Address System connection Comp. 11
point (Price includes 16 mm diameter conduit with cable,
leading from point to the LV box or to the nearest point).

13.1.10 Supply, install and connect Fire Alarm connection point (Price Comp. 105
includes 16 mm diameter conduit with cable, leading from point
to the LV box or to the nearest point).
13.1.11 Supply, install and connect TV connection point (Price includes Comp. 19
23 mm diameter conduit with cable, boxes , and the socket
outlet leading from point to the LV box).

13.1.12 Supply, install and connect SAT connection point (Price includes Comp. 19
23 mm diameter conduit with cable, boxes , and the socket
outlet leading from point to the LV box).

13.1.13 Supply, install and connect Nurse Call connection point (Price Comp. 125
includes 16 mm diameter conduit with cable, leading from point
to the nurse call station).

13.1.14 Supply, install and connect Computer outlet connection point Comp. 10
(Price includes 16 mm diameter conduit with 4 pairs shielded
cable and socket, leading from point to the nearest HUB in the
nearest LV box).

18 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

13.1.15 Supply, install and connect Telephone socket point in a 23 mm Comp. 19


conduit - to include a 23 mm diameter conduit from nearest
telephone cabinet to accessory output in junction box, standard
socket telephone accessory, and standard 2x2x.5mm2-
telephone lead, inserted from cabinet to accessory including
connection at both ends.
13.1.16 Supply, install and connect point for thermostat to include a 16 Comp. 40
mm diameter conduit installed on one side near socket for fan
coils and termination with a suitable box on other side at
thermostat output. 3 mm thick Nylon draw-string shall be
inserted inside conduit.
13.1.17 Supply, install and connect 6 sq. mm grounding point - to Comp. 20
include a 16 mm diameter conduit, connect at one end to
grounding bus-bar in nearest switchboard, and at other end to
grounded element (air-conditioning ducts, acoustic ceiling, alum.
partitions etc.
13.1.18 Supply, install and connect Emergency push-button point, to Comp. 5
include a 16 mm diameter conduit, (3x1.5) sq.mm cross-section
leads, and a dual contact emergency push-button installed in a
box with frame, transparent plastic cover to be broken in case of
emergency, and engraved bakelite "sandwich" type sign, per
plan (box such as TELEMENIA model ZAS-E25).
13.1.19 Supply, install and connect power point for bed head units, the No. 160
price to include 3x2.5mm2 NYY cable and 23mm dia conduit
from electrical switchboard to BHU junction box with all required
accessories and materials.
13.1.20 Supply, install and connect point as above, but by a 3x1.5 No. 190
sq.mm NYY cable and16mm dia conduit.
13.1.21 Supply, install and connect point as above, but by a 6 sq.mm No. 61
cross-section grounding lead and 23 mm diameter conduit.
13.1.22 Supply, install and connect point as above, but for No. 50
communication, by a 23 mm conduit diameter conduit.
13.1.23 Supply, install and connect point as above, but for telephone in No. 50
B.H.U, by a 23 mm conduit and standard 2x2x.5mm2- telephone
lead.
13.1.24 Supply, install and connect point as above, but for data, by a 23 No. 61
mm conduit and standard CAT 6 lead.
13.1.25 Supply, install and connect lighting point for the suspended No. 9
lighting fixtures in the delivery rooms, the price shall include 16
mm dia. conduit and 3*2.5 sq.mm cable or lead.
13.1.26 Ditto as item 13.1.25, but with 5*4 sq. mm cable or lead and No. 4
23mm dia. conduit for the operating lighting fixtures.
13.1.27 Supply, install and connect a 16A Power Point including 16A No. 40
(1PH) isolator switch, conduits, boxes and cables for the fan coil
units , the works all according to drawings, specifications and
Engineer instructions.
13.1.28 Ditto as item 13.1.27 but for the Exhaust fans on the roof. No. 9
13.1.29 Ditto as item 13.1.27 but for Booster Pumps. No. 10
13.1.30 Ditto as item 13.1.27 but 16A ( 3PH) for Booster Pumps. No. 4
13.1.31 Supply, install and connect a 25A Power Point including 25A No. 1
(3PH) isolator switch, conduits, boxes, cables for the Package
Unit, the works according to drawings, specifications and
Engineer instructions.
Total Sec. 13.1)- Points….carried to summary.

19 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

13.2 - Conduit, Rigid Piping and


Excavation Works
Supply, install and connect Self-extinguishing type plastic
conduit, processed over or under plaster or inside castings,
including junction boxes, unions, connectors, etc. including
excavation , backfilling , sand , tape , manholes and covers and
galvanized draw-strings, ready for use (for works not included in
points works).

13.2.1 23 mm diameter. ML 50
13.2.2 29 mm diameter. ML 50
13.2.3 36 mm diameter. ML 50
13.2.4 50 mm diameter. ML 50
13.2.5 4" diameter. ML 50
13.2.6 6" diameter. ML 50

Total sec. 13.2) - Conduit, Rigid Piping and Excv…..carried


to summary
20 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec. 13.3) - Cables

Supply, install and connect XLPE non-armored type


thermoplastic copper cables, including insertion into conduit or
attachment to structural elements or laying in ductwork,
including all associated materials, insulation materials, unions,
and connection of cable at both ends.

13.3.1 3x400+200mm2+200mm2 cable M.L. 40


13.3.2 3x240+120sq. mm+120sq.mm Cu. M.L. 150
13.3.3 3x185+90mm2+90mm2 cable M.L. 150
13.3.4 3x70+35mm2+35mm2 cable M.L. 50
13.3.5 3x50+25mm2+25mm2 cable M.L. 50
13.3.6 5x16 sq.mm cross section. M.L. 50
13.3.7 5x10 sq.mm cross section. M.L. 210
13.3.8 5x6 sq.mm cross section. M.L. 100
13.3.9 5x4 sq.mm cross section. M.L. 100
13.3.10 3x2.5 sq.mm cross section. M.L. 50
13.3.11 3x1.5 sq.mm cross section. M.L. 50

Total Sec. 13.3) - Cables ……carried to summary

21 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec. 13.4) - Structural Elements, Cabinets and Ductwork

Supply, install and connect Prefabricated ductwork . mounted on


walls or attached to ceilings. Price to include all reinforcing and
attaching hardware, structural elements, brackets, hangers etc,
also price to include all required covers and stands for trunks
fixed on roof or out site.
13.4.1 10/7 cm. M.L. 150
13.4.2 20/7 cm. M.L. 150
13.4.3 40/7 cm. M.L. 150

Total 13.4) Structural Elements, Cabinets….. carried to


summary

22 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec .13.5 ) Grounding Systems


Sec. 13.5.1) - Lightning System
13.5.1 Supply, install and connect Complete lightning system (using L.S 1
pulsars system) including all required materials and accessories,
all according to drawings and specifications and Engineer
instructions.(The contractor is requested to make the required
calculation for the system and take the Engineer approval).

Sec. 13.5.2) - Operational Theaters Grounding


13.5.2 Supply, install and connect a complete earthing system L.S 1
(separated from the general earthing system) for the operation
theaters (4-op.th.) including pits, rods& all required materials
and accessories, all according to drawings and specifications
and Engineer instructions .

Sec. 13.5.3) - Building Grounding (Provisional Item)


13.5.3 Supply, install, connect and test the earthing system including L.S 1
cables , rods , pits ,checking boxes ,main earthing box with
equipotential bus bars ,and connecting to the existing foundation
earthing ready for operation according to specifications,
drawings and engineers instructions .

Total sec. 13.5) - Grounding …..carried to summary

23 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec. 13.6) - Electrical Switchboards


a. Supply, install and connect the electrical switchboards to the
site, including all associated materials and labor, as described in
the technical specifications.
b. Cabinets with no access from the rear, made up of transparent
polycarbonate cells, or sheet-metal cabinets with a 25% surplus
space.
c. The switchboards are to be placed on the floor, in a niche
against the wall.
d. Main supply lines enter from the switchboard bottom, top or
side, while outgoing lines exit the switchboard from both its
bottom and top sides.
e. Price to include all structural elements required in order to install
the switchboard, including bus-bars, terminals, wiring, bolts,
clamps, etc. and for the equipment listed below.

f. The switchboards shall contain accessories shall be according


to the approved manufacturer list.
g. Prices for supply, installation and connection of various
accessories including all associated labor and materials such as
bus-bars, terminals, wiring reinforcements, mounts, engraved
"sandwich" type identification plates, etc. including connection to
mains supply - complete ready for use.

h. The price shall include connection of the distribution board to the


existing MDB.

13.6.1 P31 Unit 1


13.6.2 P32 Unit 1
13.6.3 P33 Unit 1
13.6.4 P34 Unit 1
13.6.5 POP Unit 1
13.6.6 MCC Unit 1
13.6.7 P-Lift ( Provisional Item) Unit 1
13.6.8 MCCB 320 A inside the existing MDB (Provisional) Unit 1
13.6.9 MCCB 250 A inside the existing MDB (Provisional) Unit 1

Total sec. 13.6) Electrical Switchboards…..carried to


summary.

24 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec. 13.7- Luminaries Supply and Installation


a. Supply and installation of lighting fixtures as described below,
including all necessary accessories, required in order to light it
with lamps and electronic rapid starter, complete, according to
the approved manufacturer list.
b. All lamps shall be of the energy-saving type (18,36, 58 Watts).

13.7.1 Type (A) 2x36W fluorescent light fixture Prismatic type. Unit 43

13.7.2 Type (AE) Ditto as A but with emergency charger. Unit 18

13.7.3 Type (B) Down light, with reflector lamp recessed in false ceiling Unit 61
40W, IP44 die cast aluminum and stainless steel safety glass
reflector of pure anodized aluminum.
13.7.4 Type (C)18W fluorescent light fixture with polycarbonate body Unit 31
white and opal diffuser, wall mounted, IP54.
13.7.5 Type (E) 1 x 8W fluorescent emergency exit sign luminaries Unit 12
with white steel body, for maintained emergency lighting of 3
hour duration, legend panels (3) included (down, left and right).

13.7.6 Type) 5W Recessed night light corrosion proof IP65. Unit 18


13.7.7 Type) Ceiling mounted lighting 2XPL-L 11 lamp compact Unit 10
fluorescent with opal diffuser controller IP20.

13.7.8 Type (JE) Ditto as J but with emergency charger. Unit 4

13.7.9 Type (O1) 2x34W sealed fluorescent lighting fixture , recessed Unit 8
in false ceiling, with prismatic diffuser, IP65.

13.7.10 Type (EO1) Ditto as O1 but with emergency charger.. Unit 2

13.7.11 Type (O2) 4x18W sealed fluorescent lighting fixture , recessed Unit 60
in false ceiling, with prismatic diffuser, IP65.

13.7.12 Type (EO2) Ditto as O2 but with emergency charger. Unit 16

13.7.13 Type (K) 2x36W, fluorescent lighting fixture, ceiling mounted Unit 60
with prismatic diffuser ( Internal primes) IP20.
13.7.14 Type (KE) Ditto as K but with emergency charger. Unit 19

13.7.15 Type (L) Down light, recessed in false ceiling, with PL-C 13 W Unit 19
compact fluorescent energy saving lamp, cast aluminum cover
and ring silver ( frosted) aluminum reflector, IP20.
13.7.16 Type (M) 2x36W, fluorescent lighting fixture, ceiling / pendant. Unit 4
Body of grey fiber-glass reinforced polyester, prismatic
polycarbonate diffuser, IP54.
13.7.17 Type (ME) Ditto as M but with emergency charger. Unit 2

13.7.18 Type (P) 4x18W, fluorescent lighting fixture, recessed in false Unit 18
ceiling, with prismatic diffuser ( Internal primes), IP20.
13.7.19 Type (QE) Ditto as P but with emergency charger. Unit 2

13.7.20 Type (Q) 4x18W, fluorescent lighting fixture, recessed in false Unit 10
ceiling, with double parabolic reflector and louvers, IP20.

13.7.21 Type (QE) Ditto as Q but with emergency charger. Unit 9

Total sec. 13.7 )Luminaries Supply…carried to summary

25 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec 13.8- Nurse Calling System


Note: All equipment items for the nurse- calling system shall be
according to the approved manufacturer list.. The work to
include the supply of the equipment specified, installation of
same, connection, wiring, commissioning and all other details,
as specified in the technical specification and drawings.

13.8.1 Master station 30- call master. Unit 1


13.8.1 Master station 20- call master. Unit 1
13.8.2 Reset button. Unit 17
13.8.3 Bedside call switch. Unit 65
13.8.4 NBY-1A metal jack. Unit 65
13.8.5 Corridor lamp. Unit 34
13.8.6 Call button. Unit 2
13.8.7 Ceiling mount 180mm O(7-1/8"O) NB-L Unit 17
13.8.8 Moisture resistant pull cord switch. Unit 17
13.8.9 Power supply. Unit 2

Total Sec.13.8) Nurse Calling System Carried to Summary

26 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec 13.9-Fire Alarm System


Supply install and connect complete in place and in an operable
manner the fire alarm system. The work is to include the supply
of the equipment specified, installation of same connection,
wiring, cables, commissioning and all of the details and
connecting to the existing system as specified in the technical
specifications and drawing type shall be according to the
approved manufacturer list.
13.9.1 (Provisional Item) Main addressable fire alarm control panel for Unit 1
500 addressable points, expandable up to 1000 points with
batteries and charger.

13.9.2 Manually operated alarm call point . Unit 13


13.9.3 Indoor fire alarm siren . Unit 4
13.9.4 Ionization smoke detector. Unit 78
13.9.5 Intelligent heat detector. Unit 1
13.9.6 (Provisional Item) Automatic telephone dialer. Unit 1
13.9.7 24v DC Magnetic Door Holder for fire doors Unit 3

Total Sec. 13.9) Fire Alarm System Carried to Summary

27 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec 13.10 - Intercom System


Note: All equipment items for the intercom system shall be
according to the approved manufacturer list.. Work is to include
the supply of the equipment specified installation of same,
connection, wiring, commissioning and all other details, as
specified in the technical specifications and drawings.

13.10.1 Hands free master station. Unit 6


13.10.2 Power supply adaptor. Unit 6
13.10.3 Door phone adaptor. Unit 6
13.10.4 Door station . Unit 6
13.10.5 Power supply adaptor. Unit 6
13.10.6 Door release. Unit 6
13.10.7 AC transformer for door release . Unit 6
13.10.8 Digital keypad Unit 6
13.10.9 12V AC power supply transformer Unit 6

Total of Sec 13.10) Intercom System carried to summary

28 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec 13.11- Public Address System


Supply, install, test and commission a public address system,
the system shall be according to the approved manufacturer list,
including all required connections with the existing system of
the Hospital including all required cables and conduits complete
ready for work.
13.11.1 9/6 watt ceiling loudspeaker, 8” round with metal grille, screw Unit 11
mount.

Total of Sec 13.11) Public Address System carried to


summary

29 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec-13.12- Telephone System


13.12.1 Supply install and connect main telephone cables from the low Job 1
voltage boxes to the main low voltage box in the proposed floor
and from the main low voltage box to the telephone exchange
of the Hospital. Rate to include 2 NO's. 36 pair cables, conduits,
terminal blocks and all accessories as specified in the technical
specification and drawings.

Total of Sec 13.12) Telephone System carried to summary

30 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec- 13.13- LV Boxes


Supply install and connect the following LV boxes. Rate to
include all required materials, condiuts, wires, cables and
accessories manufacturing from galvanized sheet metal sheets
, painted with the same color of the switch boards all as
specified in the technical specification and drawings.

13.13.1 LVM Approximate dim.3 (80x60x25) cm No. 1


13.13.2 LVB Approximate dim.( 60x60x25) cm No. 4

Total of Sec-13.13) LV Boxes carried to summary

31 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Sec- 13.14- UPS System Boxes ( Provesional)

13.14.1 Supply install and connect 30KVA uninterruptible power supply No. 1
(U.P.S.) system, consisting of a charger/rectifier unit, a solid-
state inverter unit, and a static bypass transfer switch, Power
and control connecting cables between the U.P.S. system and
the battery bank, including protective devices, all in accordance
with the technical specifications .The UPS System back up time
15 min.
(Complete and ready for work, including all required materials
and connections)

Total of Sec-13.14) UPS System carried to summary

32 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

Mechanical Works Bill


PREAMBLE
1 - include for excavation to any depth and width
necessary to provide working spaces planking
and strutting keeping excavations free from water,
trimming bottom to required levels, stockpiling all
suitable excavated materials for backfill and fill on
site for careful backfilling and well consolidating
excavated material and for disposal of the
surplus material as directed , all as specified .

2 - Rates for plumbing work and sanitary


installations shall include for :

a - Bends, elbows, tees, junctions, branches


and the like .

b - Joints, union, flanges and couplings in


the running lengths of pipes .

c - Nipples , air chambers , cleaning eyes and


access doors .

d - Holderbats, brackets, pipe clip and support,


hangers and piers .

e - Pipes sleeves and escutcheons .

f - Cutting and pinning ends of supports


for pipes equipments, appliances, fixtures,
fittings and all the like .

g - Flushing and testing as specified .

h - All cuttings, borings, making holes and the


like including making good .

i - Conduit, conduit fittings, wiring and the like.


j - Hoisting, lifting and fixing in position .

k - Painting as specified .
l - Protection of all sanitary installations .

3 - Rates for all heating installations shall include :

a - Assembling and jointing .

b - Factory priming paint .

c - Fixing, including nails, bolts , nuts, screws,


plugs and the like .

d - Cutting and pinning including all making good.

e - Plugging and screwing .


f - Testing all installations in accordance with a
selected International standard by the
engineer including, providing equipment and

33 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

personnel necessary for testing .

g - Protection of all works .

4 - Rates for all items of equipment and materials


shall be inclusive of all certificates samples test,
supply of all information and data , supply of
catalogues, charts, curves, submittals certified
drawings , and all other information services
called for in the specifications and fully
connected up in good working order .

5 - Rates shall also include for :

a - Marking positions of holes,mortices chases,


and the like etc..

b - Cutting and forming holes, chases, etc,


including pipe sleeves and making good
all works.

c - Cutting and pinning ends of supports to


structure.

d - Painting as specified .

e - Protection and maintaining the works in


good order .

f - Electrical installations including panels,


controls wiring, conduits, conduit fittings etc.

g - Preparation of plans or diagrams , working


drawings , as-built drawings , schedules,
instruction manuals, etc.

h - Insulation as required .

i - Tags, nameplates, belt guard and all


accessories and appurtenances described in
the specifications dealing with each item
or equipment.

j - Any necessary motors , starters and


necessary wiring on the equipment having
electrical goods together with such items
as insulation , piping instruments, controls
and all other items mentioned or implied in
specifications and drawings as being
supplied with the equipment and not
separately measured and enumerated in
the Bills of Quantities .
6 - Equivalent materials and equipments are
considered so , only when they are up to the
specified standard quality,price,and, moreover,
they have reliable local agent, who can provide
the after sales services.
Priority is given to high quality local products,
all according to the Engineers' judgement.

34 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

7 - See specifications for taking over supply item.

8 - Jointing of PVC pipes by heating is not allowed.

9 - If any item is stipulated in more than one section and has


been priced differently in each section, then the lowest priced
unit rate will be considered for all the quantities of the item in the
various sections.

10 - The price of all items in the bill includes Supplying,


Installing, Testing and Commissioning.

11- Over-all understanding of the electrical wiring and cabling in


the mechanical works section is that the mechanical sub-
contractor has the responsibility for the supply and installation of
all the electrical works within his work limits. Others (main or
electrical contractor) will have the responsibility of providing
power to the electro-mechanical power and control boards. This
implies the following criteria:
- The supply and installation of all power and control cables and
wires (including rigid conduits, hangers, supports, clips, glands,
flexible conduits, cable trays, earthing …etc) from equipment
(all kind of equipment) to the designated sub or main power
and/or control board, as well as the power and control wires and
cables between any inter-related equipment, should all be
included in the respective equipment unit rate. This applies to all
wiring and cabling works, regardless to where their respective
electric panels are described and included;

whether in the mechanical or electrical works sections.


- Wherever two or more similar equipment are specified to
serve the same purpose, alternating mode should be applied in
the control scheme.
- Any equipment, regardless to its type, power consumption and
location, should be supplied with compatible and suitable power
isolating switch for maintenance purposes.
- All power and control panels serving the mechanical works,
and are included in the mechanical bill, should be priced in full.
The price should cover the panels and all related gadgets -such
as but not limited to relays, contactors, breakers, isolating
switches, selector switches, lights, meters, buss-bars, terminals,
etc- according to the power and control scheme requirements.

- Essential equipment are always energized by the primary and


the stand-by power sources, while non-essential equipment are
energized by the primary power source. Experienced contractors
should be able to differentiate between both types, and should
be able to envisage an acceptable control scheme if such
scheme is not already defined in the tender documents,
which should subsequently give them the ability to price the works
accurately.

35 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

- All related electro-mechanical sub-equipment and gadgets,


whether control, sensing, protective, alarming, or On-Off,
installed on the main equipment should be wired to meet a
reasonable control scheme, while the price of such wiring should
be included in the unit rate of the main equipment, or of the
gadget if it is specified in a separate bill item. This includes, but
not limited to, pressure switches, flow switches, cut-outs, shunt
pumps, motorized valves, thermostats (both duct and wall
mounted), float switches, etc.

36 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

14 Waste and drainage system:

The Contractor shall, when pricing the rates of this bill,


take into consideration including and allow for the costs or
expenses of all requirements stipulated in the preambles,
drawings and technical specification of the contract.

The following notes should be considered when pricing:

1- The price shall include all required digging or excavation


backfilling and cement covering as specified.

2- The price shall include all connections to existing drainage


cast iron pipes.

3- The contractor must consider keeping the system running


during the whole construction period.

14.1 Supply and install (S & I) PVC pipes (UAP, Royal, or equally
approved (E.A)) for air conditioning drainage network. Price
includes all kinds of digging in concrete slabs and walls,
supports, hangers and all rubber joints and sealants, syphone
and connection to floor drain and flexible connections and all
types of fittings. All done according to drawings, specifications
and approval of the Engineer.

14.1.1 2" Lm 250

14.1.2 11/2" Lm 23

14.1.3 11/4" Lm 70

14.2 S & I cast iron type Dukar or E.A 4" waste or stand pipes, Lm 28
running exposed along partitions, false ceiling, walls, shafts,
under tiles or laid in walls. Price include all type of fittings,
supports, hooks, connection to existing manholes, stainless
steel fasteners and all excavation and quarrying, all done
according to drawings specifications and the approval of the
Engineer.

14.3 S & I HDPE as made by Costline or E.A waste or stand pipes,


running exposed along partitions, false ceiling, walls, shafts,
under tiles or laid in walls. Price include all type of fittings,
supports, hooks, connection to existing sewage and drainage
system, stainless steel fasteners and all excavation and
quarrying, HDPE connections to be done according to
specifications, all done according to drawings, specifications and
the approval of the Engineer.

14.3.1 6" pipe Lm 10

14.3.2 4" pipe Lm 490

14.3.3 3" pipe Lm 15

14.3.4 2" pipe Lm 320

37 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

14.4 S & I Floor drain 4" threaded 15x15cm chrome plated cover No 50
multi inlet adjustable with trap. All complete with floor clean out
plug, HDPE syphone and all types of fittings. The rate shall
include excavation and backfilling for all connections with drain
pipes and fixtures. All done according to drawings, specifications
and approval of the Engineer.

14.4.1 Ditto, but connection box 4"/2" type Lipski or E.A, all done No 10
according to drawings, specifications and approval of the
Engineer.

14.5 S & I heavy duty non adjustable 11x11 cm floor clean out with No 40
HDPE body, with gas and water tight ABS plug and frame,
complete with all needed elbow and all types of fittings, all done
according to drawings, specifications and the approval of the
Engineer.

Total of waste and drainage systems Carried to Summary


Sheet

38 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

15 Roof drain system:


The Contractor shall, when pricing the rates of this bill,
take into consideration including and allow for the costs or
expenses of all requirements stipulated in the preambles,
drawings and technical specification of the contract. All
removed pieces from the existing roof should be submitted
to the engineer of the hospital.

15.1 S & I HDPE pipe and fittings as made by Costline or E.A. The
rate shall include all needed connections to existing rain water
pipes and all types of fittings, all done according to drawings,
specifications and the approval of the Engineer.

15.1.1 4" pipe LM 60

15.1.2 3" pipe LM 15

15.2 S & I Polypropelyne (PP) Roof rain water drain size 4" with No 10
cover of 20x20 plastic mesh (REDI make or E.A) to be
connected to rain water vertical pipes with all required fittings,
price shall include the piping works until the connection to the
vertical rain pipe, all done according to drawings, specifications
and the approval of the Engineer.

15.3 S & I REDI or E.A. 4" roof vent with screened cap for vent No 34
stacks including connection to the vent pipe by solvent welding.
The rate include all needed connection accessories, all done
according to drawings, specifications and the approval of the
Engineer.

Total of Roof drain system Carried to Summary Sheet

39 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

16 Sanitary fixture and their accessories:


The Contractor shall, when pricing the rates of this bill,
take into consideration including and allow for the costs or
expenses of all requirements stipulated in the preambles,
drawings and technical specification of the contract.

16.1 S & I Porcelain wall hung Semi pedestal wash basin for patient No. 31
toilets type SAN-REMO Ideal Standard (IS) or E.A of size
600x490 mm model A7460. The rate shall include Fixing
galvanized screws, White Color syphone" heavy duty" and all
the needed accessories to complete the job as per drawings,
specifications and the approval of the Engineer.

16.1.1 Ditto, But of size 550x450 Model A7450 or E.A. No. 11

16.2 S & I Chrome plated gear mixer type CERADISC (IS) model No. 42
A5390 or E.A complete with all the needed fixing accessories,
sockets, copper adaptors and 3"/8" angle valves type (Giacomini
or E.A.) to connection with water pipes. All to be done as per
drawings, specifications and the approval of the Engineer.

16.3 S & I Porcelain floor monted W.C white color size 670x355 No. 29
European type SANREMO (IS) S-trap model G6401 or E.A.
Price shall include all fixation and hanging bracket, 9-lt capacity
cistern, valves, fittings, hard solid seat and 13mm stop angle
valves, chrome plated 13mm hose, and accessories, side l m
length 13mm Chrome plated hand shower for wc (heavy duty)
with spring nozzle outlet and all other required materials,
including connection to drainage system and water system
including 3/8" Angle valve (type Giacomini or E.A.). All to be
done as per drawings, specifications and the approval of the
Engineer.

16.4 S & I stainless steel paper holder type BOBRICK model B-6699 No. 29
or E.A for single roll fixed to wall with all needed fixing
accessories, all to be done as per drawings, specifications and
the approval of the Engineer.

16.5 S & I stainless steel sink for kitchens of size 40x50 cm (single No. 9
bowl) like (Rocca or E.A ) of thickness 18/10 Price shall include
connecting to drain of system by 2" HDPE pipes inside sanitary
blocks, also propper fixation to marble, all to be done as per
drawings, specifications and the approval of the Engineer.

16.6 S & I chrome plated mixer type Cerlaman (IS) A5396. With steel No. 9
wire mesh, and connection to water supply with 3/8" Angle valve
type Giacomini or E.A.), including all the required fittings, all to
be done as per drawings, specifications and the approval of the
Engineer.

16.7 Supply and install 316 stainless steel gauge 12 sluice sink No. 1
complete with chrome plated swivel - spout mixer type (IS)
A5396 or E.A. with steel wire mesh. Price includes connection to
water supply with 3"/8" angle valve type (Giacomini or E.A.),
including all the required fittings, all to be done as per drawings,
specifications and the approval of the Engineer.

40 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

16.8 Heavy duty soap dispenser type BOBRICK model B2111or EA. No 9
with all fixing accessories needed. All to be done as per
drawings, specifications and the approval of the Engineer.

16.9 Heavy duty towel paper holder type 304 st st BOBRICK model B- No 4
6699 for single roll to be fixed at wall with all fixing accessories
needed. All to be done as per drawings, specifications and the
approval of the Engineer.

16.10 S & I Porcelain floor mounted janitor closet type (IS) model No 1
R3852or EA. The rate includes grilled cover, fixing screws,
rubber and all needed fixing accessories. The rate shall include
S & I of 11/2" Flush valve type (IS) and Chrome plated single
tap for cold water. All to be done as per drawings, specifications
and the approval of the Engineer.

16.11 S & I Chrome plated shower gear mixer type CERADISC (IS) No 26
model A5394 or E.A and for the connecting rod model A3052 or
E.A, compete with hand shower, flexible hose 150mm length,
fixing anchor and all needed accessories, All to be done as per
drawings, specifications and the approval of the Engineer. And
S & I the following:

16.11.1 Shower syphone heavy duty type Lipski or E.A. with round cover No 26
of 4" size.

16.11.2 Folding shower seat, padded seat, right hand seat type No 5
BOBRICK model B517 or E.A.

16.11.3 Single robe/clothes hook with concealed mounting type No 26


BOBRICK model B2116 or E.A.

16.11.4 Recessed soap dish type BOBRICK model B6607 or E.A. No 26

16.11.5 Horizontal two way grab bar for handicapped shower 914x1372 No 26
mm type BOBRICK model B-5837 or E.A. The rate shall include
for fixing the bar at wall using special mortar mix.

16.12 S & I mirror aluminum frame suitable to be used for hospitals No 45


with different sizes. The rate shall include fixing the mirror to wall
and according to provided drawings.

Sanitary fixture and their accessories. Carried to


mechanical summery sheet

41 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

17 Domestic hot and cold water system:


The Contractor shall, when pricing the rates of this bill,
take into consideration including and allow for the costs or
expenses of all requirements stipulated in the preambles,
drawings and technical specification of the contract.

17.1 Supply and install galvanized Sch-40 pipes for domestic cold
and hot water. The work includes all fittings, valves, required
flow direction signs, TOLGO type hangers, all required fittings,
connection to existing system and all needed accessories.

17.1.1 1/2" LM 90

17.1.2 3/4" LM 270

17.1.3 1" LM 200

17.1.4 11/4" LM 155

17.1.5 11/2" LM 140

17.1.6 2" LM 105

17.1.7 3" LM 30

17.2 Supply and install 13mm thick insulation for domestic hot water
and circulation pipes type ANAVID or E.A. The work includes
insulating all fittings, valves, non-return valve … etc., and
wrapping with 10cm plastic wrap, also required flow direction
signs,.

17.2.1 1/2" LM 90

17.2.2 3/4" LM 270

17.2.3 1" LM 200

17.2.4 11/4" LM 155

17.2.5 11/2" LM 140

17.2.6 2" LM 105

17.2.7 3" LM 30

17.2.8 Ditto but 6 mm thick insulation for cold water supply pipes LM 140
inside the wall. The work includes insulating all fittings, valves,
and wrapping with 10cm plastic wrap.

17.3 Supply and install 0.5mm Galvanized sheet cladding for


protection of exposed pipes for hot and air conditioning and
heating systems including all screws and fittings needed. The
work also includes covering all valves, strainer, unions, nipples,
fittings, hangers and all other needed accessories and marks to
protect the pipes along thier paths.

17.3.1 11/4" LM 67

17.3.2 11/2" LM 70

42 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

17.3.3 2" LM 120

17.3.4 21/2" LM 50

17.3.5 3" LM 110

17.4 Supply and install hot and cold water collectors type GIACOMINI
or E.A. The collectors are installed above the ceiling of
bathroom with all required hangers (type GIACOMINI) and
support, air vents, shut-off valves on the collectors outlets, shut-
off valves on the collectors inlets, record valves, and all required
accessories to complete the job.

17.4.1 3/4" Eye 240

17.4.2 1" Eye 30

17.5 S & I crossed linked PE pipe 16mm pipe with 25 mm sleeve Lm 1300
type Aquapex or E.A. The rate shall include all fittings eg:
copper elbow inside walls (type GIACOMINI), 1/2" male and
female adaptors and all needed accessories for connection
between copper collectors to fixtures.

Domestic hot water system:

17.6 S & I Heat exchanger of copper coil type cap. 180000 Kcal/hr of L.S 1
manufacturer (zilmat or E.A) price includes all necessary fittings
and all pipes fittings and all control system (including Electrical
Control Board), thermostate and differential (Honeywell or E.A )
and all the required materials and gadgets to complete the job,
according to drawings, specifications, and approval of the
Engineer.

17.7 S & I In line centrifugal water pump (in alternating mode) for
circulating domestic hot water as made by Grundfos, Armstrong
or E.A. The rate includes all fixing accessories , mounting base,
flexible connection , pressure gage at suction and discharge,
strainer, complete insulation, water proof power switch,
aluminum cover to protect the pump from rain, concrete base,
rubber isolators, flow direction signs, supply and return headers
as shown on drawings, electrical controlers and electrical control
boards with all required electrical connections, and all needed
parts to complete the job according to drawings and
specifications and the approval of the Engineer.

17.7.1 Q=8.14L/s , H=16.6m (PUMP- S.P-1) No. 2

17.7.2 Q=6.4L/s , H=21m (PUMP- H.W.P-2) No. 2

17.7.3 Q=3.8L/s , H=20m (PUMP - H.W.R.P-3) No. 2

17.7.4 Q=1.4L/s , H=5m (PUMP - S.P-4) No. 2

43 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

17.8 S & I expansion vessel of size 400 L, closed vertical diaphragm L.S 1
type, operating conditions: 10 bar, 110 °C The unit price shall
include isolating, pressure regulating, drain, relief, double check
and automatic air vent valves, pressure gauge, gas filling
connection, base frame and all works and accessories required
to complete the work as shown on the drawings and as per the
supervision engineer's requirements.

17.9 S & I domestic hot water calorifiers, vertical shell & tube storage L.S 1
type of size 200 L, 8 bar working pressure, hydrostatically tested
for 1-1/2 times the working pressure. The unit price shall include
a thermometer, an ASME rated pressure and temperature relief
valve, isolating valves, drain valves, check valve on cold water
make-up line, automatic air vent, support, insulation with 1-1/2"
foam insulation and protected with 0.7mm GI sheet cladding, all
as required as on drawings and as per supervision engineer's
requirements.

Total of Domestic hot and cold water Carried to Summary


Sheet

44 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

18 Fire Fighting system:


The contractor shall, when pricing the rates of this bill take
into consideration including and allow for the cost
expenses of all requirements stipulated in the preambles,
drawings and technical specifications of the contract.

Supply, install, and test the following items complete with


necsseray fixing accessories as specified and as shown on
drawings:

18.1 Wall mounted fire cabinet 120x80x30 cm equiped with 1" No. 5
swinging hose reel 25 m polystrene hose 1" aluminum nozzle, 1"
ball valve, 12 kg powder extinguisher, 2" linen hose (2 x 15 m)
with quick coupling, 2" nozzle, 2" landing valve, 2" ball valve,
and all required fittings and valves.

18.2 6 kg automatic fire extinguisher dry chemical powder to be No. 5


installed in existing boiler room at high level with all required
mounting accessories.

18.3 Supply and install black steel Sch40 pipes jointed by welding for
diameters above 2" and by threads for 2" pipesand below, all as
made by MODGAL or E.A. The work also include all valves,
strainer, unions, nipples, fittings, hangers and all needed other
accessories including painting with the final red color paint
according to specifications and the approval of the Engineer.

18.3.1 3" LM 20

18.3.2 21/2" LM 13

18.3.3 2" LM 95

Total of Fire Fighting System carried to mechanical


summary sheet

45 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

19 HVAC system:
The contractor shall, when pricing the rates of this bill take
into consideration including and allow for the cost
expenses of all requirements stipulated in the preambles,
drawings and technical specifications of the contract. Also
the contractor must consider the fact that this project is a
running complex and must be kept as so during the whole
period of construction.

19.1 S & I of an air cooled chiller of capacity 152 Ton as made by L.S 1
Daikin (Japan), Carrier (France), York (USA) or EA.The chiller is
a heat pump type operating with friendly to nature refrigerant
(R407-C) and runs with hermatic scroll type compressor, leaving
water Temperature = 7.2 C and inlet water Temperature = 12 C,
all in accordance with the prevailing climate conditions of the city
of Tulkarem. The unit shall be equipped with direct drive
condenser propeller, condenser fan motor, heat exchanger, high
and low pressure switch, anti freez sensor, braided flexible
connections, outlet water temperature sensor, return water
temperature sensor, ambient temperature sensor, crank case
heater, supply and return headers as shown on drawings,
double regulating valves, filter drier, sight glass, service valves,
water flow switch and pressure gage (high & low), electrical
controlers and electrical control board with all required electrical
connections,. The work includes but not limited to concrete base
and all requirements for proper installation and operation, all
done according to drawings specifications and approval of the Engi

19.2 S & I fan coil unit with forwad curved fans as made by Daikin
(Japan), Carrier (France), York (USA) or EA. The unit shall be
with a single coil, stainless steel drain pan, and with all parts
such as 3-way valve, inlet & outlet ball valves type GIACOMINI
or E.A, strainer, inlet and outlet rubber flexible connections with
braided steel, test point valves, washable flat filter, multi speed
electric motor and room thermostat with three speed switch (wall
mounted type installed inside lockable protection box). The rate
includes connecting the unit to piping including S & I of the
following:

19.2.1 Cooling Load = 6.55 kw No. 1

19.2.2 Cooling Load = 8.48 kw No. 9

19.2.3 Cooling Load = 10.2 kw No. 4

19.2.4 Cooling Load = 11.7 kw No. 8

19.2.5 Cooling Load = 11.73 kw No. 1

19.2.6 Cooling Load = 12.9 kw No. 9

19.2.7 Cooling Load = 14.8 kw No. 2

19.2.8 Cooling Load = 16.0 kw No. 1

19.2.9 Cooling Load = 18.7 kw No. 5

46 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

19.3 S&I aluminum supply air ceiling diffusers as made by cooling No. 88
industries or E.A, four-way square type with removable core, key
operated opposed-blade volume damper and equalizing grid,
suitable for mounting flush with false ceiling. The unit price shall
include connection to duct with flexible insulated duct of
compatible diameter and of maximum 1 meter in length , and all
accessories and works required to complete the work, all done
according to drawings, specifications and approval of the
Engineer. Size 12"X12"

19.4 S&I aluminum supply air wall mounted diffusers (grill type) as
made by cooling industries or E.A, key operated opposed-blade
volume damper and equalizing grid, suitable for mounting flush
with the wall. The unit price shall include connection to duct with
flexible insulated duct of compatible diameter and of maximum 1
meter in length , and all accessories and works required to
complete the work, all done according to drawings,
specifications and approval of the Engineer.

19.4.1 size 10"X6" No. 5

19.4.2 size 10"X8" No. 70

19.5 S & I exhaust air aluminum grills made by cooling industries or


E.A, fixed 45-degree blades, double deflection, 1" thick frame,
3/4" spacing. The unit price shall include connection to duct, and
all accessories and works required to complete the work, alll
done according to drawings specifications and approval of the
Engineer.

19.5.1 6"X6" No. 45

19.5.2 9"X9" No. 14

19.5.3 12"X12" No. 28

19.5.4 16"X8" No. 21

19.5.5 18"X12" No. 2

19.6 Supply and install perforated aluminum ceiling diffusers for the No. 4
operating theatres of size 18"X18", ceiling module with neck size
as shown on the drawings, flush face, adjustable 4-way
deflectors, with integral or field fabricated plenum box, key
operated opposed-blade volume damper and equalizing grid
with plazma filter. The unit price shall include connection to duct
via flexible connection not exceeding i meter in length, and all
accessories and works required to complete the work as shown
on the drawings and as per the specifications and supervision
engineer's instructions.

47 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

19.7 S & I modular, weather proof type 100% fresh air packaged unit
constructed from aluminum penta post with double skin panels
and insulated with injected polyurethane 2" thick as made by
Daikin (Japan), Carrier (France), York (USA) or EA of capacity
6.5 Ton. The unit shall be equipped with scroll type
compressor(s) and shall run by friendly to environment
refrigerant. The rate includes built-in electrical heating battery of
18KW capacity made of stainless steel finned tube heating
elements covering all the face area of the air flow and including
all protection gadgets such as air flow switch, automatic and
manual reset thermal cut-outs, and controlled via 4 stages
controller. It should also include a built-in plate heat exchanger
for energy recovery between the return (exhausted) air and the
fresh air supply.
The unit shall be supplied with backward curved propeller fans No. 1
(supply and exhaust) suitable for external static pressure of 1.5"
each, installed on vibration isolators, dampers for fresh and
supply air, aluminium washable type pre-filter, V-type bag filter,
and 99.997% HEPA filter. An audiable and visual alarm should
be built-in also for the HEPA filter maintenance purposes, all
including the needed fixing accessories and electrical controlers
and electrical control board with all required power and control
connections to the unit, as well as, air temperature sensors,
where all shall be rendered according to drawings, specifications
and the approval of the Engineer. Packaged Unit: P.R.C/H -
OP.TH

19.8 Supply and install minimum two stage cooling and four stage No. 1
heating thermostat for the packaged unit made by Honeywell or
EA.

19.9 S&I exhaust and fresh air fans as manufactured by Vortice or


E.A, all of sturdy industrial structure, galvanized steel parts and
aluminum impellers, directly driven by IP 65 electric motors,
powered by 380V/3phase/50Hz electric power supply. Price
shall include all materials needed for complete Installation,
electrical controllers and electrical control boards with all
required electrical connections from the main electrical boards,
including cables, wires, cable trays, steel stands and
protections, as well as, weather proof disconnet switch for
maintenance needs, where all shall be done as per detailed
drawings, specifications, and Engineer's instructions.

19.9.1 Exhaust: 600 CFM (model c35/4m) No. 1

19.9.2 Exhaust: 690 CFM (model c35/4m) No. 1

19.9.3 Fresh Air: 690 CFM (model c35/4m) No. 1

19.9.4 Exhaust: 1000 CFM (model c37/4m) No. 3

19.9.5 Exhaust: 1235 CFM (model c40/4m) No. 1

19.9.6 Fresh Air: 1235 CFM for fresh air (model c40/4m) No. 1

19.9.7 Exhaust: 1364 CFM (model c40/4m) No. 1

19.9.8 Fresh Air: 1364 CFM (model c40/4m) No. 1


19.9.9 Exhaust: 1400 CFM (model c40/4m) No. 2

48 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

19.10 Supply and install single skin galvanized steel duct made M2 940
according to SMACNA standard and requirements vis-a-vis
support, sizing, branching, air tightening, jointing, etc, with 2"
thick, 12kg/m3 density glass wool insulation wrapped with
reinforced aluminum foil, which shall be confined in place by
aluminium adhesive tape at the joints and spirally wound
aluminium wire all around and along.The rate shall include all
required hangers, supports, isolators, splitting dampers, canvas
type flexible connections at units inlets and outlets, and all
required accessories needed as shown on drawings, according
to specifications, and to the Engineer's instructions.

19.10.1 Ditto, but with 0.6mm galvanized metal sheet cladding for M2 40
protection of exposed duct work on roof including all screws and
fittings needed, excluding the spirally wound aluminium wires,
where the job shall be rendered according to SMACNA , all in
accordance with the drawings, specifications and the approval of
the Engineer.

19.11 Supply and install galvanized steel duct for exhaust system M2 380
made according to SMACNA. The rate shall include all required
hangers, supports, plitting dampers, canvas flexible connections
and all required accessories made as shown drawings,
according to specifications, and to the approval of the Engineer.

19.12 Supply and install black steel Sch.40 pipes for the A/C network
with 19mm insulation and nylon wrapping. The work also
includes all unions, nipples, tees, elbows, hangers, required flow
direction signs, and all other needed accessories to lay the pipe
along its path, all done according to drawings specifications and
approval of the Engineer.

19.12.1 3" LM 26

19.12.2 21/2" LM 117

19.12.3 2" LM 100

19.12.4 11/2" LM 110

19.12.5 11/4" LM 45

19.12.6 1" LM 125

19.12.7 3/4" LM 45

19.13 Supply and install isolation ball type valves as made by


Giacomini for the A/C piping network, as follows:

19.13.1 3" No. 4

19.13.2 21/2" No. 6

19.13.3 2" No. 6

19.13.4 11/2" No. 6

19.13.5 11/4" No. 6

49 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

19.13.6 1" No. 8

19.13.7 3/4" No. 10

19.14 S & I circulating chilled water pumps (in alternating mode) as


made by Grundfos, Armstrong or E.A. The rate includes all fixing
accessories , concrete mounting base and neoprene pads,
flexible connections at inlets and outlets, pressure gages at
inlets and outlests, strainers at inlets, Globe valves at inlets and
outlets, complete insulation for the related fittings, galvanized
sheet metal shelter to protect the pumps from rain, flow direction
signs. The price shall include also the electrical controlers and
electrical power and control sub-board where needed, with all
required electrical connections including cable, wires, cable
trays, and all needed parts to complete the job according to
drawings, specifications and the approval of the Engineer.

19.14.1 Q=8.7L/s , H=16m (NORTH N.C.H.P.-1 PUMP ) No. 2

19.14.2 Q=9.7L/s , H=16m (SOUTH S.C.H.P.-2 PUMP ) No. 2

19.14.3 Q=0.695L/s , H=7m (HITING P.R.H.P.-3 PUMP ) No. 2

19.15 S & I 8" diameter headers at the pumps inlets & outlets as No. 2
shown on drawings. The headers shall include all needed
outlets (with 2" extra clogged outlets on each for future
expasion), ball valves (Giacomini or equivalent), pressure
gauges, thermometers, convexed abd end caps, 24kg/m3
fiberglass insulation, 0.7 galvanized metal steel sheet claddings,
and steel supports.

19.16 S & I and connect motor starter panel with all necessary MCC L.S 1
breakers, starter controllers, protective deivces for pumps,
chillers, air handling units, and all the equipment on the roof.
The price shall include (power cables control wires - galvanized
cable tray, flexible connections ... etc.) from panels to equipment
and all electrical connections for fresh and extract fans on roof,
all done according to drawings specifications and approval of
the Engineer.

19.17 S & I and connect all needed power and control gadgets into the L.S 1
existing electrical panel in boiler room to serve the proposed
boiler. Price shall include MCCB's, relays, power cables, control
wires, indication lights,protective and safety devices, … etc.

Total of HVAC System carried to Mechanical Summary


Sheet

50 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20 Medical Systems:
20.1 Supply and Installation of Medical gas copper piping as per
HTM02.01:

20.1 Degreased medical oxygen compatible seam-less copper pipes


type L. The pipes must be cleaned and treated for medical gas
usage including capping the ends of each pipe at ex-works, to
ensure that no foreign bodies, dust or vapors infiltrate the the
pipes during transpiortation, handling, and installation. The
copper pipes must meet the international standard of
ASTM B-819 and to be cleaned for medical usage (degreased)
in accordance with CE 0473.
Each pipe must be pre-factory marked continuously with:_
OXY/MED ASTM B-819
Pipeline network must be welded and hanged according to the
latest welding and hanging methods of health care technical
memorandum HTM 02.01, ASTM B819 and G-01
Price includes proper isolation for piping under plastering and
wall penetrations , hangers, brackets, fasteners, etc.., as well
as, the various fittings and accessories needed to complete the
works as shown on drawings and as per the set specifications.
Price also includes proper flushing of the entire piping network
prior to commissioning the Works, using purified Nitrogen or
Medical Compressed Air.

20.1.1 1/2” inch O.D. LM 385

20.1.2 5/8” inch O.D. LM 435

20.1.3 7/8” inch O.D. LM 305

20.1.4 1 1/8” inch O.D. LM 80

20.1.5 1 3/8” inch O.D. LM 100

20.1.6 1 5/8” inch O.D. LM 100

20.1.7 2 1/8” inch O.D. LM 95

51 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20.2 Supply and Installation of Area Valves Control Boxes as per


Silbermann or E.A:

20.2.1 Recessed area valve control box for medical oxygen and Unit 5
vacuum, including 2 full-port 3-parts NIBCO shut off valves
which controls the supply of gases or vacuum through the
pipelines, and line pressure and vacuum gauges. The valves
diameter varies between 15 up to 35 mm, as per drawings.
The area valves control boxes should also include an
emergency external supply port, equipped with disk and clutch
mechanism for quick plug-in connection of the emergency
external supply source.
As per SILBERMANN model 7210-000 or EA. The front should
be made of labeled transparent polycarbonate flexible
unbreakable cover for easy access in emergency cases.

20.2.2 Same as Item No. 20.2.1 but for medical oxygen, medical Unit 1
compressed air and vacuum. As per SILBERMANN
model 7214-000 or E.A

20.2.3 Same as Item No. 20.2.1 but for medical oxygen, nitrous-oxide, Unit 2
medical compressed air and vacuum. As per SILBERMANN
model 7204-000 or E.A

20.3 Supply and installation of Local Area Pressure and Vacuum


Alarm Boxes as per Silbermann or E.A:

20.3.1 Local audio-visual pressure alarm box for medical oxygen and Unit 5
vacuum to indicate pressure and vacuum failures by means of
green LED, red LED, audio buzzer and pressure or vacuum
gauge for each gas, as well as shut-off valves for each gas or
vacuum, operated by means of one central PC card
(microprocessor card) and pressure/vacuum switches for each
gas, recessed type with anodized aluminum panel.

As per SILBERMANN model 7176-110 or E.A

20.3.2 Same as .Item No. 20.3.1 but for medical oxygen, medical Unit 1
compressed air and vacuum As per SILBERMANN model 7177-
1100 or E.A

20.3.3 Same as Item No. 20.3.1 but for medical oxygen, nitrous-oxide, Unit 2
medical compressed air and vacuum as per SILBERMANN
model 7178-110 or E.A

52 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20.5 Supply and Installation of Fully-automatic Electronically


controlled Oxygen local Back-Up stations, According to CE-
0473, EN-46001, ISO-9001 as per Silbermann or E.A:

20.5.1 Fully automatic electronically controlled gaseous medical oxygen Unit 0


local Back-Up station consisting of 4 high pressure oxygen
manifolds with high pressure valves, stainless steel pigtails, and
common regulators with in/out gauges, connected to the
automatic control switch-over cabinet of 80 CMH capacity.
Automatic control cabinet for continuous supply and smooth
automatic bank switchover by means of pneumatic shuttle valve,
complete with line pressure regulators, line pressure gauges
and indicators, with by-pass valves for manual operation in case
of malfunction with stand-by working pressure regulator with by-
pass, and electronic microprocessor control board, complete
with alarm panel with pilot lamps indicating reserve in-use and
low-press. Main supply, with mutable alarm for local alarm, with
mute switch and lamp test switch, with facility for displaying
alarms on two separate remote alarm panels and data loggers
for stage computer interface to connect between the automatic
change over unit indication and the distance alarm from one
side and with the BMS computer system from the
other side as per SILBERMANN model LEO-EM 7086-815

20.6 Supply and installation of diamond service wall outlets for


oxygen and vacuum as per Silbermann or E.A:

20.6.1 Recessed type, chrome plated, color and pin coded die-cast Unit 8
front assembly, primary check inlet/outlet valve with decorative
frame for two different codes of Oxygen and Vacuum, a hanging
slide for 2 liters vacuum collecting bottle must be included as per
SILBERMANN model 3236016 or E.A

20.6.2 Same as Item No. 20.6.1 but for Oxygen, Nitrous Oxide, Unit 1
Compressed Air and Vacuum as per SILBERMANN model
3236019 or E.A

53 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20.7 Supply and Installation of :


Factory-preassembled Bed head unit for one bed,
according to CE-0473, EN-46001, ISO 9001 as per
Silbermann or E.A:

20.7.1 Encompassing extruded aluminum duct system, with four Unit 34


cavities, three of which are directly accessed using snap-on
covers. Supplying electrical and lighting service, as well as
medical gas service. The gas outlets should be installed in a
separate compartment. The number of electrical circuits, apart
of the low voltage circuit, should be three : main line power
circuit, UPS power circuit, and lighting circuit, each connected to
a separate terminal at the main special electrical connection
compound in the bed-head unit.

The bed head unit is equipped with the following services :


• One oxygen outlet
• One compressed air outlet
• One vacuum outlet
• 2 electrical sockets, Main line
• 2 electrical sockets, coded-UPS line
• one potential grounding socket
• indirect light
• direct light (2 PL BIAX lamps)
• cut-off switch for direct / indirect lights
• one telephone socket
• preparation for nurse call socket

The Price should include complete interior wiring, cabling,


piping, insulating, etc , for complete installation.

20.7.2 Same as Item No. 20.7.1 but for two beds Unit 4

20.7.3 Same as Item No. 20.7.1 but for three beds Unit 3

20.7.4 Same as Item No. 20.7.1 but for four beds Unit 5
As per SILBERMANN modular system model 2000-000, or EA.

54 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20.8 Supply and Installation of Vital Life Support Column for one
Emergency bed, according to EN-793 and EN-60601-1-2 as
per Silbermann or E.A:

20.8.1 Vertical column surface made of medical high pressure laminate Unit 6
decorative Trespa, electro-polished anodized 2000 mm x 600
mm x 250 mm. Aluminum. structure
Horizontal hanging rail and vertical anodized Aluminum tracks
provides three-dimensional hanging of various type of
equipment, complete with two medical oxygen outlets, two
medical compressed air outlets, two vacuum outlets, four
essential electrical sockets and four UPS coded sockets, each
socket is equipped with built-in normal-power on LED indication
connected to independent electrical circuit and marked terminals
for each socket, with two potential equalization grounding
sockets connected to main grounding line by two separate
grounding bridges
as per SILBERMANN model FreeStand 2000 or E.A

20.9 Supply and installation of AGSS outlet as per silbermann


or E.A:

20.9.1 Anesthesia gas scavenging system with on-off switching Unit 6


indicator, to remove surplus anesthetic gas and explosive gas
mixtures from operating theatres and anesthesia rooms,
recessed type, with 22 mm. evacuation port to DIN standard as
per SILBERMANN model 3212700

20.10 Integrated Combinational Ceiling-suspended System for


the Operating Theatre as per KLS MARTIN or E.A:

20.10.1 Central Ceiling-suspended system for the OR, comprising Unit 1


prismatic cool operating light, with 130,000 lux light intensity at
1m distance, with day-light color temperature of 4,300 K, with
automatic switch-over standby lamp, electronic intensity and
focus control, with power module and emergency relay, as per
Martin-Germany marLux H5 Plus, and tandem ceiling pendant
with double boom arms, drop tube, modular service head, and
medical rail with pneumatic control, including : two medical
oxygen outlets, two medical compressed air outlets, two nitrous-
oxide outlets, two vacuum outlets, one AGSS outlet, one air
motor outlet, with four electrical sockets for main power wired to
two separate electrical circuits, with two electrical sockets for
UPS power wired to a separate electrical circuit, and two
potential equalization sockets, as per Martin-Germany
Independant 300, both suspended from central ceiling flange,
interface plate, and ceiling canopy, all in accordance with
93/42/EEC conformity.

55 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

20.11 Delivery, Labor, Preparation Room Lights as per KLS


MARTIN or E.A:

20.11.1 Ceiling-mounted Labor, Preparation, and Examination Rooms Unit 3


Lights as per Martin - Germany ML301D KLS MARTIN
examination light for ceiling mounting, of 300 mm diameter with
40,000. lux intensity at 1m distance, complies with Protection
class I according to IEC The hermetically sealed aluminum light
housing is dust- and fracture-proof. The light housing has been
plastic-coated for fast and easy cleaning.
The powerful halogen lighting system ensures the optimum
illumination of the operating field. Special filter components
guarantee cool, white light free from any deep shadows. The
high-quality reflector technology ensures a uniform light field and
first-rate color rendering properties.
The light exit surface consists of hardened safety glass that is
highly resistant to mechanical and chemical influences, with
spring regulated arm for easy height adjustment.

20.12 Baby Bath Tubs as per SOEMA or E.A:

20.12.1 Baby Bath Tub as per Soema model Lido Baby/01 and shall Unit 3
comprise of:
• Acrylic Ceramic
• Bath tub & washing sink
• Hand shower
• Electronic water tab
• Thermostatic water mixer
• Transformer
20.13 Electronic hand washing scrub sinks, SOEMA or E.A:

20.13.1 Stain-less steel suspended electronic hand washing units with Unit 1
channel type tank and paneling under basin, two electronic taps,
one electronic soap dispenser and thermostatic mixer.
Made of AISI 316 stainless steel , size 120x55x110 cm.
overflow-proof tank (35 cm deep) with rounded inner edges and
inclined front part to prevent water from spraying outside
Cat. No. # C618MXSR

20.14 Supply and installation of Ceiling Column, rigid, according


to EN 737, 793, 12218 as per Silbermann or E.A:

20.14.1 Ceiling column surface is made of Trespa, polished anodized or Unit 1


painted Aluminum.
Horizontal hanging rail and vertical anodized Aluminum tracks
provide for hanging various type of equipment, complete with
two medical oxygen outlets, two medical compressed air outlets,
two nitrous-oxide outlets, two vacuum outlets, one AGSS
outlets, one air motor outlet, four electrical sockets for mains
power, connected in two separate electrical circuits, and two
electrical sockets for UPS power, connected in a separate
electrical circuit, with two potential equalization sockets.

Total of Medical Systems carried to summary sheet

56 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

21 Lifts:
The contractor shall, when pricing the rates of this bill take
into consideration including and allow for the cost
expenses of all requirements stipulated in the preambles,
bill of quantities, drawings and technical specifications of
the contract.
The described work shall include moving all the parts from
the existing machine room to the new location.
Additionally, price of installation shall include, but not
limited to the following essential parts, workmanship,
erection equipment and tools, labor, as well as any
required accessories, metal cutting and paint:

Detailed description of required parts and materials is as


follows:
- PIT CABLE FOR LSP ELEVATORS.
- TRAVEL CABLE 24x0.75
- DHG -161 PCB - (Di+Si) NO AEG02C376.
- MICRO PUSH BOTTON NO.2R23914- VANDAL.
- HALL INDICATOR (VID-M422, Di) NO.AEN38C231*N.
- HALL PUSH BUTTON PANEL 2 P/B+2 IND TYPE "VID-M422T"
NO.: 3W09884.
- Narrow land door frame1300mm st.st.h.l-DAV.
- Land door panel side 1300 st.st.h.l.DAV.
- Land door hanger side opening 1300 DAV.
- Land door sill side opening 1300 DAV.
- STEEL CABLES 13MM- WITH FIBER CORE .
- LIFT ROPING CABLE 8MM- WITH FIBER CORE.
- DANGER LIFE HALL PLATE 100X100.
- INFORMATION PLATE UP THE CAR 100X100MM "ARABIC".

- SHELTER PLATE NO.3R69234A.


- BRACKET FOR RAIL 70 - 120x100x250 NO.2.
- GUIDE RAIL BRAKETS FOR R90*75*16 DIM (260*150*6MM L,
SHAPE FOR WALL).
- RAIL CLIPS M-12 FOR GUID RAIL 70.
- GUIDE RAIL(18K) - 144x89x16 NO.AEA10C613*C.
- SOFTWARE.
- GUIDE RAIL(7K)- 96x88x19 NO.3R52870C.
- GUIDE RAIL 125#82#16.
- GUIDE RAIL(18K) - 144x89x16 NO.AEA10C613*C.
- GUIDE RAIL BRAKETS FOR R90*75*16 DIM (260*150*6MM L,
SHAPE FOR WALL).
- ELECTRIC JUNCTION WIRE 3.25 MM .
- SHELTER PLATE NO.3R69234A.
Price shall include also the following accessories:
- FIRE EXTINGUISHERS 6 KG.
- Trash Can.
- RECHARGEABLE LIGHT - 20W DURATION 10 HOURS.
- COMPLETE NEON LAMP-DOUBLE 36 W.
- SOCKET FOR INSPECTION BOX.
- LAMP 230V - 75W.
- CABLE 5x1.5 .
- GLOBE NORMAL LAMP.
- SOLID ELECTRIC TUBES 3#4.
- PET SWITCH .
- LADDER.
- BEAM LENGTH 3M.
- PROPER LIQUID BABBIT METAL 1KG- NO.: 8GT10030.
- BRACKET FOR RAIL 70 - 120x100x250 NO.2.

57 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

- EXTERNAL BOX -24 SAFTY KEYS.

21.1 Remove all the parts of the elevators from the existing machine L.S. 1
rooms to new locations as shown on drawing including the
electric switchboard and all electrical and mechanical works
needed (and labor). The price should include also all iron
structure(material and labor) needed to complete and fix the
new location in the room as per drawings, specifications and the
approval of the Engineer.

21.2 Supply and install stainless steel sheet 2 mm thick door posts Unit 3
same as the existing, complete with side and up panels and all
the required electrical and mechanical works needed to
complete the job as per the preamble drawings, specifications
and the approval of the Engineer.

21.3 Supply and install all the required parts inside the elevator shaft Unit 3
that are needed to complete the extension process to the next
floor. Price includes all the required electrical and mechanical
works needed to complete the job as per the preamble
drawings, specifications and the approval of the Engineer.

Total of Lifts carried to summary sheet

58 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

22 Removing Existing HVAC Equipment and Accessories to


New Roof:
The contractor shall, when pricing the rates of this bill, take
into consideration including and allow for the cost
expenses of all requirements stipulated in the preambles,
drawings and technical specifications of the contract.
Before the removal of the existing parts, the contractor
shall submit a detailed report about the quantity of the
parts, units and machines that have to be relocated on the
future roof. The contractor afterwards shall examine and
present a detailed report about the status and the
conditions of all the parts, units, machines, and inform of
any damaged existing part or machine, prior to
disassembling the system.

The contractor then has to submit his methodology for


relocating all the existing units to the future roof, and sould
take into consideration that in all stages work shall be done
in conjunction with the various work activities on site. This
implies propper planning with UNDP and MoH authorized
personel, to ensure smooth relocation of equipment and
minimal HVAC interruption time inside the hospital
building. When disassembling, the contractor has to
maintain all the disassembled parts in good condition and
take full responsibility for the intactness of all the
disassembled parts.

Damaged or broken parts on the existing system should be


noted prior to disassembling the system and shall be paid
for upon replacement according to the offered unit rate.
Any damage done to the parts during the relocation shall
be covered by the contractor.
The price shall include Dismantling all existing electrical
installations, panel boards and all accessories from
existing mechanical A.C. room on the roof and reinstalling
and reconnecting all electrical needs in the new mechanical
room and changing all cables if required. The contractor
must protect the panel boards and all accessories to install
them in the new mechanical room on the roof as per the
engineers instructions.

22.1 Removing all existing vent caps at roof and re-instalation on No. 18
future roof where required as shown in drawings. The work shall
include all piping works, openings in concrete for the existing
slab, and all required labor, materials and fitting equipment
according to the instruction of engineer. Price also includes the
replacement of any of the following damaged parts with new
(same in size, capacity and quality) part:

22.1.1 Vent Cap as existing. No. 1

22.1.2 Vent Pipes 4" Cast Iron as existing. LM 10

22.1.3 Vent Pipes 4" PVC as existing. LM 10

59 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

22.2 Removing all existing domestic hot and cold water units and LS 1
pipes at roof and re-instalation on future roof as shown in
drawings. The work shall include all piping from main riser to the
units, pumps, valves, strainers, and galvanized ducts, booster
pumps, openings in concrete for the existing slab, electrical
panel and all required labor, materials and fitting equipment
according to the instruction of engineer. Price also includes the
replacement of any of the following damaged parts with new
(same in size, capacity and quality) part:

22.2.1 Insulated 3" Sch-40 galvanized steel pipe as existing. LM 10

22.2.2 Insulated 21/2" Sch-40 galvanized steel pipe as existing. LM 10

22.2.3 Insulated 2" Sch-40 galvanized steel pipe as existing. LM 10

22.2.4 Insulated 1" Sch-40 galvanized steel pipe as existing. LM 10

22.2.5 Shut-off valve 3" as existing. No 1

22.2.6 Shut-off valve 21/2" as existing. No 1

22.2.7 Shut-off valve 2" as existing. No 1

22.2.8 Shut-off valve 1" as existing. No 1

22.2.9 3" flange as existing. No 1


22.3 Removing all existing AHUs at roof and re-instalation on future No. 7
roof as shown in drawings. The work shall include all piping from
main riser to the units, pumps, valves, strainers, and galvanized
ducts, openings in concrete for the existing slab, electrical panel
and all required labor, materials, conduits and electrical wiring
and fitting equipment according to the instruction of engineer.
Price also includes the replacement of any of the following
damaged parts with new (same in size, capacity and quality)
part:

22.3.1 Insulated 4" Sch-40 black steel pipe as existing. LM 10

22.3.2 Insulated 3" Sch-40 black steel pipe as existing. LM 10

22.3.3 Insulated 21/2" Sch-40 black steel pipe as existing. LM 10

22.3.4 Insulated 2" Sch-40 black steel pipe as existing. LM 10

22.3.5 Butterfly valve 4" as existing. No 1

22.3.6 Butterflyvalve 3" as existing. No 1

22.3.7 Butterfly valve 21/2" as existing. No 1

22.3.8 4" flange as existing. No 1

22.3.9 3" flange as existing. No 1

22.3.10 21/2" flange as existing. No 1

22.3.11 4" strainer as existing. No 1

22.3.12 3" strainer as existing. No 1

60 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

22.3.13 Flow switch as existing. No 1

22.3.14 Temperature gauge as existing. No 1

22.3.15 Pressure gauge as existing. No 1

22.3.16 4" flexible connection as existing. No 1

22.3.17 3" flexible connection as existing. No 1

22.3.18 4" non-return valve as existing. No 1

22.3.19 3" non-return valve as existing. No 1

22.3.20 Duct Works as existing. M2 10

22.3.21 Metal Stand as existing No 1

22.3.22 Double Regulating valve 4" as existing. No 1

22.3.23 Double Regulating valve 3" as existing. No 1

22.3.24 Double Regulating valve 21/2" as existing. No 1

22.4 Removing all existing exhaust fans at roof and re-instalation on No 8


future top roof as shown in drawings. The work shall include
galvanized ducts, PVC piping, openings in concrete for the
existing slab, connection to existing electrical panel and all
required labor, conduits and electrical wiring, materials and
lifting equipment all made according to the instruction of the
engineer. Price also includes the replacement of any of the
following damaged parts with new (same in size, capacity and
quality) part:

22.4.1 Duct Works as existing. M2 100

22.4.2 Metal Stand as existing No 1

22.5 Removing all existing chillers at roof and re-instalation on future No 2


roof as shown in drawings. The work shall include piping
connections, pumps, heat exchanger, valves, foundation
isolation, all existing equipment, electrical connections and all
required labor, conduits and electrical wiring, materials and
lifting equipment, all must be made according to the instruction
of the engineer. Price also includes the replacement of any of
the following damaged parts with new (same in size, capacity
and quality) part:
22.5.1 Insulated 4" Sch-40 black steel pipe as existing. LM 10

22.5.2 Insulated 3" Sch-40 black steel pipe as existing. LM 10

22.5.3 Insulated 21/2" Sch-40 black steel pipe as existing. LM 10

22.5.4 Insulated 2" Sch-40 black steel pipe as existing. LM 10

22.5.5 Butterfly valve 4" as existing. No 1

22.5.6 Butterfly valve 3" as existing. No 1

22.5.7 Butterfly valve 21/2" as existing. No 1

61 out of 62
Tulkarem Hospital
-BOQ-

Section Description Unit QTY Unit Rate Total

22.5.8 4" flange as existing. No 1

22.5.9 3" flange as existing. No 1

22.5.10 21/2" flange as existing. No 1

22.5.11 4" strainer as existing. No 1

22.5.12 3" strainer as existing. No 1

22.5.13 Flow switch as existing. No 1

22.5.14 Temperature gauge as existing. No 1

22.5.15 Pressure gauge as existing. No 1

22.5.16 4" flexible connection as existing. No 1

22.5.17 3" flexible connection as existing. No 1

22.5.18 4" non-return valve as existing. No 1

22.5.19 3" non-return valve as existing. No 1

22.5.20 Duct Works as existing. M2 10

22.5.21 Metal Stand as existing No 1

22.5.22 Double Regulating valve 4" as existing. No 1

22.5.23 Double Regulating valve 3" as existing. No 1

22.5.24 Double Regulating valve 21/2" as existing. No 1

Total of Removing Existing HVAC Equipment and


Accessories to New Roof carried to mechanical summary
sheet

62 out of 62
Project: Tulkarem Hospital

Civil works Summary

Sec. Description Amount

1 1) Total of Preliminary Works

2 2) Total of Concrete Works

3 3) Total of Stone Works

4 4) Total of Block Works

5 5) Total of Plastering Works

6 6) Total of Flooring and Covering Works

7 7) Total of Water Proofing Works

8 8) Total of Carpentry Works

9 9) Total of Suspended Ceiling Works

10 10) Total of Painting Works

11 11) Total of Metal Works

12 12) Total of Other Works

Total of the Civil Works..carried to main summary


Project: Tulkarem Hospital

Electrical Summary

Sec. Description Amount

13.1 Total for Sec. 13.1) - Electrical Points.

13.2 Total for Sec.13.2) Conduit, piping, and excavations

13.3 Total for Sec.13.3) Cables

13.4 Total for Sec.13.4) Structural elelement cabinet

13.5 Total for Sec.13.5) Grounding

13.6 Total for Sec.13.6) Electrical Switchboards

13.7 Total for Sec.13.7 ) Lumenaire supply and Installation.

13.8 Total for Sec.13.8) Nurse call System

13.9 Total for Sec.13.9) Fire alarm system.

13.10 Total for Sec.13.10) Intercome system.

13.11 Total for Sec.13.11) Public adress system

13.12 Total for Sec.13.12 ) Telephone system

13.13 Total for Sec.13.13 ) LV Boxes

13.14 Total for Sec.13.14 ) UPS System

Bill 13 Total for Electrical Works..carried to main summary


Project: Tulkarem Hospital

Mechanical works Summary

Sec. Description Amount

14
Total of waste and drainage works:

15
Total of roof drain works:

16
Total of Sanitary fixtures and their accessories works:

17
Total of Domestic Cold and Hot Water system works:

18
Total of Fire Fighting system works:

19
Total of HVAC System works:

20
Total of Medical Systems works:

21
Total of Lifts works

Total of Removing Existing HVAC Equipment and Accessories to New Roof


22
works:

Total of the Mechanical works ..carried to main summary


Project: Tulkarem Hospital

Main Summary

Bill No. Description Total

Bill # 1 Civil Works Summary

Bill # 2 Electrical Works Summary

Bill # 3 Mechanical Works Summary

Total of All Works

Percentage % discount or addition

Amount of discount or addition

Net Grand Total

The sum of ________________________________________

Contractor:

Signature:
Date:

Вам также может понравиться