Tanjung Bin PP T4

Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data

Steam turbine generator unit (general)


Number of steam turbine generator units - 1
Turbine type Reheat condensing
steam turbine
Operation mode - refer to Section B0
Turbine design - According to
ambient/operating
conditions;
refer to Section B0
Permissible deviations of live steam pressure and live steam - According to IEC
temperature recommendations,
latest edition
Absorption capacity at increased nominal live steam pressure % 105
Permissible tolerance of absorption capacity % -0/+4
Frequency Hz 50
Permissible frequency deviations at Maximum Continuous - refer to Section B0
Rating

Following operating cases are to be considered as minimum:


Operation time h At least 200,000,
refer also to Section
B0
Number of cold, warm and hot starts - refer to Section B0

Max. overspeed in case of full load rejection % 8

Condenser
Cooling water inlet temperature °C Refer to Section B0
Cooling water temperature increase K Refer to Section B0
Terminal temperature difference of condenser at operating K to be determined by
conditions the Tenderer /
Contractor
Maximum cooling water velocity in condenser tubes with 10% m/s 2.2
blocked tubes
Design pressure bar full vacuum
Max. cleanliness factor referred to design cooling surface % 110

B2/FB-1
Tanjung Bin PP T4
Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data

Minimum cooling water velocity in condenser tubes m/s According to


requirement of
sponge ball cleaning
equipment, at least
1.5
Minimum tube bore of condenser tubes mm 17

Feed water heater


Number of feed water heaters - to be optimized by
the Tenderer

Combined deaerator/feedwater tank


Mode of operation of deaerator - Variable pressure
with fixed minimum
pressure
Design pressure - 120% of the
respective maximum
possible turbine
bleed pressure and
full vacuum

Design temperature °C Max. turbine low


load temperature

Boiler feed water supply and feed water pumps


Design code - German regulations,
e.g. TRD 401, or an
other equivalent
international
standard
Minimum number and capacity (per unit) No. x % 2 x 50%
Number of spare pumps (complete, incl. motor) per plant No. 1

B2/FB-2
Tanjung Bin PP T4
Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data

Generator
Rated voltage at generator terminals kV 20 or higher  5%
Rated frequency Hz 50
Rated power factor (lagging) cos phi 0.9
Rated power factor (leading) cos phi 0.95
Saturated subtransient reactance x"d % later
Rated short-circuit ratio kc (without minus tolerance) - 0.50
Inertia constant H of complete turbine and generator set kWs later
(based on rated generator output, (without minus tolerance) kVA
Insulation class for generator and exciter - F
Permissible operation at MCR according to insulation class - B
Current transformer secondary rate A 1
Voltage transformer secondary rate V 100 : 3

Definitions:
Rated generator output
defined to be at maximum continuous rating (MCR) at all
ambient site conditions of the ST unit, operation within
insulation class B limits.

Generator main connections


Operating voltage kV 20 or higher
Rated frequency Hz 50
Type of ducts - single-phase
Secondary current of current transformer A 1
Class of current transformer measuring core . 0.5M5
Class of current transformer protection core - 5P20
Secondary voltage of voltage transformer V 100/3/3
Class of voltage transformer - 0.5/0.2

Generator circuit breaker


Operating voltage kV 20 or higher
Rated frequency Hz 50
Control voltage V 220 DC

B2/FB-3
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Steam turbine
Steam pressure at HP-turbine inlet at MCR bar
Steam temperature at HP-turbine inlet at MCR °C
Steam temperature at IP-turbine inlet at MCR °C
Maximum Continuous Rating of turbine generator MW
Live steam flow at MCR of turbine generator kg/s
No-load steam consumption kg/s
Number of feedwater preheating stages -
Final feedwater temperature at MCR -
Exhaust pressure at MCR bar
Exhaust moisture %
Coupled critical speeds up to 150% of nominal speed rpm

Manufacturer -
Type -
Sectional drawing No. -
Applied Standard
Casings
Number of casings -
Casing design HP -
Casing design IP/LP -
Casing design LP -
Applied Standard
Rotors
Number of turbine shafts -
Distance between bearing centres HP shaft mm
IP/LP shaft mm
LP shaft mm
Applied Standard
Blading
HP regulating stage:
Type of wheel -
Mean blading diameter mm
Pressure in the regulating wheel chamber at MCR Bar

B2/FD-1
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

HP blading:
Type of H.P. blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row -
IP/LP blading:
Type of LP blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row mm
2
Exhaust area of last row (axially) m
LP blading:
Type of LP blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row mm
2
Exhaust area of last row (axially) m

Materials
HP outer casing -
HP inner casing -
HP blade carriers -
IP/LP outer casing -
IP/LP inner casing -
IP/LP blade carriers
HP rotor -
IP/LP rotor -
HP nozzles -
HP rotor blades -
IP/LP nozzles -
IP/LP rotor blades -
Casing of emergency stop valves (HP-steam; reheat-steam) -
Casing of HP-steam governor valves -
Casing of reheat steam governor valves -

B2/FD-2
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Emergency stop valves


Number of valves -
 HP-steam -
 reheat-steam -

HP-steam governor valve


Number of valves -
Size (Diameter of one valve) mm
Type -
Actuator -

Reheat-steam governor valve


Number of valves -
Size (diameter of one valve) mm
Type -
Actuator -

Bleed steam emergency shut-off valves


Manufacturer -
Type -

Turbine glands
Type -

Bearings
Number of journal/thrust bearings -
Type: Journal -
Thrust -
Maximum oil outlet temperature °C

Dimensions
Total length of the unit m
Length of foundation m
Width of foundation m

B2/FD-3
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Height of foundation m

Weights
Weight of rotor t
Weight of heaviest part to be handled by crane t
Operating weight of the complete unit t

Starting and loading time to MCR


 Cold start more than 1 week (168 hr) outage
 boiler firing to turbine run min.
 steam turbine to synchronous min.
 synchronous to full load min.

 Warm start after more than 48 hr outage


 boiler firing to turbine run min.
 steam turbine to synchronous min.
 synchronous to full load min.

 Hot start after more than 8 hr outage


 boiler firing to turbine run min.
 steam turbine to synchronous min.
 synchronous to full load min.

Turning device
Method of operation -
Turbine rotor speed rpm
Drive -
Rating kW

Gland steam condenser


Type
Number of condensers -
2
Cooling surface (outside diameter) m

B2/FD-4
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Materials:
Tubes -
Tube plates -
Shell -
Applied Standard

Gland exhauster
Number of exhausters -
Type -
Rating kW

Oil supply
3
Tank capacity m
Number of recirculations (per hour) l/h
Lubrication oil system pressure bar(g)

Main oil pump


Type -
Drive -
Speed rpm
Material of pump casing -

Auxiliary oil pump


Number/capacity of pumps -/%
Type -
Rating kW
Speed rpm
Material of pump casing -

Emergency oil pump


Number of pumps -
Type -
Drive -
Rating kW

B2/FD-5
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Speed rpm
Material of pump casing -

H.P. jacking oil pump


Number of pumps -
Type -
Rating kW
Speed rpm
Material of pump casing -
Oil vapor extraction
Number of extraction fans -
Type -
Rating kW

Oil cooler
Number of coolers -
Capacity per cooler %
Erection (horiz./vert.) -
2
Cooling surface per cooler (outside diameter) m
Max. oil outlet temperature °C
Cooler length mm
Materials:
Tubes -
Tube plates -
Shell -

Oil separator
Manufacturer -
Type -
Flow rate per separator of lubrication oil flow %
Heat rating kW
Rating of drive kW

B2/FD-6
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Lubrication oil filter


Type -
Flow rate per filter %
Grade of filtration µm

Control oil system


System pressure bar(g)

Control oil pump (where applicable)


Number of pumps -
Capacity per pump %
Type -
Rating kW
Speed rpm
Material of pump casing -

Control oil filter


Type -
Flow rate per filter %
Grade of filtration µm

Condenser
Total number of condensers -
Manufacturer -
Type -
Arrangement -
Turbine max. capability (TMC):
Steam flow kg/s
3
Cooling water flow m /h
Cooling water temperature rise K
Cooling water pressure loss bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
2
Cooling surface (outside diameter) m

B2/FD-7
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Number of flow passes -


Diameter of tubes (bore) mm
Wall thickness of tubes mm
Length between tube plates mm
Number of tube support plates -
Number and size of cooling water connections -/mm
Materials:
Tubes -
Tube plates -
Shell -
Water boxes -
Lining of water boxes -
Hotwell capacity referring to TMC minutes

Main condensate pumps


Number/capacity of pumps -/%
Manufacturer -
Type -
3
Nominal capacity m /h
Delivery head m
Motor rating kW
Closed valve head m
Speed rpm
Type of bearings -
Type of shaft sealing -
Material of pump casing/shaft/impeller -
If vertical pump: Overall depth of pump below floor level mm

Control and monitoring equipment


Electro-hydr. governor:
Manufacturer -
Designation of system -
Type or name of system -
Number of sensors in total -

B2/FD-8
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Interface to DCS-system
 hard wired -
 DCS-system bus -
Local operating station per plant
 Manufacturer -
 Type -

Turbine protection system


Manufacturer -
Designation of system -
Type or name of system -
Principle of monitoring (e.g. 1 out of 2, 2 out of 3, 2 out of 2
with selfmonitoring etc.) to be entered for:
Steam inlet pressure -
Steam inlet temperature -
Speed, high -
Condenser pressure and level high -
Temperature of exhaust steam or bypass steam, high -
Relative expansion, high -
Shaft displacement, high -
Difference temperature of casing (diametrical clearance), -
high
Vibration, high (housing or rotor) -
Bearing metal temperature, high -
Control oil pressure low -
Lube oil pressure, low -
Generator protection -
Lube oil tank level, low -
Wall temperature difference of turbine casing -

Vibration measurements
Manufacturer -
Designation of system -
Type or name of system -
Total number of shaft vibration sensors -

B2/FD-9
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Total number of bearing vibration sensors -

Downtime ventilation plant


Manufacturer -
Maximum air humidity downstream the turbine %
(ref. to ambient temperature)
Method of operation -

Fire protection system


System pressure required bar
Pressure vessel (if applicable)
 No. of vessels -
 Volume m
3

 design pressure bar


 safety valve design flow m /h
3

booster pumps (if applicable)


 No. of pumps
3
 capacity of pumps m /h
 delivery head m

HP Feedwater heater 1
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK

B2/FD-10
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Fouling factor (which is considered in the cooling surface) %


Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

HP Feedwater heater 2
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m

B2/FD-11
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

HP Feedwater heater 3
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -

B2/FD-12
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Diameter of tubes (bore) mm


Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

Deaerator for feedwater system


Manufacturer -
Type -
Mode of operation -
Maximum outflow rate of deaerator kg/s
Outside diameter (where applicable) mm
Total length (where applicable) mm
Materials:
Shell (where applicable) -
Internals -

Feedwater tank
Manufacturer -
3
Nominal capacity m
3
Normal working capacity m
Outside diameter mm
Total length mm
Materials:
Shell -
Internals -
Operating weight kg
Water pressure loss at inlet (MCR) bar(g)
Design temperature deaerator °C
Design pressure deaerator bar(g)

B2/FD-13
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

LP Feedwater heater 1
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

B2/FD-14
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

LP Feedwater heater 2
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

B2/FD-15
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

LP Feedwater heater 3
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

B2/FD-16
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

LP Feedwater heater 4
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -

B2/FD-17
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

HP/IP feedwater pump


Design code to be applied for the feed water supply -
Number of pumps per unit/capacity referring to BMCR -/%
Manufacturer -
Type -
3
Minimum capacity m /h
No. of stages -
Type of journal bearings -
Method of axial thrust hydraulic compensation -
Type of axial bearings -
Type of bearing lubrication -
Oil supply from -
Type of glands or seals -
Closed valve head m
Materials:
Pump casing -
Shaft -
Impeller
Total power requirement of feedpump sets of one unit when kW
the turbine is running at MCR

One pump set in single operation (at max. speed):


Delivery rate HP/IP m3/h/m3/h
Delivery head HP/IP m/m
Net position suction head required m
Power requirement of one pump set at motor terminals kW
Pump efficiency at rated capacity %

Coupling
Type -
Maximum allowable transmitted load kW

B2/FD-18
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Booster pump (where applicable)


Number of pumps -
Manufacturer -
Type -
3
Minimum capacity m /h
Type of journal bearings -
Type of thrust bearings -
Type of bearing lubrication -
Oil supply from -
Type of glands or seals -

Materials:
Pump casing -
Shaft -
Impeller -

One pump in single operation (at max. speed):


3
Delivery rate m /h
Delivery head m
Power requirement of one pump set at motor terminals kW

Coupling
Type -
Maximum allowable transmitted load kW

HP/IP feedwater pump motor


Manufacturer -
Type -
Rated power kW
Rated voltage kV
Rated current A
Locked rotor current A
Rated speed rpm
Rated efficiency %

B2/FD-19
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Rated power factor -


Starting time sec.
Protection system -
Insulation class -
Type of bearings -
Type of lubrication -
Method of cooling the motor -
(external fan/internal fan/water-cooled)

HP-steam bypass station


Number per unit - / %BMCR
Capacity of steam t/h / %BMCR

LP-steam bypass station


Number per unit - / %BMCR
Capacity of steam t/h / %BMCR

Cold condensate tank


3
Net capacity m
Design pressure bar(g)
Design temperature °C

Generator cooler (air/hydrogen to closed water system)


Manufacturer -
Type of cooling water/H2
Number of coolers and capacity -/%
Location of coolers -
Material of tubes -
Secondary cooling water inlet temperature °C
Cold gas temperature °C
Primary water inlet temperature (downstream cooler) °C
Mean temperature rise
- motor winding K
- stator winding K

B2/FD-20
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Synchronous generator
Applicable standards -
Manufacturer -
Type -
Type of cooling water/ H2
Protection class -
Generator power characteristic curve Dwg. No. -
Generator unbalanced load-time-curve Dwg. No. -
Generator saturation curves Dwg. No. -
Rated generator output according to class B insulation MVA
Rated generator output according to class F insulation MVA
Rated power factor lagging cos phi
Rated power factor leading cos phi
Rated active power (at rated gen. output) MW
Rated voltage kV
Voltage variation range %
Rated current (at rated gen. output) A
Rated frequency Hz
Rated speed rpm
Maximum asym. three-phase short-circuit current (at rated kA(peak)
gen. output)
Permissible unbalanced load
- continuous %
- (J2 / Jr )² x t sec
Short circuit ratio kc -
Interia constant (H) of STG (at rated gen. output) kWs
kVA
Test voltage of stator winding kV
Test voltage of rotor winding kV

Generator efficiency at P.F. = 0,85 lagging %


- 4/4 load %
- 3/4 load %
- 2/4 load %
- 1/4 load
Direct axis sub-transient reactance saturated/minimum value %
x"d

B2/FD-21
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Direct axis sub-transient reactance unsaturated minimum %


value x"d
Xd (saturated) %
XD (unsaturated) %
X2 (negative sequence) %
Xo (zero sequence) %

Stator
Number of bushings -
Type of winding -
Core length m
Inside diameter of core mm
Insulation class -
Type of insulation -

Rotor
Diameter of rotor body mm
Length between bearing centres m
Type of windings -
Type of damper winding -
Insulation class -
Type of insulation -

Dimensions
Generator -
Total length m
Total height m
Total width m

Weights
Stator weight (with end shields) t
(without end shields) t
Rotor weight t
Transport weight complete generator T

B2/FD-22
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Excitation system
Manufacturer -
Type -
Protection class of cubicles IP
Rated voltage V
DC current at no load A
DC current at rated continuous load and rated power factor A
Overload current for 10 sec. A
No. of the thyristors in parallel -
Rated current of individual thyristors A
Number of cubicles -
Dimensions L x W x H mm

Excitation transformer:

 rated power kVA

 rated primary voltage kV

 rated secondary voltage V

 number of percentage of taps ±%

 impedance voltage %

Dimension L x W x H mm

Excitation cubicles heaters

 total rating -

 rated voltage V

Max. permissible angle between generator and grid voltage °El.

Automatic voltage regulator


Manufacturer -
Type -
Accuracy of control over load range within 0,5 % -
Steady state voltage regulation grade -

B2/FD-23
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Transient state voltage regulation grade -


Power factor setpoint adjustment range -
Recovery time to within 2% volts when shedding rated MVA Sec
Number of channels
 Automatic -

 Manual
-

Manual control range %


Power system stabilizer (PSS) yes/no

Synchronizing equipment
Manufacturer -
Type -
Double channel yes/no
Power supply voltage V
Input range from – to V
Frequency range from – to Hz
Circuit breaker closing time, from - to msec.

Digital unit protection system


Manufacturer of protection system -
Type -
Number of cabinets -
Auxiliary voltage V
Control voltage / ± % V/%
Size (height x width x depth) mm
Weight kg
Each relay with self check facilities yes/no
List of all protection relay functions on separate sheets -

Generator main connections


Manufacturer -
Type -
Rated system voltage kV
Rated frequency Hz

B2/FD-24
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Rated current
a) generator to generator transformer A
b) generator neutral A
c) Tie branch to unit aux. transformer A
Impulse withstand voltage (to earth) kV(peak)
Power frequency withstand voltage kV
Rated short time current (3 sec)
a) generator to generator transformer kA
b) generator neutral kA
c) Tie branch to unit aux. transformer kA
Max. asymmetric three-phase short-circuit withstand current
a) generator to generator transformer KA (peak)
b) generator neutral kA (peak)
c) Tie branch to unit aux. transformer kA (peak)
Type of busbars/material -
Type of enclosure/material -
Busbar overpressure bar(g)

Generator circuit breaker


Manufacturer -
Type of circuit breaker -
Circuit breaker withdrawable yes/no
Rated voltage kV
Rated frequency Hz
Rated current A
Rated short-circuit making current kA(peak)
Rated short-circuit breaking current (sym.) kA
Rated short-circuit breaking current (asym.) kA
Rated short-time current (1/3 sec.) kA/kA
Total opening times:
• Closing time (till contact touch) msec
• Opening time (including arc extinguishing msec
Transient recovery voltage rating kA/µs
Impulse withstand voltage 1.2/50 µs (across open contacts) kV(peak)
Power frequency withstand voltage, 1 min (across open kV
contacts)

B2/FD-25
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Maintenance intervals after switching cycles with


nominal current -
rated short circuit current -
Motor driven circuit breakers (yes/no) -
Protection class of cubicles IP
Cubicles dimensions (LxWxH) mm

Current and voltage transformer


Manufacturer -
Secondary current of current transformers A
Accuracy class: measuring -
Metering -
Protection -
Rated short circuit withstand current (3 sec.) kA

Manufacturer -
Secondary voltage of voltage transformers V
Accuracy class: measuring -
Metering -
Protection -
voltage regulation -

Earthing switch
Manufacturer -
Type of earthing switch -
Rated voltage kV
Rated frequency Hz
Rated current A
Rated short circuit making current kA(peak)
Rated short time withstand current (3 sec.) kA
Power frequency withstand voltage kV
Rated impulse withstand voltage kV(peak)
Motor driven earthing switch yes/no

B2/FD-26
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data

Protective capacitors
Manufacturer -
Type -
Number of capacitors Nos
Rated voltage kV
Rated frequency Hz
Rated capacity - generator side nF
- transformer side nF

Surge arrestor
Manufacturer -
Type -
Rated voltage kV

B2/FD-27