Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data
Condenser
Cooling water inlet temperature °C Refer to Section B0
Cooling water temperature increase K Refer to Section B0
Terminal temperature difference of condenser at operating K to be determined by
conditions the Tenderer /
Contractor
Maximum cooling water velocity in condenser tubes with 10% m/s 2.2
blocked tubes
Design pressure bar full vacuum
Max. cleanliness factor referred to design cooling surface % 110
B2/FB-1
Tanjung Bin PP T4
Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data
B2/FB-2
Tanjung Bin PP T4
Minimum Requirements
Section B2: Steam Turbine Generator Plants
Performance and Design Criteria Unit Data
Generator
Rated voltage at generator terminals kV 20 or higher 5%
Rated frequency Hz 50
Rated power factor (lagging) cos phi 0.9
Rated power factor (leading) cos phi 0.95
Saturated subtransient reactance x"d % later
Rated short-circuit ratio kc (without minus tolerance) - 0.50
Inertia constant H of complete turbine and generator set kWs later
(based on rated generator output, (without minus tolerance) kVA
Insulation class for generator and exciter - F
Permissible operation at MCR according to insulation class - B
Current transformer secondary rate A 1
Voltage transformer secondary rate V 100 : 3
Definitions:
Rated generator output
defined to be at maximum continuous rating (MCR) at all
ambient site conditions of the ST unit, operation within
insulation class B limits.
B2/FB-3
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Steam turbine
Steam pressure at HP-turbine inlet at MCR bar
Steam temperature at HP-turbine inlet at MCR °C
Steam temperature at IP-turbine inlet at MCR °C
Maximum Continuous Rating of turbine generator MW
Live steam flow at MCR of turbine generator kg/s
No-load steam consumption kg/s
Number of feedwater preheating stages -
Final feedwater temperature at MCR -
Exhaust pressure at MCR bar
Exhaust moisture %
Coupled critical speeds up to 150% of nominal speed rpm
Manufacturer -
Type -
Sectional drawing No. -
Applied Standard
Casings
Number of casings -
Casing design HP -
Casing design IP/LP -
Casing design LP -
Applied Standard
Rotors
Number of turbine shafts -
Distance between bearing centres HP shaft mm
IP/LP shaft mm
LP shaft mm
Applied Standard
Blading
HP regulating stage:
Type of wheel -
Mean blading diameter mm
Pressure in the regulating wheel chamber at MCR Bar
B2/FD-1
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
HP blading:
Type of H.P. blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row -
IP/LP blading:
Type of LP blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row mm
2
Exhaust area of last row (axially) m
LP blading:
Type of LP blading (impulse/reaction) -
Number of stages -
Length of blades last row mm
Mean blading diameter last row mm
2
Exhaust area of last row (axially) m
Materials
HP outer casing -
HP inner casing -
HP blade carriers -
IP/LP outer casing -
IP/LP inner casing -
IP/LP blade carriers
HP rotor -
IP/LP rotor -
HP nozzles -
HP rotor blades -
IP/LP nozzles -
IP/LP rotor blades -
Casing of emergency stop valves (HP-steam; reheat-steam) -
Casing of HP-steam governor valves -
Casing of reheat steam governor valves -
B2/FD-2
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Turbine glands
Type -
Bearings
Number of journal/thrust bearings -
Type: Journal -
Thrust -
Maximum oil outlet temperature °C
Dimensions
Total length of the unit m
Length of foundation m
Width of foundation m
B2/FD-3
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Height of foundation m
Weights
Weight of rotor t
Weight of heaviest part to be handled by crane t
Operating weight of the complete unit t
Turning device
Method of operation -
Turbine rotor speed rpm
Drive -
Rating kW
B2/FD-4
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Materials:
Tubes -
Tube plates -
Shell -
Applied Standard
Gland exhauster
Number of exhausters -
Type -
Rating kW
Oil supply
3
Tank capacity m
Number of recirculations (per hour) l/h
Lubrication oil system pressure bar(g)
B2/FD-5
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Speed rpm
Material of pump casing -
Oil cooler
Number of coolers -
Capacity per cooler %
Erection (horiz./vert.) -
2
Cooling surface per cooler (outside diameter) m
Max. oil outlet temperature °C
Cooler length mm
Materials:
Tubes -
Tube plates -
Shell -
Oil separator
Manufacturer -
Type -
Flow rate per separator of lubrication oil flow %
Heat rating kW
Rating of drive kW
B2/FD-6
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Condenser
Total number of condensers -
Manufacturer -
Type -
Arrangement -
Turbine max. capability (TMC):
Steam flow kg/s
3
Cooling water flow m /h
Cooling water temperature rise K
Cooling water pressure loss bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
2
Cooling surface (outside diameter) m
B2/FD-7
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
B2/FD-8
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Interface to DCS-system
hard wired -
DCS-system bus -
Local operating station per plant
Manufacturer -
Type -
Vibration measurements
Manufacturer -
Designation of system -
Type or name of system -
Total number of shaft vibration sensors -
B2/FD-9
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
HP Feedwater heater 1
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK
B2/FD-10
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
HP Feedwater heater 2
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
B2/FD-11
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -
HP Feedwater heater 3
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
B2/FD-12
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Feedwater tank
Manufacturer -
3
Nominal capacity m
3
Normal working capacity m
Outside diameter mm
Total length mm
Materials:
Shell -
Internals -
Operating weight kg
Water pressure loss at inlet (MCR) bar(g)
Design temperature deaerator °C
Design pressure deaerator bar(g)
B2/FD-13
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
LP Feedwater heater 1
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -
B2/FD-14
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
LP Feedwater heater 2
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Desuperheater surface m
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -
B2/FD-15
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
LP Feedwater heater 3
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -
B2/FD-16
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
LP Feedwater heater 4
Number per unit / capacity in % TMC -/%
Manufacturer -
Type -
Arrangement (horizontal / vertical) -
Drain condensate pumps : number / % TMC -/%
Design code -
Design pressure bar(g)
Design temperature °C
Turbine max. capability (TMC):
Steam flow kg/s
Condensate flow kg/s
Average log. temp. difference K
Pressure loss condensate side bar(g)
2
Heat transfer coefficient kJ/m sK
Fouling factor (which is considered in the cooling surface) %
Heating surface (outside diameter)
2
Condenser surface m
2
Drain cooler surface m
Number of flow passes -
Diameter of tubes (bore) mm
Wall thickness of tubes mm
Outside Diameter mm
Overall Length mm
Weight tons
Materials:
Tubes -
Tube plates -
Shell -
B2/FD-17
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Coupling
Type -
Maximum allowable transmitted load kW
B2/FD-18
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Materials:
Pump casing -
Shaft -
Impeller -
Coupling
Type -
Maximum allowable transmitted load kW
B2/FD-19
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
B2/FD-20
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Synchronous generator
Applicable standards -
Manufacturer -
Type -
Type of cooling water/ H2
Protection class -
Generator power characteristic curve Dwg. No. -
Generator unbalanced load-time-curve Dwg. No. -
Generator saturation curves Dwg. No. -
Rated generator output according to class B insulation MVA
Rated generator output according to class F insulation MVA
Rated power factor lagging cos phi
Rated power factor leading cos phi
Rated active power (at rated gen. output) MW
Rated voltage kV
Voltage variation range %
Rated current (at rated gen. output) A
Rated frequency Hz
Rated speed rpm
Maximum asym. three-phase short-circuit current (at rated kA(peak)
gen. output)
Permissible unbalanced load
- continuous %
- (J2 / Jr )² x t sec
Short circuit ratio kc -
Interia constant (H) of STG (at rated gen. output) kWs
kVA
Test voltage of stator winding kV
Test voltage of rotor winding kV
B2/FD-21
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Stator
Number of bushings -
Type of winding -
Core length m
Inside diameter of core mm
Insulation class -
Type of insulation -
Rotor
Diameter of rotor body mm
Length between bearing centres m
Type of windings -
Type of damper winding -
Insulation class -
Type of insulation -
Dimensions
Generator -
Total length m
Total height m
Total width m
Weights
Stator weight (with end shields) t
(without end shields) t
Rotor weight t
Transport weight complete generator T
B2/FD-22
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Excitation system
Manufacturer -
Type -
Protection class of cubicles IP
Rated voltage V
DC current at no load A
DC current at rated continuous load and rated power factor A
Overload current for 10 sec. A
No. of the thyristors in parallel -
Rated current of individual thyristors A
Number of cubicles -
Dimensions L x W x H mm
Excitation transformer:
impedance voltage %
Dimension L x W x H mm
total rating -
rated voltage V
B2/FD-23
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Manual
-
Synchronizing equipment
Manufacturer -
Type -
Double channel yes/no
Power supply voltage V
Input range from – to V
Frequency range from – to Hz
Circuit breaker closing time, from - to msec.
B2/FD-24
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Rated current
a) generator to generator transformer A
b) generator neutral A
c) Tie branch to unit aux. transformer A
Impulse withstand voltage (to earth) kV(peak)
Power frequency withstand voltage kV
Rated short time current (3 sec)
a) generator to generator transformer kA
b) generator neutral kA
c) Tie branch to unit aux. transformer kA
Max. asymmetric three-phase short-circuit withstand current
a) generator to generator transformer KA (peak)
b) generator neutral kA (peak)
c) Tie branch to unit aux. transformer kA (peak)
Type of busbars/material -
Type of enclosure/material -
Busbar overpressure bar(g)
B2/FD-25
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Manufacturer -
Secondary voltage of voltage transformers V
Accuracy class: measuring -
Metering -
Protection -
voltage regulation -
Earthing switch
Manufacturer -
Type of earthing switch -
Rated voltage kV
Rated frequency Hz
Rated current A
Rated short circuit making current kA(peak)
Rated short time withstand current (3 sec.) kA
Power frequency withstand voltage kV
Rated impulse withstand voltage kV(peak)
Motor driven earthing switch yes/no
B2/FD-26
Tanjung Bin PP T4 Tenderer:
Section B2: Steam Turbine Generator Plants
Technical Data by Tenderer Unit Data
Protective capacitors
Manufacturer -
Type -
Number of capacitors Nos
Rated voltage kV
Rated frequency Hz
Rated capacity - generator side nF
- transformer side nF
Surge arrestor
Manufacturer -
Type -
Rated voltage kV
B2/FD-27