Low Voltage Cables

Table of content

About Nexans 4

Symbols 5

QICC ISO Certicates 6

QICC BASEC 10

Design Criteria 11

Electrical Characteristics 14

Selection of Cables 19

Electrical Calculation Guide 21

Current Rating Assumptions for LV Cables 25

Derating Factors for LV cables 26

Short Circuit Rating – Conductors 35

Transportation, Handling, Storage of the Drums and Laying of the Cables 42

Distribution cables 57

BS LV, PVC Insulation, PVC 0.6/1KV 58

BS LV, PVC Insulation, SWA, PVC 0.6/1KV 62

BS LV, XLPE Insulation, AWA, PVC 0.6/1 kV 66

BS LV, XLPE Insulation, PVC 0.6/1KV 69

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - AD 73

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - QCS 77

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV 81

IEC LV, PVC Insulation, ATA, PVC 0.6/1 kV 85

IEC LV, PVC Insulation, AWA, PVC 0.6/1 kV 88

IEC LV, PVC Insulation, PVC 0.6/1KV 90

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV 96

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV 101

IEC LV, XLPE Insulation, ATA, PVC 0.6/1 kV 106

IEC LV, XLPE Insulation, AWA, PVC 0.6/1 kV 109

IEC LV, XLPE Insulation, CWA, PVC 0.6/1 kV - KM 112

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV 114

IEC LV, XLPE Insulation, PVC 0.6/1KV 119

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV 125

6/3/15 - http://www.nexans.qa Page 2 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
IEC LV, XLPE Insulation, SWA+TCWA, PVC 0.6/1 kV - KM 130

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV - QP 132

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV 134

Pilot Cable 1kV 139

Copper conductors 141

Bare copper conductor 142

Copper Lead 144

6/3/15 - http://www.nexans.qa Page 3 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
About Nexans

Nexans is the worldwide leader in the cable industry


With energy as the basis of its development, Nexans is a global player in the infrastructure, industry, building and Local
Area Network (LAN) markets.
As a worldwide leader in the cable industry, it offers an extensive range of cables and cabling systems to raise industrial
productivity, improve business performance, enhance security, enrich the quality of life, and assure long-term network
reliability.
With an industrial presence in 40 countries and commercial activities worldwide, Nexans employs 25,000 people and had
sales in 2012 of 7.2 billion euros. Nexans is listed on NYSE Euronext Paris, compartment A.

Infrastructure
Nexans provides complete cables and cabling solutions for power transmission and distribution. New technologies,
which are environmentally-friendly, increase capacity and reduce the danger of blackouts.
To reinforce rail safety and efciency, we have products especially designed for the demanding railroad environment.
And to meet diverse needs of incumbent and new telecoms operators, Nexans has customized solutions aimed at lowering
capital expenditure and operating costs.
For the world’s busy airports, we offer cables and cabling systems for energy and communication networks, terminals,
baggage handling systems, runway lights, control towers, etc.

Industry
Nexans offers a complete portfolio of cables and solutions for market segments as diverse as the automotive, rolling
stock and aerospace industries, shipbuilding, nuclear power, oil & gas and petrochemicals, medical and wind
applications, material handling and automation, created industrial Ethernet solutions to unite the ofce and the factory
oor platform, and ensured the highest standards of environmental friendliness and recyclability.
We add value through advanced technologies and durable high-performance products.

Building
Nexans suppliescables and network solutions for structures of all types: from small residences to public and ofce
buildings and big industrial complexes.
Nexans pioneered re-performance cables for public safety.
From standard products to renewable energy solutions, these products contribute to the substainable buildings of the future.

Local Area Networks


Nexans providescopper and optical ber cabling systems for new resource-intensive applications, like Data Centers,
Security services, and Storage Area Networks.
Nexans’ advanced solutions are handling core business data, protecting operations in sensitive conditions, and giving
organizations highspeed transmission and the ability to protect and retrieve vital information.

6/3/15 - http://www.nexans.qa Page 4 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Symbols

Halogen free

Bending factor when laying

Flame retardant

Conductor exibility

Bending factor when installed

Rated Voltage Uo/U (Um)

Max. conductor temperature in service

6/3/15 - http://www.nexans.qa Page 5 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
QICC ISO Certicates

6/3/15 - http://www.nexans.qa Page 6 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 7 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 8 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 9 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
QICC BASEC

6/3/15 - http://www.nexans.qa Page 10 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Design Criteria

A power cable is an assembly of one or more electrical conductors, usually held together with an overall sheath.
The assembly is used for transmission of electrical power. Power cables may be installed as
permanent wiring within buildings, buried in the ground, run overhead, or exposed.

Flexible power cables are used for portable devices, mobile tools and machinery.

CONDUCTOR:

Is an object or type of material that permits the ow of electrical current in one or more directions.
Conductor materials are:
• Plain annealed or tin coated copper conductor (to BS EN 1977, ASTM B3, ASTM B49 &ASTM B 33)

• Aluminum (to ASTM B233)

The conductor structure is complying with the requirements of IEC 60228 Calss 1 , 2 and 5; Solid, Stranded, non
compacted, compacted or compacted sector shaped conductors and Flexible.

INSULATION:

The insulating materials used include:


• Polyvinylchloride (PVC): (PVC/A 70 oC) complying with IEC 60502-1 requirements or Types (TI1 70 oC) &
Heat Resistant PVC type TI-3 (90 oC to 105 oC) complying with BS EN 50363-3.

• Halogen-Free, Flame Retardant compound (HFFR).

• Cross-linked polyethylene (XLPE): complying with IEC 60502 and GP8 as per BS 7655-1.3

The insulation of building wires is covered by Ultra-violet (UV) resistant Masterbatch.

INSULATED CORE COLOR CODES:

Number of cores Colors to IEC 60502-1 Colors to BS 5467

1 Red or Black Brown or Blue


2 Red & Black Brown & Blue
3 Red, Yellow and Blue Brown, Black and Grey
4 Red, Yellow, Blue and Black Blue, Brown, Black and Grey

5 Red, Yellow, Blue, Black and Green / Yellow Green / Yellow, Blue, Brown, Black and Grey

6/3/15 - http://www.nexans.qa Page 11 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
SCREEN DESIGNS:

The standard range of QICC Medium Voltage XLPE cables rated up to and including 33 kV incorporates copper
wire screens based on fault levels of either 3 kA or 10 kA for 1 second. If either of the standard screen designs does
not suit a particular installation, the screen constructions can be tailored in size to meet the specic fault
requirements of any operating system.

WIRE SCREEN CROSS SECTIONAL AREAS:

In the case of three core cables which have screens around each individual core, the total screen cross sectional
area is spread evenly over the three cores.
There are several other factors which can override the above criteria.
Firstly, the screens are designed so that the average gap between the wires does not exceed 4 mm. This result in
the screen area being increased above that required for the required fault level in certain cases. Secondly, the
screen area is limited to a value so that its fault rating does not exceed that of the conductor. In some cases, the
smaller cables in a range have fault levels of less than either 3 kA or 10 kA for 1 second respectively.

CABLE ASSEMBLY:

The Insulated cores are assembled together to form the laid up cable cores in case of multi core cables.
Extruded suitable polymer compound or non-hygroscopic polypropylene ller is applied (when required) between
laid up cores to provide a circular shape to the cable.

JACKETINGS:

There are 3 different types of extruded sheaths:


• Outer sheath
It provides protection of the cable from outside.
• Inner sheath
It applies under a metallic protection and - optional - under a lead sheath.
• Bedding
It separate the sheath applied between a lead sheath and a metallic protection (may also consists of plastic
tapes).

The following materials can be used for the sheath:

Polyvinylchloride (PVC) Type ST2 compounds as specied in IEC 60502-1, or its equivalent PVC Type 9
to BS 7655-4.2.

Polyethylene (PE) compound fulll and exceed the requirements of Type ST7 IEC 60502-1 for cables that
require being abrasion resistant, protected against water ingress and strong Environmental Stress Crack
Resistant (ESCR).

Halogen Free Flame Retardant (HFFR) compounds complying with ST8 to IEC 60502-1 or Types LTS 1 &
LTS 4 to BS 7655: section 6 for cables installed in intrinsically safe locations and where the cables require
being low smoke, low fume and low toxic gas emitting in case of re. Cables to this category are complying
with the requirements of BS 6724.

All cables produced at QICC – a Nexans Company with PVC or HFFR jackets are complying with the ame
retardant test to IEC 60332-1 and Ultra-violet (UV) resistant Master batch.

6/3/15 - http://www.nexans.qa Page 12 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Whenever a requirement for more severe tests as IEC 60332-3 is needed, Oil resistant and Hydrocarbon resistant
for Oil and Gas projects.

ARMOUR:

There are 3 different types of armouring are listed below:

Galvanized round steel wire armour “SWA”:


(The wire diameter depends on the cable diameter under armour, min. diameter 0.8/0.9 mm).

Single or double layer of steel “STA” :


(The minimum thickness of a tape shall be 0.2 mm).

Aluminum or Copper/Tin Copper wire armour “AWA / CWA/TCWA”:


(The wire diameter depends on the cable diameter under armour, min. diameter 0.8/0.9 mm).

JACKETING MARKETING:

Standard engraving outer Jacket Marking consisting of:


Type designation, conductor size, voltage range, and standards
Name of Manufacture "QICC - Nexans"
Year, Continuous length marking every meter.

Any special part no. on request

6/3/15 - http://www.nexans.qa Page 13 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Electrical Characteristics

6/3/15 - http://www.nexans.qa Page 14 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 15 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 16 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 17 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 18 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Selection of Cables

It is essential to consider the specic system and installation conditions to be able to select the right cable.
The following criteria should be taken into account to choose the suitable cable.

1.Cable Laying:

Depending on the nature of the cable system (xed or mobile) a rigid or exible cable should be selected. The
appropriate protection of a cable will be determined taking into account the mechanical stress and presence of
chemical, oils or hydrocarbons.

2.Ambient and ground Temperature:

The quality of the material used to manufacture a cable shall be determined according to the maximum and
minimum temperatures to which the cable will be submitted.

3.Nature of Conductors:

Copper or aluminum conductors can be used.


For equal current rating aluminum cross-section
= 1.28 copper cross-section
For equal ohmic resistance aluminum cross-section
= 1.65 copper cross-section
For copper, sector shaped conductors are available
On request from 70 mm2 and above

1.Maximum operating voltage.


2. Insulation level.
3.Load to be carried.
4.Frequency.
5.Magnitude and duration of possible overload “Emergency current”.
6.Magnitude and duration of short-circuit current for conductor and screen.
7.Length of line.
8.Voltage drop.
9.Chemical and physical properties of soil.
10.Min. and Max. Ambient air temperatures and soil temperature.
11.Specication and requirements to be follow.

VOLTAGE:

The Voltage Is the electric potential difference between two points, or the difference in electric potential energy of
a unit charge transported between two points, The standard rate voltage are dened by three values Uo / U (Um),
where :
Uo = rated rms power frequency voltage, core to screen or sheath.
U = rated rms power frequency voltage, core to core.
Um = max. rms power frequency voltage, core to core.

6/3/15 - http://www.nexans.qa Page 19 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Cable design for 6/10, 12/20 and 18/30 kV is applicable for 6.35/11, 12.7/22 and 19/33 kV respectively.

6/3/15 - http://www.nexans.qa Page 20 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Electrical Calculation Guide

1. RESISTANCE:

The Values of conductor DC resistance are dependent on temperature as given by :

Rt=R20x[l+α20(t-20)] W/km

Rt : conductor DC resistance at t ° C W/km


R20 : conductor DC resistance at 20 ° C W/km
t : operating temperature °C
α : resistance temperature coefcient
= 0.00393 for copper
= 0.00403 for aluminum
Generally DC resistance is based on IEC 60228.

To calculate AC resistance of the conductor at the operating temperature as the following:

RAC = Rt x[ 1+ ys+ yp]

ys : skin effect factor


yp : proximity effect
Generally AC resistance is based on IEC 60287

2. CAPACITANCE:

Is the ability of a body to store an electrical charge.

C : Operating capacitance μF/km


D : Diameter over insulation mm
d : Conductor diameter mm
Єr :Relative permittivity of insulation material

Єr = 4.8 for PVC


Єr = 2.3 for XLPE

6/3/15 - http://www.nexans.qa Page 21 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
3. INDUCTANCE:

Is the property of a conductor by which a change in current owing through it induces" (creates) a voltage (electromotive
force) in both the conductor itself (self-inductance) and in any nearby conductors (mutual inductance).

L=K+0.2 ln ( 2s/d) mH/km

L : Inductance mH/km
K :Constant depends on number of wires of conductor
d: Conductor diameter
S : Axial spacing between cables (Trefoil formation )
S : 1.26 x axial spacing between cables ( Flat formation)

4. REACTANCE:

The inductive reactance per phase of a cable may be obtained by the formula:

X = 2πf L x 10-3 W/km

X: Reactance W/kmz
f : Frequency Hz
L : Inductance mH/km

5. IMPEDANCE:

Is the measure of the oppostion that a circuit presents to a current when a voltage is applied.

Z :Phase impedance of cable W/km

Rac : AC resistance at operating temperature W/km

X : Reactance W/km

6/3/15 - http://www.nexans.qa Page 22 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6. INSULATION RESISTANCE:

R : Insulation resistance at 20° C MΩ.km


D : Insulated conductor diameter mm
d : Conductor diameter mm

7. CHARGING CURRENT:

I = Uo x 2Πf x C x 10-6

I : Charging current A/km


Uo : voltage between phase and earth V
C : Capacitance to neutral μF/km

8. DIELECTRIC LOSSES:

D = 2πf C Uo2tan δ10-6 watt/km/phase

D : Dielectric losses watt/km/phase


Uo : Voltage between phase and earth V
C : Capacitance to neutral μF/km
tan δ : Dielectric power factor

9. CABLE SHORT CIRCUIT CAPACITY:

ISC(t) = ISC(1) / √t kA

ISC(t): Short circuit for t second kA

ISC(1): Short circuit for 1 second kA

Data about short circuit are tabulated from table 9 to table 11

6/3/15 - http://www.nexans.qa Page 23 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
10. VOLTAGE DROP:

When the current ows in conductor, there is a voltage drop between the ends of the conductor. For low voltage cable
network of normal operation.

We recommend voltage drops not to exceed:


3 % for lighting wire systems
5 % for driving force wire systems
10 % on starting time for motors

To calculate the voltage drop, follow the below formulas:

∆u : Voltage drop V
Rc : conductor resistance in D.C. at operating temperature (W/km)
Ra : conductor resistance in A.C. at operating temperature (W/km)
L : core inductance (H/km)
ω : pulsation equal to 2 π f (314 for f= 50 Hz)
I : Load current A
X : Reactance W/km
ℓ : Length km
cosΦ : Power factor

- Relation between Cos Φ and Sin Φ as following:

6/3/15 - http://www.nexans.qa Page 24 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Current Rating Assumptions for LV Cables

THE ELECTRIC CURRENT: is a ow of electric charge. In electric circuits this charge is often carried by
moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions and electrons such as in
a plasma.

The calculation of the current ratings, Current rating equations(100% load factor) and calculation of losses
are based on IEC 60287 series , and the values of Current ratings for underground applications (In Duct or
Direct Buried) are derived from the latest issue of ERA Report ‘Current Rating Standards 69.30 Part V’.

And the values of current ratings are veried with the tabulated value in IEC 60364-5-52 for LV cables, and IEC
60502-2 for MV cables.

The Current Carry Capacity calculated based on one circuit installed thermally isolated from other circuits or any
other heat source.

Ambient Air Temperature : 30 °C

Ambient Ground Temperature : 20°C

Depth of laying in ground : 0.70 m

Soil Thermal Resistivity :2.5 °K.m/W

For other installation conditions or any value of differant air / ground temperature, depth of lay or soil thermal
resistivity you can use the tabulated current rating by the de-rating factor values as in tables 1 to 8.

6/3/15 - http://www.nexans.qa Page 25 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Derating Factors for LV cables

1. INSTALLATION CONDITIONS FOR CABLES IN AIR:

Table 1 : Rating factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for
cables in the air:

2. INSTALLATION CONDITIONS FOR DIRECT BURIAL CABLES:

For a cable installed direct buried, the following tables will be used to calculate the current rates based on the actual
soil thermal resistivity, Ground ambient temperature and the Depth of Laying.

Table 2: Rating factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying
capacities for cables in ducts in the ground:

6/3/15 - http://www.nexans.qa Page 26 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Table 3: Rating factors for cables buried direct in the ground or in buried ducts for soil thermal resistivities other than
2,5 K·m/W to be applied to the current-carrying capacities for reference method D:

6/3/15 - http://www.nexans.qa Page 27 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
3. INSTALLATION CONDITIONS FOR CIRCUIT GROUPS:
Table 4: Rating factors for one circuit or one multi-core cable or for a group of more than one circuit:

6/3/15 - http://www.nexans.qa Page 28 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Table 5: Rating factors for more than one circuit cables laid directly in the ground - single or one multi-core cable:

6/3/15 - http://www.nexans.qa Page 29 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 30 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 31 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 32 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 33 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
6/3/15 - http://www.nexans.qa Page 34 / 146
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Short Circuit Rating – Conductors

The permissible short-circuit currents as presented in gures 1 to 6 are calculated in accordance with IEC
60724:2008.

The calculation method neglects heat loss and is accurate enough for the majority of practical cases. Any error is on
the safe side. However, caution should be exercised when using large size conductors and an installation radius less
than 8 x cable diameter where high deforming forces may occur.

Where such conditions cannot be avoided, it is recommended to reduce the short circuit rating by 15% or contact
SCC technical department.

The following formulae have been derived from 60724:2008

Figure 1:

Ik = (0.155 / √ t) x S

Figure 2:

Ik = (0.1038 / √ t) x S

Figure 3:

Ik = (0.075 / √ t) x S

Figure 4:

Ik = (0.068 / √ t) x S

Figure 5:

Ik = (0.143 / √ t) x S

Figure 6:

Ik = (0.0937 / √ t) x S

I : Short-circuit current (kA)


k : Duration of short-circuit current t (sec.)
S : Cross-sectional area of conductor (mm2)

6/3/15 - http://www.nexans.qa Page 35 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Maximum Short circuit temperature for cable components:

PVC (based on 70°C type TI-1 or 90°C type TI-3) cables copper and aluminum conductor:

6/3/15 - http://www.nexans.qa Page 36 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
XLPE cables copper and aluminum conductor:

6/3/15 - http://www.nexans.qa Page 37 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Graph 1 : PVC (90 °C type) insulated cables short circuit (Copper Conductor):

6/3/15 - http://www.nexans.qa Page 38 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Graph 2 : PVC (90 °C type) insulated cables short circuit (Aluminum Conductor):

6/3/15 - http://www.nexans.qa Page 39 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Graph 3 : XLPE (90 °C type) insulated cables short circuit (Copper Conductor):

6/3/15 - http://www.nexans.qa Page 40 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Graph 4 : XLPE (90 °C type) insulated cables short circuit (Aluminum Conductor):

6/3/15 - http://www.nexans.qa Page 41 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Transportation, Handling, Storage of the Drums and Laying of the Cables

INTRODUCTION:
This document is a collection of instructions and methods for safe cable usage once the cables leave the manufacturing
unit. Document consists of 5 parts:

Cable & Drum Handling and Movement


Cable & Drum Inspection
Long Term Cable Storage
Cable Installation
How to manage Cable & Drum Damage

This document is intended to offer guidance to the cable transporter and/or installer compiling methods and recommended
practices for safe cable handling and storage once the cables leave the manufacturing unit for standard/generic types of
Power cables ( HV-MV-LV) , Control cables ,Instrumentation cables and Telecommunication cables.

It is intended for evaluation and use by technically skilled transporters and/or installers and is not meant to serve as a
guarantee nor be a substitute for the expertise of skilled professional transporters and/or installers: although the information
is believed to be accurate as of its date of publication, Nexans makes no representations or warranties, expressed or
implied with respect to the accuracy or completeness of this document and assume no obligation to update or correct the
same in the future. You should always consult a trained professional for the most current industry practices and procedures
unique for your application.

CABLE DRUM HANDLING AND MOVEMENT:

Introduction:

Electrical and Fibre Optic cable will be supplied on wooden drums unless the total cable weight exceeds 10 tonnes, in which
case steel drums are supplied. Both types of drums are treated to give protection against premature deterioration of
component parts.
The cable drum is given extra mechanical strength by the provision of wooden cleats (or slats or battens) xed between
drum ange edges which give additional protection to the cable against accidental damage.
Drum anges are marked to provide vital information to assist with the handling of the drums and the installation of the
cable. This information includes drum weight, a mark on the ange indicating the end of the cable, and an arrow indicating
the direction the drum is to be rolled during rolling or transportation.

The rolling of the drum in the direction of the arrow ensures that there is no tendency for the cable to loosen its wind on the
drum. It should be noted that when pulling the cable off the drum and installing the cable, the arrow will point in the opposite
direction to the rotation of the drum.

Drum Handling:

6/3/15 - http://www.nexans.qa Page 42 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
The movement of cable drums by motorised forklift truck is the preferred method. Most drums of cable are within a weight
range that permits their movement by this method.
In general, the forklift truck method of drum handling is only applicable where a hard and level ground surface is available.
This is required in the intended storage area. In this case a forklift capable of lifting about 12 tonnes will be required
(maximum drum weight plus contingency). It is also necessary to ensure that the forklift truck tines are capable of
traversing the width of the drum and provide support to both anges.
For the smaller drums, tines of 1200 mm length will be satisfactory. The larger drums will require tines of 1800 mm length.
For the larger drums, for example containing 33 kV or 132 kV cables or long lengths of cable, it will be necessary to have
tines at least 2500 mm so that the cable drums are adequately supported by both drum anges.

Some drums may be of sufcient length and weight to require cranes to load and unload from transport vehicles. In this
case, it will be necessary to ensure that a spreader bar of sufcient length is used to ensure the lifting chains do not
compress the drum anges.

During the transportation, cable drums must be securely restrained to prevent their movement and possibility of serious
mishap in which the cable could be damage beyond repair.

When forklift or crane is not available, a makeshift ramp with approximate inclination of 1:4 should be constructed. The
cable drum should then be rolled over this ramp by means of ropes or winches. Additionally, a sand bed at the foot of the
ramp can be build to brake the rolling cable drum.

6/3/15 - http://www.nexans.qa Page 43 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Drum Handling in Truck:

When the drums are loaded on trucks, binding must be made with ropes crossing through the central hole and if necessary
on the drum anges.

A special chocking system is required when transporting drums with lorry or trucks. Rafters are fastened to the vehicle bed
before positioning the drums.

6/3/15 - http://www.nexans.qa Page 44 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
DRUM AND CABLE INSPECTION:

Inspection
Cable and drum should be inspected when received at the storage area.

Cable and drum should also be inspected before removal from the storage area.

Both wooden and steel cable drums should be inspected to ensure that the drum cleats (or slats or battens) are not
damaged.

If any damage has occurred in transit the cleats should be carefully removed to verify if any damage has occurred to the
cable. Normally the outer layer of cable on the drum has adequate space between it and the inside of the drum cleats to
prevent cable damage.

Additionally, inspection must include an assessment of the state of the drum due to transport vibration and movement,
weathering or environmental damage.

In changeable dry and wet weather, or consistently dry and hot weather (near or above 30oC), the wooden section of the
drum shrinks and the whole drum could become unstable and cause damage to the cable when the drum is moved.

Therefore, the transverse bolts must be tightened with a torque wrench before the drums are moved otherwise the drums
could collapse during this operation. To ensure they are “tight” these bolts must also be re-tightened during cable
installation. The force (torque) shall be as follows:

Drum size 700–1400 mm = force 80 Nm


Drum size 1600–2200 mm = force 100 Nm
Drum size 2500–2800 mm = force 120 Nm

6/3/15 - http://www.nexans.qa Page 45 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
The corrective action is to identify the 4 (or more) bolts extending from one ange to the other with hexagonal nuts at each
end. These nuts must be tightened before any unstable drum is moved.

The design of wooden drums for heavy power cable includes a metal spindle assembly to provide added strength at the
spindle hole. So, where tted, the 4 (or more) bolts holding the steel plate at the spindle hole are to be tightened or the drum
will not turn smoothly on the shaft or spindles during cable installation.

This procedure is to be adhered to in all installation projects before wooden drums are handled since the effects of vibration,
movement, the climate and duration of exposure to the environment can be extensive.

Note that timbers of the drum anges and barrels that have shrunk are likely to have loose nails as well as the bolts, but
loose nails are harder to correct. It will be necessary to apply caution and vigilance during the cable unwinding to identify
and reduce the damage to the cable produced by the loose nails.

If the cable ends are accessible, it is possible to inspect the presence and condition of the end caps. The end cap is
designed to prevent the ingress of moisture into the end of the cable. Any damage, holes or cracks, in the end cap must be
identied and the end cap replaced so to avoid any moisture or water from entering the cable either due to further storage
time or during installation.

If the end cap is absent, although the cable ends may have been sealed by a mastic or adhesive applied on the cable end
by the supplier, but if no end sealing is seen, a heat shrink cap should be applied ensuring a tight seal to the cable outer
layer.

It is also implied that, if the end cap or sealing is absent from the outer end of the cable (the end from which the cable would
normally be pulled), then the cable end must be examined and assessed.

The following is recommended, so if the cap or sealing has been absent for a long time (more than one month); or the cable
end faces up toward the sky; or the end cap has been absent during periods of rain; or any form of cable end deterioration /
ageing / swelling / or soiling is observed, then the cable end should be cut back 300 mm and re-examined for presence of
moisture and cut back further when moisture is found, and a new end cap must be applied to the cable end, ensuring a tight
seal to the cable outer layer.

Warning

When any damage to the drum cleats (or slats or battens), or slackening of the cable layers has occurred, or drums moved
when unstable, then cable damage is possible and it is necessary to contact the nearest Nexans representative to assess
the situation and advise of an appropriate solution.

LONG TERM CABLE STORAGE:


(more than 3 or 4 months)

The instructions below are directed to assist in the case of any of the following:

Drums and the timber used in drums deteriorates with time and weather
Cable end caps deteriorate with time and weather
Exposed cable surfaces can deteriorate or colours fade
Cable can be damaged by the environment
Cable may be damaged during movements or transport

Drum Storage

Drums should be stored on a level and rm surface (e.g. timber baulks, rm gravel, or concrete), on the ange
edges (not with the ange at on the ground), such that they will not be standing in water or in continually damp
conditions, and restricted from rolling.

6/3/15 - http://www.nexans.qa Page 46 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Failure to provide these conditions is likely to result in timber rot and weakening of the ange with potential breaks
of the ange or collapse of the drum to the point where the cable itself will rest on the ground. Any of these
outcomes will make installation of the cable more problematic or impossible.

Wedges must be used to retain drums. Wedges must be positioned at ange edges and not between anges. The
use of stones are not recommended.

6/3/15 - http://www.nexans.qa Page 47 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Wooden cable drums can be stored in the open for a period of at least 18 months.
Rate of deterioration and ageing is dependent on the environmental conditions and seasons, so inspection and
maintenance of the drum will be required during the storage period.
The interval between inspections is a maximum of 12 months in frequently wet weather conditions and reduced to
6 months in tropical environments where wet or humid conditions are concurrent with high temperatures and also
when the drums are stored in very dry and very hot (near and above 35°C) environments.
Maintenance involves the tightening of the transverse bolts (ange to ange, also known as “barrel bolts”). At the
same time, the bolts holding the steel plate at the spindle hole are to be tightened. These actions are to prevent the
collapse of the drum during movement and during cable installation.
If cable drums are required to be stored for periods longer than two years it is recommended that they are stored in
an enclosed area sheltered from the environment. If considered necessary, the cable could be rewound on to steel
cable drums (if not already supplied). The rewinding process can be organised by contacting the nearest Nexans
representative.
Normally, the drum dimensions are so chosen that the cable wound onto drums almost lls the space between the
anges up to their outer edge. In these cases, the cable assists in the stability of the drum anges and their
respective positioning, but the heavy weight of the cable may induce the ange to bend if left unmoved.
On occasions, the purchased length does not ll the drum and sometimes drums are stored after installation of part
of the length, so the drum contains a portion of the total length of cable (ie only the spare length is stored). In these
cases, the ange extends well beyond the supporting cable and is more likely to are or bend under the weight of
the cable, when left in the one position over time.
Therefore, in either case of the full drum or the partially empty drum, any sign of ange distortion is indicative that it
is necessary to occasionally turn these drums some amount (example a 90° rotation in the direction indicated by the
arrow painted on the ange) so that a “new” part of the ange is employed to support the cable weight. Failure to do
this could result in a ange distortion that will make it difcult to wind the cable off the drum and may result in
damage to the cable.
Arresting or slowing the rate of deterioration for any drum, but particularly for those drums most affected, can only
be done by storage in a covered dry area.

Cable Storage

Cables are supplied with end cap sealing to prevent ingress of moisture or water. Cable drums should be handled
such that damage to the cable sheath or to sealing caps does not occur as this would subsequently permit the
ingress of moisture.

If the cable is used progressively (partial length is cut off and used) the exposed end must be immediately sealed
with a new end cap. Heat shrinkable end caps are recommended for this purpose for installation as follows:

The cable end to be sealed must be cut at right angles and at so that the cores do not protrude from the
sheath. To t the end cap, position the cable end so that it is facing vertically upwards.

6/3/15 - http://www.nexans.qa Page 48 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Some hard plastic sheathing materials are quite smooth and slippery. These materials may not adhere to
the end cap and may not adhere even if mastic lined end caps are used.
To enable adhesion to take place, such sheath materials must be abraded with coarse sand paper before
shrinking the end cap over the cable surface.
Place the end cap over the cable end and gently apply heat using a propane ame. Heat should be applied
evenly over the whole surface of the end cap, by smooth movements of the ame (Only a small ame is
necessary), but starting at the very end of the cable and shrinking the cap sleeve away from the cable end.
Allow the cable end to cool and then check that the end cap has rmly gripped the cable end and that a
satisfactory seal has been achieved. Electricians' PVC tape is then wrapped around the junction of the end
cap and the cable sheath to reinforce the seal.
Cables with coloured outer sheaths should not be stored in direct sunlight to prevent fading of the colour. Cables
should be protected against direct sun light with suitable protection package such as black plastic sheeting, lagging
etc…

CABLE INSTALLATION
Preparation for Cable Installation
Route preparation
The cable route needs to be prepared and inspected to ensure a proper installation can take place without
obstructions, protrusions, or debris in the way of the cable during a pull.
Cable ducting, if used, should also be checked to ensure they are clear and will not cause a jamming or scraping of
the cable sheath. In the case of very long duct runs, they may only be able to be checked using special camera
systems to verify the integrity of ducts, duct joins are not misaligned, and the ducts are clean.

Drum and cable preparation


If the external temperature is below 5° C, you should postpone cable pulling. If installation of cables is necessary, it
is imperative to store them, before unreeling, in warmed room above +10° C for at least 24 hours. Unreeling has to
be done within 2 hours using a slow and regular speed (around 20m/minute) without shock.

A drum and cable inspection must be performed and appropriate actions taken, before taking any cable off the
drum.
Therefore, when removing drum cleats (or slats or battens), care should be taken that the cable sheath is not
accidentally damaged. Any lever or device being used must NOT make any contact with the cable. For example a
removed cleat should not be used to prise off other cleats as the end of the cleat bearing on the cable could cause
damage to the sheath. (This method of cleat removal is a reported cause for sheath damage).
The design of wooden drums for heavy power cable includes a metal spindle assembly to provide added strength at
the spindle hole.

6/3/15 - http://www.nexans.qa Page 49 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Prior to winding off the cable, reference should be made to the information on the ange and the spindle hole
diameter measured, so that the drum can be positioned correctly using a suitable axle or spindle in an appropriate
handling device. Suitable axle” means of a diameter preferably within 5 mm of the spindle hole, but not more than
10 mm difference. Greater difference in the diameter of the shafts will cause damage to the spindle hole and steel
sleeve.
It is also necessary to check that the cable does come off the drum cleanly and smoothly.
It has been found that some cables with sheath materials that are affected by warmer ambient temperatures (near
or above 30°C, which means that actual cable surface temperature will be higher than ambient temperature) or that
are affected by the tension with which they are wound onto the drum, may tend to exhibit some adhesion between
the layers and turns of the cable. This adhesion, if strong enough, may cause the cable to resist the unwinding and
interfere with the installation. Remedial action is to ensure that the turns are pulled off by hand or equipment, to
ensure a smooth installation pull.
Rotation of drum and drum brake
It should be noted that when pulling the cable off the drum, the arrow (painted on the ange of the drum) will point in
the opposite direction to the rotation of the drum. This is an expected practice.

A brake or other means of preventing unnecessary rotation of the drum is required. The lack of a brake will result in
extra rotation of the drum and surplus cable being forced off the drum. This presents a safety risk for any adjacent
operators and is likely to cause unacceptable damage to the cable.
The aim is to have the drum rotating only when cable is intentionally being pulled off. Excessive braking is not
necessary and may cause cable damage or make the pull unnecessarily difcult or induce too much tension in the
cable.
Pulling strength based on conductor types should be as follows:

5 daN/mm² of cross section for copper conductors


3 daN/mm² of cross section for aluminium conductors

During unreeling, drum rotational velocity and cable pulling velocity should be even, and should not exceed 20
metre/minute.

Cable end caps and pulling eyes


Cable ends will be protected by end caps or by pulling eyes. For longer lengths of cable (perhaps over 800 m) or for
large conductor sizes (over 630 mm2), Nexans recommends the use of pulling eyes xed to the main conductors of
the cable. Pulling long and heavy cables by pulling socks can lead to cable or sheath damage.

6/3/15 - http://www.nexans.qa Page 50 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
The end caps and pulling eyes prevent moisture from entering the end of the cable and it is necessary to inspect
the condition of the end cap or pulling eye when accessing the cable ends before the installation.

Any damage, holes or cracks, in the end cap must be identied and the end cap replaced before installation is
started, so to avoid any moisture or water from entering the cable during the installation.

Any damage, holes or cracks, in the heat shrink sleeve of a pulling eye must be identied and the heat shrink
replaced before installation is started, so to avoid any moisture or water from entering the cable during the
installation.

End caps and pulling eyes must also be inspected after the installation to identify if end cap or sealing has been
broken during installation, so that repair or corrective actions can be taken.

Checking and sealing the ends after installation is important even if the cable end is to remain unconnected for just
a short time (3 hours). Ends that are to remain exposed or buried must be sealed against the possibility of ingress
by water.

Maintaining the tightness of timber drums

Timber drums may be transported long distances or moved many times in storage, which can cause a loosening of
the bolts that hold the cable drum rm and functional. It is therefore appropriate to check and tighten bolts whenever
it appears that the bolts or nuts are loose.

This particularly applies in the case of an aged timber drum, when the bolts may have to be tightened before
moving the drum for installation and it may be necessary to re-tighten the bolts after a few turns of the drum as
cable is pulled off. This applies to both the bolts across the drum (ange to ange) and also the bolts holding the
steel spindle plate.
To further explain, the effectiveness of the bolt tightening normally recommended before drum movement or
transport, is dependent on the relative positioning of the timbers of the drum, since these timbers have moved and
aged in a stationary position. Once the cable drum is turned during installation, the weight of the cable moving
inside the drum will re-position some of the timbers which will move to relative positions where the compression by
the bolts is reduced. This will result is a loosening of the bolts and they require to be re-tightened.

It is also advised that re-checking the nuts on these bolts be done at stops during the pull and any signs of
loosening is indicative that further re-tightening is appropriate.

One effect of loose barrel bolts is that the tension on the cable during installation may be sufcient for the cable end
being pulled to force its way between other cable turns on the drum or between cable and the drum ange. Trying to
pry that embedded cable out can become difcult and may result in damage to the cable.

Note that timbers of the drum anges and barrels that have shrunk are also likely to have loose nails as well as the
bolts, but loose nails are harder to correct. It will be necessary to apply caution and vigilance during the cable
unwinding to identify and reduce the damage to the cable produced by the loose nails.

6/3/15 - http://www.nexans.qa Page 51 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Loose nails in the ange can be pulled tight from the outside surface and clinched / bent hard against the ange so
they no longer will protrude on the inside of the drum.

Cable Make or Cable Creepage:

During installation, it is expected that the inner end of the cable will extend because of the rotating direction of the
drum. It occurs less, or not at all, with steel drums and is normally a small extension with timber drums. This
extension is sometimes called “Cable-Make” or “Cable Creepage”.
The inside end of the cable has a tendency to creep through the hole in the ange when the drum is revolved in the
opposite direction to that originally employed when winding the cable onto it. This tendency cannot be prevented.
The amount of creepage depends on the length of the cable on the drum, the size of the cable and the number of
times the drum is revolved. The accumulated slack due to unwinding long lengths of cable may amount to several
metres. It can become extensive when the timber drums bolts have loosened or the timber has aged and shrinkage
has taken place.

Cable-Make or Cable Creepage is sometimes alleviated by pulling the cable off the drum from the bottom rather
than the top of the drum and so the reeling is in the same direction of the arrow painted on the ange of the drum. In
this case, it may occur that the cable inner end, intentionally left out for testing, will in fact withdraw into the drum
and will be “lost” unless it is xed rmly to the drum ange. If the end is allowed to move inside the drum, it is
possible that the friction and tight space will exert pressure on any cable end cap and cause it to be pulled off.

Note that to enable a pull to be moved from a top to a bottom feed, it is necessary to stop the pulling process,
relieve the cable tension, and lift the cable drum off the stand, rotate the drum 180° on the vertical axis, and re-
position in the stand, while ensuring that the cable end being pulled is not damaged. Not impossible, but care and a
risk assessment is required.

To avoid creepage and sinuous shape on the barrel of the drum during paying off, the inner end of the cable on the
drum ange should be free, not xed to the drum.

Cable Installation

Installation of the cable must be performed within these guidelines:

6/3/15 - http://www.nexans.qa Page 52 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Maximum pulling tension.

The cable must not be pulled with a tension above the maximum pulling tension.
It is recommended that a load cell is in-line with the cable to measure the tension. Calculations should be
done before the pull to ensure an appropriate number of cable-pullers and cable-pushers are used to keep
cable tension below the maximum value and the load cell is monitored to ensure the maximum tension is
not exceeded. Many installers will have recording devices so that the digital output from the load cell is
stored and proof can be presented that each cable pull was performed below maximum tension.
For long circuits, where long lengths or heavy cables are used, pulling tension calculations should be
performed for each cable section. Pulling methodology should be prepared clearly detailing the drum
position, position of winches or caterpushers, and the number and type of rollers to be employed. For direct
buried installations, rollers should be used at 3-4 metre intervals, with more frequent rollers at bends.

To reduce the pulling tension, the installer may use lubricating liquids specically formulated for cable
pulling. Signicant reductions in tension can occur by the use of lubricants.

Minimum bending radius (during installation)

The cable must not be subjected to a bend smaller than the minimum bending radius (given as the
“minimum bending radius during installation” and not to be confused with the “minimum bending radius after
installation”)
Ducting at cable bends must be selected so the curvature is not below the minimum bending radius during
installation. When using rollers at cable changes in direction, it is recommended a number of rollers are
used forming a radius that is larger than the minimum bending radius.

6/3/15 - http://www.nexans.qa Page 53 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Special care needs to be taken at duct entry points, where sharp bending of the cable can take place, when
a bend is close to the duct entry. It is necessary that supports are used so that the cable is directed into the
duct in parallel to the duct direction and that any bending radius is greater than the minimum bending radius
during installation.
An alternative is the use of bell mouth entries at the duct ends to guide the cable into the duct and reduce
the possibility of cable sheath damage.
The aim is to have the cable guided so that the duct edge does not scrape, catch, tear, or wrinkle the outer
cable layer. While this care is necessary for all cables, we particularly advise installers that damage is more
likely with softer cable sheathing materials (such as the range of PVC materials) and is more likely for
installations performed when ambient temperatures are near or above 30°C.

Sidewall bearing pressure


The cable must not be subjected to lateral pressure that exceeds the sidewall bearing pressure.
Calculations must be done prior to installation to determine the likely sidewall pressure on the cable at the
bends in the route. Bends may occur within ducts and the duct acts as a good support for the cable.
However, bends can also occur at rollers or deection points and these must also be evaluated to ensure
the maximum sidewall bearing pressure is not exceeded.
Excessive pressure may result in the outer layer on the cable being torn and pulled off. If this takes place, it
is a common effect that the tear will continue during the cable pull and the torn sheath will accumulate at
one point within the bend and create an increase in cable pulling tension.

Deformation of the sheath

A combination or action of any of the above three items, even without exceeding any of the manufacturers
recommendations, can result in the elongation of outer layer of the cable and form a “rucking” or
“corrugation” of the cable sheath during installation.
Deformation of the sheath during installation is known to occur when the sheath material is softened by
elevated temperatures, such as the range of PVC sheathing materials, particularly when the cable is
installed in warmer ambient temperatures (near and above 30°C). Note that actual cable surface
temperature can be higher than ambient temperature.
It is also known to occur when the outer layer is thinner than a full sheath, such as may occur when
installing a Nylon covered cable, which is covered by a thin Sacricial Sheath.
Such deformation should be monitored to avoid an escalation to very severe puckering, which could induce
the tearing of the sheath. Rucking, corrugation, and puckering can be reduced by the use of lubricating
substances which will reduce the friction experienced at turns or bends on xed deectors and on rollers
and even on long straight sections.
Note that longer runs and heavier cables will experience this deformation more often.
Corrective action includes the pausing of the installation pull and the easing of tension and pulling the
affected cable length past the bend or roller or friction point that is causing the effect.
Once the affected area is moved along, there is often a re-settling of the elongated sheath and the effect is
reduced. Stopping and allowing the cable to cool, will tend to set the corrugations in place and they will not
easily be removed.
Where this deformation takes place, there is a small reduction of the thickness where the material is
stretched, but such deformation as a whole is considered to be of minor consequence.
Usually, no repair or corrective action is required on the cable itself.
Repair is only necessary when there is a breaking or tearing of the sheath.

Thermal backll

When special thermal backll is required, it is important that the installer to be fully informed of the
arrangement planned. There will be a dened minimum thickness of backll below the cable and a minimum
thickness above the cable, as well as a width of trench that must be lled with backll material.
In order for the cables to avoid overheating during operation, it is important that the minimum thicknesses of
backll are maintained along the complete route of the cable.
Also, the backll material must not be mixed with native soil or other available materials as they are not
likely to have the same thermal properties as the backll materials selected.

6/3/15 - http://www.nexans.qa Page 54 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Failure to comply with minimum thickness or failure to ensure that only clean backll material is used will
result in the cable overheating during operation.
A cable failure is not likely in the short term, but eventually the excessive heat will cause a breakdown of the
cable insulation. It is likely that a cable repair will be expensive and difcult to perform and the loss of
supply could incur very high costs for the operation of the plant.

Free movement of the drum

It is also necessary to check that the cable does come off the drum cleanly and smoothly.
Sufcient tension is required to ensure the cable comes off the drum and moves in the direction of the pull
without a bend that is smaller than the bending radius of the cable.
Obstructions, protrusions, and equipment frames should not interfere with the path of the cable and the
installer must ensure the cable is not damaged.

Summary
The installer must take precautions to ensure the cable is installed correctly and without damage. The
above specic points must be observed, but additional observation and care may be needed by the installer
to ensure a successful installation.

HOW TO MANAGE DRUM AND CABLE DAMAGE


Timber drums do deteriorate over time when exposed to the weather and the level of deterioration is
dependent on the variety and type of weather to which the drum is exposed.

Temperate or colder environments are the most kind to the ageing process, but wetness can induce rot in
the timber and wetness concurrent high temperatures (as may be found in tropical areas) will accelerate the
rotting process. The most obvious point of fastest deterioration is the contact point of the timber drum to the
ground, so it is essential for the drums to be stored on a rm gravel surface or on concrete and that the
drum is not allowed to rest with the ange in water.

Dry and hot environments (near and above 35°C) will have the effect of drying out the timber and inducing
timber shrinkage. The metal components (bolts, shafts, and nails) that hold the timbers in place will
therefore need to be tightened to avoid a loose assembly of timber that will not tolerate the forces of
transport and unwinding of the cable during an installation.

With a drum that has aged or deteriorated, it is necessary that the transverse bolts (ange to ange, also
known as “barrel bolts”) are inspected and tightened and the bolts holding the steel plate at the spindle hole
are to be tightened. Inspection is required before lifting or moving the drum and also after a few turns of the
drum at installation and at intervals during the installation.

One effect of loose barrel bolts is that the tension on the cable during installation may be sufcient for the
cable end being pulled to force its way between other cable turns on the drum or between cable and the
drum ange. Trying to pry that embedded cable out can become difcult and may result in damage to the
cable.

It is also important that the shaft or spindles used to support the drum during unwinding or installation of the
cable are close to the size of the hole provided in the drum. Shafts or supports that are too small will tend to
gouge the spindle hole so that rotation of the drum becomes uneven, usually leading to additional damage
and greater gouging of the spindle hole which leads to greater difculty in using the drum and cable and
could even escalate to a point that winding is no longer possible.

Should it be apparent that spindle hole damage continues to occur then a larger spindle hole needs to be
formed or a Nexans representative be contacted for assistance.

Looseness in the bolts around a spindle plate may induce similar problems. This is why these bolts also
need to be tightened.

6/3/15 - http://www.nexans.qa Page 55 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Lubrication of the shaft or spindle is advised when the timbers around the spindle hole or around the spindle
plate are suspected of being weakened by ageing. The lubrication will relieve rotational forces on the
timbers and on the spindle plate bolts and the timbers they are bolted to.

It is more difcult to tighten loose nails and some nails that are under the cable will not be accessible. Thus
care is required to make observations and take corrective actions to avoid cable damage.

In those cases where damage is not avoidable then the following corrective actions are recommended:
In the case of the damage being sustained on the surface of the cable sheath and not penetrating much of
the thickness (say depth of damage less than 1.5 mm or 50% of the total thickness, whichever is smallest)
then no repair action is required.

Should it be desired to repair deeper damage or broken or torn or slit sheath, then a heat shrink sleeve to
cover all such damage is acceptable and most commonly used for such repairs.

In terms of cable longevity, for damage deeper than 1.5 mm or 50% of the sheath thickness, a heat shrink
sleeve over the damage restores the function of the sheath.

And should the cable sheath be torn or broken or slit, a heat shrink sleeve over this damage restores the
function of the sheath.

6/3/15 - http://www.nexans.qa Page 56 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar Contact
Phone: +974 4 467 3009
sales.qatar@nexans.com

Distribution cables
Medium and low-voltage cables (1kV to 60 kV) are used in the basic distribution
network that brings power from high-voltage substations to cities and
remote areas.
To provide this needed power for change, Nexans has been leading the way in
new materials and designs for distribution cables and networks. We also master
installation techniques in some of the toughest environments imaginable,
including submarine, aerial and dense urban conditions.
Accessories, too, are key elements in any powergrid. That is why we custom
design joints, terminations and connections to user's specications. We offer a full
range of standard products, and have the logistics to deliver turnkey projects
worldwide.

6/3/15 - http://www.nexans.qa Page 57 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, PVC 0.6/1KV


BS 6346

Unarmoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to BS EN 60228
Standards
2. Insulation
Polyvinyl chloride "PVC" International IEC 60332-1
National BS 6346
3. OuterSheath
Polyvinyl chloride "PVC"
Option:
- Flame retardant, Cat A, Cat B or Cat C to BS 4066 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / PVC / PVC 600/1000 V Standard MADE
IN QATAR QICC-Nexans Year Meters
Custom marking available

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 58 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, PVC 0.6/1KV

Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC compound
Armour type Unarmoured
Outer sheath PVC
Colour Black
Halogen free No
Conductor exibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, PVC Insulation, Unarmoured 0.6/1KV 1 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050GVZOUB09BD0 1x 50 13.0 525 0.387 174 156 0.83
21070GVZOUB09BD0 1x70 15.0 710 0.268 225 192 0.6
21095GVZOUB09BD0 1x95 16.0 985 0.193 275 230 0.46
21120GVZOUB09BD0 1x120 18.0 1200 0.153 321 261 0.38
21150GVZOUB09BD0 1x150 20.0 1480 0.124 372 293 0.33
21185GVZOUB09BD0 1x185 22.0 1840 0.0991 427 331 0.28
21240GVZOUB09BD0 1x240 24.0 2350 0.0754 507 382 0.24
21300GVZOUB09BD0 1x300 27.0 2920 0.0601 587 427 0.21
21400GVZOUB09BD0 1x400 30.0 3730 0.047 689 492 0.18
21500GVZOUB09BD0 1x500 34.0 4790 0.0366 789 564 0.16
21630GVZOUB09BD0 1x630 37.0 6010 0.0283 905 646 0.15

BS LV, PVC Insulation, Unarmoured 0.6/1KV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002GVZOUB09BD0 2x1.5 11.0 170 12.1 18 19 22.6
22003GVZOUB09BD0 2x2.5 11.0 215 7.41 25 24 14.0

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 59 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22004GVZOUB09BD0 2x4 13.0 290 4.61 34 33 8.7
22006GVZOUB09BD0 2x6 14.0 350 3.08 43 41 5.9
22010GVZOUB09BD0 2x10 16.0 470 1.83 60 54 3.5
22016GVZOUB09BD0 2x16 17.0 630 1.15 80 70 2.2
22025GVZOUB09BD0 2x25 20.0 920 0.727 101 92 1.5
22035GVZOUB09BD0 2x35 22.0 1160 0.524 126 110 1.1
22050GVZOUB09BD0 2x50 25.0 1540 0.387 153 130 0.81
22070GVZOUB09BD0 2x70 29.0 2115 0.268 196 162 0.58
22095GVZOUB09BD0 2x95 33.0 2840 0.193 238 193 0.44
22120GVZOUB09BD0 2x120 36.0 3455 0.153 276 220 0.37
22150GVZOUB09BD0 2x150 40.0 4260 0.124 319 246 0.31
22185GVZOUB09BD0 2x185 44.0 5260 0.0991 364 278 0.27

BS LV, PVC Insulation, Unarmoured 0.6/1KV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002GVZOUB09BD0 3x1.5 11.0 200 12.1 18 19 22.6
23003GVZOUB09BD0 3x2.5 12.0 250 7.41 25 24 14.0
23004GVZOUB09BD0 3x4 13.0 300 4.61 34 33 8.7
23006GVZOUB09BD0 3x6 14.0 380 3.08 43 41 5.9
23010GVZOUB09BD0 3x10 16.0 540 1.83 60 54 3.5
23016GVZOUB09BD0 3x16 17.0 740 1.15 80 70 2.2
23025GVZOUB09BD0 3x25 22.0 1170 0.727 101 92 1.5
23050GVZOUB09BD0 3x50 23.0 1560 0.387 153 130 0.81
23035GVZOUB09BD0 3x35 24.0 1490 0.524 126 110 1.1
23070GVZOUB09BD0 3x70 26.0 2170 0.268 196 162 0.58
23095GVZOUB09BD0 3x95 30.0 2960 0.193 238 193 0.44
23120GVZOUB09BD0 3x120 33.0 3650 0.153 276 220 0.37
23150GVZOUB09BD0 3x150 36.0 4490 0.124 319 246 0.31
23185GVZOUB09BD0 3x185 40.0 5570 0.0991 364 278 0.27
23240GVZOUB09BD0 3x240 45.0 7040 0.0754 430 320 0.23
23300GVZOUB09BD0 3x300 50.0 8920 0.0601 497 359 0.2

BS LV, PVC Insulation, Unarmoured 0.6/1KV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002GVZOUB09BD0 4x1.5 12.0 240 12.1 18 19 22.6

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 60 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24003GVZOUB09BD0 4x2.5 13.0 295 7.41 25 24 14.0
24004GVZOUB09BD0 4x4 15.0 410 4.61 34 33 8.7
24006GVZOUB09BD0 4x6 16.0 510 3.08 43 41 5.9
24010GVZOUB09BD0 4x10 19.0 570 1.83 60 54 3.5
24016GVZOUB09BD0 4x16 20.0 995 1.15 80 70 2.2
24025GVZOUB09BD0 4x25 24.0 1450 0.727 101 92 1.5
24050GVZOUB09BD0 4x50 25.0 2020 0.387 153 130 0.81
24035GVZOUB09BD0 4x35 26.0 1860 0.524 126 110 1.1
24070GVZOUB09BD0 4x70 29.0 2810 0.268 196 162 0.58
24095GVZOUB09BD0 4x95 33.0 3830 0.193 238 193 0.44
24120GVZOUB09BD0 4x120 36.0 4760 0.153 276 220 0.37
24150GVZOUB09BD0 4x150 40.0 5860 0.124 319 246 0.31
24185GVZOUB09BD0 4x185 45.0 7300 0.0991 364 278 0.27
24240GVZOUB09BD0 4x240 50.0 9490 0.0754 430 320 0.23
24300GVZOUB09BD0 4x300 57.0 11910 0.0601 497 359 0.2

BS LV, PVC Insulation, Unarmoured 0.6/1KV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002GVZOUB09BD0 5x1.5 13.0 270 12.1 18 19 22.6
25003GVZOUB09BD0 5x2.5 14.0 350 7.41 25 24 14.0
25004GVZOUB09BD0 5x4 16.0 490 4.61 34 33 8.7
25006GVZOUB09BD0 5x6 18.0 620 3.08 43 41 5.9
25010GVZOUB09BD0 5x10 20.0 870 1.83 60 54 3.5
25016GVZOUB09BD0 5x16 22.0 1210 1.15 80 70 2.2
25025GVZOUB09BD0 5x25 26.0 1780 0.727 101 92 1.5
25035GVZOUB09BD0 5x35 29.0 2340 0.524 126 110 1.1
25050GVZOUB09BD0 5x50 33.0 2700 0.387 153 130 0.81
25070GVZOUB09BD0 5x70 38.0 3700 0.268 196 162 0.58

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 61 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, SWA, PVC 0.6/1KV


BS 6346

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application

These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to BS 6360 and IEC 60228
Standards
International IEC 60332-1
2. Insulation National BS 6346
Polyvinyl chloride "PVC"

3. Inner Sheath or Bedding


Extruded PVC

4. Armour
Galvanized Steel Wire Armour "SWA"

5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 62 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V
Standard MADE IN QATAR QICC-Nexans Year Meters
BS LV, PVC Insulation, SWA, PVC 0.6/1KV
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC compound
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC compound
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, PVC Insulation, SWA, PVC 0.6/1KV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002GVZVSB09BD0 2x1.5 12.0 300 12.1 18 19 22.6
22003GVZVSB09BD0 2x2.5 13.0 350 7.41 25 24 14.0
22004GVZVSB09BD0 2x4 15.0 540 4.61 34 33 8.7
22006GVZVSB09BD0 2x6 16.0 620 3.08 43 41 5.9
22010GVZVSB09BD0 2x10 18.0 830 1.83 60 54 3.5
22016GVZVSB09BD0 2x16 20.0 990 1.15 80 70 2.2
22025GVZVSB09BD0 2x25 23.0 1470 0.727 101 92 1.5
22035GVZVSB09BD0 2x35 25.0 1775 0.524 126 110 1.1
22050GVZVSB09BD0 2x50 28.0 2260 0.387 153 130 0.81
22070GVZVSB09BD0 2x70 33.0 3160 0.268 196 162 0.58
22095GVZVSB09BD0 2x95 37.0 4030 0.193 238 193 0.44
22120GVZVSB09BD0 2x120 40.0 4780 0.153 276 220 0.37
22150GVZVSB09BD0 2x150 45.0 6070 0.124 319 246 0.31

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 63 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, SWA, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22185GVZVSB09BD0 2x185 49.0 7300 0.0991 364 278 0.27

BS LV, PVC Insulation, SWA, PVC 0.6/1KV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002GVZVSB09BD0 3x1.5 13.0 340 12.1 18 19 22.6
23003GVZVSB09BD0 3x2.5 13.0 390 7.41 25 24 14.0
23004GVZVSB09BD0 3x4 16.0 620 4.61 34 33 8.7
23006GVZVSB09BD0 3x6 17.0 720 3.08 43 41 5.9
23010GVZVSB09BD0 3x10 19.0 940 1.83 60 54 3.5
23016GVZVSB09BD0 3x16 21.0 1300 1.15 80 70 2.2
23025GVZVSB09BD0 3x25 25.0 1770 0.727 101 92 1.5
23035GVZVSB09BD0 3x35 27.0 2170 0.524 126 110 1.1
23050GVZVSB09BD0 3x50 28.0 2370 0.387 153 130 0.81
23070GVZVSB09BD0 3x70 32.0 3300 0.268 196 162 0.58
23095GVZVSB09BD0 3x95 36.0 4285 0.193 238 193 0.44
23120GVZVSB09BD0 3x120 38.0 5095 0.153 276 220 0.37
23150GVZVSB09BD0 3x150 43.0 6450 0.124 319 246 0.31
23185GVZVSB09BD0 3x185 47.0 7730 0.0991 364 278 0.27
23240GVZVSB09BD0 3x240 52.0 9580 0.0754 430 320 0.23
23300GVZVSB09BD0 3x300 57.0 11760 0.0601 497 359 0.2

BS LV, PVC Insulation, SWA, PVC 0.6/1KV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002GVZVSB09BD0 4x1.5 13.0 310 12.1 18 19 22.6
24003GVZVSB09BD0 4x2.5 14.0 370 7.41 25 24 14.0
24004GVZVSB09BD0 4x4 15.0 460 4.61 34 33 8.7
24006GVZVSB09BD0 4x6 17.0 650 3.08 43 41 5.9
24010GVZVSB09BD0 4x10 22.0 1250 1.83 60 54 3.5
24016GVZVSB09BD0 4x16 23.0 1530 1.15 80 70 2.2
24025GVZVSB09BD0 4x25 27.0 2120 0.727 101 92 1.5
24035GVZVSB09BD0 4x35 29.0 2620 0.524 126 110 1.1
24050GVZVSB09BD0 4x50 31.0 3120 0.387 153 130 0.81
24070GVZVSB09BD0 4x70 34.0 4050 0.268 196 162 0.58
24095GVZVSB09BD0 4x95 40.0 5595 0.193 238 193 0.44
24120GVZVSB09BD0 4x120 43.0 6710 0.153 276 220 0.37

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 64 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, PVC Insulation, SWA, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24150GVZVSB09BD0 4x150 45.0 7560 0.124 319 246 0.31
24185GVZVSB09BD0 4x185 52.0 9770 0.0991 364 278 0.27
24240GVZVSB09BD0 4x240 58.0 12290 0.0754 430 320 0.23
24300GVZVSB09BD0 4x300 64.0 14950 0.0601 497 359 0.2

BS LV, PVC Insulation, SWA, PVC 0.6/1KV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002GVZVSB09BD0 5x1.5 14.0 400 12.1 18 19 22.6
25003GVZVSB09BD0 5x2.5 16.0 570 7.41 25 24 14.0
25004GVZVSB09BD0 5x4 18.0 820 4.61 34 33 8.7
25006GVZVSB09BD0 5x6 20.0 980 3.08 43 41 5.9
25010GVZVSB09BD0 5x10 21.0 1240 1.83 60 54 3.5
25016GVZVSB09BD0 5x16 25.0 1810 1.15 80 70 2.2
25025GVZVSB09BD0 5x25 29.0 2540 0.727 101 92 1.5
25035GVZVSB09BD0 5x35 33.0 3420 0.524 126 110 1.1
25050GVZVSB09BD0 5x50 37.0 3900 0.387 153 130 0.81
25070GVZVSB09BD0 5x70 42.0 5080 0.268 196 162 0.58

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 65 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, AWA, PVC 0.6/1 kV


BS 5467, DEWA, FEWA, SEWA

Aluminium wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This family is fully compling with DEWA, FEWA and SEWA specications from
UAE.

Design

1. Conductor
Stranded bare copper class 2 acc. to BS EN 60228

2. Insulation
Cross Linked Polyethylene "XLPE"

3. Inner Sheath or Bedding


Extruded PVC

4. Armour
Aluminium wire armour "AWA" Standards
Outer Sheath International IEC 60332-1
5.
Extruded Polyvinyl Chlorid "PVC" National BS 5467
Option:
- Flame retardant, Cat A, Cat B or Cat C to BS 4066 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 66 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, AWA, PVC 0.6/1 kV


Marking
no. of cores x conductor sizes mm2 Cu / XLPE / AWA / PVC 600/1000 V Standard
BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Aluminium Wire
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, XLPE Insulation, AWA 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050FXZVAB09BD0 1x50 18.0 700 0.387 216 153 0.84
21070FXZVAB09BD0 1x70 20.0 950 0.268 278 188 0.61
21095FXZVAB09BD0 1x95 22.0 1230 0.193 342 226 0.47
21120FXZVAB09BD0 1x120 24.0 1490 0.153 400 257 0.39
21150FXZVAB09BD0 1x150 25.0 1800 0.124 464 287 0.34
21185FXZVAB09BD0 1x185 27.0 2220 0.0991 533 324 0.29
21240FXZVAB09BD0 1x240 29.0 2800 0.0754 634 375 0.25
21300FXZVAB09BD0 1x300 31.0 3420 0.0601 736 419 0.22
21400FXZVAB09BD0 1x400 35.0 4300 0.047 868 717 0.19
21500FXZVAB09BD0 1x500 41.0 5490 0.037 998 791 0.17
21630FXZVAB09BD0 1x630 44.0 6850 0.028 1151 861 0.16

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 67 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, AWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21800FXZVAB09BD0 1x800 48.0 8700 0.022 1246 904 0.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 68 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, PVC 0.6/1KV


BS 5467

Unarmoured LV cable PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
system.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to BS EN 60228

2. Insulation
Cross Linked Polyethylene "XLPE"

3. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg. Standards
2. Ground Temperature: 20 Deg.
International IEC 60332-1
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m National BS 5467

All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / PVC 600/1000 V Standard
BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Armour type Unarmoured

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 69 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, PVC 0.6/1KV


Construction characteristics
Outer sheath PVC
Colour Black
Halogen free No
Conductor exibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, XLPE Insulation, Unarmoured 0.6/1KV 1 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050FXZOUB09BD0 1x50 13.0 480 0.387 216 183 0.83
21070FXZOUB09BD0 1x70 15.0 670 0.268 279 225 0.6
21095FXZOUB09BD0 1x95 16.0 920 0.193 342 270 0.46
21120FXZOUB09BD0 1x120 18.0 1140 0.153 400 306 0.38
21150FXZOUB09BD0 1x150 20.0 1400 0.124 464 343 0.33
21185FXZOUB09BD0 1x185 22.0 1740 0.0991 533 387 0.28
21240FXZOUB09BD0 1x240 25.0 2250 0.0754 634 448 0.24
21300FXZOUB09BD0 1x300 27.0 2780 0.0601 736 502 0.21
21400FXZOUB09BD0 1x400 31.0 3530 0.047 868 717 0.18
21500FXZOUB09BD0 1x500 35.0 4570 0.0366 896 539 0.16
21630FXZOUB09BD0 1x630 39.0 5810 0.0283 1035 678 0.15
21800FXZOUB09BD0 1x800 43.0 7375 0.0221 1246 726 0.14

BS LV, XLPE Insulation, Unarmoured 0.6/1KV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002FXZOUB09BD0 2x1.5 10.0 265 12.1 23 21 22.8
22003FXZOUB09BD0 2x 2.5 11.0 215 7.41 32 30 14.0
22004FXZOUB09BD0 2x 4 12.0 170 4.61 42 39 8.7
22006FXZOUB09BD0 2x 6 13.0 140 3.08 54 49 5.9
22010FXZOUB09BD0 2x10 15.0 380 1.83 75 65 3.5
22016FXZOUB09BD0 2x16 17.0 500 1.15 100 84 2.2

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 70 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22025FXZOUB09BD0 2x25 20.0 730 0.727 127 107 1.5
22035FXZOUB09BD0 2x35 22.0 940 0.524 158 129 1.1
22050FXZOUB09BD0 2x50 24.0 1220 0.387 192 153 0.81
22070FXZOUB09BD0 2x70 28.0 1700 0.268 246 188 0.58
22095FXZOUB09BD0 2x95 32.0 2280 0.193 298 226 0.44
22120FXZOUB09BD0 2x120 35.0 2830 0.153 346 257 0.37
22150FXZOUB09BD0 2x150 39.0 3465 0.124 399 287 0.31
22185FXZOUB09BD0 2x185 44.0 4350 0.0991 456 324 0.27

BS LV, XLPE Insulation, Unarmoured 0.6/1KV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002FXZOUB09BD0 3x 1.5 11.0 160 12.1 23 21 22.8
23003FXZOUB09BD0 3x 2.5 12.0 200 7.41 32 30 14.0
23004FXZOUB09BD0 3x 4 13.0 250 4.61 42 39 8.7
23006FXZOUB09BD0 3x 6 14.0 320 3.08 54 49 5.9
23010FXZOUB09BD0 3x10 16.0 450 1.83 75 65 3.5
23016FXZOUB09BD0 3x16 18.0 635 1.15 100 84 2.2
23025FXZOUB09BD0 3x25 21.0 930 0.727 127 107 1.5
23050FXZOUB09BD0 3x50 22.0 1250 0.387 192 153 0.81
23035FXZOUB09BD0 3x35 23.0 1200 0.524 158 129 1.1
23070FXZOUB09BD0 3x70 25.0 1770 0.268 246 188 0.58
23095FXZOUB09BD0 3x95 29.0 2390 0.193 298 226 0.44
23120FXZOUB09BD0 3x120 32.0 3000 0.153 346 257 0.37
23150FXZOUB09BD0 3x150 35.0 3700 0.124 399 287 0.31
23185FXZOUB09BD0 3x185 39.0 4590 0.0991 456 324 0.27
23240FXZOUB09BD0 3x240 43.0 5880 0.0754 538 375 0.23
23300FXZOUB09BD0 3x300 48.0 7380 0.0601 621 419 0.2
23400FXZOUB09BD0 3x400 55.0 9440 0.047 765 468 0.18

BS LV, XLPE Insulation, Unarmoured 0.6/1KV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002FXZOUB09BD0 4x 1.5 12.0 190 12.1 23 21 22.8
24003FXZOUB09BD0 4x 2.5 13.0 230 7.41 32 30 14.0
24004FXZOUB09BD0 4x 4 14.0 300 4.61 42 39 8.7
24006FXZOUB09BD0 4x 6 15.0 390 3.08 54 49 5.9

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 71 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24010FXZOUB09BD0 4x10 17.0 550 1.83 75 65 3.5
24016FXZOUB09BD0 4x16 19.0 780 1.15 100 84 2.2
24025FXZOUB09BD0 4x25 23.0 1160 0.727 127 107 1.5
24050FXZOUB09BD0 4x50 24.0 1620 0.387 192 153 0.81
24035FXZOUB09BD0 4x35 25.0 1515 0.524 158 129 1.1
24070FXZOUB09BD0 4x70 28.0 2300 0.268 246 188 0.58
24095FXZOUB09BD0 4x95 31.0 2280 0.193 298 226 0.44
24120FXZOUB09BD0 4x120 35.0 3910 0.153 346 257 0.37
24150FXZOUB09BD0 4x150 39.0 4830 0.124 399 287 0.31
24185FXZOUB09BD0 4x185 43.0 6030 0.0991 456 324 0.27
24240FXZOUB09BD0 4x240 49.0 7850 0.0754 538 375 0.23
24300FXZOUB09BD0 4x300 55.0 9850 0.0601 621 419 0.2
24400FXZOUB09BD0 4x400 61.0 12555 0.047 765 468 0.18

BS LV, XLPE Insulation, Unarmoured 0.6/1KV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002FXZOUB09BD0 5x 1.5 13.0 220 12.1 23 21 22.8
25003FXZOUB09BD0 5x 2.5 14.0 270 7.41 32 30 14.0
25004FXZOUB09BD0 5x 4 15.0 350 4.61 42 39 8.7
25006FXZOUB09BD0 5x 6 16.0 465 3.08 54 49 5.9
25010FXZOUB09BD0 5x10 19.0 670 1.83 75 65 3.5
25016FXZOUB09BD0 5x16 21.0 955 1.15 100 84 2.2
25025FXZOUB09BD0 5x25 25.0 1425 0.727 127 107 1.5
25035FXZOUB09BD0 5x35 28.0 2280 0.524 158 129 1.1
25050FXZOUB09BD0 5x50 32.0 2170 0.387 192 153 0.81
25070FXZOUB09BD0 5x70 37.0 3050 0.268 246 188 0.58

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 72 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - AD


BS 5467 & ADWEA

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application

These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This family is fully compling with ADWEA specications from UAE.

Design

1. Conductor
Stranded bare copper class 2 acc. to BS 6360 and IEC 60228

2. Insulation
Cross Linked Polyethylene "XLPE"

3. Inner Sheath or Bedding


Extruded PVC
Standards
4. Armour International IEC 60332-3 Cat.A
Galvanized Steel Wire Armour "SWA"
National ADWEA-LV-UAE; BS 5467
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 CAT A or equivalent,
Oil and Sulphide resistance

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Halogen free Conductor exibility Max.conductor temp.in Flame retardant Bending factor when Bending factor
No Stranded class 2 service Yes laying installed
90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 73 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - AD


Marking

no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V BS 5467
BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (chemical)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Conductor exibility Stranded class 2
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

ADWEA LV, XLPE Insulation, SWA, PVC 0.6/1KV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002FXZVSB99BS0 2x1.5 12.0 270 12.1 25 23 22.8
22003FXZVSB99BS0 2x2.5 13.0 335 7.41 33 30 14.0
22004FXZVSB99BS0 2x4 14.0 400 4.61 44 39 8.7
22006FXZVSB99BS0 2x6 15.0 475 3.08 56 49 5.9
22010FXZVSB99BS0 2x10 17.0 620 1.83 78 65 3.5
22025FXZVSB99BS0 2x25 19.0 950 0.727 131 107 1.65
22016FXZVSB99BS0 2x16 20.0 915 1.15 99 84 2.2
22035FXZVSB99BS0 2x35 22.0 1325 0.524 162 129 1.15
22050FXZVSB99BS0 2x50 25.0 1660 0.387 197 153 0.89
22070FXZVSB99BS0 2x70 28.0 1860 0.268 251 188 0.6
22095FXZVSB99BS0 2x95 31.0 2530 0.193 304 226 0.45

Halogen free Conductor exibility Max.conductor temp.in Flame retardant Bending factor when Bending factor
No Stranded class 2 service Yes laying installed
90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 74 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - AD


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22120FXZVSB99BS0 2x120 34.0 3020 0.153 353 257 0.37
22150FXZVSB99BS0 2x150 37.0 3590 0.124 406 287 0.3
22185FXZVSB99BS0 2x185 42.0 4660 0.0991 463 324 0.26

ADWEA LV, XLPE Insulation, SWA, PVC 0.6/1KV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002FXZVSB99BS0 2x1.5 12.0 270 12.1 25 23 22.8
22003FXZVSB99BS0 2x2.5 13.0 335 7.41 33 30 14.0
22004FXZVSB99BS0 2x4 14.0 400 4.61 44 39 8.7
22006FXZVSB99BS0 2x6 15.0 475 3.08 56 49 5.9
22010FXZVSB99BS0 2x10 17.0 620 1.83 78 65 3.5
22025FXZVSB99BS0 2x25 19.0 950 0.727 131 107 1.65
22016FXZVSB99BS0 2x16 20.0 915 1.15 99 84 2.2
22035FXZVSB99BS0 2x35 22.0 1325 0.524 162 129 1.15
22050FXZVSB99BS0 2x50 25.0 1660 0.387 197 153 0.89
22070FXZVSB99BS0 2x70 28.0 1860 0.268 251 188 0.6
22095FXZVSB99BS0 2x95 31.0 2530 0.193 304 226 0.45
22120FXZVSB99BS0 2x120 34.0 3020 0.153 353 257 0.37
22150FXZVSB99BS0 2x150 37.0 3590 0.124 406 287 0.3
22185FXZVSB99BS0 2x185 42.0 4660 0.0991 463 324 0.26

ADWEA LV, XLPE Insulation, SWA, PVC 0.6/1KV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002FXZVSB99BS0 4x1.5 13.0 320 12.1 25 23 22.8
24003FXZVSB99BS0 4x2.5 15.0 410 7.41 33 30 14.0
24004FXZVSB99BS0 4x4 16.0 510 4.61 44 39 8.7
24006FXZVSB99BS0 4x6 18.0 720 3.08 56 49 5.9
24010FXZVSB99BS0 4x10 20.0 960 1.83 78 65 3.5
24016FXZVSB99BS0 4x16 23.0 1240 1.15 99 84 2.2
24025FXZVSB99BS0 4x25 25.0 1720 0.727 131 107 1.65
24035FXZVSB99BS0 4x35 28.0 2160 0.524 162 129 1.15
24050FXZVSB99BS0 4x50 31.0 2750 0.387 197 153 0.89
24070FXZVSB99BS0 4x70 36.0 3400 0.268 251 188 0.6
24095FXZVSB99BS0 4x95 40.0 4310 0.193 304 226 0.45
24120FXZVSB99BS0 4x120 45.0 5640 0.153 353 257 0.37

Halogen free Conductor exibility Max.conductor temp.in Flame retardant Bending factor when Bending factor
No Stranded class 2 service Yes laying installed
90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 75 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - AD


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24150FXZVSB99BS0 4x150 48.0 6670 0.124 406 287 0.3
24185FXZVSB99BS0 4x185 53.0 8080 0.0991 463 324 0.26
24240FXZVSB99BS0 4x240 59.0 10205 0.0754 546 375 0.21
24300FXZVSB99BS0 4x300 64.0 12360 0.0601 628 419 0.18
24400FXZVSB99BS0 4x400 73.0 16170 0.047 731 439 0.17

ADWEA LV, XLPE Insulation, SWA, PVC 0.6/1KV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002FXZVSB99BS0 5x1.5 14.0 370 12.1 25 23 22.8
25003FXZVSB99BS0 5x2.5 16.0 460 7.41 33 30 14.0
25004FXZVSB99BS0 5x4 17.0 590 4.61 44 39 8.7
25006FXZVSB99BS0 5x6 19.0 830 3.08 56 49 5.9
25010FXZVSB99BS0 5x10 22.0 1110 1.83 78 65 3.5
25016FXZVSB99BS0 5x16 26.0 1660 1.15 99 84 2.2
25025FXZVSB99BS0 5x25 29.0 2220 0.727 131 107 1.65
25035FXZVSB99BS0 5x35 32.0 2770 0.524 162 129 1.15
25050FXZVSB99BS0 5x50 37.0 3840 0.387 197 153 0.89
25070FXZVSB99BS0 5x70 42.0 4350 0.268 251 188 0.6

Halogen free Conductor exibility Max.conductor temp.in Flame retardant Bending factor when Bending factor
No Stranded class 2 service Yes laying installed
90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 76 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - QCS


BS 5467, QCS, DEWA

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application

These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This family is fully compling with DEWA from UAE and QCS from Qatar.

Design

1. Conductor
Stranded bare copper class 2 acc. to BS 6360 and IEC 60228

2. Insulation
Cross Linked Polyethylene "XLPE"
Standards
3. Inner Sheath or Bedding
Extruded PVC International IEC 60332-1
National BS 5467; DEWA-LV-UAE;
4. Armour QCS - LV
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 77 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - QCS


no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V BS 5467
BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (chemical)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV QCS 2C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002FXZVSB09BS0 2x1.5 12.0 260 12.1 25 23 22.8
22003FXZVSB09BS0 2x2.5 13.0 330 7.41 33 30 14.0
22004FXZVSB09BS0 2x4 14.0 390 4.61 44 39 8.7
22006FXZVSB09BS0 2x6 15.0 475 3.08 56 49 5.9
22010FXZVSB09BS0 2x10 17.0 610 1.83 78 65 3.5
22025FXZVSB09BS0 2x25 19.0 950 0.727 131 107 1.65
22016FXZVSB09BS0 2x16 20.0 910 1.15 99 84 2.2
22035FXZVSB09BS0 2x35 22.0 1320 0.524 162 129 1.15
22050FXZVSB09BS0 2x50 25.0 1660 0.387 197 153 0.89
22070FXZVSB09BS0 2x70 28.0 1860 0.268 251 188 0.6
22095FXZVSB09BS0 2x95 31.0 2530 0.193 304 226 0.45
22120FXZVSB09BS0 2x120 34.0 3020 0.153 353 257 0.37
22150FXZVSB09BS0 2x150 37.0 3590 0.124 406 287 0.3

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 78 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - QCS


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22185FXZVSB09BS0 2x185 42.0 4660 0.0991 463 324 0.26

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV QCS 3C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002FXZVSB09BS0 3x1.5 12.0 280 12.1 25 23 22.8
23003FXZVSB09BS0 3x2.5 14.0 360 7.41 33 30 14.0
23004FXZVSB09BS0 3x4 15.0 450 4.61 44 39 8.7
23006FXZVSB09BS0 3x6 16.0 530 3.08 56 49 5.9
23010FXZVSB09BS0 3x10 19.0 810 1.83 78 65 3.5
23016FXZVSB09BS0 3x16 21.0 1080 1.15 99 84 2.2
23025FXZVSB09BS0 3x25 23.0 1440 0.727 131 107 1.65
23035FXZVSB09BS0 3x35 26.0 1770 0.524 162 129 1.15
23050FXZVSB09BS0 3x50 28.0 2200 0.387 197 153 0.89
23070FXZVSB09BS0 3x70 31.0 2500 0.268 251 188 0.6
23095FXZVSB09BS0 3x95 36.0 3440 0.193 304 226 0.45
23120FXZVSB09BS0 3x120 39.0 4160 0.153 353 257 0.37
23150FXZVSB09BS0 3x150 44.0 5310 0.124 406 287 0.3
23185FXZVSB09BS0 3x185 48.0 6380 0.0991 463 324 0.26
23240FXZVSB09BS0 3x240 52.0 7980 0.0754 546 375 0.21
23300FXZVSB09BS0 3x300 57.0 9620 0.0601 628 419 0.18
23400FXZVSB09BS0 3x400 64.0 12030 0.047 731 439 0.17

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV QCS 4C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002FXZVSB09BS0 4x1.5 13.0 320 12.1 25 23 22.8
24003FXZVSB09BS0 4x2.5 15.0 410 7.41 33 30 14.0
24004FXZVSB09BS0 4x4 16.0 510 4.61 44 39 8.7
24006FXZVSB09BS0 4x6 18.0 720 3.08 56 49 5.9
24010FXZVSB09BS0 4x10 20.0 960 1.83 78 65 3.5
24016FXZVSB09BS0 4x16 23.0 1240 1.15 99 84 2.2
24025FXZVSB09BS0 4x25 25.0 1720 0.727 131 107 1.65
24035FXZVSB09BS0 4x35 28.0 2160 0.524 162 129 1.15
24050FXZVSB09BS0 4x50 31.0 2750 0.387 197 153 0.89
24070FXZVSB09BS0 4x70 36.0 3400 0.268 251 188 0.6
24095FXZVSB09BS0 4x95 40.0 4310 0.193 304 226 0.45

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 79 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV - QCS


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24120FXZVSB09BS0 4x120 45.0 5640 0.153 353 257 0.37
24150FXZVSB09BS0 4x150 48.0 6670 0.124 406 287 0.3
24185FXZVSB09BS0 4x185 53.0 8080 0.0991 463 324 0.26
24240FXZVSB09BS0 4x240 59.0 10200 0.0754 546 375 0.21
24300FXZVSB09BS0 4x300 64.0 12360 0.0601 628 419 0.18

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 80 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV


BS 5467

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application

These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This family is fully compling with BS 5467.

Design

1. Conductor
Stranded bare copper class 2 acc. to BS 6360 and IEC 60228

2. Insulation
Cross Linked Polyethylene "XLPE"

3. Inner Sheath or Bedding


Extruded PVC Standards
Armour International IEC 60332-1
4.
Galvanized Steel Wire Armour "SWA" National BS 5467

5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 81 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV


no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V BS 5467
BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (chemical)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV, 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002FXZVSB09BD0 2x1.5 12.0 260 12.1 25 23 22.8
22003FXZVSB09BD0 2x2.5 13.0 330 7.41 33 30 14.0
22004FXZVSB09BD0 2x4 14.0 390 4.61 44 39 8.7
22006FXZVSB09BD0 2x6 15.0 475 3.08 56 49 5.9
22010FXZVSB09BD0 2x10 17.0 610 1.83 78 65 3.5
22025FXZVSB09BD0 2x25 19.0 950 0.727 131 107 1.65
22016FXZVSB09BD0 2x16 20.0 910 1.15 99 84 2.2
22035FXZVSB09BD0 2x35 22.0 1320 0.524 162 129 1.15
22050FXZVSB09BD0 2x50 25.0 1660 0.387 197 153 0.89
22070FXZVSB09BD0 2x70 28.0 1860 0.268 251 188 0.6
22095FXZVSB09BD0 2x95 31.0 2530 0.193 304 226 0.45
22120FXZVSB09BD0 2x120 34.0 3020 0.153 353 257 0.37
22150FXZVSB09BD0 2x150 37.0 3590 0.124 406 287 0.3

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 82 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22185FXZVSB09BD0 2x185 42.0 4660 0.0991 463 324 0.26

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV, 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002FXZVSB09BD0 3x1.5 12.0 280 12.1 25 23 22.8
23003FXZVSB09BD0 3x2.5 14.0 360 7.41 33 30 14.0
23004FXZVSB09BD0 3x4 15.0 450 4.61 44 39 8.7
23006FXZVSB09BD0 3x6 16.0 530 3.08 56 49 5.9
23010FXZVSB09BD0 3x10 19.0 810 1.83 78 65 3.5
23016FXZVSB09BD0 3x16 21.0 1080 1.15 99 84 2.2
23025FXZVSB09BD0 3x25 23.0 1440 0.727 131 107 1.65
23035FXZVSB09BD0 3x35 26.0 1770 0.524 162 129 1.15
23050FXZVSB09BD0 3x50 28.0 2200 0.387 197 153 0.89
23070FXZVSB09BD0 3x70 31.0 2500 0.268 251 188 0.6
23095FXZVSB09BD0 3x95 36.0 3440 0.193 304 226 0.45
23120FXZVSB09BD0 3x120 39.0 4160 0.153 353 257 0.37
23150FXZVSB09BD0 3x150 44.0 5310 0.124 406 287 0.3
23185FXZVSB09BD0 3x185 48.0 6380 0.0991 463 324 0.26
23240FXZVSB09BD0 3x240 52.0 7980 0.0754 546 375 0.21
23300FXZVSB09BD0 3x300 57.0 9620 0.0601 628 419 0.18
23400FXZVSB09BD0 3x400 64.0 12030 0.047 731 439 0.17

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV, 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002FXZVSB09BD0 4x1.5 13.0 320 12.1 25 23 22.8
24003FXZVSB09BD0 4x2.5 15.0 410 7.41 33 30 14.0
24004FXZVSB09BD0 4x4 16.0 510 4.61 44 39 8.7
24006FXZVSB09BD0 4x6 18.0 720 3.08 56 49 5.9
24010FXZVSB09BD0 4x10 20.0 960 1.83 78 65 3.5
24016FXZVSB09BD0 4x16 23.0 1240 1.15 99 84 2.2
24025FXZVSB09BD0 4x25 25.0 1720 0.727 131 107 1.65
24035FXZVSB09BD0 4x35 28.0 2160 0.524 162 129 1.15
24050FXZVSB09BD0 4x50 31.0 2750 0.387 197 153 0.89
24070FXZVSB09BD0 4x70 36.0 3400 0.268 251 188 0.6
24095FXZVSB09BD0 4x95 40.0 4310 0.193 304 226 0.45

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 83 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24120FXZVSB09BD0 4x120 45.0 5640 0.153 353 257 0.37
24150FXZVSB09BD0 4x150 48.0 6670 0.124 406 287 0.3
24185FXZVSB09BD0 4x185 53.0 8080 0.0991 463 324 0.26
24240FXZVSB09BD0 4x240 59.0 10200 0.0754 546 375 0.21
24300FXZVSB09BD0 4x300 64.0 12360 0.0601 628 419 0.18
24400FXZVSB09BD0 4x400 73.0 16170 0.047 731 439 0.17

BS LV, XLPE Insulation, SWA, PVC 0.6/1KV, 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002FXZVSB09BD0 5x1.5 14.0 370 12.1 25 23 22.8
25003FXZVSB09BD0 5x2.5 16.0 460 7.41 33 30 14.0
25004FXZVSB09BD0 5x4 17.0 590 4.61 44 39 8.7
25006FXZVSB09BD0 5x6 19.0 830 3.08 56 49 5.9
25010FXZVSB09BD0 5x10 22.0 1110 1.83 78 65 3.5
25016FXZVSB09BD0 5x16 26.0 1660 1.15 99 84 2.2
25025FXZVSB09BD0 5x25 29.0 2220 0.727 131 107 1.65
25035FXZVSB09BD0 5x35 32.0 2770 0.524 162 129 1.15
25050FXZVSB09BD0 5x50 37.0 3840 0.387 197 153 0.89
25070FXZVSB09BD0 5x70 42.0 4350 0.268 251 188 0.6

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 84 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, ATA, PVC 0.6/1 kV


IEC 60502-1

Aluminium tape armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Polyvinyl chloride "PVC". International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Aluminium Tape Armour "ATA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Option:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / PVC / ATA / PVC 600/1000 V IEC

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 15 (xD)
2

6/3/15 - http://www.nexans.qa Page 85 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, ATA, PVC 0.6/1 kV


60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation PVC
Inner sheath PVC
Armour type Aluminium tape
Outer sheath PVC
Colour Black
Halogen free No
Conductor exibility Stranded class 2
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Minimum Bend Radius - Installed 15 mm
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 15 (xD)

IEC LV, PVC Insulation, ATA 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050BXZVEB09BD0 1x50 16.0 650 0.387 174 156 0.83
21070BXZVEB09BD0 1x70 18.0 870 0.268 225 192 0.6
21095BXZVEB09BD0 1x95 20.0 1140 0.193 275 230 0.46
21120BXZVEB09BD0 1x120 22.0 1395 0.153 321 261 0.38
21150BXZVEB09BD0 1x150 24.0 1715 0.124 372 293 0.33
21185BXZVEB09BD0 1x185 26.0 2080 0.0991 427 331 0.28
21240BXZVEB09BD0 1x240 28.0 2610 0.0754 507 382 0.24
21300BXZVEB09BD0 1x300 31.0 3220 0.0601 587 427 0.21
21400BXZVEB09BD0 1x400 35.0 4090 0.047 689 530 0.18
21500BXZVEB09BD0 1x500 39.0 5220 0.0366 789 607 0.16

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 15 (xD)
2

6/3/15 - http://www.nexans.qa Page 86 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, ATA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21630BXZVEB09BD0 1x630 43.0 6520 0.0283 905 696 0.15

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 15 (xD)
2

6/3/15 - http://www.nexans.qa Page 87 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, AWA, PVC 0.6/1 kV


IEC 60502-1

Aluminium wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Polyvinyl chloride "PVC". International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Aluminium Wire Armour "AWA"
5. Outer Sheath
Polyvinyl Chloride "PVC".
Option:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / PVC / AWA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 88 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, AWA, PVC 0.6/1 kV


Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation PVC
Inner sheath PVC
Armour type Aluminium Wire
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Minimum Bend Radius - Installed 8 mm
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, PVC Insulation, AWA 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050BVZVAB09BD0 1x50 19.0 740 0.387 174 156 0.83
21070BVZVAB09BD0 1x70 21.0 990 0.268 225 192 0.6
21095BVZVAB09BD0 1x95 23.0 1270 0.193 275 230 0.46
21120BVZVAB09BD0 1x120 25.0 1545 0.153 321 261 0.38
21150BVZVAB09BD0 1x150 26.0 1850 0.124 372 293 0.33
21185BVZVAB09BD0 1x185 28.0 2220 0.0991 427 331 0.28
21500BVZVAB09BD0 1x500 29.0 5510 0.0366 789 607 0.16
21240BVZVAB09BD0 1x240 31.0 2800 0.0754 507 382 0.24
21300BVZVAB09BD0 1x300 33.0 3410 0.0601 587 427 0.21
21400BVZVAB09BD0 1x400 37.0 4340 0.047 689 530 0.18
21630BVZVAB09BD0 1x630 46.0 6880 0.0283 905 696 0.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 89 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV


IEC 60502-1 & MEW

Unarmoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Polyvinyl chloride "PVC" International IEC 60332-1;
IEC 60502-1
Outer Sheath National MEW - LV Kuwait
3.
Polyvinyl Chloride "PVC"
Option:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / PVC / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 90 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV

Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC compound
Armour type Unarmoured
Outer sheath PVC
Colour Black
Halogen free No
Conductor exibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 1 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050BVZOUB09BD0 1x 50 14.0 550 0.387 174 156 0.83
21070BVZOUB09BD0 1x70 16.0 750 0.268 225 192 0.6
21095BVZOUB09BD0 1x95 18.0 1030 0.193 275 230 0.46
21120BVZOUB09BD0 1x120 19.0 1260 0.153 321 261 0.38
21150BVZOUB09BD0 1x150 21.0 1560 0.124 372 293 0.33
21185BVZOUB09BD0 1x185 24.0 1940 0.0991 427 331 0.28
21240BVZOUB09BD0 1x240 26.0 2480 0.0754 507 382 0.24
21300BVZOUB09BD0 1x300 29.0 3080 0.0601 587 427 0.21
21400BVZOUB09BD0 1x400 32.0 3930 0.047 689 530 0.18
21500BVZOUB09BD0 1x500 36.0 5040 0.0366 789 607 0.16
21630BVZOUB09BD0 1x630 40.0 6320 0.0283 905 696 0.15

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 91 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV


IEC LV, PVC Insulation, Unarmoured 0.6/1KV 2 C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BVZOUB09BD0 2x1.5 11.0 180 12.1 18 19 22.6
22003BVZOUB09BD0 2x2.5 12.0 220 7.41 25 24 14.0
22004BVZOUB09BD0 2x4 14.0 300 4.61 34 33 8.7
22006BVZOUB09BD0 2x6 15.0 370 3.08 43 41 5.9
22010BVZOUB09BD0 2x10 17.0 500 1.83 60 54 3.5
22016BVZOUB09BD0 2x16 19.0 670 1.15 80 70 2.2
22025BVZOUB09BD0 2x25 22.0 975 0.727 101 92 1.5
22035BVZOUB09BD0 2x35 24.0 1230 0.524 126 110 1.1
22050BVZOUB09BD0 2x50 27.0 1620 0.387 153 130 0.81
22070BVZOUB09BD0 2x70 31.0 2220 0.268 196 162 0.58
22095BVZOUB09BD0 2x95 36.0 2990 0.193 238 193 0.44
22120BVZOUB09BD0 2x120 39.0 3630 0.153 276 220 0.37
22150BVZOUB09BD0 2x150 43.0 4490 0.124 319 246 0.31
22185BVZOUB09BD0 2x185 48.0 5540 0.0991 364 278 0.27

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002BVZOUB09BD0 3x1.5 12.0 220 12.1 18 19 22.6
23003BVZOUB09BD0 3x2.5 13.0 260 7.41 25 24 14.0
23004BVZOUB09BD0 3x4 14.0 320 4.61 34 33 8.7
23006BVZOUB09BD0 3x6 15.0 400 3.08 43 41 5.9
23010BVZOUB09BD0 3x10 17.0 560 1.83 60 54 3.5
23016BVZOUB09BD0 3x16 19.0 785 1.15 80 70 2.2
23025BVZOUB09BD0 3x25 24.0 1230 0.727 101 92 1.5
23050BVZOUB09BD0 3x50 25.0 1640 0.387 153 130 0.81
27025BVZOUB09BD0 3x25+16 26.0 1310 0.727 101 92 1.5
23035BVZOUB09BD0 3x35 26.0 1575 0.524 126 110 1.1
27035BVZOUB09BD0 3x35+16 28.0 1660 0.524 126 110 1.1
27050BVZOUB09BD0 3x50+25 28.0 1700 0.387 153 130 0.81
23070BVZOUB09BD0 3x70 28.0 2280 0.268 196 162 0.58
27070BVZOUB09BD0 3x70+35 31.0 2370 0.268 196 162 0.58
23095BVZOUB09BD0 3x95 32.0 3110 0.193 238 193 0.44
27095BVZOUB09BD0 3x95+50 35.0 3200 0.193 238 193 0.44
23120BVZOUB09BD0 3x120 35.0 3850 0.153 276 220 0.37
23150BVZOUB09BD0 3x150 39.0 4720 0.124 319 246 0.31
27120BVZOUB09BD0 3x120+70 41.0 4020 0.153 276 220 0.37
23185BVZOUB09BD0 3x185 43.0 5860 0.0991 364 278 0.27

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 92 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
27150BVZOUB09BD0 3x150+70 45.0 4930 0.124 319 246 0.31
27185BVZOUB09BD0 3x185+95 49.0 6060 0.0991 364 278 0.27
23240BVZOUB09BD0 3x240 49.0 7410 0.0754 430 320 0.23
23300BVZOUB09BD0 3x300 54.0 9390 0.0601 497 359 0.2
27240BVZOUB09BD0 3x240+120 55.0 7830 0.0754 430 320 0.23
27300BVZOUB09BD0 3x300+150 62.0 9680 0.0601 497 359 0.2

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BVZOUB09BD0 4x1.5 13.0 250 12.1 18 19 22.6
24003BVZOUB09BD0 4x2.5 14.0 310 7.41 25 24 14.0
24004BVZOUB09BD0 4x4 16.0 430 4.61 34 33 8.7
24006BVZOUB09BD0 4x6 18.0 540 3.08 43 41 5.9
24010BVZOUB09BD0 4x10 20.0 600 1.83 60 54 3.5
24016BVZOUB09BD0 4x16 22.0 1040 1.15 80 70 2.2
24025BVZOUB09BD0 4x25 26.0 1530 0.727 101 92 1.5
24050BVZOUB09BD0 4x50 27.0 2120 0.387 153 130 0.81
24035BVZOUB09BD0 4x35 28.0 1960 0.524 126 110 1.1
24070BVZOUB09BD0 4x70 31.0 2960 0.268 196 162 0.58
24095BVZOUB09BD0 4x95 36.0 4035 0.193 238 193 0.44
24120BVZOUB09BD0 4x120 39.0 5010 0.153 276 220 0.37
24150BVZOUB09BD0 4x150 43.0 6170 0.124 319 246 0.31
24185BVZOUB09BD0 4x185 48.0 7690 0.0991 364 278 0.27
24240BVZOUB09BD0 4x240 54.0 9990 0.0754 430 320 0.23
24300BVZOUB09BD0 4x300 61.0 12540 0.0601 497 359 0.2

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BVZOUB09BD0 5x1.5 14.0 290 12.1 18 19 22.6
25003BVZOUB09BD0 5x2.5 15.0 360 7.41 25 24 14.0
25004BVZOUB09BD0 5x4 18.0 520 4.61 34 33 8.7
25006BVZOUB09BD0 5x6 19.0 655 3.08 43 41 5.9
25010BVZOUB09BD0 5x10 21.0 910 1.83 60 54 3.5
25016BVZOUB09BD0 5x16 24.0 1270 1.15 80 70 2.2
25025BVZOUB09BD0 5x25 28.0 1880 0.727 101 92 1.5

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 93 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25035BVZOUB09BD0 5x35 32.0 2470 0.524 126 110 1.1
25050BVZOUB09BD0 5x50 36.0 2840 0.387 153 130 0.81
25070BVZOUB09BD0 5x70 41.0 3890 0.268 196 162 0.58

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 7 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BVZOUB09BD0 7x1.5 16.0 390 12.1 18 19 22.6
2C003BVZOUB09BD0 7x2.5 17.0 450 7.41 25 24 14.0

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 9 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BVZOUB09BD0 9x1.5 17.0 470 12.1 18 19 22.6
2K003BVZOUB09BD0 9x2.5 19.0 605 7.41 25 24 14.0

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 12 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BVZOUB09BD0 12x1.5 18.0 550 12.1 18 19 22.6
2E003BVZOUB09BD0 12x2.5 20.0 710 7.41 25 24 14.0

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 19 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BVZOUB09BD0 19x1.5 21.0 750 12.1 18 19 22.6
2F003BVZOUB09BD0 19x2.5 23.0 990 7.41 25 24 14.0

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 94 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, PVC 0.6/1KV


IEC LV, PVC Insulation, Unarmoured 0.6/1KV 24 C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BVZOUB09BD0 24x1.5 24.0 980 12.1 18 19 22.6
2I003BVZOUB09BD0 24x2.5 27.0 1300 7.41 25 24 14.0

IEC LV, PVC Insulation, Unarmoured 0.6/1KV 37 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BVZOUB09BD0 37x1.5 27.0 1320 12.1 18 19 22.6
2M003BVZOUB09BD0 37x2.5 30.0 1770 7.41 25 24 14.0

Halogen free Conductor Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
No exibility (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 95 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV


IEC 60502-1

Galvanized steel tape armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Polyvinyl chloride "PVC" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Galvanized Steel Tape Armour "STA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Options:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 96 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV


no. of cores x conductor sizes mm2 Cu / PVC / STA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC compound
Inner sheath PVC
Armour type Double steel tapes
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, PVC Insulation, STA 0.6/1 kV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BVZVTB09BD0 2x1.5 12.2 240 12.1 18 19 22.8
22003BVZVTB09BD0 2x2.5 13.1 295 7.41 25 24 14.0
22004BVZVTB09BD0 2x4 14.9 380 4.61 34 33 8.7
22006BVZVTB09BD0 2x6 15.9 450 3.08 43 41 5.9
22010BVZVTB09BD0 2x10 17.7 600 1.83 60 54 3.5
22016BVZVTB09BD0 2x16 19.5 780 1.15 80 70 2.2
22025BVZVTB09BD0 2x25 22.8 1100 0.727 101 92 1.5
22035BVZVTB09BD0 2x35 24.8 1370 0.524 126 110 1.1
22050BVZVTB09BD0 2x50 28.0 1780 0.387 153 130 0.81
22070BVZVTB09BD0 2x70 32.1 2410 0.268 196 162 0.58
22095BVZVTB09BD0 2x95 36.4 3215 0.193 238 193 0.44
22120BVZVTB09BD0 2x120 40.8 4245 0.153 276 220 0.37
22150BVZVTB09BD0 2x150 45.0 5160 0.124 319 246 0.31

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 97 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22185BVZVTB09BD0 2x185 49.6 6290 0.0991 364 278 0.27

IEC LV, PVC Insulation, STA 0.6/1 kV 3 C


Nom. Max. DC Current
Approx. Perm. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open air 3 conductors
diam. 20°C buried
[kg/km] [A] [V/A.km]
[mm] [Ohm/km] [A]
23002BVZVTB09BD0 3x1.5 13.0 280 12.1 18 19 22.8
23003BVZVTB09BD0 3x2.5 14.0 340 7.41 25 24 14.0
23004BVZVTB09BD0 3x4 16.0 450 4.61 34 33 8.7
23006BVZVTB09BD0 3x6 17.0 540 3.08 43 41 5.9
23010BVZVTB09BD0 3x10 19.0 730 1.83 60 54 3.5
23016BVZVTB09BD0 3x16 20.9 960 1.15 80 70 2.2
23025BVZVTB09BD0 3x25 24.4 1370 0.727 101 92 1.5
27025BVZVTB09BD0 3x25+16 26.6 1480 0.727 101 92 1.5
23035BVZVTB09BD0 3x35 26.6 1730 0.524 126 110 1.1
23050BVZVTB09BD0 3x50 27.3 1920 0.387 153 130 0.81
27035BVZVTB09BD0 3x35+16 29.0 1850 0.524 126 110 1.1
27050BVZVTB09BD0 3x50+25 30.2 2000 0.387 153 130 0.81
23070BVZVTB09BD0 3x70 31.0 2620 0.268 196 162 0.58
27070BVZVTB09BD0 3x70+35 34.2 2720 0.268 196 162 0.58
23095BVZVTB09BD0 3x95 36.4 4600 0.193 238 193 0.44
23120BVZVTB09BD0 3x120 39.2 4610 0.153 276 220 0.37
27095BVZVTB09BD0 3x95+50 40.4 3980 0.193 238 193 0.44
23150BVZVTB09BD0 3x150 43.1 6840 0.124 319 246 0.31
27120BVZVTB09BD0 3x120+70 43.6 4800 0.153 276 220 0.37
23185BVZVTB09BD0 3x185 47.5 6820 0.0991 364 278 0.27
27150BVZVTB09BD0 3x150+70 48.0 5800 0.124 319 246 0.31
27185BVZVTB09BD0 3x185+95 53.3 7100 0.0991 364 278 0.27
23240BVZVTB09BD0 3x240 53.4 10850 0.0754 430 320 0.23
23300BVZVTB09BD0 3x300 58.4 13330 0.0601 497 359 0.2
27240BVZVTB09BD0 3x240+120 59.9 9930 0.0754 430 320 0.23
23400BVZVTB09BD0 3x400 66.0 16390 0.047 522 341 0.18
27300BVZVTB09BD0 3x300+150 66.6 11110 0.0601 497 359 0.2
27400BVZVTB09BD0 3x400+185 68.0 12440 0.047 522 341 0.18

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 98 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV


IEC LV, PVC Insulation, STA 0.6/1 kV 4 C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BVZVTB09BD0 4x1.5 13.8 320 12.1 18 19 22.8
24003BVZVTB09BD0 4x2.5 14.8 390 7.41 25 24 14.0
24004BVZVTB09BD0 4x4 17.0 530 4.61 34 33 8.7
24006BVZVTB09BD0 4x6 18.3 640 3.08 43 41 5.9
24010BVZVTB09BD0 4x10 20.5 870 1.83 60 54 3.5
24016BVZVTB09BD0 4x16 22.7 1170 1.15 80 70 2.2
24025BVZVTB09BD0 4x25 25.2 1590 0.727 101 92 1.5
24035BVZVTB09BD0 4x35 29.0 2130 0.524 126 110 1.1
24050BVZVTB09BD0 4x50 29.8 2440 0.387 153 130 0.81
24070BVZVTB09BD0 4x70 34.7 3630 0.268 196 162 0.58
24095BVZVTB09BD0 4x95 39.5 4790 0.193 238 193 0.44
24120BVZVTB09BD0 4x120 43.2 5880 0.153 276 220 0.37
24150BVZVTB09BD0 4x150 47.3 7130 0.124 319 246 0.31
24185BVZVTB09BD0 4x185 52.6 8800 0.0991 364 278 0.27
24240BVZVTB09BD0 4x240 58.7 11240 0.0754 430 320 0.23
24300BVZVTB09BD0 4x300 65.9 14008 0.0601 497 359 0.2
24400BVZVTB09BD0 4x400 70.0 17440 0.047 522 341 0.18

IEC LV, PVC Insulation, STA 0.6/1 kV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BVZVTB09BD0 5x1.5 14.6 370 12.1 18 19 22.8
25003BVZVTB09BD0 5x2.5 15.8 450 7.41 25 24 14.0
25004BVZVTB09BD0 5x4 18.3 620 4.61 34 33 8.7
25006BVZVTB09BD0 5x6 19.7 760 3.08 43 41 5.9
25010BVZVTB09BD0 5x10 22.1 1040 1.83 60 54 3.5
25016BVZVTB09BD0 5x16 24.6 1420 1.15 80 70 2.2
25025BVZVTB09BD0 5x25 29.0 2055 0.727 101 92 1.5
25035BVZVTB09BD0 5x35 32.3 2665 0.524 126 110 1.1
25050BVZVTB09BD0 5x50 36.6 3060 0.387 153 130 0.81
25070BVZVTB09BD0 5x70 42.7 4530 0.268 196 162 0.58

EC LV, PVC Insulation, STA 0.6/1 kV 7 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BVZVTB09BD0 7x1.5 16.6 480 12.1 18 19 22.8

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 99 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, STA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C003BVZVTB09BD0 7x2.5 18.1 590 7.41 25 24 14.0

EC LV, PVC Insulation, STA 0.6/1 kV 9 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BVZVTB09BD0 9x1.5 18.0 570 12.1 18 19 22.8
2K003BVZVTB09BD0 9x2.5 19.7 710 7.41 25 24 14.0

EC LV, PVC Insulation, STA 0.6/1 kV 12 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BVZVTB09BD0 12x1.5 19.1 660 12.1 18 19 22.8
2E003BVZVTB09BD0 12x2.5 21.0 837 7.41 25 24 14.0

EC LV, PVC Insulation, STA 0.6/1 kV 19 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BVZVTB09BD0 19x1.5 21.7 870 12.1 18 19 22.8
2F003BVZVTB09BD0 19x2.5 24.0 1130 7.41 25 24 14.0

EC LV, PVC Insulation, STA 0.6/1 kV 24 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BVZVTB09BD0 24x1.5 24.8 1180 12.1 18 19 22.8
2I003BVZVTB09BD0 24x2.5 27.5 1470 7.41 25 24 14.0

EC LV, PVC Insulation, STA 0.6/1 kV 37 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BVZVTB09BD0 37x1.5 27.9 1485 12.1 18 19 22.8
2M003BVZVTB09BD0 37x2.5 31.2 1965 7.41 25 24 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 70 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 100 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV


IEC 60502-1

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Polyvinyl chloride "PVC". International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 or equivalent
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 70 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 101 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV


no. of cores x conductor sizes mm2 Cu / PVC / SWA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BVZVSB09BD0 2x1.5 14.0 320 12.1 18 19 22.8
22003BVZVSB09BD0 2x2.5 15.0 405 7.41 25 24 14.0
22004BVZVSB09BD0 2x4 16.0 480 4.61 34 33 8.7
22006BVZVSB09BD0 2x6 17.0 570 3.08 43 41 5.9
22010BVZVSB09BD0 2x10 19.0 740 1.83 60 54 3.5
22016BVZVSB09BD0 2x16 22.0 1100 1.15 80 70 2.2
22025BVZVSB09BD0 2x25 22.0 1145 0.727 101 92 1.5
22035BVZVSB09BD0 2x35 25.0 1590 0.524 126 110 1.1
22050BVZVSB09BD0 2x50 27.0 2000 0.387 153 130 0.81
22070BVZVSB09BD0 2x70 31.0 2240 0.268 196 162 0.58
22095BVZVSB09BD0 2x95 35.0 3040 0.193 238 193 0.44
22120BVZVSB09BD0 2x120 38.0 3640 0.153 276 220 0.37
22150BVZVSB09BD0 2x150 41.0 4320 0.124 319 246 0.31
22185BVZVSB09BD0 2x185 46.0 5610 0.0991 364 278 0.27

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 70 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 102 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV


IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 3 C
Nom. Max. DC Current
Approx. Perm. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open air 3 conductors
diam. 20°C buried
[kg/km] [A] [V/A.km]
[mm] [Ohm/km] [A]
23002BVZVSB09BD0 3x1.5 14.0 340 12.1 18 19 22.8
23003BVZVSB09BD0 3x2.5 16.0 430 7.41 25 24 14.0
23004BVZVSB09BD0 3x4 17.0 540 4.61 34 33 8.7
23006BVZVSB09BD0 3x6 18.0 640 3.08 43 41 5.9
23010BVZVSB09BD0 3x10 21.0 985 1.83 60 54 3.5
23016BVZVSB09BD0 3x16 23.0 1300 1.15 80 70 2.2
23025BVZVSB09BD0 3x25 25.0 1730 0.727 101 92 1.5
23035BVZVSB09BD0 3x35 28.0 2140 0.524 126 110 1.1
27025BVZVSB09BD0 3x25+16 29.0 2270 0.727 101 92 1.5
27035BVZVSB09BD0 3x35+16 31.0 2450 0.524 126 110 1.1
23050BVZVSB09BD0 3x50 32.0 2660 0.387 153 130 0.81
23070BVZVSB09BD0 3x70 35.0 3010 0.268 196 162 0.58
27050BVZVSB09BD0 3x50+25 35.0 3125 0.387 153 130 0.81
27070BVZVSB09BD0 3x70+35 39.0 3710 0.268 196 162 0.58
23095BVZVSB09BD0 3x95 40.0 4140 0.193 238 193 0.44
27095BVZVSB09BD0 3x95+50 42.0 4700 0.193 238 193 0.44
23120BVZVSB09BD0 3x120 43.0 5010 0.153 276 220 0.37
27120BVZVSB09BD0 3x120+70 46.0 5790 0.153 276 220 0.37
23150BVZVSB09BD0 3x150 48.0 6390 0.124 319 246 0.31
27150BVZVSB09BD0 3x150+70 52.0 7220 0.124 319 246 0.31
23185BVZVSB09BD0 3x185 53.0 7690 0.0991 364 278 0.27
27185BVZVSB09BD0 3x185+95 57.0 8790 0.0991 364 278 0.27
23240BVZVSB09BD0 3x240 58.0 9610 0.0754 430 320 0.23
27240BVZVSB09BD0 3x240+120 62.0 10990 0.0754 430 320 0.23
23300BVZVSB09BD0 3x300 63.0 11590 0.0601 497 359 0.2
27300BVZVSB09BD0 3x300+150 67.0 13295 0.0601 497 359 0.2

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BVZVSB09BD0 4x1.5 15.0 390 12.1 18 19 22.8
24003BVZVSB09BD0 4x2.5 17.0 490 7.41 25 24 14.0
24004BVZVSB09BD0 4x4 18.0 610 4.61 34 33 8.7
24006BVZVSB09BD0 4x6 20.0 860 3.08 43 41 5.9
24010BVZVSB09BD0 4x10 22.0 1150 1.83 60 54 3.5
24016BVZVSB09BD0 4x16 25.0 1505 1.15 80 70 2.2
24025BVZVSB09BD0 4x25 28.0 2080 0.727 101 92 1.5
24035BVZVSB09BD0 4x35 31.0 2600 0.524 126 110 1.1

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 70 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 103 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24050BVZVSB09BD0 4x50 35.0 3320 0.387 153 130 0.81
24070BVZVSB09BD0 4x70 40.0 4090 0.268 196 162 0.58
24095BVZVSB09BD0 4x95 44.0 5190 0.193 238 193 0.44
24120BVZVSB09BD0 4x120 49.0 6790 0.153 276 220 0.37
24150BVZVSB09BD0 4x150 54.0 8040 0.124 319 246 0.31
24185BVZVSB09BD0 4x185 59.0 9740 0.0991 364 278 0.27
24240BVZVSB09BD0 4x240 65.0 12295 0.0754 430 320 0.23
24300BVZVSB09BD0 4x300 71.0 14890 0.0601 497 359 0.2

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BVZVSB09BD0 5x1.5 16.0 450 12.1 18 19 22.8
25003BVZVSB09BD0 5x2.5 18.0 560 7.41 25 24 14.0
25004BVZVSB09BD0 5x4 19.0 710 4.61 34 33 8.7
25006BVZVSB09BD0 5x6 21.0 1000 3.08 43 41 5.9
25010BVZVSB09BD0 5x10 24.0 1340 1.83 60 54 3.5
25016BVZVSB09BD0 5x16 28.0 2000 1.15 80 70 2.2
25025BVZVSB09BD0 5x25 33.0 2685 0.727 101 92 1.5
25035BVZVSB09BD0 5x35 36.0 3340 0.524 126 110 1.1
25050BVZVSB09BD0 5x50 41.0 4620 0.387 153 130 0.81
25070BVZVSB09BD0 5x70 46.0 5240 0.268 196 162 0.58

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 7 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BVZVSB09BD0 7x1.5 17.0 470 12.1 18 19 22.8
2C003BVZVSB09BD0 7x2.5 20.0 690 7.41 25 24 14.0

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 9 C


Nom. outer Approx. Max. DC Resist. Perm. current rating Current rating,
Nexans ref. Name diam. weight Cond. 20°C open air buried
[mm] [kg/km] [Ohm/km] [A] [A]
2K002BVZVSB09BD0 9x1.5 19.0 660 12.1 18 19
2K003BVZVSB09BD0 9x2.5 21.0 810 7.41 25 24

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 70 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 104 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, PVC Insulation, SWA, PVC 0.6/1 kV


IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 12 C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BVZVSB09BD0 12x1.5 20.0 750 12.1 18 19 22.8
2E003BVZVSB09BD0 12x2.5 22.0 940 7.41 25 24 14.0

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 19 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BVZVSB09BD0 19x1.5 23.0 970 12.1 18 19 22.8
2F003BVZVSB09BD0 19x2.5 26.0 1375 7.41 25 24 14.0

IEC LV, PVC Insulation 0.6/1KV - Galvanised steel wire armour 24 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BVZVSB09BD0 24x1.5 26.0 1310 12.1 18 19 22.8
2I003BVZVSB09BD0 24x2.5 29.0 1670 7.41 25 24 14.0

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 70 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 105 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, ATA, PVC 0.6/1 kV


IEC 60502-1

Aluminium tape armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Aluminium Tape Armour "ATA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Options:

- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.


- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / ATA / PVC 600/1000 V IEC

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 106 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, ATA, PVC 0.6/1 kV


60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Aluminium tape
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insulation 0.6/1KV - Aluminum Tape armour


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050BXZVEB09BD0 1x50 16.0 610 0.387 216 153 0.84
21070BXZVEB09BD0 1x70 18.0 820 0.268 278 188 0.61
21095BXZVEB09BD0 1x95 20.0 1080 0.193 342 226 0.47
21120BXZVEB09BD0 1x120 22.0 1320 0.153 400 257 0.39
21150BXZVEB09BD0 1x150 24.0 1620 0.124 464 287 0.34
21185BXZVEB09BD0 1x185 26.0 1970 0.0991 533 324 0.29
21240BXZVEB09BD0 1x240 28.0 2480 0.0754 634 375 0.25
21300BXZVEB09BD0 1x300 31.0 3050 0.0601 736 419 0.22
21400BXZVEB09BD0 1x400 35.0 3870 0.047 868 717 0.19
21500BXZVEB09BD0 1x500 39.0 4950 0.0366 998 791 0.17
21630BXZVEB09BD0 1x630 43.0 6175 0.0283 1151 861 0.16

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 107 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, ATA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21800BXZVEB09BD0 1x800 48.0 7790 0.0221 1246 904 0.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 108 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, AWA, PVC 0.6/1 kV


IEC 60502-1, FEWA, SEWA

Aluminium wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Aluminium Wire Armour "AWA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Option:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / AWA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 109 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, AWA, PVC 0.6/1 kV


Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Aluminium Wire
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Minimum Bend Radius - Installed 8 mm
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insulation 0.6/1KV - Aluminum wire armour


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050BXZVAB09BD0 1x50 19.0 725 0.387 216 153 0.84
21070BXZVAB09BD0 1x70 21.0 940 0.268 278 188 0.61
21095BXZVAB09BD0 1x95 23.0 1210 0.193 342 226 0.47
21120BXZVAB09BD0 1x120 25.0 1460 0.153 400 257 0.39
21150BXZVAB09BD0 1x150 26.0 1750 0.124 464 287 0.34
21185BXZVAB09BD0 1x185 28.0 2100 0.0991 533 324 0.29
21240BXZVAB09BD0 1x240 31.0 2660 0.0754 634 375 0.25
21300BXZVAB09BD0 1x300 33.0 3230 0.0601 736 419 0.22
21400BXZVAB09BD0 1x400 37.0 4110 0.047 868 717 0.19
21500BXZVAB09BD0 1x500 42.0 5225 0.0366 998 791 0.17
21630BXZVAB09BD0 1x630 46.0 6510 0.0283 1151 861 0.16

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 110 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, AWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21800BXZVAB09BD0 1x800 50.0 8340 0.0221 1246 904 0.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 111 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, CWA, PVC 0.6/1 kV - KM


IEC 60502-1 & KAHRAMAA

Copper wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This group is fully comply with IEC 60502-1 and Kahramaa EP-MS-P4/
S3-040 specs.

Design

1. Conductor Standards
Stranded bare copper class 2 acc. to IEC 60228 International IEC 60332-1;
IEC 60502-1
2. Insulation
National EP-MS-P4/S3-040
Cross Linked Polyethylene "XLPE"

3. Inner Sheath or Bedding


Lapped bedding or extruded PVC

4. Armour
Copper Wire Armour "CWA" / Water swelling tape above and under the
armour layer
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to IEC60332 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / CWA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 112 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, CWA, PVC 0.6/1 kV - KM

Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Copper Wires
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Minimum Bend Radius - Installed 8 mm
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insulation, CWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air single phase
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21050EXZVCB09BA0 1x50 21.0 920 0.387 216 153 0.84
21070EXZVCB09BA0 1x70 23.0 1190 0.268 278 188 0.61
21095EXZVCB09BA0 1x95 25.0 1525 0.193 342 226 0.47
21120EXZVCB09BA0 1x120 27.0 1840 0.153 400 257 0.39
21150EXZVCB09BA0 1x150 28.0 2205 0.124 464 287 0.34
21185EXZVCB09BA0 1x185 30.0 2650 0.0991 533 324 0.29
21240EXZVCB09BA0 1x240 33.0 3350 0.0754 634 375 0.25
21300EXZVCB09BA0 1x300 35.0 4070 0.0601 736 419 0.22
21400EXZVCB09BA0 1x400 41.0 6400 0.047 868 717 0.19
21500EXZVCB09BA0 1x500 44.0 6600 0.0366 998 791 0.17
21630EXZVCB09BA0 1x630 48.0 8200 0.0283 1151 861 0.16
21800EXZVCB09BA0 1x800 52.0 10510 0.0221 1246 904 0.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 113 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV


IEC 60502-1 & EEMUA 133

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding National EEMUA Pub. N°133
Lapped bedding or extruded PVC

4. Metalic Sheath
Extruded Lead sheath layer

5. Armour
Galvanized Steel Wire Armour "SWA"
6. Outer Sheath
Polyvinyl Chloride "PVC"
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 20 (xD) 10 (xD)
2

6/3/15 - http://www.nexans.qa Page 114 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV


Marking
no. of cores x conductor sizes mm2 Cu / XLPE / Lead / SWA / PVC 600/1000 V
IEC 60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Lead Sheath Yes
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 20 (xD)
Bending factor when installed 10 (xD)

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BXZVSB09BO0 2x1.5 15.0 430 12.1 25 23 22.8
22003BXZVSB09BO0 2x2.5 16.0 530 7.41 33 30 14.0
22004BXZVSB09BO0 2x4 17.0 640 4.61 44 39 8.7
22006BXZVSB09BO0 2x6 18.0 760 3.08 56 49 5.9
22010BXZVSB09BO0 2x10 21.0 990 1.83 78 65 3.5
22016BXZVSB09BO0 2x16 24.0 1460 1.15 99 84 2.2
22025BXZVSB09BO0 2x25 24.0 1520 0.727 131 107 1.65
22035BXZVSB09BO0 2x35 28.0 2120 0.524 162 129 1.15
22050BXZVSB09BO0 2x50 30.0 2660 0.387 197 153 0.89
22070BXZVSB09BO0 2x70 33.0 2990 0.268 251 188 0.6

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 20 (xD) 10 (xD)
2

6/3/15 - http://www.nexans.qa Page 115 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22095BXZVSB09BO0 2x95 38.0 4050 0.193 304 226 0.45
22120BXZVSB09BO0 2x120 41.0 4850 0.153 353 257 0.37
22150BXZVSB09BO0 2x150 45.0 5750 0.124 406 287 0.3
22185BXZVSB09BO0 2x185 51.0 7470 0.0991 463 324 0.26

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 3 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
23002BXZVSB09BO0 3x1.5 15.0 460 12.1 25 23 22.8
23003BXZVSB09BO0 3x2.5 17.0 580 7.41 33 30 14.0
23004BXZVSB09BO0 3x4 18.0 720 4.61 44 39 8.7
23006BXZVSB09BO0 3x6 20.0 860 3.08 56 49 5.9
23010BXZVSB09BO0 3x10 23.0 1310 1.83 78 65 3.5
23016BXZVSB09BO0 3x16 25.0 1730 1.15 99 84 2.2
23025BXZVSB09BO0 3x25 28.0 2300 0.727 131 107 1.65
23035BXZVSB09BO0 3x35 31.0 2840 0.524 162 129 1.15
23050BXZVSB09BO0 3x50 35.0 3540 0.387 197 153 0.89
23070BXZVSB09BO0 3x70 38.0 4010 0.268 251 188 0.6
23095BXZVSB09BO0 3x95 44.0 5510 0.193 304 226 0.45
23120BXZVSB09BO0 3x120 47.0 6660 0.153 353 257 0.37
23150BXZVSB09BO0 3x150 53.0 8500 0.124 406 287 0.3
23185BXZVSB09BO0 3x185 58.0 10230 0.0991 463 324 0.26
23240BXZVSB09BO0 3x240 63.0 12780 0.0754 546 375 0.21
23300BXZVSB09BO0 3x300 69.0 15420 0.0601 628 419 0.18
23400BXZVSB09BO0 3x400 77.0 19270 0.047 731 439 0.17

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BXZVSB09BO0 4x1.5 16.0 520 12.1 25 23 22.8
24003BXZVSB09BO0 4x2.5 18.0 660 7.41 33 30 14.0
24004BXZVSB09BO0 4x4 20.0 810 4.61 44 39 8.7
24006BXZVSB09BO0 4x6 22.0 1155 3.08 56 49 5.9
24010BXZVSB09BO0 4x10 24.0 1540 1.83 78 65 3.5
24016BXZVSB09BO0 4x16 28.0 2000 1.15 99 84 2.2
24025BXZVSB09BO0 4x25 31.0 2760 0.727 131 107 1.65
24035BXZVSB09BO0 4x35 33.0 3460 0.524 162 129 1.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 20 (xD) 10 (xD)
2

6/3/15 - http://www.nexans.qa Page 116 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24050BXZVSB09BO0 4x50 38.0 4410 0.387 197 153 0.89
24070BXZVSB09BO0 4x70 44.0 5450 0.268 251 188 0.6
24095BXZVSB09BO0 4x95 48.0 6910 0.193 304 226 0.45
24120BXZVSB09BO0 4x120 54.0 9040 0.153 353 257 0.37
24150BXZVSB09BO0 4x150 59.0 10700 0.124 406 287 0.3
24185BXZVSB09BO0 4x185 64.0 12960 0.0991 463 324 0.26
24240BXZVSB09BO0 4x240 71.0 16350 0.0754 546 375 0.21
24300BXZVSB09BO0 4x300 77.0 19800 0.0601 628 419 0.18
24400BXZVSB09BO0 4x400 89.0 25920 0.047 731 439 0.17

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BXZVSB09BO0 5x1.5 17.0 600 12.1 25 23 22.8
25003BXZVSB09BO0 5x2.5 20.0 740 7.41 33 30 14.0
25004BXZVSB09BO0 5x4 21.0 955 4.61 44 39 8.7
25006BXZVSB09BO0 5x6 23.0 1330 3.08 56 49 5.9
25010BXZVSB09BO0 5x10 26.0 1780 1.83 78 65 3.5
25016BXZVSB09BO0 5x16 31.0 2660 1.15 99 84 2.2
25025BXZVSB09BO0 5x25 36.0 3570 0.727 131 107 1.65
25035BXZVSB09BO0 5x35 39.0 4440 0.524 162 129 1.15
25050BXZVSB09BO0 5x50 45.0 6150 0.387 197 153 0.89
25070BXZVSB09BO0 5x70 51.0 6980 0.268 251 188 0.6

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 7 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BXZVSB09BO0 7x1.5 18.0 620 12.1 25 23 22.8
2C003BXZVSB09BO0 7x2.5 22.0 920 7.41 33 30 14.0

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 9 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BXZVSB09BO0 9x1.5 21.0 880 12.1 25 23 22.8
2K003BXZVSB09BO0 9x2.5 23.0 1070 7.41 33 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 20 (xD) 10 (xD)
2

6/3/15 - http://www.nexans.qa Page 117 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, Lead, SWA, PVC 0.6/1 kV

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 12 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BXZVSB09BO0 12x1.5 22.0 1000 12.1 25 23 22.8
2E003BXZVSB09BO0 12x2.5 24.0 1250 7.41 33 30 14.0

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 19 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BXZVSB09BO0 19x1.5 25.0 1300 12.1 25 23 22.8
2F003BXZVSB09BO0 19x2.5 29.0 1820 7.41 33 30 14.0

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 24 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BXZVSB09BO0 24x1.5 29.0 1750 12.1 25 23 22.8
2I003BXZVSB09BO0 24x2.5 32.0 2220 7.41 33 30 14.0

IEC LV, XLPE Insulation, Lead, SWA 0.6/1 kV 37 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BXZVSB09BO0 37x1.5 32.0 2260 12.1 25 23 22.8
2M003BXZVSB09BO0 37x2.5 37.0 3570 7.41 33 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 20 (xD) 10 (xD)
2

6/3/15 - http://www.nexans.qa Page 118 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV


IEC 60502-1 & SEC & MEW

Unarmoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
The cables are fully complyin to IEC and SEC, 1-SDMS-01, Rev.02 from KSA.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 Standards
International IEC 60332-1;
2. Insulation IEC 60502-1
Cross Linked Polyethylene "XLPE"
National MEW - LV Kuwait; SEC,11-
SMDS-01,Rev.02
3. Outer Sheath
Polyvinyl Chloride "PVC"
Options:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / PVC 600/1000 V IEC 60502-1
MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 119 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Unarmoured
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 1 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
21010BXZOUB09BD0 1x10 8.0 160 1.83 85 77 3.6
21016BXZOUB09BD0 1x16 9.0 220 1.15 113 100 2.3
21025BXZOUB09BD0 1x25 11.0 330 0.727 135 129 1.5
21035BXZOUB09BD0 1x35 12.0 425 0.524 169 155 1.1
21050BXZOUB09BD0 1x50 13.0 480 0.387 216 183 0.83
21070BXZOUB09BD0 1x70 15.0 670 0.268 279 225 0.6
21095BXZOUB09BD0 1x95 16.0 920 0.193 342 270 0.46
21120BXZOUB09BD0 1x120 18.0 1140 0.153 400 306 0.38
21150BXZOUB09BD0 1x150 20.0 1400 0.124 464 343 0.33
21185BXZOUB09BD0 1x185 22.0 1740 0.0991 533 387 0.28
21240BXZOUB09BD0 1x240 25.0 2250 0.0754 634 448 0.24
21300BXZOUB09BD0 1x300 27.0 2780 0.0601 736 502 0.21
21400BXZOUB09BD0 1x400 31.0 3530 0.047 868 717 0.18
21500BXZOUB09BD0 1x500 35.0 4570 0.0366 896 539 0.16
21630BXZOUB09BD0 1x630 39.0 5810 0.0283 1035 678 0.15
21800BXZOUB09BD0 1x800 43.0 7375 0.0221 1246 726 0.14

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 120 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 2 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BXZOUB09BD0 2x1.5 11.0 175 12.1 23 21 22.8
22003BXZOUB09BD0 2x2.5 12.0 220 7.41 32 30 14.0
22004BXZOUB09BD0 2x4 13.0 270 4.61 42 39 8.7
22006BXZOUB09BD0 2x6 14.0 330 3.08 54 49 5.9
22010BXZOUB09BD0 2x10 16.0 440 1.83 75 65 3.5
22016BXZOUB09BD0 2x16 18.0 570 1.15 100 84 2.2
22025BXZOUB09BD0 2x25 21.0 840 0.727 127 107 1.5
22035BXZOUB09BD0 2x35 23.0 1070 0.524 158 129 1.1
22050BXZOUB09BD0 2x50 26.0 1400 0.387 192 153 0.81
22070BXZOUB09BD0 2x70 30.0 1950 0.268 246 188 0.58
22095BXZOUB09BD0 2x95 33.0 2610 0.193 298 226 0.44
22120BXZOUB09BD0 2x120 37.0 3240 0.153 346 257 0.37
22150BXZOUB09BD0 2x150 41.0 3960 0.124 399 287 0.31
22185BXZOUB09BD0 2x185 46.0 4980 0.0991 456 324 0.27

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002BXZOUB09BD0 3x1.5 12.0 185 12.1 23 21 22.8
23003BXZOUB09BD0 3x2.5 13.0 235 7.41 32 30 14.0
23004BXZOUB09BD0 3x4 14.0 295 4.61 42 39 8.7
23006BXZOUB09BD0 3x6 15.0 375 3.08 54 49 5.9
23010BXZOUB09BD0 3x10 17.0 525 1.83 75 65 3.5
23016BXZOUB09BD0 3x16 19.0 725 1.15 100 84 2.2
27035BXZOUB09BD0 3x35+16 20.0 1600 0.524 158 129 1.1
23025BXZOUB09BD0 3x25 22.0 1060 0.727 127 107 1.5
23050BXZOUB09BD0 3x50 23.0 1435 0.387 192 153 0.81
27025BXZOUB09BD0 3x25+16 24.0 1200 0.727 127 107 1.5
23035BXZOUB09BD0 3x35 25.0 1380 0.524 158 129 1.1
27050BXZOUB09BD0 3x50+25 27.0 1900 0.387 192 153 0.81
23070BXZOUB09BD0 3x70 27.0 2020 0.268 246 188 0.58
27070BXZOUB09BD0 3x70+35 30.0 2700 0.268 246 188 0.58
23095BXZOUB09BD0 3x95 30.0 2745 0.193 298 226 0.44
23120BXZOUB09BD0 3x120 33.0 3430 0.153 346 257 0.37
27095BXZOUB09BD0 3x95+50 34.0 3300 0.193 298 226 0.44
23150BXZOUB09BD0 3x150 37.0 4240 0.124 399 287 0.31

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 121 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
27120BXZOUB09BD0 3x120+70 39.0 4200 0.153 346 257 0.37
23185BXZOUB09BD0 3x185 41.0 5250 0.0991 456 324 0.27
27150BXZOUB09BD0 3x150+70 43.0 5100 0.124 399 287 0.31
23240BXZOUB09BD0 3x240 45.0 6730 0.0754 538 375 0.23
27185BXZOUB09BD0 3x185+95 47.0 6300 0.0991 456 324 0.27
23300BXZOUB09BD0 3x300 51.0 8450 0.0601 621 419 0.2
27240BXZOUB09BD0 3x240+120 53.0 7300 0.0754 538 375 0.23
23400BXZOUB09BD0 3x400 58.0 10800 0.047 765 468 0.18
27300BXZOUB09BD0 3x300+150 59.0 9000 0.0601 621 419 0.2
27400BXZOUB09BD0 3x400+185 65.0 11160 0.047 765 468 0.18

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BXZOUB09BD0 4x1.5 13.0 210 12.1 23 21 22.8
24003BXZOUB09BD0 4x2.5 14.0 270 7.41 32 30 14.0
24004BXZOUB09BD0 4x4 15.0 350 4.61 42 39 8.7
24006BXZOUB09BD0 4x6 16.0 440 3.08 54 49 5.9
24010BXZOUB09BD0 4x10 18.0 635 1.83 75 65 3.5
24016BXZOUB09BD0 4x16 20.0 890 1.15 100 84 2.2
24025BXZOUB09BD0 4x25 24.0 1330 0.727 127 107 1.5
24050BXZOUB09BD0 4x50 25.0 1860 0.387 192 153 0.81
24035BXZOUB09BD0 4x35 27.0 1730 0.524 158 129 1.1
24070BXZOUB09BD0 4x70 29.0 2630 0.268 246 188 0.58
24095BXZOUB09BD0 4x95 33.0 2610 0.193 298 226 0.44
24120BXZOUB09BD0 4x120 37.0 4480 0.153 346 257 0.37
24150BXZOUB09BD0 4x150 41.0 5530 0.124 399 287 0.31
24185BXZOUB09BD0 4x185 46.0 6900 0.0991 456 324 0.27
24240BXZOUB09BD0 4x240 51.0 8980 0.0754 538 375 0.23
24300BXZOUB09BD0 4x300 58.0 11270 0.0601 621 419 0.2
24400BXZOUB09BD0 4x400 65.0 14370 0.047 765 468 0.18

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 5 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BXZOUB09BD0 5x1.5 13.0 250 12.1 23 21 22.8
25003BXZOUB09BD0 5x2.5 15.0 310 7.41 32 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 122 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25004BXZOUB09BD0 5x4 16.0 410 4.61 42 39 8.7
25006BXZOUB09BD0 5x6 17.0 530 3.08 54 49 5.9
25010BXZOUB09BD0 5x10 20.0 760 1.83 75 65 3.5
25016BXZOUB09BD0 5x16 22.0 1090 1.15 100 84 2.2
25025BXZOUB09BD0 5x25 27.0 1630 0.727 127 107 1.5
25035BXZOUB09BD0 5x35 30.0 2610 0.524 158 129 1.1
25050BXZOUB09BD0 5x50 33.0 2480 0.387 192 153 0.81
25070BXZOUB09BD0 5x70 39.0 3480 0.268 246 188 0.58

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 7 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BXZOUB09BD0 7x1.5 15.0 340 12.1 23 21 22.8
2C003BXZOUB09BD0 7x2.5 17.0 450 7.41 32 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 9 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BXZOUB09BD0 9x1.5 16.0 410 12.1 23 21 22.8
2K003BXZOUB09BD0 9x2.5 18.0 545 7.41 32 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 12 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BXZOUB09BD0 12x1.5 18.0 480 12.1 23 21 22.8
2E003BXZOUB09BD0 12x2.5 19.0 640 7.41 32 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 19 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BXZOUB09BD0 19x1.5 20.0 655 12.1 23 21 22.8
2F003BXZOUB09BD0 19x2.5 22.0 880 7.41 32 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 123 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, PVC 0.6/1KV


IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 24 C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BXZOUB09BD0 24x1.5 23.0 860 12.1 23 21 22.8
2I003BXZOUB09BD0 24x2.5 26.0 1150 7.41 32 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV - Unarmoured 37 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BXZOUB09BD0 37x1.5 26.0 1130 12.1 23 21 22.8
2M003BXZOUB09BD0 37x2.5 29.0 1550 7.41 32 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 124 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV


IEC 60502-1

Galvanized steel tape armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.

They are well adapted to underground use in industrial applications where


chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Galvanized Steel Tape Armour "STA"

5. Outer Sheath
Polyvinyl chloride "PVC".
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:

1. Air Temperature : 30 Deg.


2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 125 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV


Marking
No. of cores x conductor sizes mm2 Cu / XLPE / STA / PVC 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel tapes
Outer sheath PVC
Colour Black
Conductor exibility Stranded class 2
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insullation 0.6/1 KV -STA 2C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BXZVTB09BD0 2x1.5 11.8 210 12.1 25 23 22.8
22003BXZVTB09BD0 2x2.5 12.7 250 7.41 33 30 14.0
22004BXZVTB09BD0 2x4 13.7 310 4.61 44 39 8.7
22006BXZVTB09BD0 2x6 14.7 370 3.08 56 49 5.9
22010BXZVTB09BD0 2x10 16.5 500 1.83 78 65 3.5
22016BXZVTB09BD0 2x16 18.3 670 1.15 99 84 2.2
22025BXZVTB09BD0 2x25 21.6 960 0.727 131 107 1.65
22035BXZVTB09BD0 2x35 23.6 1200 0.524 162 129 1.15

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 126 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22050BXZVTB09BD0 2x50 26.4 1555 0.387 197 153 0.89
22070BXZVTB09BD0 2x70 30.5 2120 0.268 251 188 0.6
22095BXZVTB09BD0 2x95 34.2 2800 0.193 304 226 0.45
22120BXZVTB09BD0 2x120 39.2 3800 0.153 353 257 0.37
22150BXZVTB09BD0 2x150 42.8 4570 0.124 406 287 0.3
22185BXZVTB09BD0 2x185 48.0 5670 0.0991 463 324 0.26

IEC LV, XLPE Insullation 0.6/1 KV -STA 3C


Nom. Max. DC Current
Approx. Perm. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open air 3 conductors
diam. 20°C buried
[kg/km] [A] [V/A.km]
[mm] [Ohm/km] [A]
23002BXZVTB09BD0 3x1.5 12.5 240 12.1 25 23 22.8
23003BXZVTB09BD0 3x2.5 13.5 300 7.41 33 30 14.0
23004BXZVTB09BD0 3x4 14.6 370 4.61 44 39 8.7
23006BXZVTB09BD0 3x6 15.7 450 3.08 56 49 5.9
23010BXZVTB09BD0 3x10 17.7 610 1.83 78 65 3.5
23016BXZVTB09BD0 3x16 19.6 830 1.15 99 84 2.2
23025BXZVTB09BD0 3x25 23.1 1190 0.727 131 107 1.65
23035BXZVTB09BD0 3x35 25.3 1420 0.524 162 129 1.15
23050BXZVTB09BD0 3x50 25.5 1680 0.387 197 153 0.89
23070BXZVTB09BD0 3x70 29.5 2330 0.268 251 188 0.6
27025BXZVTB09BD0 3x25+16 30.4 1400 0.727 131 107 1.65
23095BXZVTB09BD0 3x95 32.8 3810 0.193 304 226 0.45
27035BXZVTB09BD0 3x35+16 33.4 1900 0.524 162 129 1.15
27050BXZVTB09BD0 3x50+25 36.4 2400 0.387 197 153 0.89
23120BXZVTB09BD0 3x120 37.3 4120 0.153 353 257 0.37
27070BXZVTB09BD0 3x70+35 39.4 3200 0.268 251 188 0.6
23150BXZVTB09BD0 3x150 41.4 6200 0.124 406 287 0.3
27095BXZVTB09BD0 3x95+50 42.4 4400 0.193 304 226 0.45
27120BXZVTB09BD0 3x120+70 45.4 5200 0.153 353 257 0.37
23185BXZVTB09BD0 3x185 45.5 6130 0.0991 463 324 0.26
27150BXZVTB09BD0 3x150+70 48.4 7000 0.124 406 287 0.3
23240BXZVTB09BD0 3x240 51.0 9840 0.0754 546 375 0.21
27185BXZVTB09BD0 3x185+95 51.4 8000 0.0991 463 324 0.26
23300BXZVTB09BD0 3x300 55.6 12120 0.0601 628 419 0.18
27240BXZVTB09BD0 3x240+120 57.5 10200 0.0754 546 375 0.21
23400BXZVTB09BD0 3x400 62.4 12470 0.047 731 439 0.17
27300BXZVTB09BD0 3x300+150 63.7 12800 0.0601 628 419 0.18
27400BXZVTB09BD0 3x400+185 66.7 13910 0.047 731 439 0.17

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 127 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV


IEC LV, XLPE Insullation 0.6/1 KV -STA 4C
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BXZVTB09BD0 4x1.5 13.3 280 12.1 25 23 22.8
24003BXZVTB09BD0 4x2.5 14.4 340 7.41 33 30 14.0
24004BXZVTB09BD0 4x4 15.6 430 4.61 44 39 8.7
24006BXZVTB09BD0 4x6 16.9 530 3.08 56 49 5.9
24010BXZVTB09BD0 4x10 19.0 730 1.83 78 65 3.5
24016BXZVTB09BD0 4x16 21.2 1010 1.15 99 84 2.2
24025BXZVTB09BD0 4x25 25.2 1470 0.727 131 107 1.65
24050BXZVTB09BD0 4x50 27.4 2110 0.387 197 153 0.89
24035BXZVTB09BD0 4x35 27.6 1890 0.524 162 139 1.15
24070BXZVTB09BD0 4x70 31.8 2950 0.268 251 188 0.6
24095BXZVTB09BD0 4x95 36.8 4230 0.193 304 226 0.45
24120BXZVTB09BD0 4x120 41.1 5270 0.153 353 257 0.37
24150BXZVTB09BD0 4x150 45.1 6395 0.124 406 287 0.3
24185BXZVTB09BD0 4x185 50.0 7875 0.0991 463 324 0.26
24240BXZVTB09BD0 4x240 56.0 10110 0.0754 546 375 0.21
24300BXZVTB09BD0 4x300 62.8 12600 0.0601 628 419 0.18
24400BXZVTB09BD0 4x400 69.6 15830 0.047 731 439 0.17

IEC LV, XLPE Insullation 0.6/1 KV -STA 5C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BXZVTB09BD0 5x1.5 14.1 320 12.1 25 23 22.8
25003BXZVTB09BD0 5x2.5 15.3 390 7.41 33 30 14.0
25004BXZVTB09BD0 5x4 16.6 490 4.61 44 39 8.7
25006BXZVTB09BD0 5x6 18.1 620 3.08 56 49 5.9
25010BXZVTB09BD0 5x10 20.5 870 1.83 78 65 3.5
25016BXZVTB09BD0 5x16 23.0 1220 1.15 99 84 2.2
25025BXZVTB09BD0 5x25 27.4 1780 0.727 131 107 1.65
25035BXZVTB09BD0 5x35 30.3 2310 0.524 162 129 1.15
25050BXZVTB09BD0 5x50 34.2 2680 0.387 197 153 0.89
25070BXZVTB09BD0 5x70 40.9 4060 0.268 251 188 0.6

IEC LV, XLPE Insullation 0.6/1 KV -STA 7C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BXZVTB09BD0 7x1.5 15.9 430 12.1 25 23 22.8

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 128 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, STA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C003BXZVTB09BD0 7x2.5 17.5 540 7.41 33 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV -STA 9C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BXZVTB09BD0 9x1.5 17.2 510 12.1 25 23 22.8
2K003BXZVTB09BD0 9x2.5 19.0 650 7.41 33 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV -STA 12C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BXZVTB09BD0 12x1.5 18.3 580 12.1 25 23 22.8
2E003BXZVTB09BD0 12x2.5 20.2 750 7.41 33 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV -STA 19C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BXZVTB09BD0 19x1.5 20.7 770 12.1 25 23 22.8
2F003BXZVTB09BD0 19x2.5 23.0 1010 7.41 33 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV -STA 24C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BXZVTB09BD0 24x1.5 23.6 990 12.1 25 23 22.8
2I003BXZVTB09BD0 24x2.5 26.3 1310 7.41 33 30 14.0

IEC LV, XLPE Insullation 0.6/1 KV -STA 37C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BXZVTB09BD0 37x1.5 26.5 1290 12.1 25 23 22.8
2M003BXZVTB09BD0 37x2.5 29.6 1720 7.41 33 30 14.0

Conductor Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame Bending factor when Bending factor
exibility No (Um) service retardant laying installed
Stranded class 0.6/1 kV 90 °C Yes 15 (xD) 8 (xD)
2

6/3/15 - http://www.nexans.qa Page 129 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA+TCWA, PVC 0.6/1 kV - KM


IEC 60502-1 & Kahramaa

Galvanized steel + Tin copper wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
The cables are fully complying to IEC and Kahramaa EP-MS-P4/
S3-040 specication.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor Standards
Stranded bare copper class 2 acc. to IEC 60228. International IEC 60332-1;
IEC 60502-1
2. Insulation
Cross Linked Polyethylene "XLPE". National EP-MS-P4/S3-040

3. Inner Sheath or Bedding


Extruded bedding "PVC".

4. Armour
Single layer consisting of both galvanized Steel and tinned copper wires
"SWA+TCWA" / Water blocking tape above and under the armour layer.
5. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or equivalent

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 KAHRA MAA EP-MS-P4/S3-040 600/1000

Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor
No (Um) service Yes laying installed
0.6/1 kV 90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 130 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA+TCWA, PVC 0.6/1 kV - KM


V XLPE MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wire + tin copper wire
Outer sheath PVC
Colour Black
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

KAHRAMAA LV, XLPE Insulation 0.6/1KV - Galvanised steel + Tinned copper wire armour
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24016EXZVDB09BA0 4x16 24.0 1610 1.15 99 84 2.2
24025EXZVDB09BA0 4x25 26.5 2235 0.727 131 107 1.65
24035EXZVDB09BA0 4x35 29.0 2790 0.524 162 129 1.15
24050EXZVDB09BA0 4x50 33.0 3560 0.387 197 153 0.89
24070EXZVDB09BA0 4x70 38.0 4390 0.268 251 188 0.6
24095EXZVDB09BA0 4x95 42.0 5580 0.193 304 226 0.45
24120EXZVDB09BA0 4x120 47.0 7290 0.153 353 257 0.37
24150EXZVDB09BA0 4x150 51.0 8630 0.124 406 287 0.3
24185EXZVDB09BA0 4x185 56.0 10460 0.0991 463 324 0.26
24240EXZVDB09BA0 4x240 62.0 13190 0.0754 546 375 0.21
24300EXZVDB09BA0 4x300 67.0 15980 0.0601 628 419 0.18
24400EXZVDB09BA0 4x400 77.0 20925 0.047 731 439 0.17

Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor
No (Um) service Yes laying installed
0.6/1 kV 90 °C 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 131 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV - QP


IEC 60502-1 & QP

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)
This family is fully compling with Qatar Petroleum specication

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 Standards
International IEC 60332-1;
2. Insulation IEC 60502-1
Cross Linked Polyethylene "XLPE"
National QP–ES.2.14.0070-LV
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC

4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant CAT A to IEC 60332-3 or
equivalent, Oil resistant, Anti termite

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V
Standard MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 132 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV - QP

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

QP, LV, XLPE Insulation, SWA 0.6/1 kV 4 C


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24010BXZVSB09BNS 4x10 25.0 1265 1.83 78 65 3.5
24016BXZVSB09BNS 4x16 27.0 1610 1.15 99 84 2.2
24025BXZVSB09BNS 4x25 32.0 2275 0.727 131 107 1.65
24035BXZVSB09BNS 4x35 34.0 2450 0.524 162 129 1.15
24050BXZVSB01B20 4x50 38.0 3085 0.387 197 153 0.89
24070BXZVSB01B20 4x70 44.0 4320 0.268 251 188 0.6
24095BXZVSB01B20 4x95 48.0 5480 0.193 304 226 0.45
24120BXZVSB01B20 4x120 53.0 6945 0.153 353 257 0.37
24150BXZVSB01B20 4x150 63.0 8340 0.124 406 287 0.3
24185BXZVSB01B20 4x185 63.0 9915 0.0991 463 324 0.26
24240BXZVSB01B20 4x240 69.0 12335 0.0754 546 375 0.21
24300BXZVSB01B20 4x300 75.0 14860 0.0601 628 419 0.18
24400BXZVSB01B20 4x400 85.0 19510 0.047 731 439 0.17

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 133 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV


IEC 60502-1, FEWA, SEWA

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application
These power cables are used for electricity supply in low voltage installation
systems.
They are well adapted to underground use in industrial applications where
chemical and mechanical protections are needed (renery areas, chemical
plant…)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
Standards
2. Insulation
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
3. Inner Sheath or Bedding National FEWA-LV-UAE; SEWA-LV-
Lapped bedding or extruded PVC UAE

4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V IEC

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 134 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV


60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

IEC LV, XLPE Insulation 0.6/1KV - 2 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
22002BXZVSB09BD0 2x1.5 13.0 300 12.1 25 23 22.8
22003BXZVSB09BD0 2x2.5 14.0 385 7.41 33 30 14.0
22004BXZVSB09BD0 2x4 15.0 450 4.61 44 39 8.7
22006BXZVSB09BD0 2x6 16.0 540 3.08 56 49 5.9
22010BXZVSB09BD0 2x10 18.0 700 1.83 78 65 3.5
22016BXZVSB09BD0 2x16 21.0 1045 1.15 99 84 2.2
22025BXZVSB09BD0 2x25 21.0 1080 0.727 131 107 1.65
22035BXZVSB09BD0 2x35 24.0 1510 0.524 162 129 1.15
22050BXZVSB09BD0 2x50 26.0 1900 0.387 197 153 0.89
22070BXZVSB09BD0 2x70 29.0 2130 0.268 251 188 0.6
22095BXZVSB09BD0 2x95 33.0 2890 0.193 304 226 0.45
22120BXZVSB09BD0 2x120 36.0 3460 0.153 353 257 0.37
22150BXZVSB09BD0 2x150 39.0 4110 0.124 406 287 0.3
22185BXZVSB09BD0 2x185 44.0 5330 0.0991 463 324 0.26

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 135 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV


IEC LV, XLPE Insulation 0.6/1KV - 3 cores
Nom. Max. DC Current
Approx. Perm. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open air 3 conductors
diam. 20°C buried
[kg/km] [A] [V/A.km]
[mm] [Ohm/km] [A]
23002BXZVSB09BD0 3x1.5 13.0 330 12.1 25 23 22.8
23003BXZVSB09BD0 3x2.5 15.0 410 7.41 33 30 14.0
23004BXZVSB09BD0 3x4 16.0 510 4.61 44 39 8.7
23006BXZVSB09BD0 3x6 17.0 610 3.08 56 49 5.9
23010BXZVSB09BD0 3x10 20.0 930 1.83 78 65 3.5
23016BXZVSB09BD0 3x16 22.0 1240 1.15 99 84 2.2
23025BXZVSB09BD0 3x25 24.0 1640 0.727 131 107 1.65
23035BXZVSB09BD0 3x35 27.0 2030 0.524 162 129 1.15
27025BXZVSB09BD0 3x25+16 28.0 2165 0.727 131 107 1.65
27035BXZVSB09BD0 3x35+16 29.0 2330 0.524 162 129 1.15
23050BXZVSB09BD0 3x50 30.0 2520 0.387 197 153 0.89
23070BXZVSB09BD0 3x70 33.0 2860 0.268 251 188 0.6
27050BXZVSB09BD0 3x50+25 33.0 2960 0.387 197 153 0.89
27070BXZVSB09BD0 3x70+35 37.0 3530 0.268 251 188 0.6
23095BXZVSB09BD0 3x95 38.0 3940 0.193 304 226 0.45
27095BXZVSB09BD0 3x95+50 40.0 4470 0.193 304 226 0.45
23120BXZVSB09BD0 3x120 41.0 4760 0.153 353 257 0.37
27120BXZVSB09BD0 3x120+70 44.0 5508 0.153 353 257 0.37
23150BXZVSB09BD0 3x150 46.0 6070 0.124 406 287 0.3
27150BXZVSB09BD0 3x150+70 49.0 6860 0.124 406 287 0.3
23185BXZVSB09BD0 3x185 50.0 7310 0.0991 463 324 0.26
27185BXZVSB09BD0 3x185+95 54.0 8350 0.0991 463 324 0.26
23240BXZVSB09BD0 3x240 55.0 9135 0.0754 546 375 0.21
27240BXZVSB09BD0 3x240+120 59.0 10440 0.0754 546 375 0.21
23300BXZVSB09BD0 3x300 60.0 11015 0.0601 628 419 0.18
27300BXZVSB09BD0 3x300+150 64.0 12630 0.0601 628 419 0.18
23400BXZVSB09BD0 3x400 67.0 13760 0.047 731 439 0.17
27400BXZVSB09BD0 3x400+185 73.0 16330 0.047 731 439 0.17

IEC LV, XLPE Insulation 0.6/1KV - 4 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24002BXZVSB09BD0 4x1.5 14.0 370 12.1 25 23 22.8
24003BXZVSB09BD0 4x2.5 16.0 470 7.41 33 30 14.0
24004BXZVSB09BD0 4x4 17.0 580 4.61 44 39 8.7
24006BXZVSB09BD0 4x6 19.0 825 3.08 56 49 5.9
24010BXZVSB09BD0 4x10 21.0 1100 1.83 78 65 3.5
24016BXZVSB09BD0 4x16 24.0 1430 1.15 99 84 2.2

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 136 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
24025BXZVSB09BD0 4x25 27.0 1970 0.727 131 107 1.65
24035BXZVSB09BD0 4x35 29.0 2470 0.524 162 129 1.15
24050BXZVSB09BD0 4x50 33.0 3150 0.387 197 153 0.89
24070BXZVSB09BD0 4x70 38.0 3890 0.268 251 188 0.6
24095BXZVSB09BD0 4x95 42.0 4930 0.193 304 226 0.45
24120BXZVSB09BD0 4x120 47.0 6450 0.153 353 257 0.37
24150BXZVSB09BD0 4x150 51.0 7645 0.124 406 287 0.3
24185BXZVSB09BD0 4x185 56.0 9250 0.0991 463 324 0.26
24240BXZVSB09BD0 4x240 62.0 11680 0.0754 546 375 0.21
24300BXZVSB09BD0 4x300 67.0 14140 0.0601 628 419 0.18
24400BXZVSB09BD0 4x400 77.0 18510 0.047 731 439 0.17

IEC LV, XLPE Insulation 0.6/1KV - 5 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
25002BXZVSB09BD0 5x1.5 15.0 430 12.1 25 23 22.8
25003BXZVSB09BD0 5x2.5 17.0 530 7.41 33 30 14.0
25004BXZVSB09BD0 5x4 18.0 680 4.61 44 39 8.7
25006BXZVSB09BD0 5x6 20.0 950 3.08 56 49 5.9
25010BXZVSB09BD0 5x10 23.0 1270 1.83 78 65 3.5
25016BXZVSB09BD0 5x16 27.0 1900 1.15 99 84 2.2
25025BXZVSB09BD0 5x25 31.0 2550 0.727 131 107 1.65
25035BXZVSB09BD0 5x35 34.0 3170 0.524 162 129 1.15
25050BXZVSB09BD0 5x50 39.0 4390 0.387 197 153 0.89
25070BXZVSB09BD0 5x70 44.0 4980 0.268 251 188 0.6

IEC LV, XLPE Insulation 0.6/1KV - 7 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2C002BXZVSB09BD0 7x1.5 16.0 440 12.1 25 23 22.8
2C003BXZVSB09BD0 7x2.5 19.0 650 7.41 33 30 14.0

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 137 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE Insulation, SWA, PVC 0.6/1 kV


IEC LV, XLPE Insulation 0.6/1KV - 9 cores
Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2K002BXZVSB09BD0 9x1.5 18.0 630 12.1 25 23 22.8
2K003BXZVSB09BD0 9x2.5 20.0 770 7.41 33 30 14.0

IEC LV, XLPE Insulation 0.6/1KV - 12 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2E002BXZVSB09BD0 12x1.5 19.0 710 12.1 25 23 22.8
2E003BXZVSB09BD0 12x2.5 21.0 890 7.41 33 30 14.0

IEC LV, XLPE Insulation 0.6/1KV - 19 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2F002BXZVSB09BD0 19x1.5 22.0 930 12.1 25 23 22.8
2F003BXZVSB09BD0 19x2.5 25.0 1300 7.41 33 30 14.0

IEC LV, XLPE Insulation 0.6/1KV - 24 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2I002BXZVSB09BD0 24x1.5 25.0 1250 12.1 25 23 22.8
2I003BXZVSB09BD0 24x2.5 28.0 1590 7.41 33 30 14.0

IEC LV, XLPE Insulation 0.6/1KV - 37 cores


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop, 3
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
2M002BXZVSB09BD0 37x1.5 28.0 1610 12.1 25 23 22.8
2M003BXZVSB09BD0 37x2.5 32.0 2555 7.41 33 30 14.0

Halogen free Max.conductor temp.in service Flame retardant Bending factor when laying Bending factor installed
No 90 °C Yes 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 138 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar Contact
Phone: +974 4 467 3009
sales.qatar@nexans.com

Pilot Cable 1kV


IEC 60502-1 & KAHRAMAA

Galvanized steel wire armoured LV cable, PVC sheathed for xed installations. Rated voltage 0.6/1 KV

Description

Application

This pilot cable is used on Standard Pilot Wire Protection Schemes and
Telecommunication Purposes.
The cable is fully complying to IEC and Kahramaa EP-MS-P4/
S3-050 specication.

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228

2. Conductor of Pairs
Stranded bare copper class 2 acc. to IEC 60228

3. Insulation Standards
Cross Linked Polyethylene "XLPE" International IEC 60332-1;
IEC 60502-1
4. Inner Sheath or Bedding
Extruded bedding "PVC". National EP-MS-P4/S3-050

5. Armour
Single layer of Galvanized Steel wires "SWA" / Water blocking tape above
and under the armour layer.

6. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or
equivalent

Installation Conditions:

1. Air Temperature : 30 Deg.


2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %


Marking

no. of cores x conductor sizes mm2 KAHRA MAA EP-MS-P4/S3-050 600/1000


V XLPE MADE IN QATAR QICC-Nexans Year Meters
Custom marking available

Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor
No (Um) service Yes laying installed
0.6/1 kV 90 °C 8 (xD) 15 (xD)

6/3/15 - http://www.nexans.qa Page 139 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar Contact
Phone: +974 4 467 3009
sales.qatar@nexans.com

Pilot Cable 1kV

Characteristics
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 8 (xD)
Bending factor when installed 15 (xD)

Pilot cable 0.6/1 kV


Nom. Current
Approx. Max. DC Resist. Perm. current Voltage drop,
outer rating,
Nexans ref. Name weight Cond. 20°C rating open air 3 conductors
diam. buried
[kg/km] [Ohm/km] [A] [V/A.km]
[mm] [A]
4x4 +
2P004BXZDSB09BA0 31.0 1500 4.61 44 39 8.7
4x2x1.5

Halogen free Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor
No (Um) service Yes laying installed
0.6/1 kV 90 °C 8 (xD) 15 (xD)

6/3/15 - http://www.nexans.qa Page 140 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar Contact
Phone: +974 4 467 3009
sales.qatar@nexans.com

Copper conductors
The diversity and the applications of copper conductors are numerous.
From a single wire to a complex cable, from the lowest section to the highest, copper is available, annealed, hard, bare or
plated.
A lot of applications use the properties of copper :
• Energy
• Telecommunication
• Welding…

The copper qualities generally used for the production of conductors are :
• ETP copper, or Cu-a1, with oxygen content between 200 and 300 ppm.
• OF copper, oxygen-free or Cu-c1, with very small content in oxygen (20 ppm max.) able to resist to hydrogen brittleness
during a heating.

6/3/15 - http://www.nexans.qa Page 141 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Bare copper conductor


IEC 60228

Single-core Bare copper conductor

Description
Application
Single-core Bare copper conductor using for earthing, This group is complying
with IEC 60228.

Design
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 or equivalent

Installation Conditions: Standards


1.Air Temperature : 30 Deg. International IEC 60228
2.Ground Temperature : 20 Deg
3.Soil Thermal Resistivity : 1.5 km/w
4.Depth of lay : 0.8 m
All dimensions have tolerance +-7 %

Conductor exibility Bending factor when laying Bending factor installed


Highly exible, class 2 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 142 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Bare copper conductor


Characteristics
Construction characteristics
Conductor material Bare copper stranded
Conductor shape Circular
Conductor exibility Highly exible, class 2
Armour type Unarmoured
Dimensional characteristics
Number of cores 1
Usage characteristics
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

Conductor exibility Bending factor when laying Bending factor installed


Highly exible, class 2 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 143 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Copper Lead
IEC 60228 & Kahramaa

Single-core Copper / Lead

Description
Application
Single-core Copper / Lead cable using as an earthing, This group is complying
with IEC 60228 and Kahramaa .

Design
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 or equivalent

2. Metalic Sheath

Lead sheath layer to IEC 60502-1.

Standards
International IEC 60228

Installation Conditions:
1.Air Temperature : 30 Deg.
2.Ground Temperature : 20 Deg
3.Soil Thermal Resistivity : 1.5 km/w
4.Depth of lay : 0.8 m
All dimensions have tolerance +-7 %

Conductor exibility Bending factor when laying Bending factor installed


Stranded class 2 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 144 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Contact
Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Copper Lead
Characteristics
Construction characteristics
Conductor material Bare copper stranded
Conductor shape Circular
Conductor exibility Stranded class 2
Armour type Unarmoured
Dimensional characteristics
Number of cores 1
Usage characteristics
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

Conductor exibility Bending factor when laying Bending factor installed


Stranded class 2 15 (xD) 8 (xD)

6/3/15 - http://www.nexans.qa Page 145 / 146


All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of
Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Global expert in cables and cabling systems

Distributed by :

Nexans Qatar - Doha - Qatar


+ 974 4467 3009 - sales.qatar@nexans.com

Вам также может понравиться